DRANETZ - BMI
1000 New Durham Road
Edison, New Jersey 08818-4019
Page 2
WARNING
Death, serious injury, or fire hazard could result from improper connection of this instrument. Read and
understand this manual before connecting this instrument. Follow all installation and operating
instructio ns while using this instrument.
Connection of this instrument must be performed in compliance with the National Electrical Code (ANSI/
NFPA 70-2005) of USA and any additional safety requirements applicable to your installation.
Installation, operation, and maintenance of this instrument must be performed by qualified personnel
only. The National Electrical Code defines a qualified person as “one who has the skills and knowledge
related to the construction and operation of the electrical equipment and installations, and who has
received safety training on the hazards involved.”
Qualified personnel who work on or near exposed energized electrical conductors must follow applicable
safety related work practices and procedures including appropriate personal protective equipment in
compliance with the Standard for Electrical Safet y Re quirements for Employee Workplaces (ANSI/ NFPA
70E-2004) of USA and any additional workplace safety requirements applicable to your installation.
Published by Dranetz-BMI
1000 New Durham Road
Edison, NJ 08818-4019 USA
Telephone: 1-800-372-6832 or 732-287-3680
Fax: 732-248-1834
Web site: www.dranetz-bmi.com
No part of this book may be reproduced, stored in a
retrieval system, or transcribed in any form or by any
means—electronic, mechanical, photocopying, recording,
or otherwise—without prior written permission from the
publisher, Dranetz-BMI, Edison, NJ 08818-4019.
Printed in the United States of America.
P/N UG-61000 Rev. B
ii
Page 3
ADVERTENCIA
U
na conexión incorrecta de este instrumento puede producir la muerte, lesiones graves y riesgo de incendio. Lea y
entienda este manual antes de conectar. Observe todas las instrucciones de instalación y operación durante el uso de
este instrumento.
La conexión de este instrumento a un sistema eléctrico se debe realizar en conformidad con el Código Eléctrico
Nacional (ANSI/NFPA 70-2005) de los E.E.U.U., ad emás de cualquier otra norma de seguridad correspon di ent e a su
establecimiento.
La instalación, operación y mantenimiento de este instrumento debe ser realizada por personal calificado solamente.
El Código Eléctrico Nacional define a una persona calificada como "una que esté familiarizada con la construcción y
operación del equipo y con los riesgos involucrados."
El personal cualificado que trabaja encendido o acerca a los conductor es eléctricos energizad os expuestos debe seg uir
prácticas y procedimientos relacionados seguridad aplicable del trabajo incluyendo el equipo protector personal
apropiado en conformidad con el estándar para los requisitos de seguridad eléctricos para los lugares de trabajo del
empleado (ANS I/NFPA 70E-2004) de los E.E.U.U. y cualqu ier requisito de seguridad adicional del lugar de traba j o
aplicable a su instalación.
AVERTISSEMENT
Si l'instrument est mal connecté, la mort, des blessures graves, ou un danger d'incendie peuvent s'en suivre. Lisez
attentivement ce manuel avant de connecter l'instrume nt. Lorsque vous utilisez l'instrument, suivez toutes les
instructions d'installation et de service.
Cet instrument doit être connecté conformément au National Electrical Code (ANSI/NFPA 70-2005) des Etats-Unis
et à toutes les exigences de sécurité applicables à votre installation.
Cet instrument doit être installé, ut ilisé et entretenu uniquement par un personnel quali fi é . Sel on le National
Electrical Code, une personne est qualifiée si "elle connaît bien la co nstruction et l'utilisation de l'équipement, ainsi
que les dangers que cela implique".
Le personnel qualifié qui travaillent dessus ou s'approchent des conducteurs électriques activés exposés doit suivre
des pratiques en matière et des procédures reliées pa r sûreté applicable de trav ail comprenant le matériel de protection
personnel approprié conformémen t à la norme pour des conditions de sûreté électriques pour les lieux de travail des
employés (ANSI/NFPA 70E-2004) des Etats-Unis et toutes les conditions de sûreté additionnelles de li eu de travail
applicables à votre installation.
WARNUNG
Der falsche Anschluß dieses Gerätes kann Tod, schwere Verletzungen oder Feuer verursachen. Bevor Sie dieses
Instrument anschließen, müssen Sie die Anleitung lesen und verstanden haben. Bei der Verwendung dieses
Instruments müssen alle Installation- und Betriebsanweisungen beachtet werden.
Der Anschluß dieses Instruments muß in Übereinstimmung mit den nationalen Bestimmungen für Elektrizität
(ANSI/NFPA 70-2005) der Vereinigten Staaten, sowie allen weiteren, in Ihrem Fall anwendbaren
Sicherheitsbestimmungen, vorgenommen werden.
Installation, B etrieb und Wartung dieses Instruments dür fen nur von Fachpersonal durc hgeführt werden. In dem
nationalen Bestimmungen für Elektrizität wird ein Fachmann als eine Person bezeichnet, welche "mit der Bauweise
und dem Betrieb des Gerätes sowie den dazugehörigen Gefahren vertraut ist."
Qualifiziertes Personal, das an bearbeiten oder herausgestellte angezogene elektrische Leiter sich nähern,
muß anwendbare Sicherheit bezogener Arbeit Praxis und Verfahren einschließlich passende persönliche
schützende Ausrüstung gemäß dem Standard für elektrische Sicherheitsauflagen für AngestelltArbeitsplätze (AN SI/NFPA 70E-2004) der Vereinigten Staaten und alle zusätzlichen
Arbeitsplatzsicherheitsauflagen folgen, die auf Ihre Installation anwendbar sind.
iii
Page 4
Safety Summary
Definitions
Symbols
Definiciones
WARNING statements inform the user that certain conditions or practices could result
in loss of life or physical harm.
CAUTION statements identify conditions or practices that could harm the 61000, its
data, other equipment, or property.
NOTE statements call attention to specific information.
The following International Electrotechnical Commission (IEC) symbols are marked
on the top and rear pa nel in the immediate vicinity of the refe ren ced terminal or device:
!
Las ADVERTENCIAS informan al usuario de ciertas condiciones o prácticas que
podrían producir lesiones mortales o daño físico.
Las PRECAUCIONES identifican condici ones o prác tica s que podrí an dañar la 61000,
sus datos, otros equipos o propiedad.
Caution, refer to accompanying documents (this manual).
Direct current (DC) operation of the terminal or device.
Power Switch
Símbolos
Las NOTAS llaman la atención hacia la información específica.
Los siguientes símbolos de la Comisión Internacional Electrotécnica (IEC) aparecen
marcados en el panel superior y el posterior inmediatos al terminal o dispositivo en
referencia:
!
Precaución, consulte los documentos adjuntos (este manual).
Operación de corriente continua (CC) del terminal o dispositivo.
Interruptor de encendido
Continued on next page
iv
Page 5
Safety Summary,
Continued
Définitions
Symboles
Definitionen
Les messages d’AVERTISSEMENT préviennent l’utilisateur que certaines conditions
ou pratiques pourraient entraîner la mort ou des lésions corporelles.
Les messages de MISE EN GARDE signalent des condi ti ons ou pratiques susceptibles
d’endommager “61000”, ses données, d’autres équipements ou biens matériels.
Les messages NOTA attirent l’attention sur certains renseignements spécifiques.
Les symboles suivants de la Commission éle ctrotechniq ue intern ationale (CEI ) figurent
sur le panneau arrière supérieur situé à proximité du terminal ou de l’unité cité:
!
WARNUNGEN informieren den Benutzer darüber, daß bestimmte Bedingungen oder
Vorgehensweisen körperliche oder tödliche Verletzungen zur Folge haben können.
VORSICHTSHINWEISE kennzeichnen Bedingungen oder Vorgehensweisen, die zu
einer Beschädigung von 61000, seiner Daten oder anderer Geräte bzw. von Eigentum
führen können.
Mise en garde, consultez les documents d’accompagnement (ce manual).
Fonctionnement du terminal ou de l’unité en courant continu (CC).
Interrupteur de tension
Symbole
HINWEISE machen auf bestimmte Informationen aufmerksam.
Die folgenden Symbole der Internationalen Elektrotechnischen Kommission
(International Electrotechnical Commission; IEC) befinden sich auf der Abdeck- und
Seitenplatte unmittelbar am betreffenden Terminal oder Gerät.
The following safety precautions must be followed whenever any type of voltage or
current connection is being made to the 61000.
• Wear proper Personal Protective Equipment, including safety glasses and insulated
gloves when making connections to power circuits.
• Hands, shoes and floor must be dry when making any connection to a power line.
• Before each use, inspect all cables for breaks or cracks in the insulation. Replace
immediately if defective.
• Set the 61000 power switch to Off.
Before connecting to electric circuits to be monitored, open their related circuit
breakers or disconnects. DO NOT install any connection of the 61000 to live power
lines.
• Pods should be connected first to the 61000, then connect to the circuit to be
monitored.
• If the equipment is used in a ma nner not specified in this user’s guide, th e pro tec tion
provided by the equipment may be impaired.
These safety precautions are repeated where appropriate throughout this manual.
vi
Page 7
Statements and Notices
Statement of
warranty
Statement of
reliability
Notice regarding
FCC compliance
All products of Dranet z-BMI are warranted to th e original pu rchaser against defective
material and workmanship for a period of one year from the date of delivery. DranetzBMI will repair or replace , at its opti on, all defec tive equ ipment that is returne d, freig ht
prepaid, during th e warrant y period. There wil l be no char ge for repair provided t here is
no evidence that the equi pment ha s been mishand led or ab used. Thi s warr anty s hall not
apply to any defects resulting from improper or inadequate maintenance, buyersupplied hardware/software interfacing, unauthorized modification or misuse of the
equipment, operation outside of environmental specifications, or improper site
preparation or maintenance.
The information in this m anual has be en reviewed and is believ ed to be entirely
reliable, however, no responsibility is assumed for any inaccuracies. All material is for
informational purposes only and is subject to change without prior notice.
This device has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable prote cti on against harmful interfere nce when the equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential are a is likel y to cause harmfu l inter feren ce in which cas e the
user will be required to correct the interference at his/her own expense.
Notice regarding
proprietary
rights
This publication contains information proprietary to Dranetz-BMI. By accepting and
using this manual, you agree that the information contained herein will be used solely
for the purpose of operating equipment of Dranetz-BMI.
Continued on next page
vii
Page 8
Statements and Notices,
Continued
Copyright
Trademarks
This publication is protected under the Copyright laws of the United States, Title 17 et
seq. No part of this p ublica tion may be rep roduced , tr ansmit ted, t ranscr ibed, s tored in a
retrieval system, or translated into any langua ge or computer language, in any form, by
any means, electronic, mechanical, magnetic, optical, chemical, manual, or otherwise,
without the prior written consent of Dranetz-BMI, 1000 New Durham Road, Edison,
New Jersey 08818.
About the 61000; Unpacking the 61000; Standard Accessories; Physical Description
About the 61000
61000
description
The Encore Series
world-class data acquisition products developed by Dranetz-BMI - the DataNode
family of products for the Signature System
integration of power measurement capabilities coupled with an innovative modular
design set the 61000 apart as a truly revolutionary product. The modular concept
applies to both the hardware configuration and firmware architecture allowing the unit
to be a multi-purpose instrument. 61000 works from being a diagnostic tool to
providing preventive and predictive information as an embedded solution. The
instrument is designed to operate either locally as a stand-alone unit with the optional
LCD panel installed or via r emote comput er using the Encore Series
is compliant with IEEE1159, IEC61000-4-30 Class A, EN50160 standards, and more.
It can be installed in a permanent or semi-permanent installation.
C
HAPTER
Introduction
TM
61000 System hereinafter referred to as 61000 encompasses two
®
and the PowerXplorer® PX5. This
TM
Software. 61000
1
Interface to
61000
Data
communication
61000 can operate locally as a stand-alone unit and/or remotely as a data acquisition
module connected to t he Encore Series Software:
Local operation with optional user interface
As a stand-alone unit, the 61000 can be outfitted with optional liquid crystal display
(LCD) as user interface. Th e optio nal touch s creen d ispla y can be mounted on the f ront
panel of the instrument (rack mount) or as a separate unit (remote display), depending
on user-selected enclosure or packaging. The LCD panel provides immediate
accessibility to monitoring all measurement parameters and instrument setup and
configurations.
Remote computer operation
The 61000 can operate as a data acquisition module connected to the Encore Series
Software. This software provides a centralized connection point for remote devices,
turning the computer into a self-contained web server. Encore Series Software permits
remote communications with th e 61000, with t he conve ntion al Inter net br owser a s user
interface. Remote operation includes instrument setup and configurations and
monitoring real-time parameters, disturbance and trend data.
61000 can communicate data to the Encore Series Software via Ethernet (wired,
wireless or fiber-optic based), RS485, USB, and land/cellular modem via RS232. The
physical modem is an external option and is not included as part of the standard
product. This extends greater flexibility in the choice of communications interface for
remote operation.
Continued on next page
1-1
Page 14
About the 61000, continued
Input/Output
modules
Virtual analyzer
platform
61000 provides dedicated processing power via the separate and independent
connection for each input/output module installed. This modular and configurable
design shatters the traditional 8-channel (4 voltage, 4 current) instrument format.
Choose from the voltage, current, and data acquisition modules to build from one to
four instruments in a single, compact, cost-effect ive format. The available modules are :
• AC Voltage Modules - 4 channels using either terminal block, safety jack, or 25-pin
connector to external voltage pod
• AC Current Modules - 4 channels for clamp-on CTs or 25-pin connector to external
CT pod
• Digital Input/Output Modules - 8 channels
• Transducer Input Modules - 4 channels
NOTE: The Modules are factory- inst alled . They cann ot be inst alle d in the fie ld and are
not user accessible.
See Chapter 2 Controls, Indicators and Connectors for more information on the input
modules. Chapter 3 Circuit Diagrams for Power Monitoring contains wiring diagrams
for when power measurements are to be made.
At the heart of the 61000 is the virtual analyzer platform or ‘instruments within an
instrument’ configuration. The virtual analyzer allows the instrument to distinguish
data operations in mul tiple modules. The user can confi gure up t o four vi rtual a nalyzers
per 61000 instrument.
This guide
The 61000 firmware architecture is based on the concept of separating the various
stages of acquisition, characterization, communications and visualization with clearly
defined interfaces that decouple one from the other. The instrument can monitor power
quality phenomena for troubleshooting and/or compliance purposes. It can record
inrush conditions, carry out long-term statistical studies to establish performance
baselines, and perfor m field-based equipment t esting and eval uation for commissionin g
and maintenance. The firmware inte grates intuit ive instrument setup procedures for
each module analyzer to ensure the capture of all relevant data for additional post
process analysis, report writing, and data archiving using other compatible DranetzBMI software applications such as PQView
®
.
This guide is only part of a complet e document set designed to provide comprehensive
information about the 61000. It primarily contains instructions on how to set up the
basic 61000 hardware for operation. It describes the input module interface and the
wiring configurati ons pos sible fo r volt age/c urr ent c onnect ion. It al so des cri bes t he dat a
communication ports availa ble in the backp lane of the ins trument. An overview on how
to set up the 61000 either as a stand-alone unit or as a data acquisition module
connected to the Encore Series Software is included in this guide.
For operational description using the local LCD panel, refer to the 61000 Optional User Interface Guide (check with Dranetz-BMI for availability).
For operational description using remote communications via Encore Series Software,
refer to the Encore Series Software User’s Guide.
1-2
Page 15
Unpacking the 61000
Chapter 1/ Introduction
Unpacking
Shipping
damage
inspection
For maximum protection against possible shipping damage, the 61000 has been sealed
in a two-piece, plastic suspension pack, enclosed within a durable shipping carton.
After opening the carton, inspect the contents for possible shipping damage and check
the carton inventory.
Unpack the 61000 from the carton as follows:
StepAction
1Remove any remaining literature inside the top of the carton.
2Carefully remove the 61000 from its shipping carton.
3Remove all accessories inside the carton. Check that the standard (see
page 1-4) and optional accessories (see Appendix A) you ordered are
included.
Visually inspect the 61000 for possible shipping damage. If any damage exists, first
notify and file an insurance claim with your carrier or underwriter or both. Then noti fy
Dranetz-BMI Customer Service Department of your intentions to return the unit. DO
NOT return the 61000 without prior instructions from Dranetz-BMI Customer Service
Department. Dranetz-BMI Customer Service Department can be reached at (732) 2873680 or 1-800-372-6832.
Repacking for
return shipment
Return notice
If the unit must be return ed to Dranetz -BMI for servi ce or repai r , wrap the unit sec urely
in heavy packaging mater ial and place in a well padded box or crate to p revent damag e.
Do not return the 61000 in an unpadded box. Dranetz-BMI will not be responsible for
damage incurred during transit due to inadequate packing on your part.
Notify Dranetz-BMI Customer Service of your intention of returning the unit. Do not
return the unit without prior instructions from Dranetz-BMI. Dranetz-B MI Customer
Service Department can be reached at (732) 287-3680 or 1-800-372-6832.
1-3
Page 16
61000 Accessories
61000 Accessories
Standard
accessories
Optional
accessories
Technical
specifications
External dc
power source
Encore Series
61000 firmware
upgrade
Calibration
The standard accessory included with the 61000 is the Encore Series 61000 System
User’s Guide, P/N UG-61000.
Refer to Appendix A for the list of hardware and software optional accessories
available for use with 61000. The unit mainframe can be custom-built with optional
input module connecto rs, co mmunica tion port c onne ctors , GPS ant enna co nnec tor, and
a 12V dc power input jack.
Specifications for the 61000 measured parameters, computed parameters, voltage
modules, current probes, and pod accessories are listed in Appendix B.
To connect to an external dc power source, refer to Appendix C.
Refer to Appendix D for instructions on how to upload the latest available firmware
version to the Encore Series 61000 System mainframe.
The recommended calibration interval for this unit is once every 12 months.
We recommend that you return the unit to the factory for calibration. If you decide to
do so, first contact the Dranetz-BMI Customer Service Department to obtain an
Authoriz ation Number.
Telephone: (732) 287-3680 or 1-800-372-6832
FAX: (732) 248-9240
Fill out the Repair /Servi ce Ord er for m enclos ed in the shippi ng car ton and ship i t alon g
with the unit to the Dranetz-BMI Repair Department. (If this form is missing, ask the
Dranetz-BMI Customer Service Department for a replacement.)
1-4
Page 17
Physical Description0
Chapter 1/ Introduction
Dimensions
Optional display
panel
Connector panel
External dc
power source
The 61000 in the desktop e ncl os ure without the optional LCD panel is a self -contained
instrument weighing 4 pounds and measu ring 11.25” width x 3.5” height x 7 3/4 depth.
When used with the LCD panel installed in 19” rack, the instrument weighs 5 pounds
and has an 8” depth.
The optional user interf ace is a 1/4 VGA LCD panel with touch screen menus for l oca l
operation and configuration.
The backplane panel consists of industrial grade, voltage/current/pod connectors,
communication port connectors, dc input power connector, and power switch. See
Chapter 2 Controls, Indicators and Connectors for description.
To connect to an external dc power source, refer to Appendix C.
1-5
Page 18
This page intentionally left blank.
1-6
Page 19
Controls, Indicators, and Connectors
External Components; Connecting to AC Power Source; Communications Interface;
Input/Output Module Connectors; Connecting Voltage Measurement Cables;
Connecting Current Probes; Connecting Voltage/Current Input Pods; Connecting
Digital Input Connectors
External Components
C
HAPTER
2
Description
Front panel
External components refer to operator related external controls, indicators and
connectors.
The 61000 front panel display may look different depending on the enclosure options
specified.
Front panel without the local LCD User Interface
See below for description of the 61000 front display without the LCD user interface.
SF-201
PartFunction
1Sta tus Indicator. LED will l ig ht steadily when abnormal condition is dete ct ed.
The unit is operating normally when light is off.
2Monitoring On. LED will light if monitoring is on. Monitoring status is off
when light is off.
3Power Indi ca tor. LED will blink when the unit power switch is turned on. The
number of blinks correspond to the number of modules installed.
Continued on next page
2-1
Page 20
External Components, continued
Front panel
(continued)
Front panel with the optional LCD User Interface in Rack Mount Eclosure
The front view primarily shows the color touch screen LCD. See below for descr ip ti on
of the 61000 front display with the LCD panel installed.
SF-202
PartFunction
1LCD Rack Mount Protective Enclosure with rack handles
2Liquid Crystal Display (LCD). Provides 3.75 x 4.75 inches display consisting
of 1/4 VGA size screen of text and graphic information. The color LCD is
equipped with touch screen technology, operable using the finger and/or
stylus. Touch screen display permits menu sel ection, alphanumeric data entry,
and has a compact fluorescent (CCFL) backlighting that is on for low light
level viewing.
2-2
The following are some basic care instructions for the LCD monitor
:
• Use and store the unit within the specified temperature and humidi ty range.
The LCD screen may be adversely affec ted by exposure to high temperat ure
or humidity. Condensation or moisture produced by sudden temperature
changes may also damage the LCD screen. Clean any moisture from su rface
immediately.
• Be careful when cleaning or removing stains on the LCD surface. Gently
wipe the surface with a soft cloth or cotton pad. Isopropyl alcohol may be
used, but make sure that all solvent residue is removed.
• Do not apply exces si ve f orce to the LCD surface. The LCD screen contains
sensitive electronic components that may be damaged due to strong impact.
Page 21
Chapter 2/ Controls, Indicators, and Connectors
r
Rear panel
The rear panel consists of the input/output module connectors, communication ports,
and power switch. See below for description of a typical 61000 rear panel. Exact
configuration is dependent on the optional input/output modules ordered.
SF-203
Power Input
See Connecting to DC Powe
Source, page 2-4 on how to
power the unit on/off
Important
Communications Ports
See Communications Interface, page 2-7
for a description of the 61000 data ports
Input Modules
See Input Module Connectors, page 2-9
for a detailed description of the input
module connectors
Dranetz-BMI recommends that you leave adequate working space for rear panel
connections to the 61000. This rear clearance space is necessary for proper installation
of the measurement cables, pr obes and pods as wel l as extern al communic ations device
for the 61000.
2-3
Page 22
Connecting to AC Power Source
Connecting to AC Power Source
Power
specifications
The 61000 AC adapter can be connected to a 90-265V ac power input source
(dependent on model version) or directly to a 12V dc external power source. Refer to
Appendix C for information about connecting to an external dc power source. For
connection to voltages outside of the specified 90-265V ac, a Phase Power Adapter is
required. Phase Power Adapter is an optional accessory available at Dranetz-BMI.
Refer to Appendix A Optional Accessories for ordering information.
CAUTIONAlways set the power switch to the off position befor e connecting or disconnecting
the input power cable.
Operation of the 61000 from an ac voltage source other than the rated voltage
input stated on the unit nameplate can cause damage to the unit.
PRECAUCIONSiempre fije el inter ruptor de encendido en la posic ión apagada antes de conect ar
o desconectar el cable de energía de entrada.
La operación del 61000 desde una fuen te de volt aje de ca que no sea la e ntrada d e
voltaje nominal indicada en la placa de identificación de la unidad puede causar
daños a la unidad.
MISE EN
GARDE
Mettez toujours l’interrupteur dans la position ouverte avant de connecter ou de
déconnecter le câble d’alimentation primaire.
Mettez toujours l’interrupteur dans la position ouverte avant de connecter ou de
déconnecter le câble d’alimentation primaire.
VORSICHTVor dem Einstecken bzw. Ausstecken des Eingangsnetzkabels den Netzschalter
immer in die Aus-Stellung bringen.
Der Betrieb des 61000 von einer Wechselspannungsquelle, die nicht dem auf der
Namensplatte der Einheit aufgeführten Nennspannungseingang entspricht, kann
zur Beschädigung der Einheit führen.
2-4
Page 23
Chapter 2/ Controls, Indicators, and Connectors
Power input/
switch diagram
The power switch panel includes LED indicators, the On/Off power button, and power
input decal and connector. See input power diagram and description below.
1
2
3
4
SF-204
PartFunction
1Power Indicator. LED will blink when power is turned on. The number of
blinks correspond to the number of modules installed.
2On/Off Power Button. Push for on, push for off.
NOTE: The on/off po wer switch shuts the unit down, but al l ows the battery to
continue to charge even with the switch in the Off position.
3Power input decal and connector. The decal provides information about input
power rating. Plug in the AC Adapter output cable into the input connector.
AC input power source is specified as follows:
• Voltage range, 90-265V ac.
• Frequency, 50/60Hz.
• Power Consumption, 10W.
See page 2-6 for the procedure on how to connect to an ac power source.
4Ground LUG. Connect with suitable wire to earth ground conductor or
connection.
2-5
Page 24
Connecting to AC Power Source, continued
Connecting to
an AC power
source
Follow these steps to connect to an ac power source.
StepAction
1Set the power switch to Off.
2Verify the operating voltage range for your 61000, as marked on the
power input decal.
Note:
For source voltages outside the range of the unit, a Phase Power
Adapter is available as an optional accessory. It converts the selected
source voltage to the output voltage needed to operate the unit. Refer to
Appendix A Optional Accessories for information.
3Connect the appropriate power cord for the voltage rating of the unit.
Make connection to the instrument first.
4Connect power cord to the power source.
5Turn power switch to On.
2-6
Page 25
Communications Interface
Chapter 2/ Controls, Indicators, and Connectors
Communications
options
The 61000 can communicate to a compute r via Ethernet networ k, RS232, RS485, USB,
or land/cellular modem. This remote communication network enables the 61000 to act
as a DataNode for the Encore Series Software, or as a stand-alone monitor.
Computer
requirem ents
The computer used must be equipped with the same communication interface as the
61000. For example, if the instr ument is using Ethernet , the comput er must li kewise be
using Ethernet.
The computer must be loaded wit h the Encore Seri es Software package, which conve rts
the computer into a web server and enables it to browse data and information col le ct ed
by the 61000.
WARNINGTo avoid the risk of electric shock, do not remove communications instrument
until all power is de-energized to all power and measurement circuits.
ADVERTENCIA
Para evitar el riesgo de descargas eléctricas, no retire el instrumento de
comunicaciones hasta desconectar todo suministro de energía hacia todos los
circuitos de energía y medición.
AVERTISSEMENT
Pour éviter le risque de choc électrique, ne retirez pas le instrument de
communications avant que tous les circuits d’alimentation et de mesure aient été
mis hors tension.
WARNUNGZur Vermeidung eines elektrischen Schlags die Kommunikationsplatte erst
instrument, wenn die Stromzufuhr zu allen Strom- und Meßschaltungen
unterbrochen wurde.
Remote
operation guide
Remote operation setup and instructions for 61000 are contained in the Encore Series
Software User’s Guide.
2-7
Page 26
Communications Interface, continued
Communication
port diagram
The communications panel below shows the location of data ports available in
61000.The communications panel diagram and description as shown below appears in
the rear panel of the instrument.
Parts table
Remote
operation guide
SF-205
PartFunction
110/100BaseT (RJ45). Allows connection via Ethernet cable.
2USB. Not activate d at this time; future option.
3COM 1. RS232 serial port for land/cellular modem connection. Allows
administrative set up of the 61000 for IP addressing, etc.
4RS485 serial port. Can be used for multi-drop serial connections.
5Optional GPS Antenna. Allows use of optional cable to active antenna.
6Power Connector for External GM28/29 Modem.
See Chapter 4 External Communications for a discussion of the external
communications device and software applications necessary for remote computer
operation of 61000.
2-8
Page 27
Input/Output Module Connectors
Chapter 2/ Controls, Indicators, and Connectors
Input/Output
module types
Users can choose different types of analog and digital input/output modules that can be
installed on the rear panel of 61000. The modules must be selected at time of order. In case
users want additional modules installe d, the unit must be return ed to the factory. The input/
output modules allow a variety of voltage and current measurement cables, probe types, or
pods to connect to the instrument for voltage, current, and/or digital signal monitoring.
The voltage and current connectors are designed in modular configuration, with the
following analog input module measurement point interface:
• AC/DC Voltage Module with safety connectors (Model 61MVB)
• AC/DC Voltage Module with terminal block connectors (Model 61MVS)
• AC/DC Current Module with connectors for external CTs (Model 61MAC)
• AC/DC Module for Voltage or Current Pod (Model 61MZP)
The eight-channel digi tal inp ut module Mo del 61MDIN allo ws users to mon itor on/o ff ty pe
digital signals, such as breaker or switch signal positions. Digital inputs can be configured
to provide demand interval synchronization, pulse counting, KYZ metering, or to provide
start/stop monitoring control.
Digital output module allows certain events to result in change of state of a relay contact.
See Appendix A for specifications of Dranetz-BMI digital output module Models
61MDOH and 61MDOL.
Transducer input module Models 61MXVS and 61MXAS can record and trigger on
analog signal levels in either the 0-24V and 4-20mA range respectively.
Input channels
WARNING
Input channels for the modules installed on the rear connector panel are labelled ±A, ±B,
±C, and ±D. You must turn on any input channel to be used for monitoring. If a channel is
not turned on, no data will be collected for it.
Death, serious injury, or fire hazard could result from improper connection of this
instrument. Read and understand this manual before connecting this instrument. Follow
all installation and opera ti ng instructions while using this instrument.
Connection of this instrument must be performed in compliance with the National
Electrical Code (ANSI/NFPA 70-2005) and any additional safety requirements applicable
to your installat i on.
Installation, operation, and maintenance of this instrument must be performed by
qualified personnel only. The National Electrical Code defines a qualified person as “o ne
who has the skills and knowledge related to the construction and operation of the electrical
equipment and installations, and who has received safety training on the hazards
involved.”
Qualified personnel who work on or near exposed energized electrical conductors must
follow applicable safety related work practices and procedures including appropriate
personal protective equipment in compliance with the Standard for Electrical Safety
Requirements for Employee Workplaces (ANSI/NFPA 70E-2004) of USA and any
additional workplace safet y requirements applicable to your installation.
Continued on next page
2-9
Page 28
Input/Output Module Connectors, continued
ADVERTENCIA
Una conexión incorrecta de este instrumento puede producir la muerte, lesiones
graves y riesgo de incendio. Lea y enti enda este manual antes de conectar. Observe
todas las instrucciones de instalación y operación durante el uso de este
instrumento.
La conexión de este instrumento a un sistema eléctrico se debe realizar en
conformidad con el Código Eléctrico Nacional (ANSI/NFPA 70-2005) de los
E.E.U.U., además de cualquier otra norma de seguridad correspondiente a su
establecimiento.
La instalación, operación y mantenimiento de este instrumento debe ser realizada
por personal calificado solamente. El Código Eléctrico Nacional define a una
persona calificada como "una que esté familiarizada con la construcción y
operación del equipo y con los riesgos involucrados."
El personal cualificado que trabaja encendido o acerca a los conductores
eléctricos energizados expuestos debe seguir prácticas y procedimientos
relacionados seguridad aplicable del trabajo incluyendo el equipo protector
personal apropiado en conformidad con el estándar para los requisitos de
seguridad eléctricos para los lugares de trabajo del empleado (ANSI/NFPA 70E-
2004) de los E.E.U.U. y cualquier requisito de seguridad adicional del lugar de
trabajo aplicable a su instalación.
AVERTISSEMENT
Si l'instrument est mal connecté, la mort, des blessures graves, ou un danger
d'incendie peuvent s'en suivre. Lisez attentivement ce manuel avant de connecter
l'instrument. Lorsque vous utilisez l'instrument, suivez toutes les instructions
d'installation et de service.
Cet instrument doit être connecté conformément au National Electrical Code
(ANSI/NFPA 70-2005) des Etats-Unis et à toutes les exigences de sécurité
applicables à votre installation.
Cet instrument doit être inst allé, util isé et entre tenu uniquement par un perso nnel
qualifié. Selon le National Electrical Code, une personne est qualifiée si "elle
connaît bien la construction et l'utilisation de l'équipement, ainsi que les dangers
que cela implique".
Le personnel qualifié qui travaillent dessus ou s'approchent des conducteurs
électriques activés exposés doit suivre des pratiques en matière et des procédures
reliées par sûreté applicable de travail comprenant le matériel de protection
personnel approprié conformément à la norme pour des conditions de sûreté
électriques pour les lieux de travail des employés (ANSI/NFPA 70E-2004) des
Etats-Unis et toutes les conditions de sûreté additionnelles de lieu de travail
applicables à votre installation.
2-10
Continued on next page
Page 29
Chapter 2/ Controls, Indicators, and Connectors
WARNUNGDer falsche Anschluß dieses Gerätes kann Tod, schwere Verletzungen oder Feuer
verursachen. Bevor Sie dieses Instrument anschließen, müssen Sie die Anleitung
lesen und verstanden haben. Bei der Verwendung dieses Instruments müssen alle
Installation- und Betriebsanweisungen beachtet werden.
Der Anschluß dieses Instruments muß in Übereinstimmung mit den nationalen
Bestimmungen für Elektrizität (ANSI/NFPA 70-2005) der Vereinigten Staaten,
sowie allen weiteren, in Ihrem Fall anwendbaren Sicherheitsbestimmungen,
vorgenommen werden.
Installation, Betrieb und Wartung dieses Instruments dürfen nur von
Fachpersonal durchgeführt werden. In dem nationalen Bestimmungen für
Elektrizität wird ein Fachmann als eine Person bezeichnet, welche "mit der
Bauweise und dem Betrieb des Gerätes sowie den dazugehörigen Gefahren
vertraut ist."
Qualifiziertes Personal, das an bearbeiten oder herausgestellte angezogene
elektrische Leiter sich nähern, muß anwendbare Sicherheit bezogener Arbeit
Praxis und Verfahren einschl ie ßli ch passende persönliche schützende Ausrüstung
gemäß dem Standard für elektrische Sicherheitsauflagen für AngestelltArbeitsplätze (ANSI/NFPA 70E-2004) der Vereinigten Staaten und alle
zusätzlichen Arbeitsplatzsicherheitsauflagen folgen, die auf Ihre Installation
anwendbar sind.
Safety
precautions
The following safety precautions must be followed whenever any type of voltage or
current connection is being made to the 61000.
• Wear proper Personal Protective Equipment, including safety glasses and insulated
gloves when making connections to power circuits.
• Hands, shoes and floor must be dry when making any connection to a power line.
• Before each use, inspect all cables for breaks or cracks in the insulation. Replace
immediately if defective.
• Set the 61000 power switch to Off.
Before connecting to electric circuits to be monitored, open their related circuit
breakers or disconnects. DO NOT install any connection of the 61000 to live power
lines.
• Pods should be connected first to the 61000, then connect to the circuit to be
monitored.
• If the equipment is used in a ma nner not specified in this user’s guide, th e pro tec tion
provided by the equipment may be impaired.
2-11
Page 30
Input/Output Module Connectors, continued
Module
connectors
diagram
The 61000 can accommodate up to four input/output modules with different types of
connectors. The modules installed on the rear panel are customized based on user
specifications. The following pages describe how the optional voltage and current
measurement cables, probes and pod accessories can connect to the 61000 for circuit
monitoring.
The photo below shows the 61000 rear panel with four analog input modules installed.
Digital input/out put mod ules a re al so av ail able (see Appendi x A Op tional Acces sorie s)
but are not shown in photo.
1.1
1.3
1
1.2
2.1
3.1
1.4
2.2
3.3
3
SF-206
3.2
4.1
3.4
Parts table
1.5
1.7
1.6
1.8
2.3
2.4
3.5
3.7
3.6
3.8
24
PartFunction
1AC Voltage Module with Safety Jack Connectors (Model No. 61MVB)
1.1CH A, + Differential Voltage Input Connector; color red
1.2CH A, - Differential Voltage Input Connector; color white
1.3CH B, + Differential Voltage Input Connector; color yellow
1.4CH B, - Differential Voltage Input Connector; color white
1.5CH C, + Differential Voltage Input Connector; color blue
1.6CH C, - Differential Voltage Input Connector; color white
1.7CH D, + Differential Voltage Input Connector; color grey
1.8CH D, - Differential Voltage Input Connector; color white
2-12
Continued on next page
Page 31
Parts
(continued)
Chapter 2/ Controls, Indicators, and Connectors
PartFunction
2AC Current Module with Connectors for External CTs (Model No. 61MAC)
2.1CH A, PROBE, Current Input Connector
2.2CH B, PROBE, Current Input Connector
2.3CH C, PROBE, Current Input Connector
2.4CH D, PROBE, Current Input Connector
3AC Voltage Module with Terminal Block Connectors (Model No. 61MVS)
3.1CH A, + Differential Voltage Input Connector
3.2CH A, - Differential Voltage Input Connector
3.3CH B, + Differential Voltage Input Connector
3.4CH B, - Differential Voltage Input Connector
3.5CH C, + Differential Voltage Input Connector
3.6CH C, - Differential Voltage Input Connector
3.7CH D, + Differential Voltage Input Connector
3.8CH D, - Differential Voltage Input Connector
Measurement
cables, probes
and pods
4AC Voltage/Current Module with 25-PIN DConnector (Model No. 61MZP)
4.125-PIN DConnector
Digital Input Module (Model Nos. 61MDIN) and Digital Output Module (Model No.
61MDOUT) are also available as input/output module options. See page 2-24 for
information on digital input connections.
The input modules and the cables, probes and pods that connect to it are optional
accessories listed in Appendix A Optional Accessories.
Voltage Measurement Cables (for Voltage Input Module with safety jack connectors Model No. 61MVB): Volta ge measure ment cable s ar e sto red i n a cabl e pouc h as part of
the measurement cable set, P/N 116042-G3. Each cable set consists of a cable and
alligator clip. Each alligator clip has an insulate d safety grip. R ed alligator clips are
used for connection to the line connection (+) of voltage channels A, B, C, and D.
Black alligator clips ar e used for the neutral or return li ne connecti on (-). See page 2-15
for more information voltage cable connections.
Current Probes (for Current Input Module - Model No. 61MAC)
: A variety of current
cables and probes are available for connecting Channels A, B, C, and D to the current
input jack. Typical current probes are illustrated on page 2-19.
Continued on next page
2-13
Page 32
Input/Output Module Connectors, continued
Measurement
cables, probes
and pods
(continued)
Voltage/Current Pods (for Voltage/Current Input Module - Model No. 61MZP)
:
Connects to the Series 5500 Voltage/Current input module via the 25-PIN interface
cable connector on the rea r panel of the instr ument. See page 2-2 2 for more informati on
on voltage/current input pod connection.
The next pages describe the possible voltage and current assembly connections to the
input connectors in the rear panel of 61000.
NOTE: VOLTAGE AND CURRENT PROBES ARE NOT SHOWN
CONNECTED TO THE SPECIFIC INPUT MODULES IN THE CONNECTION
DIAGRAMS PROVIDED BECAUSE THE ACTUAL VOLTAGE CABLE AND
CURRENT PROBES USED ARE DEPENDENT ON THE TYPE OF INPUT
MODULES AND OPTIONAL ACCESSORIES PURCHASED.
See Chapter 3 Circuit Diagrams for Power Monitoring for the wiring connection
diagrams to set up the instrument for monitoring.
2-14
Page 33
Chapter 2/ Controls, Indicators, and Connectors
Connecting Voltage Measurement Cables
Measurement
cable set
Optional fused
voltage adapter
Description
: Voltage measurement cables or customer-supplied wiring are used as
connectors for Voltage input modules with safety jack or terminal block connectors,
respectively. Each cable set consists of a cable and alligator clip.
Voltage Rating
: Direct connection of all voltage measurement cables are rated at 600
Vrms max. For measur ing vol tages gr eate r than 600 Vrms, potential transfo rmers (PT s)
must be used. Any customer-supplied wiring should be UL-listed for 600 Vrms
minimum.
Contents
: The voltage measurement cables are shown on page 2-16. A cable set
consists of eight, 6-foot channel measurement cable assemblies (probes), each with a
detachable, alligator jaw, safety clip assembly (maximum jaw opening, 3/4 in (20
mm)). The safety clip assemblie s are red (+) and black (-) for each of the four channe ls.
One cable each of red (channel A), yellow (channel B), blue (channel C), and grey
(channel D), and four each of white are provided.
A pouch for storage of the cables and the AC ada pt er/ ba ttery charger is included in the
contents of the measurement cable set, but is not shown in the figure.
There are two optional fuse accessory kits available for use with the measurement
cables. One kit (P/N FVA-1) contains one fused voltage adapter and one measurement
connecting Red cable 50 cm i n lengt h. The othe r kit ( P/N FVA-4) contains four volta ge
adapters and four measurement connecting cables 50 cm in length (one Red, one
Yellow, one Blue, and one Grey).
The single fuse voltage adapter kit is used for one single voltage measurement input.
While the four fuse voltage adapter kit is used for a three phase and neutral voltage
measurement inputs. If these fuse kits are not used, i t i s recommended that the user use
terminal strips to fused circuits, preferably with local disconnects.
Continued on next page
2-15
Page 34
Connecting Voltage Measurement Cables, continued
Measurement
cable set wi th
optional fuse
diagram
WARNING
WARNING
WARNING
NOTE: 2 FT CABLE
INCLUDED WITH
FUSE VOLTAGE
ADAPTER
OPTIONAL
FUSE
VOLTAGE
ADAPTER
OPTIONAL
FUSE
VOLTAGE
ADAPTER
OPTIONAL
FUSE
VOLTAGE
ADAPTER
OPTIONAL
FUSE
VOLTAGE
ADAPTER
A+ B+ C+ D+ A- B- C- D-
To AC Voltage Module with safety jack
SF-207
or terminal block connectors
To avoid the risk of electric shock or burns, always connect the safety (or earth)
ground before making any other connections.
To reduce the risk of fire, electrical shock, or physical injury it is strongly
recommended to fuse the voltage measurement inputs.
Fuses must be located as close to the load as possible to maximize protection.
For continued protection against risk of fire or shock hazard replace only with
same type and rating of recommended fuse.
Use only fast blow type fuse which is rated 600V. Recommended fuse type is
Littelfuse, part number KLKD0.30 rated 600V AC/DC, 0.3A fast blow.
WARNING
Do not replace fuse again if failure is repeated. Repeated failure indicates a
defective condition that will not clear with replacement of the fuse. Refer
condition to a qualified technician.
2-16
Page 35
Chapter 2/ Controls, Indicators, and Connectors
Contact Dranetz-BMI Customer Service for more information on the fused voltage
adapter. Refer to Dranetz-BMI Information Sheet titled Model FVA - Fuse Voltage
Adapter, P/N 899107 .
Voltage input
connectors
There are two categorie s of voltage conn ectors in Voltage Input Modules: one for single
phase voltage connections, designated VOLTAGE INPUTS, CH D; the other for three
phase connections, designated VOLTAGE INPUTS CH A, CH B, CH C. See the
voltage cable connections diagram below.
In general, the single phase channel D cable is used to measure the neutral to ground
voltage. In this type connection it is referenced as channel D. This cable also can be
used for any single phase connection. See Chapter 3 Circuit Diagrams for Power
Monitoring for the various circuit connections using this cable.
2-17
Page 36
Connecting Current Probes
Connecting Current Probes
T ype s of curr ent
cables
T ype s of curr ent
probes
Safety
precautions
Several Dranetz-BMI current probes can be used with the Current Input Module Model No. 61MAC of the 61000. The following are two types of current cables
available for connecting to the current input channels A, B, C, and D.
• CT Series Adapter Assembly.
• Four Channel Current Probe Cable Assembly (for TR25xx probes).
A variety of current measurement probes and transformers are available that can be
connected to these cables in a number of ways.
For instance:
• TR25xx clamp-on current probes that provide a broad range of current
measurements.
• Multiple probes and adapter cables that are currently used with Dranetz-BMI
equipment i.e. Flex Core models and Hall-effect probe models.
Typical current probes are illustrated on page 2-19. A diagram showing current
connection to a single phase circuit for general hookup is also provided on page 2-21.
The following safety precautions apply to current probe connections.
• DO NOT attempt to measure current in any circuit in which the circuit to ground
voltage exceeds the insulation rating of the current probe (600 Vrms max).
• Make sure the jaws of the current probe are tightly closed. Keep mating surfaces
clean and free from foreign matter.
2-18
Page 37
Typical current
probes
Chapter 2/ Controls, Indicators, and Connectors
NOTE: The TR2500 can perform all current measurements except high frequency
transient detection. Current probes TR2500 can be used interchangeably with
TR2500A, TR2510 with TR2510A, and TR2520 with TR2520A.
Refer to Appendix A for descriptions and part numbers of probes and adapter cables.
Refer to Appendix B for specifications of current connections.
To any Current CH A, B, C, D of Model No. 61MA C
4300 TO LEMFLEX
CURRENT PROBE
ADAPTER CABLE
116310-G1
SF-210
2-19
Page 38
Connecting Current Probes, continued
Example
WARNING
ADVERTENCIA
AVERTISSEMENT
The diagram on page 2-21 shows how to connect a cur rent probe for curr ent monitoring
of a single phase line. The channel to be monitored can be any chann el so designated by
the operator.
DO NOT USE non-insulated current probe cores around a non-insulated wire.
Probes of this type are designed for use around insulated wires only. Use only
completely insulated probe cores with no exposed conductive areas of the core
around non-insulated wires.
NO UTILIZAR transformadores de corriente sin material aislante al rededor de
conductores sin material aislante. Los Transformadores de corriente de este tipo
están diseñados para ser utilizados solamente con conductores con aislamiento
eléctrico. Utilizar transformadores de corriente completamente aislados
alrededor de conductores sin aislamiento.
N'EMPLOYEZ PAS les noyaux courants non-isolés de sonde autour d'un fil nonisolé. Des sondes de ce type sont concues pour l'usage autour des fils isolés
seulement. L'utilisatio n seul ement a compl ét ement iso lé des noy aux de s onde s ans
des secteurs conducteurs exposés du noyau autour des fils non-isolés.
WARNUNG
Probe
positioning
VERWENDEN Sie keine Stromzangen mit nicht isolierten Ferritkernen bei
Messungen an nicht isolierten Leitungen. Stromzangen dieses Typs sind nur für
Messungen an isolierten Leitern geeignet. Bitte verwenden Sie zur Messung an
nicht isolierten Leitungen Stromzangen mit vollständig isoliertem Kernmaterial.
An arrow marking on the handle is a guide to ensure that you position the probe with
the arrow pointing towards the load when monitoring the line conductor. Correct
positioning of the probe is necessary for correct power measurements, where in-phase
voltage and curre nt measure ments are neces sary. A positive watts r eading i ndicates that
the probe is pointed towards the load, and a negative reading indicates that the probe is
pointed towards the source.
Continued on next page
2-20
Page 39
Chapter 2/ Controls, Indicators, and Connectors
Single phase
current probe
connection
example
The following diagram shows how to connect a current probe to channel A for current
monitoring of a single phase line.
The current probe may be connected to the return line if desired to measure the return
current when checking for load current leakage, loop current relationships, etc. If
measuring power, position the probe with the arrow pointing towards the load.
7703-21
SF-211
To Voltage CH DTo Current CH A
NoteThe connection example shown above is not recommended without a voltage probe
connected to ensure that the measurements are synchronized to the external source. If
the configuration shown is used, an internal frequency reference must be entered.
2-21
Page 40
Connecting Volt age/C urren t Input Pods
Connecting Voltage/Current Input Pods
Pod types
Pod assembly
diagram
Two Series 5500 input pod types, voltage and current, can connect alternatively to the
same Voltage/Current Input Module Model No. 61MZP with 25-PIN interface cable
connector. The inputs are attenua te d t o low voltage signals that can be measured by the
61000.
Photos of Model 5536 voltage pod and Model 5537 current pod are shown below. See
pod assembly labels on page 2-23.
3
1
SF-212
2-22
3
2
SF-213
Continued on next page
Page 41
Pod assembly
parts
Chapter 2/ Controls, Indicators, and Connectors
PartFunction
Example:
Voltage pod
connection
1Voltage Module. Accepts four 5-600 V
(AC or DC), ±1000 Vpk channels A,
rms
B, C voltage, plus neutral and ground. Neutral to ground voltage range: 0.5 20 Vrms (AC or DC).
2Current Module. Accepts four 0.01-5 A
Measurement range allows 25 A
pk
.
and up to #12 AWG wires.
rms
3Data cables. Enables connection of measurement pods to the 61000. Cable
length is 3” (0.9m).
The figure below shows a voltage pod connected to the Voltage input module with 25PIN interface cable connector.
SF-214
2-23
Page 42
Connecting Digital Input Connectors
Connecting Digital Input Connectors
Digital input
connections
Model No.
61MDIN is an eight channel, digital input module, providing users with
the capability to monitor on/off-type digital signals, such as breaker or switch position
indicators. The functionality of the inputs can be configured on a channel basis to also
provide demand interval synchronization, pulse counting, KYZ metering or to provide
start/stop monitoring control. Each channel can be individually labeled, is triggerable,
and the polarity set as N/O or N/C.
Photo below shows the digital input module without the external connector.
2-24
A logical one or HI condition is when the voltage level goes above 3.5 volts and a
logical zero or LO condition is when the voltage level goes below 1.0 volts. Maxi mu m
input signal level is 135Vac or 200Vdc. If the inputs are configured for AC instead of
DC signals, it is the rms value of the ac signal that is used to determine the state. This
will also slow the response time down, as the rms value is computed over 100msec
window for operation on 50 or 60Hz systems.
All logic transitions are to be time stamped to the millisecond and available for
simultaneous comparison by the user to data collected via other modules (V, I, other
Digital input, etc). An "event" can be either set to occur on the change of state (edgetriggered) or at a particular state, HI/LO (level-triggered). Such events can be used to
cross-trigger other modules and/or instruments to also record data.
The Meter screens will report the present state of the inputs. Trends and Events
timeplots will indicate the signal level at the either 1 or 0 state at the time of data
storage, as will waveform data. There is no min/max/average value, just the
instantaneous value.
Page 43
Circuit Diagrams for Power Monitoring
Connecting Power to the Voltage/Current Connections; Single Phase; Split Phase;
3 Phase, Four Wire Wye; 3 Phase Delta; 3 Phase 2-Watt Delta; 2 1/2 Element without
Voltage Channel B; 2 1/2 Element without Voltage Channel C
Connecting Power to the Voltage/Current Connections
C
HAPTER
3
Voltage and
current
connections
WARNING
This section contains diagrams of voltage and current connections that are required
when power measurements are to be made.
T
he 61000 should be handled with care. After unpacking the unit, verify that all items
ordered have been accounted for. Contact Dranetz-BMI Customer Service if any items
are missing or damaged.
Position the 61000 on a dry, flat surface or mount with proper brackets or in an
appropriate enclosure. Access to the power, measurement and communication
connections is necessary.
Refer to the illustrations in Chapter 2 Controls, Indicators and Connectors for location
of the various connectors on the rear panel of the unit.
Death, serious injury, or fire hazard could result from improper connection of this
instrument. Read and understand this manual before connecting this instrument.
Follow all installation and operating instructions while using this instrument.
Connection of this instrument must be performed in compliance with the National
Electrical Code (ANSI/NFPA 70-2005) and any additional safety requirements
applicable to your installation.
Installation, operation, and maintenance of this instrument must be performed by
qualified personnel only. The National Electrical Code defines a qualified person as
“one who has the skills and knowledge related to the construction and operation of the
electrical equipment and installations, and who has received safety training on the
hazards involved.”
Qualified personnel who work on or near exposed energized electrical conductors
must follow applicable safety related work practices and procedures including
appropriate personal protective equipment in compliance with the Standard for
Electrical Safety Requirements for Employee Workplaces (ANSI/NFPA 70E-2004) of
USA and any additional workplace safety requirements applicable to your
installation.
Continued on next page
3-1
Page 44
Connecting Power to the Voltag e/Curre nt Connections , continued
ADVERTENCIA
Una conexión incorrecta de este instrumento puede producir la muerte, lesiones
graves y riesgo de incendio. Lea y enti enda este manual antes de conectar. Observe
todas las instrucciones de instalación y operación durante el uso de este
instrumento.
La conexión de este instrumento a un sistema eléctrico se debe realizar en
conformidad con el Código Eléctrico Nacional (ANSI/NFPA 70-2005) de los
E.E.U.U., además de cualquier otra norma de seguridad correspondiente a su
establecimiento.
La instalación, operación y mantenimiento de este instrumento debe ser realizada
por personal calificado solamente. El Código Eléctrico Nacional define a una
persona calificada como "una que esté familiarizada con la construcción y
operación del equipo y con los riesgos involucrados."
El personal cualificado que trabaja encendido o acerca a los conductores
eléctricos energizados expuestos debe seguir prácticas y procedimientos
relacionados seguridad aplicable del trabajo incluyendo el equipo protector
personal apropiado en conformidad con el estándar para los requisitos de
seguridad eléctricos para los lugares de trabajo del empleado (ANSI/NFPA 70E-
2004) de los E.E.U.U. y cualquier requisito de seguridad adicional del lugar de
trabajo aplicable a su instalación.
AVERTISSEMENT
Si l'instrument est mal connecté, la mort, des blessures graves, ou un danger
d'incendie peuvent s'en suivre. Lisez attentivement ce manuel avant de connecter
l'instrument. Lorsque vous utilisez l'instrument, suivez toutes les instructions
d'installation et de service.
Cet instrument doit être connecté conformément au National Electrical Code
(ANSI/NFPA 70-2005) des Etats-Unis et à toutes les exigences de sécurité
applicables à votre installation.
Cet instrument doit être inst allé, util isé et entre tenu uniquement par un perso nnel
qualifié. Selon le National Electrical Code, une personne est qualifiée si "elle
connaît bien la construction et l'utilisation de l'équipement, ainsi que les dangers
que cela implique".
Le personnel qualifié qui travaillent dessus ou s'approchent des conducteurs
électriques activés exposés doit suivre des pratiques en matière et des procédures
reliées par sûreté applicable de travail comprenant le matériel de protection
personnel approprié conformément à la norme pour des conditions de sûreté
électriques pour les lieux de travail des employés (ANSI/NFPA 70E-2004) des
Etats-Unis et toutes les conditions de sûreté additionnelles de lieu de travail
applicables à votre installation.
3-2
Continued on next page
Page 45
Chapter 3/ Circuit Diagrams for Power Monitoring
WARNUNGDer falsche Anschluß dieses Gerätes kann Tod, schwere Verletzungen oder Feuer
verursachen. Bevor Sie dieses Instrument anschließen, müssen Sie die Anleitung
lesen und verstanden haben. Bei der Verwendung dieses Instruments müssen alle
Installation- und Betriebsanweisungen beachtet werden.
Der Anschluß dieses Instruments muß in Übereinstimmung mit den nationalen
Bestimmungen für Elektrizität (ANSI/NFPA 70-2005) der Vereinigten Staaten,
sowie allen weiteren, in Ihrem Fall anwendbaren Sicherheitsbestimmungen,
vorgenommen werden.
Installation, Betrieb und Wartung dieses Instruments dürfen nur von
Fachpersonal durchgeführt werden. In dem nationalen Bestimmungen für
Elektrizität wird ein Fachmann als eine Person bezeichnet, welche "mit der
Bauweise und dem Betrieb des Gerätes sowie den dazugehörigen Gefahren
vertraut ist."
Qualifiziertes Personal, das an bearbeiten oder herausgestellte angezogene
elektrische Leiter sich nähern, muß anwendbare Sicherheit bezogener Arbeit
Praxis und Verfahren einschl ie ßli ch passende persönliche schützende Ausrüstung
gemäß dem Standard für elektrische Sicherheitsauflagen für AngestelltArbeitsplätze (ANSI/NFPA 70E-2004) der Vereinigten Staaten und alle
zusätzlichen Arbeitsplatzsicherheitsauflagen folgen, die auf Ihre Installation
anwendbar sind.
Safety
precautions
The following safety precautions must be followed whenever any type of voltage or
current connection is being made to the 61000.
• Wear proper Personal Protective Equipment, including safety glasses and insulated
gloves when making connections to power circuits.
• Hands, shoes and floor must be dry when making any connection to a power line.
• Before each use, inspect all cables for breaks or cracks in the insulation. Replace
immediately if defective.
• Set the 61000 power switch to Off.
Before connecting to electric circuits to be monitored, open their related circuit
breakers or disconnects. DO NOT install any connection of the 61000 to live power
lines.
• Pods should be connected first to the 61000, then connect to the circuit to be
monitored.
• If the equipment is used in a ma nner not specified in this user’s guide, th e pro tec tion
provided by the equipment may be impaired.
3-3
Page 46
Connecting Power to the Voltag e/Curre nt Connections , continued
WARNING
WARNING
WARNING
WARNING
WARNING
T o reduce the risk of fire, el ectri c shock, or phy sic al inju ry, it is strongly recommended
that connections be made with al l circui ts de-en ergi zed and cur rent car rying conductor s
fused. If it is necessary to make connections on energized circuits, these must be
performed by Qualified Personnel ONLY with proper Personal Protective Equipment.
To avoid the risk of electric shock or burns, always connect the safety (or earth)
ground before making any other connections.
To reduce the risk of fire, electrical shock, or physical injury it is strongly
recommended to fuse the voltage measurement inputs.
Fuses must be located as close to the load as possible to maximize protection.
For continued protection against risk of fire or shock hazard replace only with
same type and rating of recommended fuse.
Use only fast blow type fuse which is rated 600V. Recommended fuse type is
Littelfuse, part number KLKD.300 rated 600V AC/DC, 0.3A fast blow.
Do not replace fuse again if failure is repeated. Repeated failure indicates a
defective condition that will not clear with replacement of the fuse. Refer
condition to a qualified technician.
3-4
Page 47
Chapter 3/ Circuit Diagrams for Power Monitoring
Connection
Guidelines
Refer to the appropriate connection diagram on pages 3-6 to 3-12 to connect
power to the voltage/current input connections.
• Make sure all circuits are de-energized before making connections.
• Connect the data cables. Plug the measurement cables into the appropriate
connectors on the rear panel of the 61000.
• Remove the terminal protective cover(s) from the Voltage Input Module(s).
• Route power wires in a safe manner in accordance with good practice and local
codes.
• Connect the ground wire first, before making any other connections.
• Connect power source to the Voltage and Current Input Modules. Attach pha se A, B,
and C voltage connections plus neutral, if applicable, to the screw terminals on the
Voltage Input Module(s). (5-600 Vrms, up to #12 AWG wire)
• Replace the terminal protective cover(s) on the front of the Voltage Input Module(s).
• Pass the CT secondary conductors (0.01-5 Arms and up to #12 AWG wire) through
current tubes located on the face of the input module. The arrows on the input
module point from source to load.
• Turn the 61000 instrument ON by pushing the power switch. Proceed to Chapter 3,
Operation.
3-5
Page 48
Single Phase
Single Phase
Connection
Single Phase
Type:
LINE
AN
Refer to Fuse Warnings on page 3-4
Fuses
CAUTION
*NOTE
Switchgear
Chassis Ground
CT Shorting Switch
or Test Block
(optional)
LOAD
To Switchgear Chassis Ground*
SF-301
Connections must be performed in compliance with all safety requirements applicable
to your installation.
Connections of CT leg to ground is recommended, but not required for proper
operation.
3-6
Page 49
Split Phase
Connection
Split Phase
Type:
LINE
A BN
Chapter 3/ Circuit Diagrams for Power Monitoring
Refer to Fuse Warnings on page 3-4
Fuses
CAUTION
*NOTE
Switchgear
Chassis Ground
CT Shorting Swit ch
or Test Block
(optional)
LOAD
To Switchgear Chassis Ground*
SF-302
Connections must be performed in compliance with all safety requirements applicable
to your installation.
Connections of CT leg to ground is recommended, but not required for proper
operation.
3-7
Page 50
3 Phase, Four Wire Wye
3 Phase, Four Wire Wye
Connection
Type: 3 Phase, Four Wire Wye
Setup Mode: Wye
LINE
A B C N
Refer to Fuse Warnings on page 3-4
Fuses
Switchgear
Chassis Ground
CT Shorting Switch
or Test Block
LOAD
CAUTION
Connections must be performed in compliance with all safety requirements applicable
to your installation.
*NOTE
Connections of CT leg to ground is recommended, but not required for proper
operation.
3-8
(optional)
To Switchgear Chassis Ground *
SF-303
Page 51
3 Phase Delta
Chapter 3/ Circuit Diagrams for Power Monitoring
Connection
Type: 3 Phase Delta
Setup Mode: Delta
LINE
A B C
Refer to Fuse Warnings on page 3-4
Fuses
Switchgear
Chassis Ground
CT Shorting Switch
or Test Block
LOAD
CAUTION
Connections must be performed in compliance with all safety requirements applicable
to your installation.
*NOTE
Connections of CT leg to ground is recommended, but not required for proper
operation.
To Switchgear Chassis Ground*
SF-304
3-9
Page 52
3 Phase 2-Watt Delta
3 Phase 2-Watt Delta
Connection
Type: 3 Phase, 2-Watt Delta
Setup Mode: Delta
LINE
A B C
Refer to Fuse Warnings on page 3-4
Fuses
Switchgear
Chassis Ground
CT Shorting Switch
or Test Block
LOAD
CAUTION
Connections must be performed in compliance with all safety requirements applicable
to your installation.
*NOTE
Connections of CT leg to ground is recommended, but not required for proper
operation.
3-10
To Switchgear Chassis Ground*
SF-305
Page 53
Chapter 3/ Circuit Diagrams for Power Monitoring
2 1/2 Element without Voltage Channel B
Connection
Type: 2 1/2 Element without Voltage Channel B
Setup Mode: Delta
LINE
A B C
Refer to Fuse Warnings on page 3-4
Fuses
Switchgear
Chassis Ground
CT Shorting Switch
or Test Block
LOAD
CAUTION
Connections must be performed in compliance with all safety requirements applicable
to your installation.
*NOTE
Connections of CT leg to ground is recommended, but not required for proper
operation.
To Switchgear Chassis Ground*
SF-306
3-11
Page 54
2 1/2 Element without Voltage Channel C
2 1/2 Element without Voltage Channel C
Connection
Type: 2 1/2 Element without Voltage Channel C
Setup Mode: Delta
LINE
A B C
Refer to Fuse Warnings on page 3-4
Fuses
Switchgear
Chassis Ground
CT Shorting Switch
or Test Block
LOAD
CAUTION
Connections must be performed in compliance with all safety requirements applicable
to your installation.
*NOTE
Connections of CT leg to ground is recommended, but not required for proper
operation.
3-12
To Switchgear Chassis Ground*
SF-307
Page 55
Input Settings; Data Collection; Memory Functions; External Communications
Interface; Local Operation
Input Settings
Operational Description
C
HAPTER
4
Introduction
Virtual analyzer
platform
This chapter contains operational description of the hardware functions of the 61000,
configurable through Encore Series Software or through the optional user interface
when installed. Section A describes the external communications device and software
applications necessar y for remote ope ration of 610 00. Section B desc ribes the 610 00 as
a stand-alone unit with the LCD screen installed.
For detailed information on 61000 remote operation, refer to the Encore Series
Software User’s Guide. Fo r local operation and functional scre en display, refer to the
61000 Optional User Interface Guide (check with Dranetz-BMI for availability).
The 61000 uses the concept of virtu al anal yze rs to in terfa ce with the modula r des ign of
the mainframe. 61000 operation is dependent on the type of input/output modules
installed on the rear panel of the instrument. As described in Chapter 2 Controls,
Indicators, and Connectors, the 61000 can have a maximum of 4 modules, with
separate and independent connection for each input/output module. The user can
configure up to four virtual analyzers, depending on module types installed. The
instrument is factory-set to pair voltage and current modules in adjacent slots together
as a virtual analyzer. If the two sets of voltage and current modules are present, there
will be two virtual anal yzers. If one voltage a nd three cur rent modules are pre sent, each
current module will be paired up with the voltage module to make three virtual
analyzers.
Virtual analyzers operate independently of each other. Each has its own set of
functional icons in the local user interface, which when pressed allows users to view
data from. For example, af te r t he user selects Virtual Analyzer 2 configured to monitor
voltage and current data, the user can then press the Meter icon to view voltage and
current meter values. Similar concept applies to Scope, Harmonics, Trend, Events and
Setup. Virtual analyzer tag names can be specified by the user, for example “UPS#4”.
Circuit type
You must select a circuit type when you are collecting data for power parameters such
as watts, VAs, PF, and VARs. If you don’t sel ec t the proper circuit type, the ABC totals
will not be calculated correctly.
Continued on next page
4-1
Page 56
Input Settings, continued
Circuit type
(continued)
Scale factors
61000 can monitor the following power configurations:
•Single Phase
•Split Phase
•3 Phase Wye
•3 Phase Delta
• 3 Phase 2-Watt Meter Delta
•Generic
• 2 1/2 Element without V Chan B
• 2 1/2 Element without V Chan C
While monitoring any of the above configurations, 61000 can also be connected to
monitor neutral to ground voltage and neutral to ground current.
Definition
: Scale factors are the ratio of input to output for a particular current
transformer (CT) or poten tial tran sformer (PT). Scale factors are entere d into the 61000
(from the Encore Series Software or local user interface) and then multiplied
automatically by the measured voltage and current so that the correct values will be
recorded and displayed.
If voltage and current connections are made without using any of the above named
devices, the scale factor should be set to 1.
When to use
: Scale factors other than 1 must be entered for the following conditions.
• A Dranetz-BMI current probe is connected to a permanently installed CT.
• The current connections are made using a Dranetz-BMI ISO box.
• The voltage connections are made using a PT.
Range
: The scale factor that is entered into the user interface must be between 0.001
and 999,900.
4-2
Page 57
Data Collection
Chapter 4/ Operational Description
Real-time
monitoring
Event
monitoring
When to
monitor events
Parameter
threshold
61000 allows you to view power quality phenomena as it happens, when it happens.
The instrument is able to captur e and proces s data in r eal time, an d allows use rs to view
it in Scope mode and Meter mode.
The data collection function of the 61000 controls how timed and disturbance events
are recorded and saved to memory during monitoring of an electrical system. This
function consists of the settings for the interval for timed readings, parameter
thresholds, and waveform capture.
61000 can monitor an electrical system in situations where scope or meter
measurements in real time do not give the data that you need to diagnose a problem.
The length of time you monitor a circuit can vary from a few minut es to a few weeks or
more depending on your application.
Threshold is a user entered value (or limit) that the 61000 compares to a measurement
to decide if an event occurs. For example, on a circuit with a nominal voltage of 120V
rms, the high and low limits could be set to 132V and 108V, respectively. If the input
voltage exceeds 132V rms, or fall s below 108V rms, t he limit is exceede d and an event
is produced. The 61000 saves this limit crossing to memory as an event. The return to
normal would also be saved as an event.
Setup
Event
Waveform
Capture
Setup is a list of parameter thresholds and waveform capture settings for each channel
that controls the way the 61000 records event data. In essence, a setup is a list of the
criteria that the 61000 uses to determine what constitutes an event and what waveform
data is saved when an event occurs.
Event is any data that the 61000 saves to memory, usually based on exceeding a
programmed measurement threshold but also including the measurement return to
normal.
A function that saves the actual voltage and/or current waveforms that occurred at the
time of an event.
NOTE: Waveform capture consumes much more memory than just textual capture.
Careful planning for which parameters you want to capture waveforms, will help you
increase the number of events that can be saved in memory.
4-3
Page 58
Memory Functions
Memory Functions
Memory backup
Flash memory
data storage
61000 uses an internal 4M non-volatile flash memory for program storage. Data will
not be lost if the battery pack is removed.
The 61000 hardware has a flash memory storage of 1GB, depending on user
specification.
4-4
Page 59
External Communications Interface
Remote Computer Operation
Chapter 4/ Operational Description
Section A
Introduction
Remote user
interface guide
Computer
requirem ents
Communications
interface
This section provides an overview on how to connect the 61000 for external
communications to a remote computer using the Encore Series Software.
For more information about operating the 61000 from a computer, refer to the Encore
Series Software User’s Guide.
The computer used must be equipped with the same communication interface as the
61000. For example, if the instr ument is using Ethernet , the comput er must li kewise be
using Ethernet.
There are five types of connectors in the rear panel of the 61000 for remote
comunication to a computer:
• RJ-45 for 10BaseT connection via Ethernet cable to a network or computer. The RJ45 connector can also be used for external modem connections.
• RS-485 for 10BaseT connection using crossover wiring and cable
• USB communication port (future use)
• COM 1, 9-pin RS232 communication port
• GPS antenna cable connector (optional)
Caution
Refer to Chapter 2 Controls, Indicators and Connectors for diagrams of the connectors
found on the rear panel of the 61000.
Only qualified personnel should attempt installation and connection of the 61000 to a
communication network.
4-5
Page 60
Connection Setup via Modem
Connection Setup via Modem
External modem
Reference guide
The 61000 is connected for modem operation by installation of an optional external
land-based modem device and connection of the local telephone line to the RJ-45
10BaseT communications port. Model 61MDM external modem is available in
Dranetz-BMI as an optional accessory for the 61000.
Modem communication is also possible through an optional GSM service for wireless
communication. This service is provided by user, not by Dranetz-BMI.
Remote operation instructions for modem connection are contained in the Encore
Series Software User’s Guide. It describes operation of the 61000 with all connections
being made correctly and the unit fully operational.
4-6
Page 61
Connection Setup via COM 1 RS232
Chapter 4/ Operational Description
Connection
setup via RS232
NOTE
Connect one end of the 9-pin RS232 connector into the COM 1 RS232 port located on
the rear panel of the 61000. Connect the other end of the RS232 connector to any
available serial COM port on your computer. The COM 1 RS232 port can also be used
to connect optional external modem device, including cellular GSM.
RS232 connection is not operational at this time; future option.
4-7
Page 62
Connection Setup via GPS Antenna
Connection Setup via GPS Antenna
Antenna
requirem ents
Reference guide
61000 will comply with emissions and/or immunity requirements with antenna cable
lengths of 100 feet. Cable lengths exceeding 100 feet may result in undesired
interference. Shielded cables and shielded connectors must be used when connecting
external devices to the GPS antenna port of the 61000.
Remote operation instructions for antenna connection are contained in the Encore
Series Software User’s Guide. It describes the operation of the 61000 with all
connections being made correctly and the unit fully operational.
4-8
Page 63
Stand-Alone Unit
Chapter 4/ Operational Description
Section B
Local Operation
Optional user
interface
Language
selection
Reference guide
Safety
precautions
The 61000 can operate as a stand-alone unit with an optional color liquid crystal
display (LCD) as user interf ace. The t ouch scre en displa y is mou nted on t he front of the
rack-mount option or as a sta nd-alone panel, depe nding on us er speci ficatio n. The LCD
panel provides immediate access to monitoring all measurement parameters and
configurations.
Local operation of th e 610 00 consists of connecting the measurement cabl es, verifying
correct measurement c onnectio ns, and veri fying that volt age and cu rrent meas urement s
are being monitored.
Menu screens for the 61000 opt ion al user inter face ar e avail able fo r di splay i n multipl e
languages. Users have the option to set screen display in the language available. The
screens appear in the English language by default.
Refer to the 61000 Optional User Interface Guide (check with Dranetz-BMI for
availability) for detailed instructions on how to set up and operate the 61000 with the
LCD panel.
The following safety precautions must be followed whenever any type of voltage or
current connection is being made to the 61000.
• Wear proper Personal Protective Equipment, including safety glasses and insulated
gloves when making connections to power circuits.
• Hands, shoes and floor must be dry when making any connection to a power line.
• Before each use, inspect all cables for breaks or cracks in the insulation. Replace
immediately if defective.
• Set the 61000 power switch to Off.
Before connecting to electric circuits to be monitored, open their related circuit
breakers or disconnects. DO NOT install any connection of the 61000 to live power
lines.
• Pods should be connected first to the 61000, then connect to the circuit to be
monitored.
• If the equipment is used in a ma nner not specified in this user’s guide, th e pro tec tion
provided by the equipment may be impaired.
4-9
Page 64
Basic Operation
Basic Operation
Battery pack
AC power
source
Turn-on
procedure
The normal power source for the 61000 is the 50/60Hz 120/23 0V ac power source with
back-up from the interna l batt ery pac k. The exter nal powe r adapte r ( eithe r AC Adapter /
Battery Charger or DC-DC converter) is used to charge the battery. Always charge the
battery fully before use. 61000 will always operate on the power adapter and is
designed to do so, regardless of the state of charge of the battery.
The 61000 can be operated from a 50/60Hz 120/230V ac power source.
Connect the ac adapter output cable to the input connector on the rear panel of the
61000. Connect the appr opria te ac adapte r power co rd for the c ountry to an app ropri ate
outlet.
Follow these steps to turn on the 61000 and display the Home screen. Home screen is
frequently referenced as the starting point for all major functionalities of 61000.
StepAction
1Verify that the power switch on the 61000 connector panel is turned off.
2Verify that the power to the circuit to be measured is turned off.
3Connect the measurement cables for the type of circuit being measured
as described in Chapter 2 Controls, Indicators and Connectors. See the
appropriate connection diagram in Chapter 3 Circuit Diagrams for
Power Monitoring. Typical voltages measured are 120V ac nominal per
phase with a load current of 50 Amps.
4Turn on power to the circuit to be measured.
4-10
5Turn on power to the 61000.
6Verify that the LCD (if available) displays instrument-specific
information. The Home screen contains the icons used to access
instrument functions.
Page 65
Introduction
A
PPENDIX
Optional Accessories
Introduction; Hardware Accessories List; Enclosure Hardware Options; Software
Accessories List
A
Introduction
Ordering
information
This appendix lists the optional accessories for 61000. It covers the hardware
accessories available for use with the instrument and the Dranetz-BMI software
applications used to download and view event data in a computer.
To order accessories, contact Dranetz-BMI Customer Service Department
Dranetz-BMITel: (732) 287-3680
1000 New Durham Road Tel: 1-800-372-6832
Edison, NJ 08818-4019 USAFAX: (732) 248-1834
Attentio n: Customer Service www.dranetz-bmi.com
at:
A-1
Page 66
Hardware Accessories List
Hardware Accessories List
Hardware
Accessories List
Current Probe Options
Clamp-On AC/DC Probes
AC/DC Current Probe, 150A, Without AC Adapter
AC/DC Current Probe, 150A, Battery Powered
AC/DC Current Probe, 1500A, Without AC Adapter
AC/DC Current Probe, 1500A, Battery Powered
Flex-AC Probes
3 Phase Current Probe
LEMFLEX Current Probe, 30A/300A/3000A, 24”
LEMFLEX Current Probe, 30A/300A/3000A, 36”
LEMFLEX Current Probe, 30A/300A/3000A, 48”
LEMFLEX Current Probe, 60A/600A/6000A, 24”
LEMFLEX Current Probe, 60A/600A/6000A, 36”
LEMFLEX Current Probe, 60A/600A/6000A, 48”
NOTE: For split core type CTs and solid core type CTs,
contact the Dranetz-BMI factory.
Clamp-On AC Probes
Current Probe Assembly, 1 to 300A RMS
Current Probe Assembly, 1 to 30A RMS
Current Probe Assembly, 10 to 1000A RMS
Current Probe Assembly, 10 to 3000A RMS
Current Probe, 10 to 500A
AC Current probe, 1V/A, 1A
Current Probe, 1 to 10A
Current Probe, 10 to 3000A
AC Current probe, 5MV/A, 300A
AC Current probe, 1.5MV/A, 1000A
AC Current probe, 15MV/A, 100A
Adapter Cable, 658 Current Probe to 4300CA-4300
Adapter Cable, 4300/LEMFLEXCA4300LEM
Single Phase Measurement Cord, 115V, USSPMEASCORD-US
Single Phase Measurement Cord, 250V, EuropeSPMEASCORD-EURO
Single Phase Measurement Cord, 250V, UKSPMEASCORD-UK
Single Phase Measurement Cord, 250V, AustraliaSPMEASCORD-AUST
A-2
Continued on next page
Page 67
Hardware
Accessories List
(continued)
Appendix A/ Optional Accessories
AccessoryPart Numb er
Probe Adapter Cable, Hypertronics to RedelTRTOREDEL
Flex-R Probe Power Adapter TRTORFLEX
Voltage Cable Accessory PackVCP-4300
Fuse Voltage Adapter, for single phase connectionFVA-1
Fuse Voltage Adapter, for three phase connectionFVA-4
Probe Power Supplies
AC Adapter, 110VAC, 9VDC, 200MA, USACADP-PR9VUS
AC Adapter, 220VAC, 9VDC, 500MA, EuroACADP-PR9VEURO
AC Adapter, 240VAC, 9VDC, 500MA, UKACADP-PR9VUK
Main PX5 3VDC AdapterADPPX5-FLEX3V
AC Adapter with 4 Phase Adapter CableRR/PS/4P
LEMFLEX Power Supply PackageLF-PSP
Rack Mount Kit for Mainframe, With Display61RM TD
Rack Mount Kit for Mainframe, Without Display61RMT
Large NEMA Box for Mainframe, Without Display61WENCL
Single Module Enclosure for Mainframe61VENCL
Switchgear Mount Kit for Mainframe, With Display61SGENCL
Mainframe Power Supply
Power Supply, 100-250 VAC, US Cord61PSAC-US
Power Supply, 100-250 VAC, Euro Cord61PSAC-EURO
Power Supply, 100-250 VAC, UK Cord61PSAC-UK
Power Supply, 100-250 VAC, Australian Cord61PSAC-AUST
Power Supply, 125-250 VDC, Station Battery61PSDC-SB
Power Supply, 48 VDC Input61PSDC-48
Mainframes
61000 Series Mainframe, with Overlay61STD
61000 Series Mainframe, without Overlay61ST
Host Modules
Host/Comm Module, with GPS61HCG
Host/Comm Module, without GPS61HC
Time Synch Options
Antenna, GPS, with 10-foot CableGPSANT10
Antenna, GPS, with 100-foot CableGPSANT100
Field Handbook for Electrical Energy ManagementHB114415
Field Handbook for Power Quality AnalysisHB114414-S
Soft Carrying CaseSCC-4300
Reusable Shipping ContainerRSC-4300
Brackets, Wall Mounting for 61000, Pair61BRKT
A-4
Page 69
Enclosure Hardware Options
APPENDIX A/ Optional Accessories
Rack Mount
Panel with
Display
Diagram below shows the rack mount panel with provision for optional screen display
(P/N 61RMTD), showing distance specifications.
A-5
Page 70
Enclosure Hardware Options, continued
Rack Mount
Panel without
Display
Diagram below shows the rack mount enclosure without provision for screen display
(P/N 61RMT), in unassembled view. Rack mount panel and handle facing back.
Diagram below shows the same rack mount enclosure as above (P/N 61RMT), in
assembled view. Rack mount panel and handle facing front.
A-6
Page 71
Software Accessories List
Accessories List
Encore Series
Encore Series
Replacement HASP for Encore Series Software
®
Encore Series
Software
PQView
PQView V3.xPQVIEW
TM
Encore Series Software provides a centralized connection point for remote devices,
turning your computer into a self-contained server for a user designed power
monitoring network. Encore Series Software allows remote set up and operation of
61000. The user inteface is a convent ional Interne t browser, with access restricted only
to authorized users. The Encore Series Softw are program requires that the prope r
Dranetz-BMI computer hardware lock (called a HASP driver) be installed in the
computer.
APPENDIX A/ Optional Accessories
AccessoryPart Number
TM
Software
TM
SoftwareENCORE-SW
PQView
®
PQView® is a database management program that is used to archive, view and analyze
event data downloaded in the computer.
A-7
Page 72
This page intentionally left blank.
A-8
Page 73
Technical Specifications
General Specifications; Interfaces; Measurement Parameters
General Specifications
A
PPENDIX
B
Dimensions
Environmental
System Time
Clock
61000 without LCD panel
Size
: 11.25” Width x 3.5” Height x 7 3/4” Depth
Weight
61000 with LCD panel installed in 19” Rack
Size
Weight
Operating
Note: Operating range if optional local display is not included.
Storage
Humidity
Altitude
Crystal controlled; 1 second resolution for display
Event time clock displays to 1 msec resolution
Time displayed in analog or digital (12 or 24 hour) format (if optional local display is included)
Without GPS option
With GPS option
: 4 pounds
: 19” Width x 8” Depth
: 5 pounds
: -10 to 60 °C (-15 to 140 °F)
: -40 to 85 °C (-40 to 185 °F)
: 95% non-condensing
: 2000m (6560 ft) maximum
: Accurate to 30 seconds per month
: ±10 msec, does not change month over month
Power
Requirements
Use external UL/CE approved battery charger with international plugs.
Voltage
Consumption
Internal batteries
turned off (if optional local display is included).
: 90-265V ac, 50/60 Hz, 12Vdc output
: 15 watts max
: More than 1/4 hour run-time while communicating and backlight
B-1
Page 74
Interfaces
Interfaces
Installation
categories
Display
(optional)
Communication
Mains supply
Measurement inputs
For 61000 with LCD panel
Operating
Type
: 1/4 VGA color graphic, touch screen Liquid Crystal Display (LCD) with
compact fluorescent (CCFL) back lighting. Programmable backlight time-out to reduce
power consumption. Reactivates with touch.
Resolution
Viewing Area
Connect to the 61000 mainframe using either of the following external interface:
: Installation Category II, Pollution Degree 2
: Installation Category III, Pollution Degree 2
: 0 to 50 °C (32 to 122 °F)
: 360 x 240 dot matrix
: 3.75 x 4.75 inches
• RJ-45 connector for Ethernet
• RS-485 for serial multi-drop connection
• RS232 9-PIN serial port connector to external modem
• USB connector (not activated at this time)
• GPS antenna cable connector
B-2
Page 75
Measurement Parameters
: AC Voltage Modules
Voltage
Type
APPENDIX B/ Technical Specifications
Sampling rate
Connection:
Safety jack connectors
Terminal blocks
Voltage/Current external pod
• 5536 voltage pod
Channels A, B, C, D Input Range
Transient Input
±1000 Vpk full scale for low frequency
10-1000 Vpk for high frequency sample
Input imp edance
input configurations
Crest factor
RMS accuracy
±0.1% of Reading, ±0.05% Full Scale, over 7KHz bandwidth (1 second rms readings)
for low/medium frequency module
0.1% of Reading, over the nominal operating range of 50% to 100% Full Scale, as per
61000-4-30 Class A requirements, over the frequency range specified by 61000-4-30
Class A
: 512 samples per cycle
(Model 61MVB)
(Model 61MVS)
(Model 61MZP)
: 0 - 600Vrms for low frequency
:
: (Differential) 10 MΩ, minimum, Input to Ground on internal AC
: Maximum 2.0 at full scale
:
:
Transient accuracy
high frequency transient module
Transient Durati on
transient option
CMMR
Phase: Each voltage/current pair (i.e. Channel A voltage, Channel A current) are
sampled simultaneously to preserve phase relationship.
: -80 dB
: ±10% of Reading, ±0.5% Full Scale over 1MHz bandwidth for
: 32usec standard at 60Hz; 39usec at 50Hz; 1 usec with high speed
Continued on next page
B-3
Page 76
Measurement Parameters, continued
Frequency: Frequency ranges, user selectable.
For standard model:
• 15 - 70 Hz for low frequency data, with 16 2/3, 20, 50 and 60 Hz defaults in AutoConfig
Frequency (continued):
For high speed model:
• 400 Hz model, 45-70, 380-440 Hz, with 50, 60, 400 defaults in Auto-config
Environmental: All specifications are met over the operating range with influence
factors as per IEC 61000-4-30 Class A.
: AC Current Modules
Current
Type
Sampling rate
Channels A,B, C, D Input Range
Connection:
: 512 samples per cycle
: 1.5V rms
Hypertronics connectors to interface to:
• TR25xx clamp-on current probes (Model 61MAC)
• Flex-core models via external cable adapter
• Hall-effect probe models via external cable ad apter
Voltage/Current external pod
(Model 61MZP):
• 553x current pod
Channels A,B,C, D crest factor
RMS accuracy
: ±0.1% of Reading ±0.05% Full Scale plus Probe accuracy, 3KHz
: Maximum of 3 at full scale.
bandwidth (1 second rms readings) for low/medium frequency module
Transient accuracy
: ±10% of Reading, ±0.5% Full Scale over 1MHz bandwidth for
high frequency transient module
Transient Input
: 3 times Probe Rated N ominal Input (Dranetz-BMI probes)
Transient Durati on
B-4
: depends on probe bandwidth
Page 77
Transducer
: Transducer Input Modules
Type
APPENDIX B/ Technical Specifications
Digital Input
Transducer Input Range
:
• 0 - 24Vdc (Model 61MXVS)
• 4 - 20mA (Model 61MXAS)
Connectors:
• Phoenix connector type with screw terminal
Input Imp edance
RMS accuracy
: Digital Input Module (Model 61MDIN)
Type
: (Differential) >100 kΩ
: ±0.1% of Reading, ±0.05% Full Scale, plus transducer accuracy
Connectors:
• Phoenix connector type with screw terminal
Digital Input Range
:
• High state: > 3 Vdc
• Low state: < 1 Vdc
• Maximum input voltage: 125Vdc
Input imp edance
: >1 MΩ
Digital Ouput
Minimum Pulse Width
: Digital Output Module (Model 61MDOH)
Type
Contact Form:
Voltage Type
Max Voltage
Max Current:
Response Tim e
A
: AC/DC
: 250 Vrms
0.5A
: 1/2 cycle
: 1 msec
Continued on next page
B-5
Page 78
Measurement Parameters, continued
: Digital Output Module (Model 61MDOL)
Digital Ouput
Type
(continued)
Contact Form:
C
Voltage Type
Max Voltage
Max Current:
: AC/DC
: 25 Vpk
0.1A
Response Tim e
: 2 msec
B-6
Page 79
Introduction
Connecting an External DC Power Supply
Introduction; Connecting the DC Input Cable
A
PPENDIX
C
Introduction
WARNING
ADVERTENCIA
AVERTISSEMENT
An external dc source of power can be connected to the 61000 for normal operation.
This may be required where ac power is not available or operation from the internal
battery may extend pa st the batteries capabilit y.
An external stand-alo ne +12Vdc power supp ly of at leas t 5 amps capacit y may be used.
Connection is made to the input power connector through an optional dc cable
assembly.
Physical injury or damage to the instrument could result from incorrect
connections. Always observe correct polarity. Make connections to the 61000 first
and then make connections to the external dc power source.
Podrían producirse lesiones físicas o daños al instrumento debido a conexiones
incorrectas. Siempre observe la polaridad correcta. Efectúe primero las
conexiones al 61000 y luego haga las conex iones a la fuente de ene rgía de corriente
continua externa.
Des connexions incorrectes risquent de causer des blessures aux personnes ou
l’endommagement du matériel. O bservez toujours la polarité correcte. Faites les
connexions au 61000 en premier, puis branchez sur la source d’alimentation c.c.
externe.
WARNUNG
Fuses
Falsche Verbindungen können zu Verletzungen oder Schäden am Gerät führen.
Immer auf richtige Polarität achten. Zuerst Anschlüsse mit dem 61000 und dann
Anschlüsse mit der externen Gleichspannungsquelle vornehmen.
Internal 12V dc ci rcui try i s pro tecte d by r es ettab le fu ses moun ted on t he int ernal power
supply. These fuses will operate when an excessive external 12V voltage is applied or
when a fault condition within the internal circuit is experienced. To reset the fuse, turn
power off to the 61000 , dis connect the 12V p ower cor d, wait 5 s econds, the n reconn ect.
C-1
Page 80
Connecting the DC Input Cable
Connecting the DC Input Cable
WARNING
ADVERTENCIA
AVERTISSEMENT
WARNUNG
External power
source
Connecting the
cable
Physical injury, or equipment damage could result if the cable is connected
incorrectly. Verify all conn ections are correct before proceeding.
Podrían producirse lesio nes físicas o daños al equi po si se conecta incorr ectamente
el cable. Compruebe que todas las conexiones estén correctas antes de proceder.
Une connexion incorrecte du câble risque de causer des blessures aux personnes
ou l’endommagement du matériel. Vérifiez que toutes les connexions sont
correctes avant de poursuiv re.
Bei einem falschen Anschluß des Kabels kann es zu Verletzungen oder Schäden
am Gerät kommen. Vor dem Fortfahren überprüfen, ob alle Anschlüsse
ordnungsgemäß vorgenommen wurden.
The extern
Follow these steps when connecting the DC cable to the 61000.
d
al power source is 12Vdc.
StepAction
Disconnecting
the cable
C-2
1Turn off power to 61000.
2Turn off power to external power source.
3Disconnect ac power cable connected to 61000 input power
connector. Connect plug of dc cable to 61000 input power
connector.
4If external power supply is used, turn on its power. If power
supply is adjustable, set output to 12V dc.
5Connect dc cable alligator clips to ext ernal power source (battery
or power supply). Red leads to positive (+) terminal and black
leads to negative (-) terminal.
6Turn on power to the 61000.
When external DC power is no longer required, perform the connecting procedure
above in reverse order.‘
Page 81
61000 System Firmware Upgrade
Firmware upgrade instructions
Firmware Upgrade Instructions
A
PPENDIX
D
61000 firmware
upgrade
System
requirem ents
Procedure
Users can upgrade the 61000 int ernal progra m by uploa ding the latest firmwar e relea se
from an Internet site specified by Dranetz-BMI and installing it into the 61000 internal
memory. Refer to the instructions below on how to upgrade the firmware.
The system specifications for proper 61000 firmware upgrade and installation are
shown below. Dranetz-BMI recommends the use of a l aptop computer with a cross over
cable when upgrading firmware.
Operating SystemMS Windows® 98, Windows® 2000 or Windows® XP
Category 5e CableStandard RJ45 connector, crossover cable
61000 firmware upgrade consists of five major steps: setting up connections between
the 61000 unit and the computer; connecting to the IP address provided by DranetzBMI; uploading the firmware to the unit; verifying firmware update; and preparing the
Encore Series Softwa re for monitoring. Follow the instructions below to i nstall the
latest firmware version into the 61000.
STEP 1: Power up the 61000 and set up proper physical connection between the unit
and the computer.
1.1. Connect the appropri ate power cord t o the v oltage r ating o f the unit. Make
connection to the instrument first, then connect power cord to the
applicable power source. When done, turn ON the power switch located
on the rear of the unit. Verify that the Power Indicator LED blinks every
16 seconds.
NOTE: The number of blinks corresponds to the number of installed
modules.
Power Indicator
Continued on next page
D-1
Page 82
Firmware Upgrade Instructions, continued
Procedure
(continued)
1.2. Connect one end of the crossover RJ45 Category 5e cable to the 10BaseT
port of the 61000 and the other end to the computer ethernet port.
STEP 2: Use the computer to assign the Netburner IP address provided by Dranetz-
BMI and establish network connection.
2.1. Run the IPSetup.exe program from the files supplied by Dranetz-BMI.
2.2. Type in 192.168.0.20 in the IP field.
2.3. Type in 255.255.255.0 in the Network Mask field.
2.4. Click on the Set button.
2.5. The following message is displayed under Select a Unit window if the
procedure was done correctly:
MOD5272 [xx-xx-xx-xx-xx-xx] at 192.168.0.20 running :Swordfish COM
2.6. Click on Close to close the program.
STEP 3: Upload the latest firmware version to the unit.
3.1. Open Internet Explorer and type in 192.168.0.20 in the IP address bar.
Press retur n and the foll owing screen will appear.
D-2
Type in admin for User name, and password for Password.
NOTE: Use lowercase character s when ente ring user name and password.
Continued on next page
Page 83
APPENDIX D/ 61000 System Firmware Upgrade
Procedure
(continued)
3.2. After typing in the user name and password, click on the OK button. The
Summary Information screen will appear.
3.3. Click on the icon found on the left side bar. The Factory Debug
Options screen will appear.
Continued on next page
D-3
Page 84
Firmware Upgrade Instructions, continued
Procedure
(continued)
3.4. Click on the Upload Firmware
option to open the Firmware Upload
screen shown below.
3.5. Select the Host Mo d ule radio button and click on Continue to proceed.
The following screen will appear.
3.6. Select the file to upload. Click on Browse and select filename
D-4
HostCode.b4u from the files supplied by Dranetz-BMI.
Continued on next page
Page 85
APPENDIX D/ 61000 System Firmware Upgrade
Procedure
(continued)
3.7. When done selecting the file to upload, click on Continue and wait until
the following screen appears.
3.8. Click on Continue to proceed.
3.9. If a Calibration Failed page is displayed, repeat the process from Step
3.1.
NOTE: If several attempts fail, turn the power switch OFF then turn back
ON, and repeat the process from Step 3.1.
3.10. If the file was loaded properly, continue the procedure as follows.
3.11. Click on the icon found on the left side bar. The Factory Debug
Options screen will appear.
3.12. Click on the Upload Firmware
option, and the following screen will
appear.
Continued on next page
D-5
Page 86
Firmware Upgrade Instructions, continued
Procedure
(continued)
3.13. Select the Meas urement Module radio button and click on Continue to
proceed. The following screen will appear.
3.14. Select the file to upload. Click on Browse and select filena me
MeasCode.b4u from the files supplied by Dranetz-BMI.
3.15. When done select i ng t he file to upload, click on Continue and wait until
the following screen appears.
3.16. Click on Continue to proceed.
3.17. If a Calibration F ailed page is displayed, repeat the process from Step
D-6
3.11.
NOTE: If several attempts fail, turn the power switch to OFF then tu rn
back to ON, and repeat the process from Step 3.11.
Continued on next page
Page 87
APPENDIX D/ 61000 System Firmware Upgrade
Procedure
(continued)
3.18. If the file was loaded properly, continue the procedure as follows.
3.19. Click on the icon found on the l eft side bar. The Fa ct ory Debug
Options screen will app ear.
3.20. Click on the Upload Firmware
option, and the following screen will
appear.
3.21. Select the Co mmunications Module radio bu tton and click on Continue
to proceed. The following screen will appear.
3.22. Select the file to upload. Click on Browse and select filena me
NB_x_x_xx_APP.b4u from the files supplied by Dranetz-BMI.
Continued on next page
D-7
Page 88
Firmware Upgrade Instructions, continued
Procedure
(continued)
3.23. Once the file has been uploaded, click on Continue to proceed.
3.24. When firmware upload procedure is complete, the screen will return to
the Home page. Close the Internet Explorer program to exit.
STEP 4: Verify the firmware update.
4.1. Restart the unit by turning the power switch to OFF then turn back to ON.
4.2. The Status LED should blink every 16 seconds if the firmware upload
procedure was done correctly.
NOTE: The number of blinks correspond to the number of installed
modules.
4.3. Open Internet Explorer and type in 192.168.0.20 in the IP address bar.
Press retur n to display th e Encore Se ries Home page.
Continued on next page
D-8
Page 89
Procedure
(continued)
APPENDIX D/ 61000 System Firmware Upgrade
4.4. Click on the icon found on the left side bar, and then select
Dump the Host Console. The following screen will appear.
NOTE: Verify date and time should indicate the actual time and date
when the firmware was updated.
4.5. Click on the icon found on the left side bar, and then select
Dump the Input Module 1. The following screen will appear.
NOTE: Verify date and time should indicate the actual time and date
when the firmware was updated.
When done verifying firmware update, close the Internet Explorer to exit.
Continued on next page
D-9
Page 90
Firmware Upgrade Instructions, continued
Procedure
(continued)
STEP 5: Preparing the Encore Series Software and the unit for monitoring.
5.1. After uploading the latest firmware to the unit, open Internet Explorer
and type in 192.168.0.20 (or the assigned IP) in t he IP address bar . Press
return and the following screen will appear.
Type in admin for User name, and password for Password.
NOTE: Use lowercase character s when ente ring user name and password.
5.2. Click on OK and the following screen will appear.
5.3. Click on the icon found on the left side bar. Then select List
D-10
Commands.
Scroll down to Put Time enter the correct date and time. Select the
icon. This will send the cu rrent time and date entered to the
instrument.
Continued on next page
Page 91
APPENDIX D/ 61000 System Firmware Upgrade
Procedure
(continued)
The following message will appear:
<?xml version="1.0" ?>
<commandresultid="16" name="PUTTIME"
result_code="0" />
5.4. Click on the icon found on the left side bar. Then select List
Commands.
Scroll down to Put Time enter the correct date and time. Select the
icon. This will purge the data on the data card in the instrument.
5.5. Close the Internet Explorer program. The instrument is now ready to
begin monitoring using the Encore Series Software.
5.6. Click to open the Windows Start menu, select All Programs. Open the
Encore Series Software program.
Type in admin for User name, and password for Password.
NOTE: Use lowercase character s when ente ring user name and password.
Click to open the Setup tab. Scroll down to DataNodes folder and select
61000 Power Quality Data Node. Right-c lick to di splay the Add Datanode
command. Click to add DataNode1, where a setup can be edited.
5.7. Click to open the Identification and Status sub-tab of DataNode1. Click
on DataNode1 name valu e fie ld if you wan t to speci fy a ne w name for the
DataNode.
5.8. Next, click to open t he Commun ica ti ons sub-tab and enter the designated
IP address followed by “/0”, for example 198.168.0.20/0.
5.9. Next, click to open th e Polling sub-tab. Click to enable the following
checkboxes: Enable Scheduled Polling, Download and store data, Send
setting to DataNode. If a message appears, select Yes to save changes.
Return to the Communications sub-tab, and click to enable the Active
checkbox. Select Save Setups, a message appears, select Yes to save
changes.
5.10. The instrument set up is complete and is now ready for monitoring. The
Monitoring On LED (middle LED) of the unit sho uld be in a steady state,
indicating that monitoring has been turned on.
D-11
Page 92
This page intentionally left blank.
D-12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.