Drayton Combi-Stat RTS8 Installation Instructions And Instructions For Use

Combi-Stat RTS8 Room Thermostat
Installation instructions
RELEVANT EC DIRECTIVES:
2006/95/EC Low Voltage Directive 2004/108/EC Electromagnetic Compatibility 2011/65/EU RoHS Directive
EN60730-1, EN60730-2-9
Energy Class I = 1% (According to EU 811/2013,
812/2013, 813/2013, 814/2013)
Telephone: +44 (0) 845 130 5522 Facsimile: +44 (0) 845 130 0622 Technical Helpline: +44 (0) 845 130 7722 Website: www.draytoncontrols.co.uk Email: customer.care@draytoncontrols.co.uk
6490018-1 Iss D
0503
Drayton Controls reserve the right to make changes without notice and cannot accept liability for errors.
THERMOSTAT INTERCHANGE GUIDE
deifsitaSdnameDnommoCeviLlartueNhtraEledoMekaM
3LN1SRsaG hsitirB
British Gas RS2 (for 2 wire connectionwith loads of 0.1 to 0.6 A) L 2 British Gas RS2 (for 2 wire connection with loads 0.6 to 6A) L 3 British Gas RS2 (for 3 wire connection with loads under 2A) N L 3
231LN4SR saG hsitirB
Drayton RTS7 and RTS8 (for 2 wire connection with loads of 0.1 to 0.6 A) L 2 Drayton RTS7 and RTS8 (for 2 wire connection with loads 0.6 to 6A) L 3 Drayton RTS7 and RTS8 (for 3 wire connection with loads under 2A) N L 3
3LN 1 STRnotyarD 3LN 2 STRnotyarD
231 LN4 STRnotyarD
214E241 STelytsefiL LCA
2315053 AT elytsefiL LCA
Drayton (old version) 3214 TR Drayton (old version) 4ETR 123
3214032TMRlladnaR ssofnaD 43LN032TERlladnaR ssofnaD
Danfoss Randall RT1 132
2143DR lladnaR ssofnaD 214A3DR lladnaR ssofnaD
213NECTR lladnaR ssofnaD 213NEMTR lladnaR ssofnaD 213NERSR lladnaR ssofnaD 213N405R lladnaR ssofnaD
Honeywell T4360B 1 3
4312B0606T llewyenoH 4312B1606T llewyenoH 4312B3606T llewyenoH 4312B0636T llewyenoH
214E1TRH nnamtsroH
Horstmann Centuarstat 123
321E1 DAR ryG & sidnaL Landis & Gyr RAD 1N 123 Landis & Gyr RAD 1EM 123
HLN1 TRP notrettoP HLTN 2 TRP notrettoP HLTNTS 001 TRP notrettoP
CHLTNTD 001 TRP notrettoP
134E2222 XLTcivnuS 13/LNE9522 XLT civnuS
213NE6532 XLT civnuS
134E4562 XLTcivnuS
2134E2582 XLTcivnuS
231E053 AT capoS
2314E153 AT capoS
23152 TRS retsamhctiwS
214ESS rewoT
NOTE: British Gas RS2 & Drayton RTS7 details are for guide use only. ALWAYS follow above instructions.
TECHNICAL DATA
Electrical supply 24V-230V AC/DC
Double insulated no earth required
Temperature range 10°C to 30°C
Switch type SPST 6(2)A
See Figs 5 to 7 for supply voltage and maximum loads which are dependant on wiring configuration used
Temperature sensor Bi metallic
Continued from overleaf
Combi-Stat boiler compatibilty information
Make Model
Alpha 240 2 wire
Ocean 80 3 wire
Ariston Genus 27 2 wire
Euro Combi 27 2 wire
Biasi Prisma 2 wire
Riva 3 wire
Chaffoteaux Britony Combi 80 3 wire
Celtic FF 3 wire
Ferrolli Domina 80 2 wire
Modena 80 2 wire
Halstead Finest 2 wire
Finest Gold 2 wire
Radiant RSF 24 2 wire
Ravenheat RSF 820/20 2 wire
CSI 85 Condensing 2 wire
Saunier Duval 623 Combi 2 wire
Myson Midas BF 2 wire
Elm Le Blanc 2 wire
CombiStat
2. Undo the captive restraining screw
3. Hinge from bottom and pull top forward. Lower outer cover to remove
4. Fix directly to a flat wall or onto a flush mounting conduit box or optional Pattress box using suitable screws
RTS8 Combi-Stat Thermostat
The RTS8 is a 24V-230V AC/DC mechanical thermostat that can be used for either 2 or 3 wire applications, making it suitable for replacement of older 2 wire thermostats with no Neutral, or 3 wire thermostat replacement where a Neutral connection has been used. (Optimum performance is attained with 3 wire connection.)
IMPORTANT NOTES
The installation instructions must be followed for this thermostat to operate correctly. Failure to do so may result in inadequate room temperature control. Particular attention should be paid to the sections on
wiring and set up.
All electrical work should be carried out by a competent person to conform to all relevant standards and regulations.
Isolate/disconnect the power supply to the appliance and/or system before commencing any electrical work.
A switch having a contact separation of at least 3mm on both Live and Neutral poles must be incorporated in the fixed wiring of the system to provide full isolation of the mains supply.
Ensure that the system fuse is the correct rating. For Gas fired radiator heating systems this is 3A.
INSTALLATION INSTRUCTIONS
Location
Care should be taken to mount the thermostat in a position, which is not subject to direct sunlight or draughts. Preferably it should be mounted on an inside wall about 1.5m (5ft) above the floor in a position where it can respond to room temperature but away from the direct influence of radiators or other appliances giving off heat.
Fixing
Standard cable entry can be from the rear or top, if bottom entry or extra space for cabling is required use the optional Pattress box.
1. Pull temperature
setting knob forward to remove.
Set up to be followed when wiring to Fig 6 only
The thermostat utilises a series resistor as a heat anticipator when wired in accordance with Fig 6 diagram.
To avoid inaccurate room temperature control it is VERY IMPORTANT that the following set up procedure is followed.
An electrical multimeter will be required for the following procedure.
• Isolate electrical supply
• Mount base unit to wall
• Connect wires to L and 2
• Turn red setting shaft until switch contact opens
(see Fig 4)
• Set meter to 1 amp, current range
• Carry out electrical safety checks on the system/
appliance and turn system ON
• Put meter probes across L and 2
• Read current. Expected reading for Gas CH
systems = 0.1A to 0.6A
• If reading is BELOW 0.6Awire as Fig 6 (isolate
electric supply before rewiring)
• If reading is ABOVE 0.6Awire as Fig 7 (isolate
electric supply before rewiring)
• Reset the red setting shaft so that the small slot
is vertically downwards
• Reassemble thermostat
Range limiting
The setting range may be limited or a particular setting locked through the use of the mechanism to be found under the control knob.
To set the range limits:
1. Set thermostat to the desired temperature
2. Remove the setting knob by carefully pulling it
forward
3. Lift and rotate the two limiting arms to
reposition them in the required notches
4. Replace the knob in its previous position
Continued overleaf
Earth loop connection
Red setting shaft
Screw slots
Fig 1
Fig 4
N 2 3 L
Acc.
Acc.
Call for heat
LOAD
L
N
N 230V AC 50Hz Fused 3A
Fig 5. 3 wire connection. Max load = 2A
Suitable for most wet CH systems
N 2 3 L
Acc.
Acc.
Call for heat
LOADLN 24V-230V AC/DC Fused 3A
N 2 3 L
Acc.
Acc.
Call for heat
LOAD
L
N
24V-230V AC/DC Suitably rated fuse
Fig 7. 2 wire connection. No Neutral. Load = 0.6A to 6A
Typically for higher loads (ie electric heating)
Fig 3
Fig 2
Fig 6. 2 wire connection. No Neutral. Load = 0.1A to 0.6A
Suitable for most wet CH systems
Note: Use this connection for gas CH systems, where there is
no neutral wire, and follow set-up procedure. If current reading above 0.6 amps, wire as Fig 7. 2 wire connection no Neutral.
Wiring
The RTS8 is double insulated and does not require an earth, if there are existing earth wires that need to be connected, use the Earth loop connection (Fig 4).
Terminate the wiring as shown in diagrams (Figs 5 to
7), ensure that the correct diagram is followed to match the current load (Amps) and cabling of the heating system. If unsure of current load, follow Set up
procedure to determine it.
Combi-Stat boiler compatibilty information
Make Model
Worcester Series 2/3 wire*
CDi Series 2/3 wire*
Si Series 2/3 wire*
Vaillant EcoMax 2/3 wire*
TurboMax 2/3 wire*
Ideal Isar 2 wire
Response 2 wire
Mini 2 wire
Glow-Worm Energysaver 2/3 wire*
Compact E 2/3 wire*
Baxi 80 Eco 3 wire recommended
by Baxi across range
Combi 80E 3 wire recommended
by Baxi across range
105E 3 wire recommended
by Baxi across range
Maxflow 3 wire recommended
by Baxi across range
Potterton Bahama 3 wire recommended
by Pott’s across range
Puma 3 wire recommended
by Pott’s across range
Combi 3 wire recommended
by Pott’s across range
* Where 2/3 wire is indicated use 3 wire connection for optimum performance. This information is for guidance only as the boiler manufacturer may change the mode of operation at any time without warning. For further information please refer to the boiler manufacturers handbook.
Combi-Stat boiler compatibilty information
Make Model
Worcester Series 2/3 wire*
CDi Series 3 wire
Si Series 2/3 wire*
Vaillant EcoMax 2/3 wire*
TurboMax 2/3 wire*
Ideal Isar 2 wire
Response 2 wire
Mini 2 wire
Glow-Worm Energysaver 2/3 wire*
Compact E 2/3 wire*
Baxi 80 Eco 3 wire recommended
by Baxi across range
Combi 80E 3 wire recommended
by Baxi across range
105E 3 wire recommended
by Baxi across range
Maxflow 3 wire recommended
by Baxi across range
Potterton Bahama 3 wire recommended
by Pott’s across range
Puma 3 wire recommended
by Pott’s across range
Combi 3 wire recommended
by Pott’s across range
* Where 2/3 wire is indicated use 3 wire connection for optimum performance. This information is for guidance only as the boiler manufacturer may change the mode of operation at any time without warning. For further information please refer to the boiler manufacturers handbook.
Loading...