Dranetz-BMI PP4300 User's Guide [en, fr, de, es]

Page 1
Power Platform® 4300 TASKCard® 808
User’s Guide
P/N OM-4300-TASK808 Reprinted 7/98
Dranetz-BMI • 1000 New Durham Road • Edison, NJ 08818-4019
Fax 732-248-1834 • www.dranetz-bmi.com
Page 2
PP4300/Task 808
WARNING
Death, serious injury, or fire hazard could result from improper connection of this instrument. Read and understand this manual before connecting this instrument. Follow all installation and operating instructions while using this instrument.
Connection of this instrument must be performed in compliance with the National Electrical Code (ANSI/NFPA 70-1996) of USA and any additional safety requirements applicable to your installation.
Installation, operation, and maintenance of this instrument must be performed by qualified personnel only. The National Electrical Code defines a qualified person as "one familiar with the construction and operation of the equipment and the hazards involved."
ADVERTENCIA
Una conexi ón incorrecta de este instrumento puede producir la muerte, lesiones graves y riesgo de incendio. Lea y entienda este manual antes de conectar. Observe todas las instrucciones de instalación y operaci ón durante el uso de este instrumento.
La conexi ón de este instrumento debe ser hecha de acuerdo con las normas del Código El éctrico Nacional (ANSI/NFPA 70-1996) de EE. UU., además de cualquier otra norma de seguridad correspondiente a su establecimiento.
La instalaci ón, operación y mantenimiento de este instrumento debe ser realizada por personal calificado solamente. El Código El éctrico Nacional define a una persona calificada como "una que esté familiarizada con la construcci ón y operación del equipo y con los riesgos involucrados."
Page ii
Page 3
PP 4300/Task 808
AVERTISSEMENT
Si l'instrument est mal connecté, la mort, des blessures graves, ou un danger d'incendie peuvent s'en suivre. Lisez attentivement ce manuel avant de connecter l'instrument. Lorsque vous utilisez l'instrument, suivez toutes les instructions d'installation et de service.
Cet instrument doit être connecté conformément au National Electrical Code (ANSI/NFPA 70-1996) des Etats-Unis et à toutes les exigences de sécurité applicables à votre installation.
Cet instrument doit être installé, utilisé et entretenu uniquement par un personnel qualifié. Selon le National Electrical Code, une personne est qualifiée si "elle connaît bien la construction et l'utilisation de l'équipement, ainsi que les dangers que cela implique.”
WARNUNG
Der falsche Anschluss dieses Gerätes kann Tod, schwere Verletzungen oder Feuer verursachen. Bevor Sie dieses Instrument anschliessen, müssen Sie die Anleitung lesen und verstanden haben. Bei der Verwendung dieses Instruments mü ssen alle Installation- und Betriebsanweisungen beachtet werden.
Der Anschluss dieses Instruments muss in Übereinstimmung mit den nationalen Bestimmungen für Elektrizität (ANSI/NFPA 70-1996) der Vereinigten Staaten, sowie allen weiteren, in Ihrem Fall anwendbaren Sicherheitsbestimmungen, vorgenommen werden.
Installation, Betrieb und Wartung dieses Instruments dürfen nur von Fachpersonal durchgeführt werden. In dem nationalen Bestimmungen für Elektrizität wird ein Fachmann als eine Person bezeichnet, welche "mit der Bauweise und dem Betrieb des Gerätes sowie den dazugehörigen Gefahren vertraut ist."
Page iii
Page 4
PP4300/Task 808
Page iv
Page 5
PP 4300/Task 808
Safety Summary
Definitions
WARNING statements inform the user that certain conditions or practices could result in loss of life or physical harm.
CAUTION statements identify conditions or practices that could harm the Power Platform, its data, other equipment, or property.
NOTE statements call attention to specific information.
Symbols
The following International Electrotechnical Commission (IEC) symbols are marked on the top and rear panel in the immediate vicinity of the referenced terminal or device:
!
Caution, refer to accompanying documents (this manual).
Direct current (DC) operation of the terminal or device.
Power Switch
Definiciones
Las ADVERTENCIAS informan al usuario de ciertas condiciones o prá cticas que podrían producir lesiones mortales o daño físico.
Las PRECAUCIONES identifican condiciones o prácticas que podrían dañar la Power Platform, sus datos, otros equipos o propiedad.
Las NOTAS llaman la atención hacia la información específica.
Page v
Page 6
PP4300/Task 808
Símbolos
Los siguientes símbolos de la Comisión Internacional Electrot écnica (IEC) aparecen marcados en el panel superior y el posterior inmediatos al terminal o dispositivo en referencia:
!
Precaución, consulte los documentos adjuntos (este manual).
Operación de corriente continua (CC) del terminal o dispositivo.
Interruptor de encendido
Définitions
Les messages d'AVERTISSEMENT préviennent l'utilisateur que certaines conditions ou pratiques pourraient entraîner la mort ou des lé sions corporelles.
Les messages de MISE EN GARDE signalent des conditions ou pratiques susceptibles d'endommager “Power Platform”, ses données, d'autres équipements ou biens mat ériels.
Les messages NOTA attirent l'attention sur certains renseignements spé cifiques.
Symboles
Les symboles suivants de la Commission électrotechnique internationale (CEI) figurent sur le panneau arrière supérieur situé à proximit é du terminal ou de l'unit é cité:
!
Mise en garde, consultez les documents d'accompagnement (ce
manual).
Fonctionnement du terminal ou de l'unit écourant continu (CC).
Interrupteur de tension
Definitionen
WARNUNGEN informieren den Benutzer darüber, daá bestimmte Bedingungen oder Vorgehensweisen körperliche oder tödliche Verletzungen zur Folge haben können.
Page vi
Page 7
PP 4300/Task 808
VORSICHTSHINWEISE kennzeichnen Bedingungen oder Vorgehensweisen, die zu einer Besch ädigung von Power Platform, seiner Daten oder anderer Geräte bzw. von Eigentum führen können.
HINWEISE machen auf bestimmte Informationen aufmerksam. Symbole
Die folgenden Symbole der Internationalen Elektrotechnischen Kommission (International Electrotechnical Commission; IEC) befinden sich auf der Abdeck- und Seitenplatte unmittelbar am betreffenden Terminal oder Gerät.
!
Vorsichtshinweis, siehe Begleitdokumente (dieses Handbuch).
Gleichstrombetrieb im Terminal oder Gerät.
Netzschalter
Safety Precautions
The following safety precautions must be followed whenever any type of connection is being made to the instrument.
o Connect the green safety (earth) ground first, before making any other
connections.
o When connecting to electric circuits or pulse initiating equipment, open
their related breakers. DO NOT install any connection of the instrument on live power lines.
o Connections must be made to the instrument first, then connect to the
circuit to be monitored.
o Wear safety glasses and insulated gloves when making connections to
power circuits.
o Hands, shoes and floor must be dry when making any connection to a
power line.
o Make sure the unit is turned OFF before connecting probes to the rear
panel.
o Before each use, inspect all cables for breaks or cracks in the
insulation. Replace immediately if defective.
Page vii
Page 8
PP4300/Task 808
Medidas de seguridad
Las medidas de seguridad siguientes deberán observarse cuando se realice cualquier tipo de conexión al instrumento.
o Antes de hacer cualquier conexión, deberá enchufarse el conector de
seguridad verde a tierra.
o Cuando se haga conexiones a circuitos eléctricos o a equipo de
activación por pulso, deberá abrirse sus respectivas cajas de seguridad. NO deberá hacerse ninguna conexión del instrumento en líneas eléctricas bajo tensión.
o Las conexiones deberán hacerse primero al instrumento y, luego, al
circuito a ser monitorizado.
o Al hacer conexiones a circuitos eléctricos, deberá utilizar anteojos y
guantes protectores.
o Sus manos, zapatos y el piso deberán estar secos en todo momento
en que se haga una conexión a un cable eléctrico.
o Verifique que la unidad esté DESACTIVADA antes de conectar
sondas en el panel posterior.
o Previo a cada uso, deberá verificarse que los cables no estén rotos y
que el material aislante no tenga rajaduras. Reemplace de inmediato cualquier parte defectuosa.
Mesures de Sécurité
Les mesures de sécurité suivantes doivent être prises chaque fois qu’un type de connexion quelconque est effectué sur l’instrument.
o Connecter d’abord la prise de terre de sécurité verte (terre) avant
d’effectuer toute autre connexion.
o Ouvrir les disjoncteurs correspondants lors d’une connexion à des
circuits électriques ou à des équipement de génération d’impulsions. NE PAS effectuer de connexion d’instrument sur des lignes électriques sous tension.
o Une fois toutes les connexions de l’instrument effectuées, connecter
au circuit à contrôler.
o Porter des lunettes de protection et des gants isolants pour effectuer
des connexions aux circuits électriques.
o S’assurer que les mains, les chaussures et le sol soient secs lors de
connexions à une ligne électrique.
o S’assurer que l’unité est ÉTEINTE avant de connecter les sondes au
panneau arrière.
o Inspecter tous les câbles, avant chaque utilisation, pour s’assurer que
les isolants ne sont pas coupés ou fendus. Remplacer immédiatement tous les équipements défectueux.
Page viii
Page 9
PP 4300/Task 808
Sicherheitsvorkehrungen
Die folgenden Sicherheitsvorkehrungen sind immer dann zu befolgen, wenn eine Verbindung zum Instrument hergestellt wird.
o Schließen Sie zuerst die grüne Sicherheits-/Erdleitung an, bevor Sie
eine andere Verbindung herstellen.
o Öffnen Sie beim Anschluß an elektrische Stromkreise oder
Impulsauslösungseinrichtungen die entsprechenden Unterbrecher. Es dürfen KEINE Anschlüsse an das Instrument unter stromführenden Spannungsleitungen montiert werden.
o Die Verbindungen müssen zuerst am Instrument und danach an der zu
überwachenden Schaltung hergestellt werden.
o Tragen Sie Schutzbrillen und Isolierhandschuhe, wenn Sie Anschlüsse
an den Stromkreisen vornehmen.
o Hände, Schuhe und Fußboden müssen trocken sein, wenn Sie
Anschlüsse an den Stromkreisen durchführen.
o Stellen Sie sicher, daß das Gerät AUSgeschaltet ist, bevor Sie an der
rückwärtigen Konsole Meßfühler anschließen.
o Prüfen Sie vor jedem Gebrauch alle Kabel auf Bruchstellen und Risse
in der Isolierung. Wechseln Sie schadhafte Kabel sofort aus.
Page ix
Page 10
PP4300/Task 808
Statements and Notices
Notice regarding proprietary rights
This publication contains information proprietary to Dranetz-BMI. By accepting
and using this manual, the user agrees that the information contained herein will be used solely for the purpose of operating equipment of Dranetz-BMI.
Copyright
This publication is protected under the copyright laws of the United States Title 17 et seq. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form, by any means, electronic, mechanical, magnetic, optical, chemical, manual or otherwise, without the prior written consent of Dranetz-BMI, 1000 New Durham Road, Edison, New Jersey
08818. Copyright © 1997, Dranetz-BMI
All Rights Reserved. Printed in the United States of America.
Revision rights
Dranetz-BMI reserves the right to revise this publication from time to time and to make changes in its content without any obligation of notifying previous users of such revisions or changes.
Trademarks
Power Platform, TASKCard, Scope Mode, DRAN-LINK, DRAN-VIEW and Task 808 are registered trademarks of Dranetz-BMI.
Statement of reliability
The information in this manual has been reviewed and is believed to be entirely reliable, however, no responsibility is assumed for any inaccuracies. All material is for informational purposes only and is subject to change without prior notice.
Continued on next page
Page x
Page 11
PP 4300/Task 808
Statements and Notices, continued
Statement of warranty
All products of Dranetz-BMI are warranted to the original purchaser against defective material and workmanship for a period of one year from the date of delivery. Dranetz-BMI will repair or replace, at its option, all defective equipment that is returned, freight prepaid, during the warranty period. There will be no charge for repair provided there is no evidence that the equipment has been mishandled or abused. This warranty shall not apply to any defects resulting from improper or inadequate maintenance, buyer-supplied hardware/software interfacing, unauthorized modification or misuse of the equipment, operation outside of environmental specifications, or improper site preparation or maintenance.
Notice regarding FCC compliance
This device has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his/her own expense.
Page xi
Page 12
PP4300/Task 808
TABLE OF CONTENTS
SAFETY SUMMARY......................................................................................V
CHAPTER 1 GETTING STARTED..............................................................1
1.1 Introduction..............................................................................................1
1.2 Unpack The PP4300...............................................................................1
1.3 Check Contents......................................................................................2
1.3.1 Standard Accessories.......................................................................2
1.3.2 Inspect for Damage............................................................................2
1.3.3 Return Shipment.................................................................................2
CHAPTER 2 INTRODUCTION TO THE PP4300/TASK 808..................3
2.1 PP4300.......................................................................................................3
2.2 The Task 808 Application.....................................................................3
2.2.1 Task 808 Model Options ...................................................................3
2.2.2 Task 808 Power Circuit Configurations...........................................4
2.2.4 EASY START
TM
Feature...................................................................5
2.2.5 DRAN-LINK and DRAN-VIEW..........................................................5
2.2.6 Memory Cards (optional)...................................................................5
CHAPTER 3 HARDWARE OVERVIEW.....................................................7
3.1 PP4300.......................................................................................................7
3.1.1 Front and Bottom Panels...................................................................9
3.1.2 Top, Right and Left Panels.............................................................10
3.1.3 Back Panel.......................................................................................11
3.1.4 PP4300 Power Requirements.......................................................11
3.2 The Task 808.........................................................................................12
3.2.1 TASKCard Installation ......................................................................12
CHAPTER 4 TOURING THE TASK 808.................................................15
4.1 Preparing for the Guided Tours…...................................................15
4.2 Screen layout........................................................................................15
Page xii
Page 13
PP 4300/Task 808
4.3 Navigation Tips.....................................................................................16
4.3.1 Using SOFTKeys.............................................................................16
4.3.2 Numbered Options ..........................................................................17
4.3.3 Highlight Bar.....................................................................................17
4.4 Data Entry..............................................................................................18
4.4.1 Alphabetic Entry...............................................................................18
4.4.2 Numeric Entry...................................................................................18
4.5 Help Screens.........................................................................................18
CHAPTER 5 EASY START TOUR...........................................................21
5.1 Prepare the PP4300..............................................................................22
5.2 Connect the probes..............................................................................22
5.3 Power ON the PP4300.........................................................................23
5.4 Easy Start -- Configure/Monitor........................................................25
5.5 Viewing Data/Reports.........................................................................31
5.5.1 Viewing Scope Mode.......................................................................31
5.5.2 Viewing in Meter Mode....................................................................32
CHAPTER 6 ADVANCED TOUR.............................................................35
6.1 Setup Menu...........................................................................................36
6.1.1 Easy Start..........................................................................................36
6.1.2 Set Programmable Features...........................................................36
6.1.3 Turn Monitoring ON/OFF..................................................................38
6.1.4 Memory Functions ...........................................................................38
6.1.5 Set Input Configurations..................................................................45
CHAPTER 7 REPORTING TOUR............................................................53
7.1 View Data...............................................................................................54
7.2 Meter Mode............................................................................................64
7.3 Viewing Harmonics..............................................................................68
7.4 Screen Printing.....................................................................................69
APPENDIX A PRODUCT SUPPORT......................................................71
Page xiii
Page 14
PP4300/Task 808
A.1 Telephone Support..............................................................................71
A.2 Fax Line..................................................................................................71
A.3 World Wide Web...................................................................................71
A.4 Technical support email address....................................................71
APPENDIX B MAINTENANCE/SERVICING/RETURN SHIPMENT..73
B.1 Maintenance/Servicing.......................................................................73
B.1.1 Internal Battery Pack Replacement................................................73
B.1.2 Calibration........................................................................................77
B.3 Return Shipment..................................................................................77
B.3.1 Shipping Address............................................................................78
APPENDIX C OPTIONAL ACCESSORIES............................................79
C.1 Introduction..........................................................................................79
C.2 Optional Accessories List.................................................................79
C.2.1 Optional Accessories Descriptions...............................................80
C.3 Ordering information..........................................................................84
APPENDIX D PP4300 TECHNICAL SPECIFICATIONS.....................85
D.1 Overview.................................................................................................85
D.1.1 Dimensions ......................................................................................86
D.1.2 Environmental ...................................................................................86
D.1.3 System Time Clock.........................................................................86
D.1.4 Memory.............................................................................................86
D.1.5 Memory Card...................................................................................86
D.1.6 Power Requirements.......................................................................86
D.1.7 Input Resistance...............................................................................87
D.1.8 Installation Categories.....................................................................87
D.2 Interfaces...............................................................................................87
D.2.1 Display..............................................................................................87
D.2.2 Alarm.................................................................................................87
D.3 Measured Parameters........................................................................87
D.3.1 Voltage..............................................................................................87
D.3.2 Current..............................................................................................88
Page xiv
Page 15
PP 4300/Task 808
D.3.3 Phase................................................................................................88
D.3.4 Frequency.........................................................................................88
D.3.5 Environmental...................................................................................88
D.4 Computed Parameters.......................................................................89
D.4 1 Update Rate .....................................................................................89
D.4.2 ABC Volts.........................................................................................89
D.4.3 ABC Amps........................................................................................89
D.4.4 Real Power.......................................................................................89
D.4.5 Apparent Power...............................................................................90
D.4.6 Reactive Power................................................................................90
D.4.7 Environmental...................................................................................90
D.5 Resetting the PP4300 to the Factory Configuration..................91
D.5.1 Configurations..................................................................................91
APPENDIX E CONNECTING PROBES/COMMON CIRCUIT
CONNECTIONS ............................................................................................93
E.1 Making Voltage Connections...........................................................93
E.1.1 Safety Precautions..........................................................................95
E.1.2 Connection guidelines....................................................................98
E.1.3 Single phase connection example ................................................98
E.1.4 Neutral to ground connection example........................................100
E.2 Connecting a Current Probe..........................................................101
E.2.1 Safety Precautions........................................................................101
E.2.2 Available probes...........................................................................102
E.2.3 Reference to Channel Input..........................................................103
E.2.4 Connection Guidelines.................................................................104
E.2.5 Single phase current probe example..........................................104
E.3 Common Circuit Connections.......................................................105
E.3.1 Overview ..........................................................................................105
E.3.2 Safety Precautions.........................................................................105
E.3.3 Voltage and current connections..................................................107
E.3.4 Phasor diagrams............................................................................107
E.3.5 Verifying Voltage and Current Connections................................108
E.4 Single Phase.......................................................................................111
E.4.1 Introduction......................................................................................111
E.4.2 Connection diagram......................................................................111
E.4.3 Single Phase Phasor Diagrams...................................................111
E.5 Split Phase..........................................................................................112
Page xv
Page 16
PP4300/Task 808
E.5.1 Introduction ......................................................................................112
E.5.2 Connection diagram......................................................................112
E.5.3 Split Phase Phasor Diagrams......................................................112
E.6 Open Leg Delta..................................................................................113
E.6.1 Introduction ......................................................................................113
E.6.2 Connection diagram......................................................................113
E.6.3 Open Leg Delta Phasor Diagrams..............................................114
E.7 Four Wire Wye....................................................................................115
E.7.1 Introduction ......................................................................................115
E.7.2 Connection diagram......................................................................115
E.7.3 Four Wire Wye Phasor Diagrams................................................116
E.8 High-Leg Delta...................................................................................117
E.8.1 Introduction ......................................................................................117
E.8.2 Connection diagram......................................................................117
E.8.3 High Leg Delta Phasor Diagrams................................................118
E.9 Floating or Grounded Delta............................................................119
E.9.1 Introduction ......................................................................................119
E.9.2 Connection diagram......................................................................119
E.9.3 Floating or Grounded Delta Phasor Diagrams...........................120
E.10 Two-and-a-half Element................................................................121
E.10.1 Introduction...................................................................................121
E.10.2 Connection Diagram...................................................................121
E.10.3 Two-and-a-half Element Phasor Diagrams..............................122
E.11 Connecting to PTs and CTs.........................................................123
E.12 Connecting to a Potential Transformer (PT)............................124
E.12.1 Definition .......................................................................................124
E.12.2 Connections .................................................................................124
E.12.3 Procedure.....................................................................................125
E.12.4 Scale factor..................................................................................125
E.13 Connecting to a Current Transformer (CT)..............................125
E.13.1 Safety Precautions ......................................................................125
E.13.2 Description...................................................................................127
E.13.3 Types of CTs................................................................................127
E.14 Connecting to an Isolated Current Transformer (ISO)..........127
E.14.1 Introduction...................................................................................127
E.14.2 Safety Precautions ......................................................................127
E.14.3 Connections to ISO box..............................................................129
Page xvi
Page 17
PP 4300/Task 808
E.14.4 Applications..................................................................................129
E.14.5 ISO box connection to a current transformer.............................129
APPENDIX F MEMORY CARD FUNCTIONS......................................131
F.1 Memory Card Battery Replacement...............................................131
F.1.1 Introduction......................................................................................131
F.1.2 Battery check..................................................................................132
F.1.3 Battery types...................................................................................132
F.1.4 Battery Safety Precautions............................................................132
F.1.5 Replacement procedure................................................................134
F.2 Memory Card Formatting..................................................................135
F.2.1 Memory Card..................................................................................135
F.2.2 Memory Card Formatting Procedure...........................................135
APPENDIX G OPERATOR-REPLACEABLE PARTS........................137
G.1 Introduction........................................................................................137
G.2 To order parts.....................................................................................137
G.3 Parts List..............................................................................................137
APPENDIX H SYSTEM MESSAGES (PP4300)...................................139
H.1 Introduction........................................................................................139
H.2 Message Types..................................................................................139
H.2.1 Overview ..........................................................................................139
H.2.2 One-line messages........................................................................139
H.2.3 Full screen messages....................................................................139
H.3 Messages............................................................................................141
H.3.1 One-line messages........................................................................141
H.3.2 Full screen message......................................................................141
H.4 TASKCard error messages.............................................................142
INDEX...........................................................................................................143
Page xvii
Page 18
PP4300/Task 808
About this Manual…
The objectives pursued in designing and writing this manual were twofold:
1) to provide easy-to-follow, step-by-step “how to” instructions for first­time users of the Power Platform 4300 with the Task 808, and
2) to provide more experienced users with comprehensive reference documentation presented in an easy-to-find format.
Although the PP4300/Task 808 offers many powerful features, it is not a complicated instrument. Learning to use the Task 808 should not be complicated either. This manual incorporates structure, layout, fonts, graphics and lean prose – all designed to make this learning process as quick and as helpful as possible.
Organization
Basically, the information in this manual is organized into three major segments:
Chap 1 - 4 Introductory “getting started” material Chap 5 - 7 Guided Tour material, featuring three tours:
Easy Start Tour Advanced Tour Reporting Tour
Appendices -Reference material – lots of details
Page xviii
Page 19
Chapter 1 Getting Started
TASK 808
Chapter 1 Getting Started
1.1 Introduction
The Task 808 is one of a series of TASKCard-based applications from Dranetz-BMI. The Power Platform 4300 serves as the hardware platform for various applications, each of which is stored on PCMCIA-compatible memory cards called TASKCards. Optional memory cards are available for supplementary data storage.
Task 808 applications include: o Demand and energy surveys
o Power Factor studies o General three phase volt-ammeter measurements o Performance qualification o Sub-metering o Power use trends establishment o Metering/utility meter verification o Nameplate data certification o Detection of overloaded feeders o Tracking facility efficiency vs. production output o Transformer and neutral conductor derating
1.2 Unpack The PP4300
Open the carton carefully. Check the carton inventory and inspect the contents for possible shipping damage.
o Remove all literature, including warranty card o Remove the PP4300 from the carton o Remove all accessories from the carton
NOTE - You may wish to save packing cartons and materials to use in the event return shipment is required at some future date (for calibration, etc.).
Page 1
Page 20
Chapter 1 Getting Started
TASK 808
1.3 Check Contents
Check that the PP4300 and all of the standard accessories are included:
1.3.1 Standard Accessories
Description Part Number
AC Adapter/Battery Charger 116297-G1 Cable Pouch 116043-G1 Carrying Strap 116040-G1 Easel 116038-G1 Measurement Cable Set, w/Alligator Clips 116042-G1 User’s Guide OM-4300-TASK808 *Power Cord, Shielded, 115 Vac 110893-G1 *Power Cord, Shielded, 230 Vac (Euro) 115369-G1 *Power Cord, Shielded, 230 Vac (UK) 115368-G1 TASKCard 808 M (or H-M) TASK808M, or
TASK808/H/M Wire Marker Set 155520 *User specified, one standard only.
n Refer to Appendix C for a complete listing of optional accessories for the Task 808. Make sure all optional accessories ordered are included in the package. If any items are missing, contact the Dranetz-BMI Customer Service Department.
1.3.2 Inspect for Damage
Visually inspect the PP4300 and all accessories for any shipping damage. If unit has been damaged in any way, first notify and file an insurance claim with your carrier or underwriter or both.
1.3.3 Return Shipment
n Refer to Appendix B Maintenance/Servicing/Return Shipment for
important instructions regarding return shipment of any damaged items.
Page 2
Page 21
Chapter 2 Introduction
TASK 808
Chapter 2 Introduction to the PP4300/Task 808
The Task 808 is a TASKCard-based PP4300 application. The patented TASKCard is a removable flash memory card that is installed in the PP4300 and contains an operating system designed for a specific application (task).
2.1 PP4300
The Dranetz-BMI Power Platform 4300 is a portable, hand-held, TASKCard based, eight-channel power meter/monitor. The PP4300 is
capable of monitoring, recording and displaying data for four voltage and four current channels simultaneously.
n Refer to Chapter 3 Hardware Overview for illustrations and detailed descriptions of the various controls, indicators, and connectors.
2.2 The Task 808 Application
The Task 808 is an application designed primarily for long-term demand and energy surveys. It is intended for use by electrical facilities plant personnel (engineers as well as electricians), energy management consultants and utility marketing services groups.
2.2.1 Task 808 Model Options
Two Task 808 models are available: the 808/M (Memory ) with expandable memory and the 808/H-M (Harmonics-Memory).
NOTE - Any model-specific differences in descriptions or procedures will be documented throughout this manual.
Task 808 - model M
This model (808/M) provides all standard features, including 256K internal memory , plus memory card storage capability. Optional memory cards are available in various capacities, shown in Appendix C.
Page
3
Page 22
Chapter 2 Introduction
TASK 808
Task 808 - model H-M
In addition to all standard features, including 256K internal memory and memory card storage capability, this model (808/H-M) provides harmonics data, useful for determining the source and level of the effects created, e.g., by the many energy conservation devices in use today, such as electronic lighting ballasts and adjustable speed drives.
2.2.2 Task 808 Power Circuit Configurations
When TASKCard 808-equipped, the PP4300 can monitor any of the following power circuit configurations:
o Single phase o Split phase o Four wire wye o Floating or grounded delta o Open leg delta o High leg delta o Two-and-a-half element
• WARNING: Refer to Appendix E Connecting Probes/Common
Circuit Connections for detailed descriptions of common power monitoring configurations and probe connections.
• ADVERTENCIA: Consulte el Apéndice E Conexión de
sondas/Conexión de circuitos comunes para obtener descripciones detalladas sobre configuraciones comunes de monitorización eléctrica y conexiones de sondas.
• AVERTISSEMENT: Se reporter à l’Annexe E, Connexion des
sondes / Connexions simples des circuits, pour de plus amples détails concernant les configurations de contrôle de puissance et les connexions des sondes.
• WARNUNG: Im Anhang E “Meßfühler verbinden/ Gängige
Schaltverbindungen” finden Sie ausführliche Beschreibungen von gängigen Konfigurationen der Spannungsüberwachung und von Meßfühlerverbindungen.
While monitoring any of the above configurations (except the three delta configurations), the PP4300 can also be connected to monitor neutral-to­ground voltage and neutral or ground current.
Page 4
Page 23
Chapter 2 Introduction
TASK 808
2.2.4 EASY START
TM
Feature
Both Task 808 versions come equipped with the EASY START feature which prompts users for a few key items of information about the circuit being monitored. EASY START programmatically steps the user through the implementation of a basic setup. The system automatically turns on the correct channel(s) and begins monitoring.
2.2.5 DRAN-LINK and DRAN-VIEW
The PP4300/Task 808 can transfer recorded data to a personal computer for subsequent analysis by DRAN-VIEW (PC software for graphic display of Task 808 data) using either an optional memory card reader or optional isolated communications adapter and DRAN-LINK.
n Refer to Appendix C Optional Accessories for a description of these
options.
2.2.6 Memory Cards (optional)
An optional memory card may be used with the PP4300 to provide a removable, rugged, compact, solid state mass storage device. Memory cards are used to store events and setups.
Memory cards use low power and have an internal battery for data retention. Various capacities are available, see Appendix C.
The PP4300 treats memory cards much like PCs treat floppy disks, storing files in a DOS format.
n Refer to Chapter 6 Advanced Tour for a complete overview of memory functions.
Page
5
Page 24
Page 25
Chapter 3 Hardware Overview
TASK 808
Chapter 3 Hardware Overview
This chapter illustrates and describes the key hardware features of the Power Platform 4300 and the TASKCard 808.
3.1 PP4300
The PP4300 is a self-contained, portable instrument weighing less than 4 pounds and measuring 8" (20.3 cm) high by 12" (30.5 cm) wide by 2.5" (6.4 cm) deep.
The front panel contains the display area, SOFTKeys and keypad. The bottom panel contains two slots: one (on the left) for a TASKCard and one (on the right) for an optional memory card.
The top panel contains the input voltage and current connectors. The left and right side panels contain the optical interface port and AC adapter/dc input connector, respectively, along with rings for attaching the supplied carrying strap.
Page
7
Page 26
Chapter 3 Hardware Overview
TASK 808
Front and Bottom Panels
Page 8
Page 27
Chapter 3 Hardware Overview
TASK 808
3.1.1 Front and Bottom Panels
The illustration on the facing page references the following items: 1 Liquid Crystal Display (LCD). Provides 240 by 128 pixels (dots) of text
and graphic information. Has electroluminescent (EL) backlighting for low light level viewing.
2 Numeric keypad. Consists of keyboard keys 0 through 9 and decimal
point (.) Permits menu selection and numerical data entry.
3 Question mark key. Displays Help screen with reference to screen
displayed at any time.
4 LCD contrast adjustment key. Symbol: Press and hold for
continuous contrast range change, release to stop. Press and quickly release for incremental contrast change.
5 Battery charge indicator. LED glows continuously while battery is
charging and flashes when fully charged. Symbol:
6 ON/OFF Power Key. Symbol: Push for ON, push for OFF
7 Memory (data) card slot. 8 Memory card release. Ejects memory card. 9 TASKCard release. Ejects TASKCard. 10 TASKCard slot. 11 SOFTKeys. Six keys used to select options that appear on bottom of
screen. Function selected varies with screen displayed.
Page
9
Page 28
Chapter 3 Hardware Overview
TASK 808
3.1.2 Top, Right and Left Panels
4300 - 18A
Top panel connectors, from left to right (1 through 12), as shown above:
1 CH A, + Differential Voltage Input Connector; red 2 CH A, - Differential Voltage Input Connector; white 3 CH A, PROBE, Current Input Connector 4 CH B, + Differential Voltage Input Connector; yellow 5 CH B, - Differential Voltage Input Connector; white 6 CH B, PROBE, Current Input Connector 7 CH C, + Differential Voltage Input Connector; blue 8 CH C, - Differential Voltage Input Connector; white 9 CH C, PROBE, Current Input Connector 10 CH D, + Differential Voltage Input Connector; gray 11 CH D, - Differential Voltage Input Connector; white 12 CH D, PROBE, Current Input Connector
Side panel connector/port, (13 and 14), as shown above:
13 AC Adapter/Bat tery Charger DC Input Connector 14 Optical Serial Data Port
Page 10
Page 29
3.1.3 Back Panel
Chapter 3 Hardware Overview
TASK 808
3.1.4 PP4300 Power Requirements
The PP4300 can be operated using either its internal battery pack or the AC Adapter/Battery Charger. Always charge the battery fully before use. The PP4300 will always operate with the AC Adapter/Battery Charger, regardless of the state of charge of the battery.
Charging Battery
Charge the battery pack by connecting the AC adapter output cable to the DC INPUT connector on the right side of the PP4300. Connect the AC adapter power cord to an appropriate outlet. A depleted battery pack can be recharged in 2 hours with the unit OFF and 24 hours with the unit on. The battery charge indicator glows continuously while charging and flashes when fully charged. The indicator light functions only when the unit is turned off and the AC adapter is properly connected.
Page
11
Page 30
Chapter 3 Hardware Overview
TASK 808
Length of operation
The PP4300 can operate on a fully charged battery pack for up to four hours. A screen warning will appear during operation when battery charge is low.
AC Power
The PP4300 can be operated from a 50/60 Hz VAC power source using the AC adapter, with or without the battery pack installed.
3.2 The Task 808
3.2.1 TASKCard Installation
Follow these simple steps to install the Task 808 TASKCard.
Step 1 Make sure that the PP4300 is powered OFF. I f already ON,
press the PP4300 ON/OFF power key to turn unit OFF.
Step 2 Remove TASKCard from its protective holder and check that
the plug end of card is clean and free of any obstruction.
Page 12
Page 31
Chapter 3 Hardware Overview
TASK 808
If plug end of card is dirty, clean with static-free, dry, low pressure air to remove any foreign material causing obstruction of the plug holes.
Step 3 Verify that the write protect switch (end opposite plug end) is
set to the write protect position. Use a pencil point to move the switch to correct position, if required.
Step 4 At the bottom of the unit, position the TASKCard with the label
facing front and the plug end facing the TASK CARD slot in the PP4300.
Step 5 Insert the card fully into the slot until resistance is felt, then press
firmly until card engagement is felt.
NOTE - Do not force the card into the slot if no card engagement is felt. Remove card and check that there is no foreign object on or in the plug end of the card. Remove any obstruction. Reinsert card and repeat card engagement process. If card cannot be engaged, call Dranetz-BMI Customer Service for instructions.
n Refer to Appendix H System Messages for description of TASKCard
Error Messages which may be displayed when the unit is powered ON.
Page
13
Page 32
Page 33
Chapter 4 Touring the Task 808
TASK 808
Chapter 4 Touring the Task 808
4.1 Preparing for the Guided Tours…
Before jumping into the setup and operation of the Task 808, it is well worth taking a minute or two to review a few simple preliminaries which will help you get started when you begin the Guided Tours.
4.2 Screen layout
All of the Task 808 screens have common elements, such as the following: Date Time
Oct-17-96 18:34:45
CIRCUIT TYPE
SINGLE PHASE
SINGLE SPLIT 3PHASE 3PHASE 2-1/2
PHASE PHASE DELTA WYE ELEMNT EXIT
Display Area
Reverse Highlight Text Instructions (SOFTKeys)
Page
15
Page 34
Chapter 4 Touring the Task 808
TASK 808
In addition, whenever a graph is displayed, the vertical axis (and scale) for Volts will always be the left axis and the vertical axis (and scale) for Amps will always be the right axis, as shown below:
VOLTS AMPS
4.3 Navigation Tips
Navigation (moving from screen to screen) is accomplished in two ways:
1) Using SOFTKeys, sometimes in conjunction with the highlight bar, and
2) Selecting from numbered options.
4.3.1 Using SOFTKeys
The six keys on the PP4300 immediately below the display area are called SOFTKeys and are used to execute the reverse highlight text instruction (such as, SELECT CHAN, METER MODE, SETUP) displayed immediately above each key.
Some SOFTKeys move the highlight from field to field within the display area while other SOFTKeys are used to advance from screen to screen. Other SOFTKeys perform operations, such as, turning features ON and OFF.
NOTE - Throughout this manual, references to SOFTKeys and their corresponding instructions will be combined into a single phrase, e.g., press the EXIT SOFTKey.
Page 16
Page 35
Chapter 4 Touring the Task 808
TASK 808
4.3.2 Numbered Options
Several screens consist of a list of numbered options. Simply press the corresponding key on the PP4300’s numeric key pad to execute the desired option, e.g., press the 1 key on the “Setup” menu to select Easy Start:
Jan-17-97 18:34:45
SETUP MENU
1. EASY START
2. SET PROGRAMMABLE FEATURES
3. TURN MONITORING OFF
4. MEMORY FUNCTIONS
5. SET INPUT CONFIGURATIONS
SCOPE METER HAR- VIEW
MODE MODE MONICS DATA
4.3.3 Highlight Bar
Many screens consist of a highlight bar and a list of options with associated values. SOFTKeys are used to highlight, toggle and select values.
Jan-17-97 18:34:45
CHANNEL SELECTION
CHANNEL VOLTS AMPS
A ON ON
B ON ON C ON ON D ON ON
NEXT VOLTS AMPS CHAN ON/OFF ON/OFF EXIT
In the example above, the NEXT CHAN SOFTKey is used to highlight and select channels. The VOLTS ON/OFF and AMPS ON/OFF SOFTKeys are used to toggle between ON and OFF. The EXIT SOFTKey will implement the selection.
Page
17
Page 36
Chapter 4 Touring the Task 808
TASK 808
4.4 Data Entry
There are two different methods for manually entering data, depending on whether the data is alphabetic or numeric.
4.4.1 Alphabetic Entry
Alphabetic data must be entered to record the site/file name. Alphabetic data is entered using the special alphabetic entry screen shown below which will automatically be displayed when required:
The arrow SOFTKeys are used to highlight desired letters (and SPACE, BACKSPACE, DELETE ALL). The ENTER SOFTKey moves highlighted letters into the small text window at the top of the display area until the site/file name is completed.
4.4.2 Numeric Entry
Integers (whole numbers) must be entered to record dates, times and demand intervals. Decimals may be entered to record scale factors, sync parameters, vertical scales and to describe the application. Integers and decimals are entered using the numeric keys and the decimal point on the PP4300’s numeric key pad.
4.5 Help Screens
Help screens are available for every screen in the application. Simply press the ? key (question mark key) on the numeric keypad and help for the active screen will be displayed.
Page 18
Page 37
Chapter 4 Touring the Task 808
TASK 808
On to the Guided Tours...
Now that the preliminaries are completed, continue with the Guided Tours chapters to begin hands-on operation of the Task 808.
Chapters five, six and seven are designed to take the user step by step through the complete setup and operation of the PP4300/Task 808:
Chapter 5 Easy Start Tour - designed to
implement a quick, no-frills setup using the programmed EASY START feature.
Chapter 6 Advanced Tour - designed to
implement a more sophisticated setup by building on the Easy Start setup.
Chapter 7 Reporting Tour - designed to
document the wide array of reporting features in the Task 808.
Recommendation
It is recommended that all three of the guided tours be taken, starting with the Easy Start Tour.
Page
19
Page 38
Page 39
Chapter 5 EASY START Tour
The Easy Start Tour covers the following topics:
5.1 Prepare the PP4300
5.2 Connect the Probes
5.3 Power ON the PP4300
5.4 Easy Start -- Configuring/Monitoring
5.5 Viewing Data/Reports
Chapter 5 Easy Start Tour
TASK 808
Page
21
Page 40
Chapter 5 Easy Start Tour
TASK 808
5.1 Prepare the PP4300
Step 1 Insert the Task 808 TASKCard into the PP4300’s TASKCard slot.
n Refer to Chapter 3 Hardware Overview for complete TASKCard installation instructions.
Step 2 Insert a formatted memory card (if applicable) into the PP4300’s memory card slot.
n Refer to Appendix F Card Functions for complete memory card installation and formatting instructions.
Step 3 Connect the AC adapter output cable to the DC INPUT connector on the right side of the PP4300. Connect the AC adapter power cord to an appropriate outlet.
5.2 Connect the probes
• WARNING: Refer to Appendix E Connecting Probes/Common
Circuit Connections for detailed descriptions of common power monitoring configurations and probe connections.
• ADVERTENCIA: Consulte el Apéndice E Conexión de
sondas/Conexión de circuitos comunes para obtener descripciones detalladas sobre configuraciones comunes de monitorización eléctrica y conexiones de sondas.
• AVERTISSEMENT: Se reporter à l’Annexe E, Connexion des
sondes / Connexions simples des circuits, pour de plus amples détails concernant les configurations de contrôle de puissance et les connexions des sondes.
• WARNUNG: Im Anhang E “Meßfühler verbinden/ Gängige
Schaltverbindungen” finden Sie ausführliche Beschreibungen von gängigen Konfigurationen der Spannungsüberwachung und von Meßfühlerverbindungen.
Before powering ON and initiating the Easy Start tour, the probes must be connected. Before connecting anything, make sure that the circuit to be
monitored has been de-energized.
Page 22
Page 41
Chapter 5 Easy Start Tour
TASK 808
5.3 Power ON the PP4300
Step 1 Press the ON/OFF power button on the front panel of the
PP4300 to turn the power ON. A screen with the results of self-diagnostic routines will be displayed
briefly during power up. All of the self-diagnostic routine results should read PASSED.
n Refer to Appendix H System Messages for description of TASKCard Error Messages which may be displayed when the unit is powered ON.
Step 2 Wait for the next screen to be displayed:
Page
23
Page 42
Chapter 5 Easy Start Tour
TASK 808
Depending on the PP4300 model in use, the message -- SELECT CURRENT PROBE(S)? -- may be displayed across the bottom of the screen, as a reminder, because correctly identified probe types and scale factors are essential to accurate computations.
The “Scope Mode” screen is a gateway to four major functions of the system: Meter Mode, Harmonics (available to Task 808/H-M model users only), View Data and Setup. The “Scope Mode” screen also acts as a home screen from which to branch to other functions of the Task 808.
NOTE - When the PP4300 is turned ON, it will always default to the configuration values in effect when the system was last powered OFF. Values for all eight channels will always be displayed initially on the “Scope Mode” screen. If the probes are changed while the unit is OFF, all monitored values will be erroneous until the probe and scale factor information is updated.
The message – MONITORING: OFF -- may be displayed across the top of this screen (and across all other screens as well). This message indicates that the PP4300 is not monitoring any circuits, i.e., not recording event data (however, the “Meter Mode,” “Scope Mode” and “Harmonics” screens will still function properly with monitoring OFF). In addition to the obvious, i.e., when the currently active configuration specifies that monitoring is OFF, this message may also be displayed briefly under such circumstances as saving a changed configuration or during the self test. While monitoring is ON, no message is displayed.
Setting the time and date will be covered in the Advanced Tour.
Page 24
Page 43
Chapter 5 Easy Start Tour
TASK 808
5.4 Easy Start -- Configure/Monitor
Easy Start guides the user step-by-step through a basic configuration process. The final step in the configuration process automatically initiates the circuit monitoring.
Step 1 From the “Scope Mode” screen, press the NO SOFTKey to defer selecting current probes until later on in the process. Press the SETUP SOFTKey to get started.
Jan-17-97 18:34:45
SETUP MENU
1. EASY START
2. SET PROGRAMMABLE FEATURES
3. TURN MONITORING OFF
4. MEMORY FUNCTIONS
5. SET INPUT CONFIGURATIONS
SCOPE METER HAR- VIEW
MODE MODE MONICS DATA
Step 2 At the “Setup Menu,” press the 1 key on the numeric pad to begin the Easy Start process.
The following message will be displayed:
Jan-17-97 18:34:45
CAUTION!
THE EASY START PROCESS WILL CHANGE PREVIOUSLY PROGRAMMED INSTRUMENT SETTINGS AND CONFIGURATIONS. MONITORING IS ALSO SHUT DOWN DURING EASY START PROGRAMMING. PRESS CANCEL IF YOU DO NOT WANT TO CHANGE EXISTING SETTINGS.
CON-
TINUE CANCEL
Page
25
Page 44
Chapter 5 Easy Start Tour
TASK 808
NOTE - The Guided Tours are designed for and are typically followed by users with new PP4300/Task 808 units. If the Task 808 is currently collecting data, you may wish to reschedule these tours when the Task 808 is idle.
Press the CONTINUE SOFTKey to display a list of circuit types.
Step 3 Select the desired circuit type by pressing the appropriate SOFTKey.
Jan-17-97 18:34:45
CIRCUIT TYPE
3 PHASE DELTA
SINGLE SPLIT 3PHASE 3PHASE 2-1/2
PHASE PHASE DELTA WYE ELEMNT CANCEL
The following safety message will be displayed:
Jan-17-97 18:34:45
*** WARNING ***
IMPROPER CONNECTION OF THIS INSTRUMENT COULD RESULT IN THE LOSS OF LIFE PHYSICAL HARM, OR A FIRE HAZARD. ALSO CONNECTION OF THIS INSTRUMENT MUST BE PERFORMED IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE (ANSI/NFPA 70-1996) OR ANY OTHER ADDITIONAL SAFETY REQUIREMENTS APPLICABLE TO YOUR INSTALLATION. NEXT **Continued On Next Screen SCREEN CANCEL
Press the NEXT SCREEN SOFTKey to continue. Another safety message will be displayed:
Jan-17-97 18:34:45
Page 26
Page 45
Chapter 5 Easy Start Tour
TASK 808
*** WARNING ***
INSTALLATION, OPERATION, AND MAINTEN­ ANCE OF THIS INSTRUMENT MUST BE PERFORMED ONLY BY QUALIFIED PERSONNEL. THE NATIONAL ELECTRICAL CODE DEFINES A QUALIFIED PERSON AS ONE FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE EQUIPMENT AND THE HAZARDS INVOLVED.
NEXT
SCREEN CANCEL
Step 4 Press the NEXT SCREEN SOFTKey. A circuit diagram will be displayed showing how to connect the voltage and current probes for the circuit type previously selected.
The purpose of this screen is to enable users to verify that all probes have been connected properly. If not connected properly, power OFF the PP4300 immediately. Make any necessary changes to the connections, and start the tour over again at 5.3 Power ON the PP4300.
Step 5 Press the NEXT SCREEN SOFTKey. The “Current Probes” screen will be displayed.
Jan-17-97 18:34:45
Page
27
Page 46
Chapter 5 Easy Start Tour
TASK 808
CURRENT PROBES
CHANNEL PROBE TYPE A TR2500 B TR2500 C TR2500 D TR2500
NEXT NEXT NEXT CHAN PROBE SCREEN CANCEL
Use the NEXT CHAN SOFTKey to highlight channels and the NEXT PROBE SOFTKey to toggle through the available current probe types.
Specify the probe type for each channel to be monitored (or NONE if the channel will not be monitored). Press the NEXT SCREEN SOFTKey when finished with the “Current Probes” screen.
Jan-17-97 18:34:45
ENTER SITE/FILE NAME
PRESENT SITE/FILE NAME: CHILLER
NOTE: THE SITE/FILE NAME WILL BE USED TO NAME FILES STORED ON THE MEMORY CARD.
ENTER NEXT
NAME SCREEN CANCEL
Step 6 Press the ENTER NAME SOFTKey to display the alphabetic entry screen for entry of the site/file name (or press the NEXT SCREEN SOFTKey if the site/file name already exists and is OK).
Page 28
Page 47
Chapter 5 Easy Start Tour
TASK 808
NOTE - The site/file name is important for two reasons: 1) it identifies the site where the data was collected, and 2) it becomes the name of the file created when the data is saved. Although up to 20 characters may be used in the name, only the first eight will be used for the file name.
Use the special alphabetic data entry screen shown below to enter the site/file name:
The arrow SOFTKeys are used to highlight desired letters. The ENTER SOFTKey moves highlighted letters into the small text window at the top of the display area until the site/file name is completed. Use the numeric keypad for numbers.
Press the EXIT SOFTKey when finished. The “Enter Site/File Name” screen will be displayed again.
Press the NEXT SCREEN SOFTKey to continue:
Page
29
Page 48
Chapter 5 Easy Start Tour
TASK 808
Jan-17-96 18:34:45
CLEAR EVENT MEMORY & START MONITORING
- IF CLEAR IS PRESSED, ALL DATA PRESENTLY IN MEMORY WILL BE ERASED.
- IF ADD IS PRESSED, NEW DATA WILL BE ADDED TO WHAT IS ALREADY STORED IN MEMORY.
CLEAR ADD CANCEL
Step 7 Press one of the following SOFTKeys: CLEAR to clear memory and start collecting event data.
ADD to add new events to those already stored in
memory.
CANCEL to quit without changing anything. If CLEAR or ADD is selected, circuit monitoring will begin. The “Easy
Start Summary” screen will be displayed, summarizing the configuration which has just been defined:
Jan-17-96 18:34:45
EASY START SUMMARY CIRCUIT TYPE: 3 PHASE DELTA PROBES: CHAN A TR2500 CHAN B TR2500 CHAN C TR2500 CHAN D NONE SITE NAME: CHILLER DATABASE: CLEAR ** PRESS OK TO ACCEPT SETTINGS ** PRESS CANCEL TO DISREGARD SETTINGS
OK CANCEL
Step 8 Complete the EASY START configuration process by pressing either the OK or the CANCEL SOFTKey:
Page 30
Page 49
Chapter 5 Easy Start Tour
TASK 808
If the
configuration is… Then…
OK Press the OK SOFTKey to save the
configuration.
Not OK Press the CANCEL SOFTKey to quit or start the
EASY START process over again from the beginning (without saving the configuration settings). The “Scope Mode” screen will be displayed.
5.5 Viewing Data/Reports
Once monitoring is ON and data is being collected, user interest naturally shifts from monitoring the data to viewing the data.
A wealth of viewing options and data formats is available from the “Scope Mode” screen to display the data being collected, including:
o The “Scope Mode” waveform o The “Meter Mode” data display o The “Harmonics” graphic and text displays o The four reporting options from the “View Data” menu
5.5.1 Viewing Scope Mode
The “Scope Mode” screen functions as a power oscilloscope and displays real-time voltage and current waveforms for all eight channels. The display is dynamically updated every two or three seconds.
Page
31
Page 50
Chapter 5 Easy Start Tour
TASK 808
NOTE - At this point, the graph may appear cluttered if data from all eight channels is being displayed. Unwanted data may be filtered out at any time by turning each channel’s volts and amps OFF using the “Channel Selection” screen (shown in Step 1 below).
Step 1 Press the SELECT CHAN SOFTKey to access the “Channel Selection” screen.
Jan-17-96 18:34:45
CHANNEL SELECTION
CHANNEL VOLTS AMPS
A ON ON
B OFF OFF C OFF OFF D OFF OFF
NEXT VOLTS AMPS CHAN ON/OFF ON/OFF EXIT
This screen is used to filter data for display on the “Scope Mode” screen. Toggle volts and amps ON or OFF for each channel as desired. Press the
EXIT SOFTKey to return to the “Scope Mode” screen.
5.5.2 Viewing in Meter Mode
Step 1 From the “Scope Mode” screen, press the METER MODE
SOFTKey to display the first of several “Meter Mode” screens.
Page 32
Page 51
Chapter 5 Easy Start Tour
TASK 808
Jan-17-96 18:34:45
METER MODE
CHAN VOLT AMP WATT VA
A 227.8 9.097 1.800K 2.072K
B 229.0 9.100 1.801K 2.084K C 228.3 9.146 1.810K 2.088K D 0.026 0.000 0.000 0.000 ABC 228.3 27.34 5.411K 6.243K
NEXT NEXT CKT
SCREEN METER TYPE EXIT
Step 2 Press the CKT TYPE SOFTKey to verify the “Circuit Type” screen which displays the currently selected circuit type. If desired, a different circuit type may be selected. Press the EXIT SOFTKey to return to the “Meter Mode” screen.
Step 3 Spend a minute, using the NEXT SCREEN, NEXT METER, etc., SOFTKeys to navigate through some of the various displays to get a sense of the different viewing formats which are available in Meter Mode (a detailed explanation of Meter Mode is included in Chapter 7 Reporting Tour). Press the EXIT SOFTKey to exit the “Meter Mode” and return to the “Scope Mode” screen.
This completes the Easy Start Guided Tour.
A Footnote on Powering OFF…
NOTE - It is a wise practice to routinely display the “Scope Mode” screen before powering OFF the PP4300. Powering OFF from other screens may nullify configuration changes thought to be implemented. In such cases, the actual configuration, on a subsequent power up, could differ from the expected configuration.
Page
33
Page 52
Page 53
Chapter 6 Advanced Tour
The Advanced Tour covers the following topics:
6.1 Setup Menu
6.1.2 Set Programmable Features Menu
6.1.4 Memory Functions Menu
6.1.5 Set Input Configurations Menu
Chapter 6 Advanced Tour
TASK 808
Page
35
Page 54
Chapter 6 Advanced Tour
TASK 808
6.1 Setup Menu
6.1.1 Easy Start
In Chapter 5 Easy Start Tour, EASY START was the only setup option which was explored. However, the Setup Menu contains many other powerful and important options for configuring the Task 808.
Step 1 From the “Scope Mode” screen, press the SETUP SOFTKey.
Jan-17-97 18:34:45
SETUP MENU
1. EASY START
2. SET PROGRAMMABLE FEATURES
3. TURN MONITORING OFF
4. MEMORY FUNCTIONS
5. SET INPUT CONFIGURATIONS
SCOPE METER HAR- VIEW
MODE MODE MONICS DATA
Step 2 Press the 2 key on the PP4300’s numeric keypad to display the “Programmable Features” menu.
6.1.2 Set Programmable Features
The following screen/menu will be displayed:
Jan-17-97 18:34:45
SET PROGRAMMABLE FEATURES
1. SET TIME AND DATE
2. ENTER SITE/FILE NAME
3. LCD DISPLAY MODE: NORMAL
4. LCD BACKLIGHT AUTO SHUTOFF:ENABLED
5. AUDIBLE ALARM ON/OFF: ON
EXIT
Step 3 Press the 1 key on the numeric keypad to set time and date:
Jan-17-97 18:34:45
Page 36
Page 55
Chapter 6 Advanced Tour
TASK 808
SET TIME AND DATE
PRESENT TIME (hh:mm:ss) = 00:38:04
PRESENT DATE (mm-dd-yy) = Jan-01-97
ENTER ENTER
TIME DATE EXIT
To change the time, press the ENTER TIME SOFTKey; Note that the SOFTKey options have changed to facilitate setting the time:
BACK
ENTER SPACE EXIT
Use the ENTER and BACKSPACE SOFTKeys, along with the numeric keypad, to set the correct time and date.
NOTE - It is important that the time (24 hour format) and date is set correctly because they are used by the system to identify event data. If changing the time and data becomes necessary, you may wish to clear event memory as well, since any previously recorded events will have an incorrect time and date.
When finished, press the EXIT SOFTKey to return to the “Programmable Features” menu.
Step 4 Option 2 ENTER SITE/FILE NAME was reviewed previously during the Easy Start Guided Tour.
Press the 3 key on the numeric keypad to toggle the display mode from NORMAL (blue text and graphics on white background) to INVERTED (white text and graphics on a blue background). Exit and return to this menu to see the implemented result.
If Option 4 LCD BACKLIGHT AUTO-SHUTOFF is enabled, the screen will time out/dim after five minutes has elapsed without any keys being
Page
37
Page 56
Chapter 6 Advanced Tour
TASK 808
pressed. Although pressing any key will restore the screen’s brightness, the 0 (zero) key is recommended because it is the least likely to affect anything (unintended exit, changing screens, etc.). Auto-shutoff extends battery life and its use is recommended.
Option 5 AUDIBLE ALARM, when set to ON, the unit will sound a one­second beep for each event trigger and a 0.1 second beep for each error condition.
Press the EXIT SOFTKey again to return to the “Setup Menu” screen.
6.1.3 Turn Monitoring ON/OFF Press the 3 key on the numeric keypad to toggle monitoring ON and OFF.
Step 5 Press the 4 key on the numeric keypad to display the “Memory
Functions” screen.
6.1.4 Memory Functions
First, a word or two about memory…
Before exploring the memory functions, it is essential that users get a good conceptual understanding of the Task 808’s data storage and memory management techniques. For this reason, the Advanced Guided Tour will take a brief detour at this point.
Page 38
Page 57
Chapter 6 Advanced Tour
TASK 808
Data Storage
As shown above, the PP4300’s memory (referred to as internal memory) can store a modest amount of data – about 200 Kbytes (although the actual memory capacity is 256 Kbytes, overhead cuts the useable data memory space to about 200 Kbytes).
Saving Data to Internal Memory
If the system is being operated without an optional memory card, configuration data and monitoring data is automatically saved to the PP4300’s internal memory . There is no need to “save” the data in the sense that data must be saved on a PC. The PP4300 automatically writes data to the internal memory as it is accumulated.
Optional Memory Card
The optional memory card, however, can hold much more data than the internal memory . Although not an absolute requirement, a memory card is recommended for almost all applications. Various memory card capacities are available, see Appendix C.
Auto-transfer
As data is captured, it is always written directly to the PP4300’s internal memory . If a memory card is included in the configuration, data can be automatically copied from internal memory to the memory card as the internal memory fills. This feature is called Auto-transfer.
Page
39
Page 58
Chapter 6 Advanced Tour
TASK 808
Storage Techniques
When data is collected over extended periods of time, it may exceed the memory capacity of even the memory card. To address this limitation, data is always written to memory using one of the following user-specified techniques: either Fill and Stop or Overwrite.
Fill and Stop
This technique works just like it sounds: data is written to internal memory until it is full and then the data storage process shuts down. Using this technique, the oldest data is retained, the collection of data is stopped.
Overwrite
This technique also works just like it sounds: data is written to internal memory until it is full and then begins to overwrite, starting with the oldest data first. Using this technique, the most recent data is retained, the oldest data is overwritten.
The following table summarizes how these memory features work together under four different scenarios:
Page 40
Page 59
Memory Feature Table
Memory mode?
Auto­transfer?
Memory card?
Scenario #1 Scenario #2 Scenario #3 Scenario #4
Fill and Stop Overwrite
Enabled Disabled Enabled Disabled
YES N/A YES N/A
Chapter 6 Advanced Tour
TASK 808
As PP4300’s
R E S U L T
Now, back to the Advanced Guided Tour…
internal memory fills, data is copied to the memory card. When 200 Kbytes of data has been copied, copying stops, no new data is recorded.
PP4300’s internal memory fills and stops.
As PP4300’s internal memory fills, data is copied to the memory card. When the memory card is full, copying stops. Internal memory continues to be overwritten. NOTE - the memory card is never overwritten.
PP4300’s internal memory fills and is overwritten.
Page
41
Page 60
Chapter 6 Advanced Tour
TASK 808
Memory Functions, Continued
The “Memory Functions” screen is the function control menu for both the internal memory and the optional memory card.
Jan-17-97 18:34:45
MEMORY FUNCTIONS
1. MEMORY CARD FUNCTIONS
2. SET AUTO-TRANSFER TO MEMORY CARD
3. CLEAR MEMORY
4. SET MEMORY STORAGE MODE
5. RESET TO FACTORY CONFIGURATION
EXIT
Step 6 Press the 1 key on the numeric keypad to display the Memory Card Functions screen . This screen displays the status of the memory
card installed. Use this screen to read and write event and setup data on the memory card and to format the memory card (see Appendix F).
Jan-17-97 18:34:45
MEMORY CARD FUNCTIONS
CARD SIZE: 1024K CARD FREE SPACE: 10K WRITE PROTECT:OFF MEMORY CARD BATTERY:OK
WRITE READ FORMAT
CARD CARD CARD EXIT
Use the View Data menu shown in Chapter 7 to read the Auto-transfer file.
• NOTE: In order to view data stored on a memory card, it must first be
read (copied) into internal memory. Reading data from a memory card will erase all data presently in internal memory.
Page 42
Page 61
Chapter 6 Advanced Tour
TASK 808
Saving/Reading Data
When data is saved manually to the memory card using the WRITE DATA SOFTKey, an event file (.evt) is created. This file consists of all data currently in internal memory. Using the WRITE SETUPS SOFTKey creates a setup file (.set), which contains the instrument configuration. When Auto-transfer is enabled, data is saved automatically to the memory card and is stored in an Auto-transfer file (.mdb). Event files and setup files are retrieved using the Memory Card Functions screen. Auto-transfer files are retrieved using the View Data screen.
File Sizes
Since the internal memory data storage capacity is 200 Kbytes, files written to memory cards manually will always be 200 Kbyte files (even though the actual amount of data may be less). On the other hand, the size of files created using the Auto-transfer function is limited only by the size of the memory card and typically would be much larger than 200 Kbytes. A procedure has been developed for reading files which were written to the memory card by auto-transfer and which may be several times larger than the 200 Kbyte internal memory. In such cases, only 200 Kbytes can be read into internal memory at a time. Therefore, data is copied from the memory card to internal memory in 200 Kbyte blocks. The user is prompted to enter a start date and time. This becomes the starting point from which the 200 Kbyte block of event data is selected.
Press the EXIT SOFTKey to return to the “Memory Functions” screen.
Step 7 Press the 2 key on the numeric keypad to toggle between Auto­transfer enabled, Auto-transfer disabled. As could be seen from the
Memory Features Table (shown earlier), when a memory card is in use, it is usually wise to enable auto-transfer (scenario #3).
NOTE - If the PP4300 is powered ON with a new or freshly formatted memory card installed, and with Auto-transfer enabled, it will appear that much less storage space is available than would be expected. This phenomenon occurs because auto-transfer automatically allocates space. Thus, for example, a two Mbyte card will show only 48K of free space. The actual amount of stored data is shown on the View Data/ “Site Status” screen.
Page
43
Page 62
Chapter 6 Advanced Tour
TASK 808
Oct-17-96 18:34:45
AUTO-TRANSFER TO MEMORY CARD
AUTO-TRANSFER: ENABLED
ENABL/ DISABL EXIT
Press the EXIT SOFTKey to return to the “Memory Functions” screen.
Step 8 Press the 3 key on the numeric keypad to clear all events stored
in the PP4300’s internal memory .
NOTE - Perform this operation ONLY if there is no valuable information in internal memory .
Jan-17-97 18:34:45
CLEAR MEMORY
CAUTION!
ALL EVENTS IN INTERNAL MEMORY
WILL BE DELETED.
PRESS EXIT TO ABORT
CLEAR
MEMORY EXIT
Press the EXIT SOFTKey to return to the “Memory Functions” screen without actually clearing any memory.
Step 9 Press the 4 key on the numeric keypad to toggle between Fill and Stop and Overwrite using the NEXT MODE SOFTKey.
Jan-17-97 18:34:45
MEMORY STORAGE MODE
Page 44
Page 63
Chapter 6 Advanced Tour
TASK 808
PRESENT MODE: FILL AND STOP
NEXT MODE EXIT
Press the EXIT SOFTKey to return to the “Memory Functions” screen.
Step 10 Press the 5 key on the numeric keypad to reset parameter
values to the factory configuration, i.e., default settings.
Jan-17-97 18:34:45
RESET TO FACTORY CONFIGURATION
CAUTION!
THIS COMMAND RESETS ALL THRESHOLD SETTINGS, PROGRAMMABLE FEATURES, AND INPUT CONFIGURATIONS TO THEIR FACTORY DEFAULTS.
RESET EXIT
Press the EXIT SOFTKey to return to the “Memory Functions” screen (without actually resetting to factory configuration).
n Refer to Appendix D PP4300 Technical Specifications for a
complete listing of factory default settings.
Exit from the “Memory Functions” screen and return to the “Setup Menu” screen by pressing the EXIT SOFTKey.
6.1.5 Set Input Configurations
From the “Setup Menu” screen, press the 5 key on the numeric keypad to display the “Set Input Configurations” screen.
Several very important parameters are available from the “Set Input Configurations” screen:
Page
45
Page 64
Chapter 6 Advanced Tour
TASK 808
Oct-17-96 18:34:45
SET INPUT CONFIGURATIONS
1. SET CIRCUIT TYPE
2. SET ACTIVE CHANNELS
3. SET SCALE FACTORS
4. SET SYNC PARAMETERS
5. DEMAND INTERVAL SETTINGS
6. SELECT CURRENT PROBES
7. DEMAND/ENERGY PARAMETER
8. DEMAND AND ENERGY LIMIT
EXIT
Step 1 Press the 1 key on the numeric keypad to set the circuit type. This screen was previously reviewed in the Easy Start Guided Tour. Exit by pressing the EXIT SOFTKey.
Step 2 Press the 2 key on the numeric keypad to display the “Active Channels” screen.
Jan-17-97 18:34:45
ACTIVE CHANNELS CHANNEL VOLTS AMPS A ON ON B ON ON C ON ON D LOW ON
NEXT VOLTS AMPS CHAN ON/OFF ON/OFF EXIT
This screen is used to toggle ON or OFF the status of channels A, B and C. In addition – if you highlight and toggle channel D, you will notice that there are three voltage options for channel D: LOW, HIGH and OFF. The LOW voltage range is from 0.5 to 20.0 Vrms, and is available for channel D hookups, e.g., ground-to-neutral, which may require a much lower range. The HIGH voltage range is the same as ON, i.e., from 10 to 600 Vrms. The “ Scale Factors” screen (shown below ) displays the actual channel D status setting.
Page 46
Page 65
Chapter 6 Advanced Tour
TASK 808
NOTE - The “Active Channels” screen controls the channels which are actively collecting data. A very similar screen, the “Channel Selection” screen, was reviewed in the Easy Start Guided Tour. But that screen, however, only filters the data for display on the “Scope Mode” graph. Unlike the options on the “Active Channels” screen, the “Channel Selection” screen has no control over the collection of data.
Exit by pressing the EXIT SOFTKey.
Step 3 Press the 3 key on the numeric keypad to set the voltage and amperage scale factors for each channel.
Jan-17-97 18:34:45
SCALE FACTORS
CHAN VOLTS AMPS A 1.0000 1.0000 B 1.0000 1.0000 C 1.0000 1.0000 LOW D 1.0000 1.0000
NEXT ENTER CHAN SCALE EXIT
The scale factor for all of the listed optional Dranetz-BMI current probes is automatically factored in behind the scenes and should be entered as 1.0 (unless changed on the secondary of another current transformer). However, The scale factors of any non-Dranetz-BMI current or voltage transformer must be accounted for in making accurate measurements. Because the monitored output current or voltage is frequently stepped down (divided) from the original current or voltage, this ratio must be stepped up (multiplied) by the scale factor when computations are performed.
The scale factor is usually marked on the transformer. This value must be entered into the “Set Scale Factors” screen. Refer to the device or the manufacturer’s literature for the scale factor for devices which you may be using.
Page
47
Page 66
Chapter 6 Advanced Tour
TASK 808
Scale Factor Calculation - Example
Suppose the 5A secondary output current of a 5000A current transformer is being monitored. The scale factor would be calculated as follows:
CT Full Scale Input x Dranetz-BMI Probe Scale Factor = Scale Factor CT Full Scale Output
5000 x 1 = Scale Factor of 1000 5
Exit the “Scale Factors” screen by pressing the EXIT SOFTKey.
Step 4 Press the 4 key on the numeric pad to set the sync (synchronization) parameters. Sync, i.e., maintaining a constant phase relationship between AC signals, may be either external or internal. When set to external, the PP4300 attempts to sync to an incoming voltage signal. When set to internal, the PP4300 uses the nominal frequency when making measurements. External sync is recommended unless no adequate voltage source is available.
Enter a nominal frequency which matches the line frequency so that if the PP4300 loses external sync, it will have a corresponding internal sync. Failure to set this value correctly can result in erroneous data.
Page 48
Page 67
Chapter 6 Advanced Tour
TASK 808
Jan-17-97 18:34:45
SYNC PARAMETERS
SYNC MODE: EXTERNAL
NOMINAL FREQUENCY: 60.0
SELECT ENTER
SYNC FREQ EXIT
Press the SELECT SYNC SOFTKey to toggle through the sync mode options. Press the ENTER FREQ SOFTKey to enter the frequency (using the numeric keypad). Exit by pressing the EXIT SOFTKey.
Step 5 Press the 5 key on the numeric keypad to set the interval, start time and date for the collection of demand data.
Jan-17-97 18:34:45
DEMAND INTERVAL SETTING
PRESENT INTERVAL: 15 MINUTES START TIME: 02:02:13 START DATE: Jan-11-96 START OF NEXT INTERVAL: 18:47:13
NOTE: DATA WILL FILL A CLEARED MEMORY BUFFER IN 6 DAYS ASSUMING NO OTHER EVENTS OCCUR.
SET START START
INTRVL NOW AT EXIT
Press the SET INTRVL SOFTKey to change the interval start time and date (watch the screen carefully when selecting this – especially the SOFTKeys -- note that ENTER and BACKSPACE SOFTKeys become operational).
This screen is especially significant because it calculates how long it will take to fill the internal memory excluding events other than timed demand interval events.
Page
49
Page 68
Chapter 6 Advanced Tour
TASK 808
When finished, press the START NOW SOFTKey to start collecting immediately, or use the START AT SOFTKey to enter a different (and future) start time and date. When finished, the “Set Input Configuration” screen will be displayed.
Step 6 Press the 6 key on the numeric keypad to select current probes (this function was already reviewed in the Easy Start Guided Tour). After making selection, exit by pressing the EXIT SOFTKey.
Step 7 Press the 7 key on the numeric keypad to set the demand/energy parameter.
Jan-17-97 18:34:45
DEMAND/ENERGY PARAMETER
PARAMETER: WATTS
WATTS VA VARS EXIT
Press the WATTS, VA or VARS SOFTKeys to set the demand/energy parameter. Exit by pressing the EXIT SOFTKey.
Page 50
Page 69
Chapter 6 Advanced Tour
TASK 808
Step 8 Press the 8 key on the numeric keypad to enable and set demand
and energy limits:
Jan-17-97 18:34:45
DEMAND/ENERGY LIMITS
DEMAND LIMIT : 2229.0 W ENERGY RATE LIMIT : 9300.0 WHR
SET SET DISABLE DISABLE
DEMAND ENERGY DEMAND ENERGY EXIT
Use the SOFTKeys to SET, ENABLE or DISABLE the limits. The consequences of enabling and setting these limits are as follows:
Demand limit - At the end of each demand interval, the average demand is compared with this limit. If the demand is greater than this limit, it is treated as an event and is recorded.
Energy Rate Limit - The energy rate is computed once every minute. If the rate exceeds this limit, it is treated as an event and is recorded.
Exit by pressing the EXIT SOFTKey. Exit from the “Set Input Configurations” screen by pressing the EXIT
SOFTKey. Exit from the “Setup Menu” screen and return to the “Scope Mode” screen
by pressing the SCOPE MODE SOFTKey.
This completes the Advanced Guided Tour.
Page
51
Page 70
Page 71
Chapter 7 Reporting Tour
Chapter 7 Reporting Tour
The Reporting Tour covers the following topics:
7.1 View Data
7.2 Meter Mode
7.3 Viewing Harmonics (model 808/H-M only)
7.4 Screen Printing
TASK 808
Page
53
Page 72
Chapter 7 Reporting Tour
TASK 808
7.1 View Data
The “View Data” menu provides access to graphic displays, reports and the Auto-transfer files.
From the “Scope Mode” screen, press the VIEW DATA SOFTKey:
Jan-17-97 18:34:45
VIEW DATA MENU
1. TIME PLOT
2. DEMAND REPORT
3. ENERGY REPORT
4. MIN/MAX REPORT
5. READ DATA FROM MEMORY CARD
6. SITE AND 4300 STATUS
SCOPE METER
MODE MODE SETUP
Step 1 From the “View Data” screen, press the 1 key to display the first of the Time Plot graphs.
Definition
A time plot is a graph of a single parameter value, for a single channel, over time. The curve consists of timed events and is redrawn every ten seconds.
Page 54
Page 73
Chapter 7 Reporting Tour
TASK 808
Even though a time plot may cover an extended period of time, it is possible to analyze the data in great detail.
NOTE - START DATE is displayed across the top of the “Time Plot ” screen. This is the date on which the time plot data collection started.
Step 2 Select the channel and parameter to be analyzed: Press the NEXT CHAN SOFTKey to page through the channels. Press the SELECT PARAM SOFTKey to change parameters, by highlighting and
selecting the desired parameter from a list.
Step 3 Press the ZOOM SOFTKey to begin the analysis.
Select an Area of Interest
Use the arrow SOFTKeys to move right and left side brackets inward from the edge of the screen toward the area of interest, until it is bracketed on either side. Then press the ZOOM IN SOFTKey. Repeat this process, if necessary, until the exact area of interest has been selected.
Then press the EVENT REPORT SOFTKey to display a listing of events, including the date, time and event description for each:
Jan-17-97 18:34:45
Page
55
Page 74
Chapter 7 Reporting Tour
TASK 808
EVENT REPORT DATE TIME DESCRIPTION
01-13 10:23 Dmd Int-1.800KW PF 0.86
01-13 10:31 Dmd Int-1.801KW PF 0.86 01-13 10:39 MONITOR OFF 01-13 10:43 MONITOR ON 01-13 10:44 Dmd Int-1.790KW PF 0.86 01-13 10:51 Dmd Int-1.802KW PF 0.86 01-13 10:59 DATABASE FULL 01-13 10:07 Dmd Int-1.806KW PF 0.86
NEXT PAGE PAGE
EVENT DOWN UP DETAIL EXIT
Seven new Task 808-specific event types have been created:
Event Report Abbreviation Full Description
DEMAND CONFIG demand interval setting and
parameter change
THRESH CONFIG energy /demand user-defined
threshold change PROBE CONFIG current probe change Dmd Int demand interval change Dmd Lim demand threshold crossing Energy Rate Lmt energy rate threshold crossing MIDNIGHT SUMMARY midnight summary
In addition, each time data in the internal memory is overwritten, an event named “Database Full” is added to the event list.
Step 4 Using the PAGE DOWN, PAGE UP and NEXT EVENT SOFTKeys, locate and highlight the specific event of interest. Then press the DETAIL SOFTKey. The “Demand Interval Report” screen will be displayed:
Page 56
Page 75
Chapter 7 Reporting Tour
TASK 808
Jan-17-97 18:34:45
DEMAND INTERVAL REPORT
(DEMAND INTERVAL EVENT)
EVENT DATE AND TIME :Jan-14-97 20:05:37
DEMAND : 1.806KW INTERVAL ENERGY : 376.6 W-HR DAILY ENERGY : 15.23K W-HR MONTHLY ENERGY : 47.80K W-HR PF : 0.86
DAILY MONTH
PEAK PEAK STATUS ENERGY EXIT
The “Demand Interval Report” screen also provides a gateway to four additional screens, as illustrated below.
Daily Peak/Monthly Peak Reports
These reports have the same format: The Daily Peak contains the four highest peak readings for the day; the Monthly Peak report contains the four highest peak readings for the month.
Jan-17-97 18:34:45
CHANNEL ABC PEAK DEMAND REPORT
(DEMAND INTERVAL EVENT)
DAILY PEAK DEMAND: Jan-17-97 TIME W PF 14:06 41.46K 1.000 13:36 41.35K 1.000 13:21 41.29K 1.000 10:02 41.22K 1.000
INTRVL MONTH
DATA PEAK STATUS ENERGY EXIT
Status
The status report format is the same as that of the Meter Mode # 1 report, except that it does not dynamically update. It is a snapshot taken at the time of the event.
Energy
This report provides a snapshot of the energy data for the demand interval event selected.
Jan-17-97 18:34:45
CHANNEL ABC ENERGY REPORT
Page
57
Page 76
Chapter 7 Reporting Tour
TASK 808
(DEMAND INTERVAL EVENT)
ENERGY RATE: 687.2 W-MN DAILY: Jan-13-97 99.29K W-HR MONTHLY: Jan-97 99.29K W-HR DAYS INTO BILLING PERIOD: 23
INTRVL DAILY MONTH
DATA PEAK PEAK STATUS EXIT
Press the EXIT SOFTKey four times to return to the “View Data” menu.
Step 5 Press the 2 key on the numeric keypad to display the demand
report. The content of this report is determined by parameters previously set using options from the “Set Input Configurations” screen.
Oct-17-96 18:34:45
CHANNEL ABC PEAK DEMAND REPORT
PRESENT INTERVAL DATA
PRESENT DEMAND: 41.45K W PROJECTED DEMAND: 41.40K W
10 MINUTES INTO 15 MINUTE INTERVAL
DAILY MONTH EVENT
PEAK PEAK DATA EXIT
Press EXIT to return to the “View Data” menu.
Page 58
Page 77
Chapter 7 Reporting Tour
TASK 808
Step 6 Press the 3 key on the numeric pad to display the “Energy” report.
A format similar to one shown earlier will be displayed. However, this report is a summary report and is dynamically updated.
Jan-17-97 18:34:45
CHANNEL ABC ENERGY REPORT
ENERGY RATE: 687.2 W-MN DAILY: Jan-13-97 99.29K W-HR MONTHLY: Jan-97 99.29K W-HR DAYS INTO BILLING PERIOD: 23
EVENT
DATA EXIT
Press the EVENT DATA SOFTKey to display the following menu:
Jan-17-97 18:34:45
EVENT DATA MENU
1. DEMAND INTERVALS
2. LIMIT CROSSINGS
3. MIDNIGHT SUMMARY
4. ALL EVENTS
EXIT
Display the “Demand Interval” (Event) report by pressing the 1 key on the numeric keypad. This report filters out all events except demand interval events. Press EXIT to return to the “Event Data Menu” screen
Detail (Daily Peak, Monthly peak , Status and Energy) is available for the selected event. Press EXIT to return to the “Event Data Menu” screen
Press the 2 key on the numeric keypad to display another filtered version – the “Limit Crossings” screen (Demand Limit and Energy Rate Limit ), if any crossings exist. Step 7 Press the 3 key on the numeric keypad to display a listing of the “Midnight Summary ” reports available.
Page
59
Page 78
Chapter 7 Reporting Tour
TASK 808
NOTE - The “Midnight Summary ” reports are created automatically each night but displayed only on request.
Jan-17-97 18:34:45
EVENT REPORT
DATE TIME DESCRIPTION
01-13 00:00 MIDNIGHT SUMMARY
01-14 00:00 MIDNIGHT SUMMARY
01-15 00:00 MIDNIGHT SUMMARY 01-16 00:00 MIDNIGHT SUMMARY
NEXT PAGE PAGE
EVENT DOWN UP DETAIL EXIT
Use the highlight bar to select a date – then press the DETAIL SOFTKey to display the Daily Peak Demand.
Press the 4 key on the numeric keypad to display ALL, i.e., the unfiltered event report (illustrated previously).
Step 8 Press the EXIT SOFTKey to return to the “View Data” menu. Press the 4 key on the numeric keypad to display the Min/Max report. This report displays daily, weekly and monthly Min/Max data by each channel and by nine parameters:
Page 60
Page 79
Chapter 7 Reporting Tour
TASK 808
Jan-17-97 18:34:45
MIN MAX REPORT FOR CHANNEL: A
PERIOD DATE TIME VOLTS DAILY MIN. Jan-17-97 10:25 100.0 DAILY MAX. Jan-17-97 18:00 118.0 WEEKLY MIN. Jan-10-97 20:25 86.66 WEEKLY MAX. Jan-13-97 14:04 119.9 MONTHLY MIN.Jan-10-97 20:25 86.66 MONTHLY MAX.Jan-13-97 14:04 119.9
NEXT NEXT CHAN PARAM EXIT
NOTE - Week and month periods are calendar week (Sun-Sat) and month.
Reading the Auto-transfer file from the memory card
o Exit to the “View Data” menu. o Insert the memory card containing the data to be read. o Press the 5 key on the numeric keypad to display the Read Events
From Memory Card screen:
Jan-17-97 18:34:45
READ EVENTS FROM MEMORY CARD
CAUTION! EVENTS PRESENTLY IN MEMORY WILL BE DELETED WHEN EVENTS FROM THE CARD ARE COPIED INTO MEMORY.
PRESS EXIT TO CANCEL OR PRESS TRANSFER TO CONTINUE
TRANS-
FER EXIT
o Observe the caution. Press the TRANSFER SOFTKey. The “View
Events by Date and Time” screen is displayed.
o Enter the starting date and time of the desired events to be transferred
(not necessarily the default date and time, which is the oldest event date and time).
Page
61
Page 80
Chapter 7 Reporting Tour
TASK 808
o To enter the date, Press the START DATE SOFTKey. Use the
numeric keypad to enter the two digit month, then press the ENTER SOFTKey. Repeat this process for day, year, hour, minute, etc.
o Press the READ EVENTS SOFTKey to begin reading data.
NOTE - If the memory card contains more data than can fit into the internal memory, only as much data as possible will be transferred. After viewing the initial batch of data, note the date and time of the last event. Enter these values into the START DATE/TIME screen to read the remaining data.
Site and 4300 Status
Step 9 Press the 6 key on the numeric keypad to display the “Site Status”
screen:
Jan-17-97 18:34:45
SITE STATUS
SITE NAME: CHILLER START: 14 Jan 97, 12:22:46 VOLTAGE CHANNELS ON: A, D CURRENT CHANNELS ON: A, D DATABASE: 50% FULL AUTO-TRANSFER FILE: 14% FULL
4300 SELF
STATUS TEST EXIT
This screen also provides a gateway to two additional screens:
4300 STATUS
Jan-17-97 18:34:45
4300 STATUS
INPUT: GOOD MEMORY: 512K GOOD HOST CPU: V 1.0 ACP CPU: V 1.0 DATABASE: V 1.0 TASKCARD: TASK 808, EHM
Page 62
EXIT
Page 81
Chapter 7 Reporting Tour
TASK 808
NOTE - “GOOD Input” means the current and voltage measurements are OK and within range limits. The memory test results are the results of the test performed during power ON and if the result is not GOOD, call Dranetz-BMI Customer Service.
V 1.0 is an abbreviation for Version 1.0. EHM is an abbreviation for Energy/Harmonics/Memory .
Self Test
The self test performs a non-destructive test of the internal memory , although the test will interrupt data collection.
Jan-17-97 18:34:45
RUN SELF TEST
CAUTION! LOSS OF DATA WILL RESULT IF THIS TEST IS SELECTED DURING DATA ACQUISITION. RUN TEST DURING NON-CRITICAL MONITORING TIMES ONLY.
PRESS BEGIN TEST TO CONTINUE PRESS EXIT TO ABORT
BEGIN
TEST EXIT
The reason behind this warning is that the Self Test turns monitoring OFF during the test, then turns it back ON when the test is finished (unless it was already OFF when the test was begun).
Press the BEGIN TEST SOFTKey to start the self test.
Page
63
Page 82
Chapter 7 Reporting Tour
TASK 808
7.2 Meter Mode
The Meter Mode consists of four different “meters,” or formats, updating in real time. These meters present the monitored data across 35 different screens. Don’t let this number be intimidating, however, because paging through this array of information can be accomplished quickly and easily.
Navigation
Navigation through these various displays is performed using one or more of four navigation SOFTKeys:
NEXT METER NEXT SCREEN NEXT CHAN NEXT PARAM
Meter Mode consists of the following screen configuration, in meter sequence, starting with meter #1:
Meter # 1 - This meter provides a spreadsheet display of values for all 11 parameters for all four channels plus ABC. Three screens are required to display values for all 11 parameters.
Use the NEXT SCREEN SOFTKey to page from screen to screen.
Jan-17-97 18:34:45
METER MODE
CHAN VOLT AMP WATT VA
A 117.4 0.743 -5.927 87.26
B 0.879 2.091 1.554 1.839 C 1.001 2.000 1.765 2.003 D 2.316 1.264 0.866 2.929 ABC 117.4 0.743 -5.927 87.26
NEXT NEXT CKT
SCREEN METER TYPE EXIT
Page 64
Page 83
Chapter 7 Reporting Tour
TASK 808
Meter # 2 - This meter emulates a digital volt meter (DVM), displaying all
11 parameter values for each of four channels plus ABC. Three screens each are required to display the values for the 4 channels plus ABC.
A B C D ABC Use NEXT CHAN to change channels, NEXT SCREEN to page
through parameters.
Jan-17-97 18:34:45
CHANNEL: A
114.5 V
1.368 I
143.6 KW
156.7 KVA
NEXT NEXT NEXT CKT CHAN SCREEN METER TYPE EXIT
Page
65
Page 84
Chapter 7 Reporting Tour
TASK 808
Meter # 3 - This meter emulates a digital volt meter (DVM), displaying a
single parameter value for four channels plus ABC. 11 screens are required to display the values for all of the parameters.
Use NEXT PARAM to page through the 11 parameters.
Jan-17-97 18:34:45
VOLTS A: 114.5 B: 1.368 C: 143.6 D: 156.7
ABC: 115.8
NEXT PREV NEXT CKT
PARAM PARAM METER TYPE EXIT
Page 66
Page 85
Chapter 7 Reporting Tour
TASK 808
Meter # 4 - This meter is a graphical phase meter displaying the phase
angle for either a volts-only or amps-only phasor for all four channels. In addition, volts and amps phasors are available for each of the four channels.
NOTE - Channels with values below 10% of the maximum channel value will not be displayed.
Six screens are required to display the phasors.
Use SINGLE Use CHAN to switch NEXT PARAM to combined to toggle between VOLTs and AMPs phasors, VOLTs and AMPs then use NEXT CHAN to screens page through channels
Page
67
Page 86
Chapter 7 Reporting Tour
TASK 808
7.3 Viewing Harmonics
NOTE - The harmonics feature is only available on Task 808 model 808/H-M.
Step 1 Press the HARMONICS SOFTKey to view harmonics graphs and text screens:
Step 2 Explore some options -- press the NEXT CHAN SOFTKey to advance through the channels. Press the NEXT PARAM SOFTKey to change parameters (by highlighting and selecting the desired parameter from a list).
Press the SET SCALES SOFTKey to toggle the vertical scale between % of fundamental (amount of fundamental frequency, e.g., 50Hz or 60Hz) and % of RMS.
Press the TEXT MODE SOFTKey to switch from a graphical to a text format display:
Page 68
Page 87
Chapter 7 Reporting Tour
TASK 808
Jan-17-97 HARMONICS:CH A REF 117.8 V, % FUND Vthd H# MAG% PHS H# MAG% PHS H# MAG% PHS 02 0.038 094 09 0.038 074 16 0.019 115 03 4.981 205 10 0.019 218 17 0.132 143 04 0.094 186 11 0.338 020 18 0.019 269 05 2.331 177 12 0.019 332 19 0.094 024 06 0.019 138 13 0.169 339 20 0.019 341 07 0.808 175 14 0.000 206 21 0.282 193 08 0.019 044 15 0.188 279 22 0.019 088
NEXT NEXT NEXT GRAPH CHAN PARAM SET MODE EXIT
60.0Hz
18:34:45
Mag% is the amplitude of the harmonic. PHS is the phase angle between the harmonic and fundamental of the channel displayed.
NOTE - The watts parameter version of this screen indicates harmonic power direction by the sign in front of the MAG% value. A minus sign (-) indicates that the harmonic power flows from the load to the source. No sign indicates that the harmonic power flows from the source to the load.
Step 3 There are three sets of harmonics. Press the NEXT SET SOFTKey to display additional sets of harmonics until the maximum of 50 harmonics is reached. Exit from the “Harmonics” menu and return to the “Scope Mode” screen by pressing the EXIT SOFTKey.
7.4 Screen Printing
The currently displayed screen may be printed (using the optional printer) by pressing the period key (.) on the numeric keypad.
This completes the Reports Guided Tour.
Page
69
Page 88
Page 89
Appendix A Product Support
TASK 808
Appendix A Product support
Dranetz-BMI provides users with complete technical support.
A.1 Telephone Support
Technical Support and Customer Service is available toll-free, Monday through Friday during normal business hours (Eastern Time) by calling:
1-800-372-6832 or 732-287-3680
A.2 Fax Line
Customers may send fax inquiries to the Dranetz-BMI Customer Service Fax line at any time:
732-248-1834
A.3 World Wide Web
Customers may also check the Dranetz-BMI Web page for additional product and technical information:
http://www.dranetz-bmi.com
A.4 Technical support email address
Page
71
Page 90
Page 91
Appendix B Maint/Service/Return
TASK 808
Appendix B Maintenance/Servicing/Return Shipment
B.1 Maintenance/Servicing
No maintenance is required for the PP4300 other than internal battery replacement and calibration.
B.1.1 Internal Battery Pack Replacement
The internal battery pack used in the PP4300 functions as a power source and UPS. Replacement procedures follow the specifications and precautions below. See Appendix F for memory card battery replacement.
Battery Pack Specifications
Location: Battery compartment on the bottom of the unit. Number of batteries in pack: 6 Type: Sealed, rechargeable NiCad cells Voltage: 7.2 V dc Capacity: 1.6 Ah Length of operation : More than two hours when fully charged and properly
maintained. Suggested replacement interval : Two years. Part Number: BP4300
NOTE - The length of time that the PP4300 can operate on the battery pack degrades over the life of the batteries and the number of charge/discharge cycles.
Page
73
Page 92
Appendix B Maint/Service/Return
TASK 808
Memory backup
A storage capacitor on the CPU board is used for backup of the PP4300's data, configurations, and setup when the battery pack is removed. The capacitor's charge will maintain memory for two hours, meaning that if the battery pack is replaced within two hours, no data will be lost from the internal memory . The capacitor is not operator replaceable.
Battery Pack Safety Precautions
• WARNING: DO NOT intentionally short circuit the battery pack.
The batteries are capable of providing hazardous output currents if short circuited. The Power Platform is equipped with an internal battery charger circuit. Do not attempt to charge the batteries with an external charger other than the Dranetz-BMI battery charger, since improper charging could cause battery explosion.
• ADVERTENCIA: NO ponga intencionalmente la batería en
cortocircuito. Las baterías son capaces de proporcionar corrientes de salida peligrosas si están en cortocircuito. La Power Platform está equipada con un circuito interno cargador de baterías. No intente cargar las baterías con un cargador externo que no sea el cargador de baterías Dranetz-BMI, puesto que la carga indebida podría hacer que explote la batería.
• AVERTISSEMENT: NE PAS court-circuiter délibérément le bloc-
batterie. Lors d'un court-circuit, les batteries risquent d'é mettre des courants effectifs dangereux. “Power Platform” possède un circuit de chargeur de batterie int égré. Ne pas tenter de charger les batteries au moyen d'un chargeur externe autre que le chargeur de batterie Dranetz-BMI, car un rechargement fautif pourrait entraîner l'explosion de la batterie.
• WARNUNG: Die Batterien dürfen NICHT kurzgeschlossen
werden. Im Falle eines Kurzschlusses können die Batterien lebensgefährliche Ausgangsströme leiten. Power Platform ist mit einem internen Batterieladegerät ausgestattet. Die Batterien sollten nur mit dem Ladegerät von Dranetz-BMI geladen werden. Die Verwendung eines externen Ladegeräts kann zu einer Explosion der Batterien führen.
Page 74
Page 93
Appendix B Maint/Service/Return
TASK 808
Battery Safety Precautions
The following safety precautions must be adhered to. o Keep batteries away from children. Never permit a child to play with a
battery as an ornament or toy.
o Do not disassemble battery or battery pack. o Do not dispose of battery in fire. o Dispose of a used battery promptly in accordance with local
Environmental Protection Agency (EPA) regulations.
o Visually inspect the battery pack for corrosion.
Medidas de seguridad de la batería
Deberán observarse las medidas de seguridad siguientes: o No deberá mantenerse las baterías al alcance de los niños. No
deberá permitirse que un niño juegue con una batería.
o No deberá desensamblarse ninguna batería ni el compartimiento de
la misma.
o No deberá prenderse fuego a una batería. o Toda batería agotada deberá desecharse de manera rápida según
las normas locales de la Agencia de protección del medio ambiente (EPA).
o Deberá verificarse que el compartimiento de las baterías no esté
corroído.
Mesures de sécurité relatives aux batteries
Il est très important de suivre les mesures de sécurité suivantes. o Ne pas laisser les batteries à la portée des enfants. Ne jamais laisser
un enfant jouer avec une batterie.
o Ne pas démonter de batterie ou de bloc-batterie. o Ne pas jeter de batterie dans le feu. o Se débarrasser rapidement des batteries usagées en se conformant
aux règlements de l’EPA (Agence américaine pour la protection de l’environnement).
o Inspecter le bloc-batterie à l’oeil nu pour rechercher les signes de
corrosion.
Batterie-Sicherheitsvorkehrungen
Die folgenden Sicherheitsvorkehrungen müssen beachtet werden.
Page
75
Page 94
Appendix B Maint/Service/Return
TASK 808
o Halten Sie Batterien von Kindern fern. Erlauben Sie einem Kind unter
keinen Umständen, eine Batterie als Verzierung oder Spielzeug zu benutzen.
o Nehmen Sie Batterien oder Batteriepackungen nicht auseinander. o Entsorgen Sie Batterien nicht durch Verbrennen. o Entsorgen Sie verbrauchte Batterien umgehend nach den gesetzlichen
Umweltschutzbestimmungen.
o Prüfen Sie die Batteriepackung optisch auf Korrosion.
The batteries have a safety pressure vent to prevent excessive gas build-up. Corrosion indicates that venting has occurred. Possible causes of venting are: a defective charger, excessive temperature, excessive discharge rate, or a defective cell.
If corrosion is excessive, the battery pack may require replacement. Contact Dranetz-BMI Customer Service Department.
Battery Pack Replacement
The PP4300 contains an easily replaceable internal battery pack. n Refer to Appendix D for ordering information.
• WARNING: Replace with Dranetz-BMI NiCad battery pack
BP4300 only.
• ADVERTENCIA: Reemplace con bateria Dranetz-BMI NiCad
BP4300 solamente.
• AVERTISSEMENT: Remplacer par la batterie Dranetz-BMI
NiCad BP4300 exclusivement.
• WARNUNG: Nur mit Dranetz-BMI NiCad BP4300 Batteriesatz
auswechseln.
NOTE - During normal operation, the battery pack will be slightly warm to the touch.
Page 76
Page 95
Appendix B Maint/Service/Return
TASK 808
Procedure
Follow these steps to replace the battery pack.
Step Action
1 Turn OFF power to the circuit being measured. 2 Press the PP4300 power key to OFF. 3 Disconnect voltage and current probes from the circuit and
the PP4300's rear panel.
4 On the bottom of the PP4300, push the tab to release the
battery cover. 5 Remove the cover. 6 Pull up on removal strap and remove battery pack. 7 Insert the new pack into the compartment making sure to
observe polarity markings. 8 Replace the cover and press down until it latches closed. 9 If discarding the old battery pack, do so in accordance with
Environmental Protection Agency (EPA) regulations. 10 Press the PP4300 power key to on.
B.1.2 Calibration
The recommended calibration interval for the PP4300 is once every 12 months.
n Refer to Return Shipment section below for instructions.
B.3 Return Shipment
Notify Dranetz-BMI Customer Service of your intention to return any product for any reason, including calibration. Do not return the unit, for any reason, without prior approval and instructions from Dranetz-BMI.
To return the PP4300 to Dranetz-BMI for calibration, first contact Dranetz­BMI Customer Service department for a Return Material Authorization (RMA) number.
Telephone: 1-800-372-6832 or 732-287-3680 Fax: 732-248-1834
Page
77
Page 96
Appendix B Maint/Service/Return
TASK 808
Insert correspondence with instructions and RMA reference number inside the package.
If the unit is returned to Dranetz-BMI for service or repair, wrap the unit
securely in heavy packing material and place in a well padded box or crate to prevent shipping damage. If possible, return the unit in its original packing carton or container.
Dranetz-BMI will not be responsible for damage incurred during transit due
to inadequate packing by customer.
B.3.1 Shipping Address
Ship packages to:
Customer Service Department Dranetz-BMI 1000 New Durham Road Edison, NJ 08818
Page 78
Page 97
Appendix C Optional Accessories
TASK 808
Appendix C Optional Accessories
C.1 Introduction
This appendix lists the optional accessories that are available for the PP4300. Descriptions for some of the accessories follow the list.
C.2 Optional Accessories List
Accessory Part Number
Adapter Cable, 658 Current Probe to PP4300 CA4300 Battery Pack (7.2V at 1.6A) BP4300 Current Probe, 1 to 500 A TR2500 Current Probe, 1 to 30 A TR2021 Current Probe, 1 to 300 A TR2019B Current Probe, 10 to 1000 A TR2022 Current Probe, 10 to 3000 A TR2023 Current Probe, 0.1 to 10 A TR2510 Current Probe, 10 to 3000 A TR2520 DRAN-VIEW Windows PC Software 4300EA
4300EA driver External Battery Charger XBC4300 Field Handbook for Electrical Energy Management Field Handbook for Power Quality Analysis HB114414 Isolated Communications Module PP4300RS232 Isolated Current Transformer ISO-65X-5 Lockable Portable Case LPC4300 Memory Card, 512k CARD-512 Memory Card, 1M CARD-1M Memory Card, 2M CARD-2M Memory Card, 4M CARD-4M Memory Card Reader, Data Bus Plug-in Memory Card Reader, Parallel Port Memory Card Reader, Parallel Port, 230 V Memory Card Reader, Serial Port Memory Card Reader, Serial Port, 230 V Portable Field Printer PFP4300
HB114415
Page
79
Page 98
Appendix C Optional Accessories
TASK 808
Reusable Shipping Container RSC4300 Soft Carrying Case SCC4300 TASKCard 808/M Task-808M TASKCard 808/H-M Task-808H/M TASKCard-PQLite TASK-PQLITE TASKCard-PQLite w/Harmonics TASK-PQLITE/H TASKCard-PQLite w/Harmonics & Memory Card Functions TASKCard-PQLite w/Harmonics & Transient Capture TASKCard-PQLite w/Harmonics, Transient Capture, & Memory Card Functions TASKCard-PQLite w/Harmonics, Transient Capture, Memory Card & Energy Functions Voltage Cable Accessory Pack VCP4300
TASK-PQLITE/H/M TASK-PQLITE/H/T TASK-PQLITE/H/T/M TASK-
PQLITE/H/T/M/E
C.2.1 Optional Accessories Descriptions
Adapter cable, 658 current probes to PP4300
This cable allows connection of current probes made for the Dranetz-BMI Model 658 to the PP4300 current input jacks.
Battery Pack
The internal battery pack, containing six sealed, rechargeable NiCad batteries, is used as the PP4300’s primary power source and UPS. These batteries have a length of operation of more than two hours when fully charged and properly maintained.
Current probes
There are seven Dranetz-BMI current probes which can be used with the PP4300: models TR2500, TR2510, TR2520, TR2021, TR2019B, TR2022, TR2023.
TR2500, TR2510, TR2520: These models will measure rms currents from 1 to 500 A, 0.1 to 10 A, 10 to 3000 A, respectively, and plug directly into any of the current inputs on the rear panel.
TR2021, TR2019B, TR2022, TR2023: These four probes were initially made for the Dranetz-BMI model 658 but can be used with the PP4300 by using an adapter cable (part number 116002-G1). They can measure rms currents in the ranges of 0 to 30 A, 1 to 300 A, 10 to 1000 A, and 10 to 3000 A, respectively.
Page 80
Page 99
Appendix C Optional Accessories
TASK 808
Page
81
Page 100
Appendix C Optional Accessories
TASK 808
Memory cards
Memory cards are available in 512K, 1Mb, 2Mb and 4Mb capacities, and are recommended for most applications.
External Battery Charger
This device charges a battery pack while the PP4300 is in use.
Field Handbook for Electrical Energy Management
This reference handbook provides a comprehensive guide for information related to conducting a thorough energy audit, power distribution analysis, and methods of remedying inefficiencies of energy management.
Field Handbook for Power Quality Analysis
This handbook is divided into six sections containing step-by-step instructions for discovering and solving complex power quality problems. Example waveforms and case studies are included.
Isolated Communications Module
The communications module is an optically isolated device using infrared light to transfer text and graphics to a PC or printer. The communications module is designed to connect the Dranetz-BMI PP4300 optical serial port to a standard RS232 serial port. This interface can be connected to an Epson graphics-compatible printer for printing screens, or to a PC running DRAN-LINK to download data. This data can then be viewed using the DRAN-VIEW application.
Isolated Current Transformer
This device allows the connection of other industry-standard 5A output current transformers to Dranetz-BMI equipment.
Lockable Portable Case
The Lockable Portable Case is an optional accessory for the Power Platform 4300 (PP4300). It consists of a rugged, high impact plastic case, a voltage measurement cable assembly and a domestic 115 VAC cable assembly. The cables, case and all connections are waterproof and designed to meet NEMA 4X requirements. The LPC4300 allows the PP4300 to be operated and left unattended in harsh industrial environments.
Memory card readers
Three types of memory card readers are available as options. Each reader provides a different means of communications with an IBM compatible computer. The three types are: RS232 serial port, parallel port, and data bus plug-in.
Page 82
Loading...