DRANETZ - BMI
1000 New Durham Road
Edison, New Jersey 08818-4019
WARNING
Death, serious injury, or fire hazard could result from improper connection of this instrument. Read and
understand this manual before connecting this instrument. Follow all installation and operating
instructio ns while using this instrument.
Connection of this instrument must be performed in compliance with the National Electrical Code (ANSI/
NFPA 70-2005) of USA and any additional safety requirements applicable to your installation.
Installation, operation, and maintenance of this instrument must be performed by qualified personnel
only. The National Electrical Code defines a qualified person as “one who has the skills and knowledge
related to the construction and operation of the electrical equipment and installations, and who has
received safety training on the hazards involved.”
Qualified personnel who work on or near exposed energized electrical conductors must follow applicable
safety related work practices and procedures including appropriate personal protective equipment in
compliance with the Standard for Electrical Safet y Re quirements for Employee Workplaces (ANSI/ NFPA
70E-2004) of USA and any additional workplace safety requirements applicable to your installation.
Published by Dranetz-BMI
1000 New Durham Road
Edison, NJ 08818-4019 USA
Telephone: 1-800-372-6832 or 732-287-3680
Fax: 732-248-1834
Web site: www.dranetz-bmi.com
No part of this book may be reproduced, stored in a
retrieval system, or transcribed in any form or by any
means—electronic, mechanical, photocopying, recording,
or otherwise—without prior written permission from the
publisher, Dranetz-BMI, Edison, NJ 08818-4019.
Printed in the United States of America.
P/N UG-61000 Rev. B
ii
ADVERTENCIA
U
na conexión incorrecta de este instrumento puede producir la muerte, lesiones graves y riesgo de incendio. Lea y
entienda este manual antes de conectar. Observe todas las instrucciones de instalación y operación durante el uso de
este instrumento.
La conexión de este instrumento a un sistema eléctrico se debe realizar en conformidad con el Código Eléctrico
Nacional (ANSI/NFPA 70-2005) de los E.E.U.U., ad emás de cualquier otra norma de seguridad correspon di ent e a su
establecimiento.
La instalación, operación y mantenimiento de este instrumento debe ser realizada por personal calificado solamente.
El Código Eléctrico Nacional define a una persona calificada como "una que esté familiarizada con la construcción y
operación del equipo y con los riesgos involucrados."
El personal cualificado que trabaja encendido o acerca a los conductor es eléctricos energizad os expuestos debe seg uir
prácticas y procedimientos relacionados seguridad aplicable del trabajo incluyendo el equipo protector personal
apropiado en conformidad con el estándar para los requisitos de seguridad eléctricos para los lugares de trabajo del
empleado (ANS I/NFPA 70E-2004) de los E.E.U.U. y cualqu ier requisito de seguridad adicional del lugar de traba j o
aplicable a su instalación.
AVERTISSEMENT
Si l'instrument est mal connecté, la mort, des blessures graves, ou un danger d'incendie peuvent s'en suivre. Lisez
attentivement ce manuel avant de connecter l'instrume nt. Lorsque vous utilisez l'instrument, suivez toutes les
instructions d'installation et de service.
Cet instrument doit être connecté conformément au National Electrical Code (ANSI/NFPA 70-2005) des Etats-Unis
et à toutes les exigences de sécurité applicables à votre installation.
Cet instrument doit être installé, ut ilisé et entretenu uniquement par un personnel quali fi é . Sel on le National
Electrical Code, une personne est qualifiée si "elle connaît bien la co nstruction et l'utilisation de l'équipement, ainsi
que les dangers que cela implique".
Le personnel qualifié qui travaillent dessus ou s'approchent des conducteurs électriques activés exposés doit suivre
des pratiques en matière et des procédures reliées pa r sûreté applicable de trav ail comprenant le matériel de protection
personnel approprié conformémen t à la norme pour des conditions de sûreté électriques pour les lieux de travail des
employés (ANSI/NFPA 70E-2004) des Etats-Unis et toutes les conditions de sûreté additionnelles de li eu de travail
applicables à votre installation.
WARNUNG
Der falsche Anschluß dieses Gerätes kann Tod, schwere Verletzungen oder Feuer verursachen. Bevor Sie dieses
Instrument anschließen, müssen Sie die Anleitung lesen und verstanden haben. Bei der Verwendung dieses
Instruments müssen alle Installation- und Betriebsanweisungen beachtet werden.
Der Anschluß dieses Instruments muß in Übereinstimmung mit den nationalen Bestimmungen für Elektrizität
(ANSI/NFPA 70-2005) der Vereinigten Staaten, sowie allen weiteren, in Ihrem Fall anwendbaren
Sicherheitsbestimmungen, vorgenommen werden.
Installation, B etrieb und Wartung dieses Instruments dür fen nur von Fachpersonal durc hgeführt werden. In dem
nationalen Bestimmungen für Elektrizität wird ein Fachmann als eine Person bezeichnet, welche "mit der Bauweise
und dem Betrieb des Gerätes sowie den dazugehörigen Gefahren vertraut ist."
Qualifiziertes Personal, das an bearbeiten oder herausgestellte angezogene elektrische Leiter sich nähern,
muß anwendbare Sicherheit bezogener Arbeit Praxis und Verfahren einschließlich passende persönliche
schützende Ausrüstung gemäß dem Standard für elektrische Sicherheitsauflagen für AngestelltArbeitsplätze (AN SI/NFPA 70E-2004) der Vereinigten Staaten und alle zusätzlichen
Arbeitsplatzsicherheitsauflagen folgen, die auf Ihre Installation anwendbar sind.
iii
Safety Summary
Definitions
Symbols
Definiciones
WARNING statements inform the user that certain conditions or practices could result
in loss of life or physical harm.
CAUTION statements identify conditions or practices that could harm the 61000, its
data, other equipment, or property.
NOTE statements call attention to specific information.
The following International Electrotechnical Commission (IEC) symbols are marked
on the top and rear pa nel in the immediate vicinity of the refe ren ced terminal or device:
!
Las ADVERTENCIAS informan al usuario de ciertas condiciones o prácticas que
podrían producir lesiones mortales o daño físico.
Las PRECAUCIONES identifican condici ones o prác tica s que podrí an dañar la 61000,
sus datos, otros equipos o propiedad.
Caution, refer to accompanying documents (this manual).
Direct current (DC) operation of the terminal or device.
Power Switch
Símbolos
Las NOTAS llaman la atención hacia la información específica.
Los siguientes símbolos de la Comisión Internacional Electrotécnica (IEC) aparecen
marcados en el panel superior y el posterior inmediatos al terminal o dispositivo en
referencia:
!
Precaución, consulte los documentos adjuntos (este manual).
Operación de corriente continua (CC) del terminal o dispositivo.
Interruptor de encendido
Continued on next page
iv
Safety Summary,
Continued
Définitions
Symboles
Definitionen
Les messages d’AVERTISSEMENT préviennent l’utilisateur que certaines conditions
ou pratiques pourraient entraîner la mort ou des lésions corporelles.
Les messages de MISE EN GARDE signalent des condi ti ons ou pratiques susceptibles
d’endommager “61000”, ses données, d’autres équipements ou biens matériels.
Les messages NOTA attirent l’attention sur certains renseignements spécifiques.
Les symboles suivants de la Commission éle ctrotechniq ue intern ationale (CEI ) figurent
sur le panneau arrière supérieur situé à proximité du terminal ou de l’unité cité:
!
WARNUNGEN informieren den Benutzer darüber, daß bestimmte Bedingungen oder
Vorgehensweisen körperliche oder tödliche Verletzungen zur Folge haben können.
VORSICHTSHINWEISE kennzeichnen Bedingungen oder Vorgehensweisen, die zu
einer Beschädigung von 61000, seiner Daten oder anderer Geräte bzw. von Eigentum
führen können.
Mise en garde, consultez les documents d’accompagnement (ce manual).
Fonctionnement du terminal ou de l’unité en courant continu (CC).
Interrupteur de tension
Symbole
HINWEISE machen auf bestimmte Informationen aufmerksam.
Die folgenden Symbole der Internationalen Elektrotechnischen Kommission
(International Electrotechnical Commission; IEC) befinden sich auf der Abdeck- und
Seitenplatte unmittelbar am betreffenden Terminal oder Gerät.
The following safety precautions must be followed whenever any type of voltage or
current connection is being made to the 61000.
• Wear proper Personal Protective Equipment, including safety glasses and insulated
gloves when making connections to power circuits.
• Hands, shoes and floor must be dry when making any connection to a power line.
• Before each use, inspect all cables for breaks or cracks in the insulation. Replace
immediately if defective.
• Set the 61000 power switch to Off.
Before connecting to electric circuits to be monitored, open their related circuit
breakers or disconnects. DO NOT install any connection of the 61000 to live power
lines.
• Pods should be connected first to the 61000, then connect to the circuit to be
monitored.
• If the equipment is used in a ma nner not specified in this user’s guide, th e pro tec tion
provided by the equipment may be impaired.
These safety precautions are repeated where appropriate throughout this manual.
vi
Statements and Notices
Statement of
warranty
Statement of
reliability
Notice regarding
FCC compliance
All products of Dranet z-BMI are warranted to th e original pu rchaser against defective
material and workmanship for a period of one year from the date of delivery. DranetzBMI will repair or replace , at its opti on, all defec tive equ ipment that is returne d, freig ht
prepaid, during th e warrant y period. There wil l be no char ge for repair provided t here is
no evidence that the equi pment ha s been mishand led or ab used. Thi s warr anty s hall not
apply to any defects resulting from improper or inadequate maintenance, buyersupplied hardware/software interfacing, unauthorized modification or misuse of the
equipment, operation outside of environmental specifications, or improper site
preparation or maintenance.
The information in this m anual has be en reviewed and is believ ed to be entirely
reliable, however, no responsibility is assumed for any inaccuracies. All material is for
informational purposes only and is subject to change without prior notice.
This device has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable prote cti on against harmful interfere nce when the equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential are a is likel y to cause harmfu l inter feren ce in which cas e the
user will be required to correct the interference at his/her own expense.
Notice regarding
proprietary
rights
This publication contains information proprietary to Dranetz-BMI. By accepting and
using this manual, you agree that the information contained herein will be used solely
for the purpose of operating equipment of Dranetz-BMI.
Continued on next page
vii
Statements and Notices,
Continued
Copyright
Trademarks
This publication is protected under the Copyright laws of the United States, Title 17 et
seq. No part of this p ublica tion may be rep roduced , tr ansmit ted, t ranscr ibed, s tored in a
retrieval system, or translated into any langua ge or computer language, in any form, by
any means, electronic, mechanical, magnetic, optical, chemical, manual, or otherwise,
without the prior written consent of Dranetz-BMI, 1000 New Durham Road, Edison,
New Jersey 08818.
About the 61000; Unpacking the 61000; Standard Accessories; Physical Description
About the 61000
61000
description
The Encore Series
world-class data acquisition products developed by Dranetz-BMI - the DataNode
family of products for the Signature System
integration of power measurement capabilities coupled with an innovative modular
design set the 61000 apart as a truly revolutionary product. The modular concept
applies to both the hardware configuration and firmware architecture allowing the unit
to be a multi-purpose instrument. 61000 works from being a diagnostic tool to
providing preventive and predictive information as an embedded solution. The
instrument is designed to operate either locally as a stand-alone unit with the optional
LCD panel installed or via r emote comput er using the Encore Series
is compliant with IEEE1159, IEC61000-4-30 Class A, EN50160 standards, and more.
It can be installed in a permanent or semi-permanent installation.
C
HAPTER
Introduction
TM
61000 System hereinafter referred to as 61000 encompasses two
®
and the PowerXplorer® PX5. This
TM
Software. 61000
1
Interface to
61000
Data
communication
61000 can operate locally as a stand-alone unit and/or remotely as a data acquisition
module connected to t he Encore Series Software:
Local operation with optional user interface
As a stand-alone unit, the 61000 can be outfitted with optional liquid crystal display
(LCD) as user interface. Th e optio nal touch s creen d ispla y can be mounted on the f ront
panel of the instrument (rack mount) or as a separate unit (remote display), depending
on user-selected enclosure or packaging. The LCD panel provides immediate
accessibility to monitoring all measurement parameters and instrument setup and
configurations.
Remote computer operation
The 61000 can operate as a data acquisition module connected to the Encore Series
Software. This software provides a centralized connection point for remote devices,
turning the computer into a self-contained web server. Encore Series Software permits
remote communications with th e 61000, with t he conve ntion al Inter net br owser a s user
interface. Remote operation includes instrument setup and configurations and
monitoring real-time parameters, disturbance and trend data.
61000 can communicate data to the Encore Series Software via Ethernet (wired,
wireless or fiber-optic based), RS485, USB, and land/cellular modem via RS232. The
physical modem is an external option and is not included as part of the standard
product. This extends greater flexibility in the choice of communications interface for
remote operation.
Continued on next page
1-1
About the 61000, continued
Input/Output
modules
Virtual analyzer
platform
61000 provides dedicated processing power via the separate and independent
connection for each input/output module installed. This modular and configurable
design shatters the traditional 8-channel (4 voltage, 4 current) instrument format.
Choose from the voltage, current, and data acquisition modules to build from one to
four instruments in a single, compact, cost-effect ive format. The available modules are :
• AC Voltage Modules - 4 channels using either terminal block, safety jack, or 25-pin
connector to external voltage pod
• AC Current Modules - 4 channels for clamp-on CTs or 25-pin connector to external
CT pod
• Digital Input/Output Modules - 8 channels
• Transducer Input Modules - 4 channels
NOTE: The Modules are factory- inst alled . They cann ot be inst alle d in the fie ld and are
not user accessible.
See Chapter 2 Controls, Indicators and Connectors for more information on the input
modules. Chapter 3 Circuit Diagrams for Power Monitoring contains wiring diagrams
for when power measurements are to be made.
At the heart of the 61000 is the virtual analyzer platform or ‘instruments within an
instrument’ configuration. The virtual analyzer allows the instrument to distinguish
data operations in mul tiple modules. The user can confi gure up t o four vi rtual a nalyzers
per 61000 instrument.
This guide
The 61000 firmware architecture is based on the concept of separating the various
stages of acquisition, characterization, communications and visualization with clearly
defined interfaces that decouple one from the other. The instrument can monitor power
quality phenomena for troubleshooting and/or compliance purposes. It can record
inrush conditions, carry out long-term statistical studies to establish performance
baselines, and perfor m field-based equipment t esting and eval uation for commissionin g
and maintenance. The firmware inte grates intuit ive instrument setup procedures for
each module analyzer to ensure the capture of all relevant data for additional post
process analysis, report writing, and data archiving using other compatible DranetzBMI software applications such as PQView
®
.
This guide is only part of a complet e document set designed to provide comprehensive
information about the 61000. It primarily contains instructions on how to set up the
basic 61000 hardware for operation. It describes the input module interface and the
wiring configurati ons pos sible fo r volt age/c urr ent c onnect ion. It al so des cri bes t he dat a
communication ports availa ble in the backp lane of the ins trument. An overview on how
to set up the 61000 either as a stand-alone unit or as a data acquisition module
connected to the Encore Series Software is included in this guide.
For operational description using the local LCD panel, refer to the 61000 Optional User Interface Guide (check with Dranetz-BMI for availability).
For operational description using remote communications via Encore Series Software,
refer to the Encore Series Software User’s Guide.
1-2
Unpacking the 61000
Chapter 1/ Introduction
Unpacking
Shipping
damage
inspection
For maximum protection against possible shipping damage, the 61000 has been sealed
in a two-piece, plastic suspension pack, enclosed within a durable shipping carton.
After opening the carton, inspect the contents for possible shipping damage and check
the carton inventory.
Unpack the 61000 from the carton as follows:
StepAction
1Remove any remaining literature inside the top of the carton.
2Carefully remove the 61000 from its shipping carton.
3Remove all accessories inside the carton. Check that the standard (see
page 1-4) and optional accessories (see Appendix A) you ordered are
included.
Visually inspect the 61000 for possible shipping damage. If any damage exists, first
notify and file an insurance claim with your carrier or underwriter or both. Then noti fy
Dranetz-BMI Customer Service Department of your intentions to return the unit. DO
NOT return the 61000 without prior instructions from Dranetz-BMI Customer Service
Department. Dranetz-BMI Customer Service Department can be reached at (732) 2873680 or 1-800-372-6832.
Repacking for
return shipment
Return notice
If the unit must be return ed to Dranetz -BMI for servi ce or repai r , wrap the unit sec urely
in heavy packaging mater ial and place in a well padded box or crate to p revent damag e.
Do not return the 61000 in an unpadded box. Dranetz-BMI will not be responsible for
damage incurred during transit due to inadequate packing on your part.
Notify Dranetz-BMI Customer Service of your intention of returning the unit. Do not
return the unit without prior instructions from Dranetz-BMI. Dranetz-B MI Customer
Service Department can be reached at (732) 287-3680 or 1-800-372-6832.
1-3
61000 Accessories
61000 Accessories
Standard
accessories
Optional
accessories
Technical
specifications
External dc
power source
Encore Series
61000 firmware
upgrade
Calibration
The standard accessory included with the 61000 is the Encore Series 61000 System
User’s Guide, P/N UG-61000.
Refer to Appendix A for the list of hardware and software optional accessories
available for use with 61000. The unit mainframe can be custom-built with optional
input module connecto rs, co mmunica tion port c onne ctors , GPS ant enna co nnec tor, and
a 12V dc power input jack.
Specifications for the 61000 measured parameters, computed parameters, voltage
modules, current probes, and pod accessories are listed in Appendix B.
To connect to an external dc power source, refer to Appendix C.
Refer to Appendix D for instructions on how to upload the latest available firmware
version to the Encore Series 61000 System mainframe.
The recommended calibration interval for this unit is once every 12 months.
We recommend that you return the unit to the factory for calibration. If you decide to
do so, first contact the Dranetz-BMI Customer Service Department to obtain an
Authoriz ation Number.
Telephone: (732) 287-3680 or 1-800-372-6832
FAX: (732) 248-9240
Fill out the Repair /Servi ce Ord er for m enclos ed in the shippi ng car ton and ship i t alon g
with the unit to the Dranetz-BMI Repair Department. (If this form is missing, ask the
Dranetz-BMI Customer Service Department for a replacement.)
1-4
Physical Description0
Chapter 1/ Introduction
Dimensions
Optional display
panel
Connector panel
External dc
power source
The 61000 in the desktop e ncl os ure without the optional LCD panel is a self -contained
instrument weighing 4 pounds and measu ring 11.25” width x 3.5” height x 7 3/4 depth.
When used with the LCD panel installed in 19” rack, the instrument weighs 5 pounds
and has an 8” depth.
The optional user interf ace is a 1/4 VGA LCD panel with touch screen menus for l oca l
operation and configuration.
The backplane panel consists of industrial grade, voltage/current/pod connectors,
communication port connectors, dc input power connector, and power switch. See
Chapter 2 Controls, Indicators and Connectors for description.
To connect to an external dc power source, refer to Appendix C.
1-5
This page intentionally left blank.
1-6
Controls, Indicators, and Connectors
External Components; Connecting to AC Power Source; Communications Interface;
Input/Output Module Connectors; Connecting Voltage Measurement Cables;
Connecting Current Probes; Connecting Voltage/Current Input Pods; Connecting
Digital Input Connectors
External Components
C
HAPTER
2
Description
Front panel
External components refer to operator related external controls, indicators and
connectors.
The 61000 front panel display may look different depending on the enclosure options
specified.
Front panel without the local LCD User Interface
See below for description of the 61000 front display without the LCD user interface.
SF-201
PartFunction
1Sta tus Indicator. LED will l ig ht steadily when abnormal condition is dete ct ed.
The unit is operating normally when light is off.
2Monitoring On. LED will light if monitoring is on. Monitoring status is off
when light is off.
3Power Indi ca tor. LED will blink when the unit power switch is turned on. The
number of blinks correspond to the number of modules installed.
Continued on next page
2-1
External Components, continued
Front panel
(continued)
Front panel with the optional LCD User Interface in Rack Mount Eclosure
The front view primarily shows the color touch screen LCD. See below for descr ip ti on
of the 61000 front display with the LCD panel installed.
SF-202
PartFunction
1LCD Rack Mount Protective Enclosure with rack handles
2Liquid Crystal Display (LCD). Provides 3.75 x 4.75 inches display consisting
of 1/4 VGA size screen of text and graphic information. The color LCD is
equipped with touch screen technology, operable using the finger and/or
stylus. Touch screen display permits menu sel ection, alphanumeric data entry,
and has a compact fluorescent (CCFL) backlighting that is on for low light
level viewing.
2-2
The following are some basic care instructions for the LCD monitor
:
• Use and store the unit within the specified temperature and humidi ty range.
The LCD screen may be adversely affec ted by exposure to high temperat ure
or humidity. Condensation or moisture produced by sudden temperature
changes may also damage the LCD screen. Clean any moisture from su rface
immediately.
• Be careful when cleaning or removing stains on the LCD surface. Gently
wipe the surface with a soft cloth or cotton pad. Isopropyl alcohol may be
used, but make sure that all solvent residue is removed.
• Do not apply exces si ve f orce to the LCD surface. The LCD screen contains
sensitive electronic components that may be damaged due to strong impact.
Chapter 2/ Controls, Indicators, and Connectors
r
Rear panel
The rear panel consists of the input/output module connectors, communication ports,
and power switch. See below for description of a typical 61000 rear panel. Exact
configuration is dependent on the optional input/output modules ordered.
SF-203
Power Input
See Connecting to DC Powe
Source, page 2-4 on how to
power the unit on/off
Important
Communications Ports
See Communications Interface, page 2-7
for a description of the 61000 data ports
Input Modules
See Input Module Connectors, page 2-9
for a detailed description of the input
module connectors
Dranetz-BMI recommends that you leave adequate working space for rear panel
connections to the 61000. This rear clearance space is necessary for proper installation
of the measurement cables, pr obes and pods as wel l as extern al communic ations device
for the 61000.
2-3
Connecting to AC Power Source
Connecting to AC Power Source
Power
specifications
The 61000 AC adapter can be connected to a 90-265V ac power input source
(dependent on model version) or directly to a 12V dc external power source. Refer to
Appendix C for information about connecting to an external dc power source. For
connection to voltages outside of the specified 90-265V ac, a Phase Power Adapter is
required. Phase Power Adapter is an optional accessory available at Dranetz-BMI.
Refer to Appendix A Optional Accessories for ordering information.
CAUTIONAlways set the power switch to the off position befor e connecting or disconnecting
the input power cable.
Operation of the 61000 from an ac voltage source other than the rated voltage
input stated on the unit nameplate can cause damage to the unit.
PRECAUCIONSiempre fije el inter ruptor de encendido en la posic ión apagada antes de conect ar
o desconectar el cable de energía de entrada.
La operación del 61000 desde una fuen te de volt aje de ca que no sea la e ntrada d e
voltaje nominal indicada en la placa de identificación de la unidad puede causar
daños a la unidad.
MISE EN
GARDE
Mettez toujours l’interrupteur dans la position ouverte avant de connecter ou de
déconnecter le câble d’alimentation primaire.
Mettez toujours l’interrupteur dans la position ouverte avant de connecter ou de
déconnecter le câble d’alimentation primaire.
VORSICHTVor dem Einstecken bzw. Ausstecken des Eingangsnetzkabels den Netzschalter
immer in die Aus-Stellung bringen.
Der Betrieb des 61000 von einer Wechselspannungsquelle, die nicht dem auf der
Namensplatte der Einheit aufgeführten Nennspannungseingang entspricht, kann
zur Beschädigung der Einheit führen.
2-4
Chapter 2/ Controls, Indicators, and Connectors
Power input/
switch diagram
The power switch panel includes LED indicators, the On/Off power button, and power
input decal and connector. See input power diagram and description below.
1
2
3
4
SF-204
PartFunction
1Power Indicator. LED will blink when power is turned on. The number of
blinks correspond to the number of modules installed.
2On/Off Power Button. Push for on, push for off.
NOTE: The on/off po wer switch shuts the unit down, but al l ows the battery to
continue to charge even with the switch in the Off position.
3Power input decal and connector. The decal provides information about input
power rating. Plug in the AC Adapter output cable into the input connector.
AC input power source is specified as follows:
• Voltage range, 90-265V ac.
• Frequency, 50/60Hz.
• Power Consumption, 10W.
See page 2-6 for the procedure on how to connect to an ac power source.
4Ground LUG. Connect with suitable wire to earth ground conductor or
connection.
2-5
Connecting to AC Power Source, continued
Connecting to
an AC power
source
Follow these steps to connect to an ac power source.
StepAction
1Set the power switch to Off.
2Verify the operating voltage range for your 61000, as marked on the
power input decal.
Note:
For source voltages outside the range of the unit, a Phase Power
Adapter is available as an optional accessory. It converts the selected
source voltage to the output voltage needed to operate the unit. Refer to
Appendix A Optional Accessories for information.
3Connect the appropriate power cord for the voltage rating of the unit.
Make connection to the instrument first.
4Connect power cord to the power source.
5Turn power switch to On.
2-6
Communications Interface
Chapter 2/ Controls, Indicators, and Connectors
Communications
options
The 61000 can communicate to a compute r via Ethernet networ k, RS232, RS485, USB,
or land/cellular modem. This remote communication network enables the 61000 to act
as a DataNode for the Encore Series Software, or as a stand-alone monitor.
Computer
requirem ents
The computer used must be equipped with the same communication interface as the
61000. For example, if the instr ument is using Ethernet , the comput er must li kewise be
using Ethernet.
The computer must be loaded wit h the Encore Seri es Software package, which conve rts
the computer into a web server and enables it to browse data and information col le ct ed
by the 61000.
WARNINGTo avoid the risk of electric shock, do not remove communications instrument
until all power is de-energized to all power and measurement circuits.
ADVERTENCIA
Para evitar el riesgo de descargas eléctricas, no retire el instrumento de
comunicaciones hasta desconectar todo suministro de energía hacia todos los
circuitos de energía y medición.
AVERTISSEMENT
Pour éviter le risque de choc électrique, ne retirez pas le instrument de
communications avant que tous les circuits d’alimentation et de mesure aient été
mis hors tension.
WARNUNGZur Vermeidung eines elektrischen Schlags die Kommunikationsplatte erst
instrument, wenn die Stromzufuhr zu allen Strom- und Meßschaltungen
unterbrochen wurde.
Remote
operation guide
Remote operation setup and instructions for 61000 are contained in the Encore Series
Software User’s Guide.
2-7
Communications Interface, continued
Communication
port diagram
The communications panel below shows the location of data ports available in
61000.The communications panel diagram and description as shown below appears in
the rear panel of the instrument.
Parts table
Remote
operation guide
SF-205
PartFunction
110/100BaseT (RJ45). Allows connection via Ethernet cable.
2USB. Not activate d at this time; future option.
3COM 1. RS232 serial port for land/cellular modem connection. Allows
administrative set up of the 61000 for IP addressing, etc.
4RS485 serial port. Can be used for multi-drop serial connections.
5Optional GPS Antenna. Allows use of optional cable to active antenna.
6Power Connector for External GM28/29 Modem.
See Chapter 4 External Communications for a discussion of the external
communications device and software applications necessary for remote computer
operation of 61000.
2-8
Input/Output Module Connectors
Chapter 2/ Controls, Indicators, and Connectors
Input/Output
module types
Users can choose different types of analog and digital input/output modules that can be
installed on the rear panel of 61000. The modules must be selected at time of order. In case
users want additional modules installe d, the unit must be return ed to the factory. The input/
output modules allow a variety of voltage and current measurement cables, probe types, or
pods to connect to the instrument for voltage, current, and/or digital signal monitoring.
The voltage and current connectors are designed in modular configuration, with the
following analog input module measurement point interface:
• AC/DC Voltage Module with safety connectors (Model 61MVB)
• AC/DC Voltage Module with terminal block connectors (Model 61MVS)
• AC/DC Current Module with connectors for external CTs (Model 61MAC)
• AC/DC Module for Voltage or Current Pod (Model 61MZP)
The eight-channel digi tal inp ut module Mo del 61MDIN allo ws users to mon itor on/o ff ty pe
digital signals, such as breaker or switch signal positions. Digital inputs can be configured
to provide demand interval synchronization, pulse counting, KYZ metering, or to provide
start/stop monitoring control.
Digital output module allows certain events to result in change of state of a relay contact.
See Appendix A for specifications of Dranetz-BMI digital output module Models
61MDOH and 61MDOL.
Transducer input module Models 61MXVS and 61MXAS can record and trigger on
analog signal levels in either the 0-24V and 4-20mA range respectively.
Input channels
WARNING
Input channels for the modules installed on the rear connector panel are labelled ±A, ±B,
±C, and ±D. You must turn on any input channel to be used for monitoring. If a channel is
not turned on, no data will be collected for it.
Death, serious injury, or fire hazard could result from improper connection of this
instrument. Read and understand this manual before connecting this instrument. Follow
all installation and opera ti ng instructions while using this instrument.
Connection of this instrument must be performed in compliance with the National
Electrical Code (ANSI/NFPA 70-2005) and any additional safety requirements applicable
to your installat i on.
Installation, operation, and maintenance of this instrument must be performed by
qualified personnel only. The National Electrical Code defines a qualified person as “o ne
who has the skills and knowledge related to the construction and operation of the electrical
equipment and installations, and who has received safety training on the hazards
involved.”
Qualified personnel who work on or near exposed energized electrical conductors must
follow applicable safety related work practices and procedures including appropriate
personal protective equipment in compliance with the Standard for Electrical Safety
Requirements for Employee Workplaces (ANSI/NFPA 70E-2004) of USA and any
additional workplace safet y requirements applicable to your installation.
Continued on next page
2-9
Input/Output Module Connectors, continued
ADVERTENCIA
Una conexión incorrecta de este instrumento puede producir la muerte, lesiones
graves y riesgo de incendio. Lea y enti enda este manual antes de conectar. Observe
todas las instrucciones de instalación y operación durante el uso de este
instrumento.
La conexión de este instrumento a un sistema eléctrico se debe realizar en
conformidad con el Código Eléctrico Nacional (ANSI/NFPA 70-2005) de los
E.E.U.U., además de cualquier otra norma de seguridad correspondiente a su
establecimiento.
La instalación, operación y mantenimiento de este instrumento debe ser realizada
por personal calificado solamente. El Código Eléctrico Nacional define a una
persona calificada como "una que esté familiarizada con la construcción y
operación del equipo y con los riesgos involucrados."
El personal cualificado que trabaja encendido o acerca a los conductores
eléctricos energizados expuestos debe seguir prácticas y procedimientos
relacionados seguridad aplicable del trabajo incluyendo el equipo protector
personal apropiado en conformidad con el estándar para los requisitos de
seguridad eléctricos para los lugares de trabajo del empleado (ANSI/NFPA 70E-
2004) de los E.E.U.U. y cualquier requisito de seguridad adicional del lugar de
trabajo aplicable a su instalación.
AVERTISSEMENT
Si l'instrument est mal connecté, la mort, des blessures graves, ou un danger
d'incendie peuvent s'en suivre. Lisez attentivement ce manuel avant de connecter
l'instrument. Lorsque vous utilisez l'instrument, suivez toutes les instructions
d'installation et de service.
Cet instrument doit être connecté conformément au National Electrical Code
(ANSI/NFPA 70-2005) des Etats-Unis et à toutes les exigences de sécurité
applicables à votre installation.
Cet instrument doit être inst allé, util isé et entre tenu uniquement par un perso nnel
qualifié. Selon le National Electrical Code, une personne est qualifiée si "elle
connaît bien la construction et l'utilisation de l'équipement, ainsi que les dangers
que cela implique".
Le personnel qualifié qui travaillent dessus ou s'approchent des conducteurs
électriques activés exposés doit suivre des pratiques en matière et des procédures
reliées par sûreté applicable de travail comprenant le matériel de protection
personnel approprié conformément à la norme pour des conditions de sûreté
électriques pour les lieux de travail des employés (ANSI/NFPA 70E-2004) des
Etats-Unis et toutes les conditions de sûreté additionnelles de lieu de travail
applicables à votre installation.
2-10
Continued on next page