9.1Glossary on parameter and object names......................................55
4 Technical Manual | Wireless communication
1 Introduction
This document supplements the instructions for use for gas warning devices:
– Dräger Polytron
– GasSecure GS01 / GasSecure GS01-EA
– Polytron Repeater ISA100
– Polytron 6700 IR WL
This document contains additional information on the ISA100 Wireless
1.1 Target group
This document is intended for technicians with training in PLC programming,
trained electricians or persons who have received instruction from a trained
electrician. These persons must also be familiar with the applicable standards.
1.2 General safety statements
Before using this product, carefully read the associated instructions for use. This
document does not replace the instructions for use.
®
6100 EC WL
Introduction
TM
interface.
1.3 Meaning of the warning notes
The following warning notes are used in this document to notify users of possible
dangers. The meanings of the warning notes are defined as follows:
Alert iconSignal wordConsequences in case of nonob-
servance
WARNINGIndicates a potentially hazardous situation
which, if not avoided, could result in death
or serious injury.
CAUTIONIndicates a potentially hazardous situation
which, if not avoided, could result in injury.
It may also be used to alert against unsafe
practices.
NOTICEIndicates a potentially hazardous situation
which, if not avoided, could result in damage to the product or environment.
1.4 Typographical conventions
TextText marked in bold denotes labeling on the device and on-screen
messages.
►This triangle labels possible methods of avoiding the hazards men-
tioned in warning notices.
>The greater-than sign denotes the navigational path in a menu.
This symbol denotes information that make using the product easier.
Technical Manual | Wireless communication 5
Introduction
1.5 Brand names
–HART® is a registered trademark of the HART Communication Foundation.
–PROFIBUS
e. V.
– FOUNDATION
– ISA100 Wireless
Automation (ISA).
– Bluetooth
– WirelessHART
Communication Foundation.
–PROFIsafe
®
is a registered trademark of the PROFIBUS Nutzerorganisation
TM
®
is a registered trademark of Bluetooth SIG, Inc.
®
®
is a registered trademark of Siemens Aktiengesellschaft.
is a registered trademark of the Fieldbus Foundation.
TM
is a registered trademark of the International Society of
(WHART) is a registered trademark of the HART
6 Technical Manual | Wireless communication
Wireless data transmission in industrial settings
2
3
1
P6P6
2 Wireless data transmission in industrial settings
There are a number of different protocols and types of network for wireless data
transmission, which will be described in this manual in conjunction with Dräger
products. The following diagram shows the application areas for various protocols.
Other protocols (WPAN, for example) are not considered in this context.
40934
Fig. 1Wireless data transmission protocols
1WFAN
2WLAN
3
Bluetooth
®
or infrared
WLAN and WFAN
In a WFAN (Wireless Field (or Factory) Area Network), industrial field devices
communicate with one another or with a control center. The control center controls
and monitors the field devices. When communicating via WFAN, protocols such as
ISA100 Wireless
TM
and WirelessHART® (WHART) are used.
WLAN (Wireless Local Area Network) is a local, usually private wireless network.
The WLAN infrastructure of an industrial plant is used for mobile end devices and
video transmission (stationary cameras).
Technical Manual | Wireless communication 7
Wireless data transmission in industrial settings
Main application areas
There are 3 main areas of application for wireless networks:
– Plant safety
Transmitters monitor safety-critical areas and send wireless measured values.
ISA100 Wireless
TM
allows for SIL 2-compliant failsafe communication through
the transport of PROFIsafe
– Monitoring field devices
The status of field devices is monitored (e.g. temperature, sensor status of a gas
warning device).
– Process monitoring and process control
Wireless data transmission allows for detailed process monitoring and process
control without expensive cable routing costs.
These areas of application must be able to tolerate latencies of 100 ms.
Advantages of a wireless network
Wireless networks offer many advantages compared to wired networks.
– Wireless networks can be made operational more quickly and installing the
infrastructure creates less costs.
– Wireless networks can be expanded with greater ease and at less cost. Adding
new field devices and putting them into operation, as well as removing them, is
easier.
– The parameters of field devices as well as diagnostics and maintenance can be
configured centrally.
– Errors do not occur when wiring field devices (e.g. cable break, wiring problems
in the field device).
– Wireless networks can be employed in places a wired network would be
impossible, expensive, or difficult to implement (e.g. on rotating platforms).
– Temporary installations that are dismantled after a certain time also profit from
wireless networking. Temporary installations no longer need arduous and
expensive cabling.
®
messages.
Furthermore, a wired network’s infrastructure can be expanded wirelessly (creating
redundancy).
8 Technical Manual | Wireless communication
3 ISA100 WirelessTM basics
ISA100.11a is a wireless networking protocol internationally recognized as IEC
Standard 62734 and developed by the International Society of Automation (ISA). It
is based on the ISO/OSI reference model and allows for reliable, secure data
transmission for control- and regulation-related applications, process monitoring
and alerts.
ISA100 Wireless
data transmission even over long distances with low power consumption.
As with most fieldbus systems, a ISA100 Wireless
any field devices required due to standardization. All field devices in the network
can interact with one another independent of manufacturer.
ISA100 Wireless
system management, gateway requirements and security specifications.
Failsafe communication
ISA100 Wireless
between controller and field device. This secure data transfer method is performed
via tunneling. Tunneling facilitates the use of different communication protocols via
the ISA100 Wireless
PROFIsafe
outside the ISA100 Wireless
TM
is comparable to a fieldbus system in that it allows for reliable
TM
defines basic functions and requirements for field devices,
TM
allows for failsafe communication (e.g. SIL 2-compliant)
TM
®
communication protocol. This communication protocol is transmitted
infrastructure. Failsafe communication is done via the
TM
infrastructure via PROFINET.
ISA100 WirelessTM basics
TM
network can be expanded with
Advantages of ISA100 Wireless
TM
There are different wireless network protocols. Among others, the ISA100
Wireless
– Transfer of other communication standards (e.g. PROFIsafe
TM
protocol has the following advantages over other protocols:
®
, HART®)
– Bandwidth for safety-relevant data can be reserved. This reserved bandwidth
ensures the rapid transmission of safety-relevant data at any time to the control
center. The transmission of safety-relevant data is not affected by other data
traffic.
– Response times of a ISA100 Wireless
TM
network are variable and shorter than
those of other protocols.
Technical Manual | Wireless communication 9
ISA100 WirelessTM basics
3.1 Network components and participants
4
18
5
6
7
6
10
14
15
16
13
11
12
P6
Fig. 2Example topology of a wireless network
3
5
P6
8
1
9
17
38243
2
1Control center
2Control unit for wired field devices
3Control unit
4System manager
5Access point in the function as a backbone router
6Access point
7Access point in the function as a field device access point
8Hop point
9Retrofitted field device
10 I/O field device
11GasSecure GS01
12
Dräger Polytron
®
6100 EC WL
13 Backbone
14 Ethernet or fiber-optics
15 Wireless data transmission from an access point to the backbone
16 Wireless data transmission between field devices and to the backbone
17 Wired analog or digital communication
18
Wired Modbus communication or PROFIsafe
®
communication via PROFI-
BUS/PROFINET
10 Technical Manual | Wireless communication
3.1.1 System manager
The system manager monitors and manages the following system functions,
among others:
– Security management
– System performance, system latencies, redundancy
– System time
– Field device management (e.g. address allocation and routing tables)
Wireless gateway and system manager are the same thing for the purposes of this
manual. In detailed descriptions, system managers and gateways must be
considered separately from one another.
Controllers are connected to the system manager (e.g. Dräger REGARD
with Modbus Master module). Control units process the system manager’s data and
trigger alerts or countermeasures.
If PROFIsafe
F-host (failsafe host) must be used as a controller , which communicates with Fslaves (FailSafe field devices). In this case, the system manager only forwards the
messages and does not interfere with PROFIsafe
®
is used for communication purposes (e.g. for SIL 2 applications), an
ISA100 WirelessTM basics
®
communication.
®
7000
3.1.2 Backbone
The backbone is the wired part of the network, which connects the backbone router
(BBR) to the system manager. The connection is established via fiber-optic cable
(FOC) or Ethernet.
3.1.3 Access points (AP)
An access point is the transition from the wireless to the wired parts of the network.
Access points transmit the information from their end devices via cable to the
system manager. APs can be compared to the base station of a mobile landline
phone. In both cases, a wireless network is established for a multitude of mobile
end devices.
An AP performs different roles depending on the position in which it is located in the
network.
3.1.3.1 Backbone router (BBR)
If an access point is wired directly to the backbone, the access point is referred to
as the backbone router. Several backbone routers can be connected to the
backbone.
Field devices and field device access points communicate wirelessly with the
backbone router via the sub-network, which is established by the backbone router.
Technical Manual | Wireless communication 11
ISA100 WirelessTM basics
Additional access points can be wired to the backbone router.
Risk of confusion
Backbone routers are connected to the backbone via cables. Repeaters or field
devices with routing functionalities are often also referred to as routers. However,
these "routers" are not connected to the backbone via cables and only forward the
signals.
Backbone routers as part of the system manager
Backbone routers can also be part of the system manager.
3.1.3.2 Field device access points (FDAP)
Field device access points are access points that communicate wirelessly with the
backbone. Communication to the backbone is done either via access points or
directly over the backbone router.
Dräger-approved devices are listed in the appendix.
3.1.4 Field devices
Field devices may also be called terminal devices or clients. They log on to the AP
and exchange information. Field devices are also called I/O devices because they
receive (input) and send (output) data.
There are field devices that communicate with the control center via cable in
addition to communicating wirelessly. These field devices are retrofitted with an
ISA100 Wireless
TM
antenna. They additionally communicate via wire with another
interface (a 4–20 mA interface, for example).
Field devices can be mobile field devices (tablets, smartphones, laptops), stationary
field devices or slow-moving stationary field devices. Mobile field devices often
communicate with an additional system manager or gateway via a different protocol
(non-ISA100 Wireless
TM
Due to their being integral elements of the network infrastructure, access points or
field device access points are not called field devices.
3.1.4.1 Routing functionalities
Some field devices can also act as a router in addition to their normal functionality.
Field devices with this function activated create hop points in the network.
These devices are often connected to a power line due to the extra energy
requirements involved in router operation.
Field devices with routing functionalities are also available without measuring
functions. They are then only integrated into the network as routers. The Polytron
Repeater ISA100 is a router without measuring function.
).
®
12 Technical Manual | Wireless communication
3.1.4.2 Power supply
P6P6
P6
1
1
2
ISA100 WirelessTM basics
Power is supplied to field devices via batteries or the power grid. ISA100
Wireless
TM
allows for every type of power supply.
If battery operation is not possible, field devices are connected to an external power
supply. An external power supply may be necessary if the routing functionality is
active and there is a lot of wireless communication.
When operating in explosion-hazard areas, an upstream safety barrier must be
installed for external power supplies.
3.1.5 Hop points
Routers or field devices with a router function form a hop point in the sub-network.
Hop points expand a network and ensure redundant transmission routes. Signals
are forwarded without processing and no separate sub-network is established.
Data transmissions via hop points to the system manager are slower than direct
data transmissions to access points. Latencies (wait times) at the hop points can
delay communication.
The communication paths via hop points are prevented ex-factory for some
system managers. But, the function can be activated.
Restrictions for installations with short response times
Series-connected hop points can delay the response time. If response times are a
critical factor, there must be a limited number of hops (wireless interfaces) from the
field device to the access point. Fig. 3 shows a sub-network with only one (1) or two
(2) hops allowed.
Fig. 3Hop points in a sub-network
1First hop point after the sub-network access point
One further hop point is possible.
2Second hop point after the sub-network access point
Another hop point could cause too much of a delay in the response time.
System managers from Yokogawa support a maximum of 4 hops (wireless
interfaces) between a field device and the backbone router (as at September 2020).
38255
Technical Manual | Wireless communication 13
ISA100 WirelessTM basics
12
3.1.5.1 Routers
Routers are also called repeaters. Routers increase the size of the network and
cancel out weak spots. They form a hop point in the sub-network. Incoming data is
forwarded without processing.
Routers do not establish their own sub-networks.
3.2 Network topologies
There are 3 network topologies for ISA100 networks.
– Star topology
– Mesh topology
– Partial mesh topology
3.2.1 Star topology
In a star topology, field devices communicate with one or more access points. The
field devices can only exchange information via access points, not directly with one
another. Multiple access points are often employed to make the network more failsafe.
Fig. 4Star topology and communication channels
1Primary communication channel
2Secondary communication channel
40935
14 Technical Manual | Wireless communication
3.2.2 Mesh topology
In a mesh topology, all network participants that are within range communicate with
one another. Field devices, routers and access points can be network participants.
In a mesh network, the data transmission is redundant. If communication over a
field device or a repeater is interrupted, the data is transmitted via other network
participants.
Fig. 5Mesh topology
ISA100 WirelessTM basics
4093640937
3.2.2.1 Partial mesh topology
The mesh topology and star topology can be mixed. This combination is called a
partial mesh topology or star-mesh topology. In this topology, a core network, in
which all network participants are interconnected, is expanded with network
participants that are no longer connected with all network participants.
Fig. 6Partial mesh topology
1Preferred communication channel
2Redundant communication channel
1
2
Technical Manual | Wireless communication 15
ISA100 WirelessTM basics
3.2.3 Comparison of star topology and mesh topology
Network cards are best compared by using the most important criteria for networks:
Reliability and latency.
Reliability
In a mesh network, network participants exchange information with each other (IoT
approach). If one network participant fails, communication is still possible. If a
network participant fails in a star topology, communication can fail.
Latencies
The latency of star topologies is usually less than that of meshed ones due to the
field devices being directly connected to an access point.
3.3 Network performance and network configuration
The wireless connection between field devices and the access point depends
greatly on the surroundings. The connection is best when there is an unobstructed
line of sight between the two. Oftentimes, however, there is no line of sight (due to
intervening pipes or walls, for example). If the line of sight is obstructed, routers or
the reflective properties of the obstacles themselves are used.
3.3.1 Signal quality
The signal quality of wireless transmissions depends on the signal strength (RSSI)
and the signal integrity (PER or TxFail rate). The RSQI range is another indicator of
signal quality.
PER or TxFail rate
This value represents the error rate during data transmission from the field device
to the backbone. This value is displayed as a percentage. The lower the value, the
better the integrity of data transmission. High values show poor data transmission
integrity. Poor data integrity can be caused by unfavorable communication paths or
interferences (other wireless technologies or obstacles, for example).
The expression and the limit values of this error rate depend on the manufacturer of
the system manager. The error rate can be expressed either as PER (packet error
rate) or as a TxFail rate.
RSSI
RSSI (received signal strength indication) shows the received signal strength
between the field device and the access point. RSSI is expressed in dBm (decibelmilliwatts). The received signal strength is always shown as a negative number.
The closer the value is to zero, the better the wireless connection.
RSQI
RSQI (received signal qualitiy indication) shows the received signal strength
between the field device and the access point. RSQI is a calculated value. Higher
values indicate better data transmission than lower values. Four quality classes are
defined in the standard ISA-100.11a (see table below).
16 Technical Manual | Wireless communication
ISA100 WirelessTM basics
P6P6
Signal quality values and their meaning
The interpretation of the value ranges can be adjusted in some system managers.
The following table provides an example of the ranges for the purpose of
orientation.
IndicatorValue rangeMeaning
PER / TxFail rate0 to 15 %Good
15 to 100 %High
RSSI-75 to -25 dBmGood
-85 to -75 dBmAcceptable
-100 to -85 dBmPoor
RSQI196 to 255Excellent
128 to 195Good
64 to 127Acceptable
0 to 63Poor
Fresnel zone
Signal quality can be disrupted by obstacles even if transmitter and receiver have
line of sight. Disruption due to obstacles occurs when obstacles are located in the
Fresnel zone. The Fresnel zone is an elliptical area formed around the line of sight,
whose diameter increases with the transmission range. It is therefore
recommended to install antennas as high up as possible to ensure longer distances
are covered.
Fig. 7Line of sight between field device and access point with an elliptical
Fresnel zone
38862
Technical Manual | Wireless communication 17
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.