Dovre 400 Installation & Operating Instructions Manual

Aladdin Hearth Products
401 N. Wynne
ADivision of Hearth Technologies Inc.
Colville, WA99114
THE MODEL 400
WOODSTOVE
INSTALLATION & OPERATING
INSTRUCTIONS
IF THIS STOVE IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. FOR YOUR SAFETY, FOLLOW THE INSTALLATION DIRECTIONS. CONTACT LOCAL BUILD­ING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA.
SAFETY NOTICE:
5-98 2 72308B
MODEL 400 WOODSTOVE
PLEASE RETAIN THIS MANUALFOR FUTURE REFERENCE.
Table of Contents
A. Listings and Code Approvals..........................................................................................................................3
B. Woodstove System Components...................................................................................................................3
C. Pre-Installation Preparation............................................................................................................................4
1. Minimum Clearances to Combustibles.....................................................................................................4
2. Floor Protection........................................................................................................................................6
3. Chimney Height Requirements................................................................................................................7
4. Flue Systems............................................................................................................................................8
5. Masonry Chimney....................................................................................................................................9
6. Listed Factory-Built Chimney.................................................................................................................12
D. Step-By-Step Installation of the Woodstove.................................................................................................15
E. Operating Instructions ..................................................................................................................................17
F. Maintenance Instructions.............................................................................................................................21
G. Flue Draft .....................................................................................................................................................23
H. Installation of Replacement Glass................................................................................................................25
Limited Warranty...........................................................................................................................................27
Safety Precautions:
1. Please read these installation instructions com-
pletely before beginning installation procedures. Failure to follow them could cause a woodstove malfunction resulting in serious injury and/or property damage.
2. Always check your local building Codes prior to
installation. The installation must comply with all local, regional, state and national Codes and Regulations.
3. An adequate supply of replacement combustion
air from outside the house must be available to the fire for the woodstove to operate properly.
Aladdin is not responsible for any smoking or related problems that may result from the lack of adequate combustion air. It is the responsibility of the builder/contractor to ensure that adequate combustion air has been provided for the wood­stove.
4. NEVER leave children unattended when there is a fire burning in the woodstove.
5. This woodstove is built for solid fuel only. DO NOT use chimney cleaners or flame colorants in
your fireplace.
6. NEVER use gasoline, gasoline type lantern fuel, kerosene, charcoal lighter fluid, or similar liquids in this woodstove. Keep any flammable liquids a safe distance from the unit.
7. To ensure a safe woodstove system and to pre­vent the buildup of soot and creosote, inspect and clean the woodstove and chimney prior to use and periodically during the burning season.
These installation instructions describe the installation and operation of the D O V R E®Model 400 woodstove.
This stove meets the U.S. Environmental Protection Agency's 1990 particulate emission standards. Under specific test conditions this stove has been shown to deliver heat at rates ranging from 8,700 to 22,500 BTU/HR.
The D O V R E®Model 400 is listed by Underwriters Laboratories Inc. to UL Safety Standard 1482 and ULC Safety Standard S627.
Check with your local Building Code Agency before you begin your installation to ensure compliance with
local Codes, including the need for Permits and follow-up inspections. Be sure local building Codes do not supersede UL specifications and always obtain a Building Permit so that insurance protection benefits cannot be unexpectedly canceled. If any assistance is required during installation, please contact your local dealer or the Dovre Customer Relations Department, 401 N. Wynne, Colville, WA99114.
D O V R E®is a registered trademark of Aladdin Hearth Products. Aladdin Hearth Products is a Division of Hearth Technologies Inc.
I t ’s a good idea to plan your installation on paper, using exact measurements for clearances and floor protection, before actually beginning the installation. If you’re not using an existing chimney, place the stove where there will be a clear passage for a factory-built listed chimney through the ceiling and roof.
We also recommend that you have a qualified building inspector and your insurance company representative review your plans before installation.
5-98 3 72308B
MODEL 400 WOODSTOVE
A. LISTINGS AND CODE APPROVALS
B. WOODSTOVE SYSTEM COMPONENTS
The D O V R E®Model 400 has several options available for installation and appearance. These options are packaged separately and are listed below and pictured on page 4.
Catalog Number Description:
400 Non-catalytic - painted black with ash pan 400PBK Non-catalytic - black porcelain enamel with ash pan 400PCR Non-catalytic - creme porcelain enamel with ash pan 400PGR Non-catalytic - green porcelain enamel with ash pan 400PBL Non-catalytic - blue porcelain enamel with ash pan 400HSB Back shield to reduce clearances & allows use of fan kit DFK1 Fan kit (requires use of 400HSB for completion) DT6BK Door trim kit, black DT6G Door trim kit, gold
DOOR TRIM
MODEL 400 WOODSTOVE
DT6BK
DT6G
HEATSHIELD FAN KIT
400HSB
DFK1
C. PRE-INSTALLATION PREPARATION
1. MINIMUM CLEARANCES TO COMBUSTIBLES.
The clearances listed in Table I are the minimum distances that must be maintained, as demonstrated in Figures 1 and 2. It is important to note that simply covering a combustible material with a non-combustible material does not offer sufficient heat protection. For example, drywall conducts the radiant heat directly to the wood, and the effect is the same as if the wood was unprotected.
Clearances to a combustible backwall may be reduced to 8” by using Dovre Backshield, part #400HSB, and listed double wall connector pipe.
The following table and diagrams show the minimum clearance requirements between your Dovre, chimney con­nectors and unprotected combustible walls and materials. If further reduced clearances are needed, obtain requirements for construction of a protected wall from your local building code authorities and their allowable reductions of the listed clearances.
5-98 4 72308B
5-98 5 72308B
MODEL 400 WOODSTOVE
Table I
Minimum Clearances to Combustibles
FLUE TOP (WITH REAR HEATSHIELD) 8” 15” 18”
CLEARANCES FROM UNIT TO COMBUSTIBLES
BACKWALL SIDEWALL CEILING
FLUE TOP 15” 15” 18” FLUE REAR 24” 15” - -
Figure 1
Flue Top Clearances
Figure 3a
Figure 2
Flue Rear Clearances
Figure 3b
2. FLOOR PROTECTION.
Acombustible floor must be protected from the radi­ant heat given off by the unit and from the inevitable spark or falling ember. This includes almost any floor surface. Only a solid masonry or concrete floor ade­quately covering the distance around the unit is acceptable. Alayer of thin brick or ceramic tile over a combustible floor is insufficient. To protect your floor, it is necessary to install a floor protector of one layer of 3/8” non-combustible millboard having a thermal conductivity of K = 0.84 BTU IN/FTHr F, or an equally thick UL listed floor protector. The required dimen­sions of floor protector vary according to the length of chimney connector as shown. If you construct your own floor protector with the one layer of millboard, we suggest that it be covered by one sheet of 24-gauge, or heavier, galvanized sheet metal. It can then be covered with ceramic tile, or thin brick, and framed to protect the millboard and give it a finished look.
NOTE: The minimum Floor Protector Size for the Model 400 Woodstove is 31” wide x 39” deep.
Any horizontal length of chimney connector pipe must also have the floor protector beneath it and extending 2” on each side of the pipe. The required floor pro­tector size for Model 400 is 31” x 39”. Refer to Figures 3a and 3b.
WARNING!
COMPLIANCE WITH ALL MINIMUM CLEARANCES SHOWN IN
THIS MANUAL IS NECESSARY FOR YOUR SAFETY.
MODEL 400 WOODSTOVE
NOTE: In calculating equivalent thickness of alternate materials, the following formula should be used:
One layer of 3/8” (0.375 inch) thick mill-
board has a K factor of
(BTU) (INCH)
0.31 (HR) ( FT
2)
(F) at 75 F
NOTE: Dotted line indicates additional floor protection required on through-the-wall chimney installation. Floor protection must extend behind the stove to the rear wall.
Figure 4
Floor Protection
5-98 6 72308B
5-98 7 72308B
MODEL 400 WOODSTOVE
Figure 5
(Thermal Conductivity) “K” = BTU in./hr. ft2F (based on 1” thickness) To substitute alternate insulation material, you need to know the “K” factor for that material. To calculate the
required thickness for the alternate material use the following formula:
EXAMPLES OF INSULATION
Required
Thickness “K” Value
MICORE 300 1" .45
“K” Alt.
x 1 = Thickness of alternate mat. (inches)
.45
“K” of brick = 5
5
x .50 = 5.5 In. of brick.
.45
3. CHIMNEY HEIGHT REQUIREMENTS.
WARNING!
ALWAYS FOLLOW CHIMNEY CONNECTOR MANUFACTURER’S INSTRUCTIONS FOR PROPER INSTALLATION.
CHIMNEY CONNECTOR IS TO BE USED ONLY WITHIN THE ROOM, BETWEEN THE STOVE AND CEILING WALL, NEVER PASSING THROUGH A COMBUSTIBLE CEILING OR WALL. ALWAYS KEEP MINIMUM CLEARANCES TO COMBUSTIBLES AS SHOWN IN TABLE 1.
WARNING!
IF INSTALLING THIS MODELTO AMASONRY CHIMNEY, ALWAYS BE SURE THE CHIMNEY IS IN GOOD CONDITION AND THAT IT MEETS THE MINIMUM STANDARDS OF THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) STANDARD 211.
THIS APPLIANCE IS MADE WITH A6 INCH/152 MM. DIAMETER CHIMNEY CONNEC­TOR (IF YOU ARE USING A FACTORY-BUILT CHIMNEY SYSTEM, AS RECOMMEND­ED) AS THE FLUE COLLAR ON THE UNIT.
CHANGING THE DIAMETER OF THE CHIMNEY CAN AFFECT DRAFT AND CAUSE POOR PERFORMANCE. IT IS NOT RECOMMENDED TO USE OFFSETS OR ELBOWS AT ALTITUDES ABOVE 4000 FEET ABOVE SEA LEVEL OR WHEN THERE ARE OTHER FACTORS THAT AFFECT FLUE DRAFT.
Amasonry chimney or a factory-built chimney must
Figure 7
Chimney Connector
be the required height above the roof and any other nearby obstructions. The chimney must be at least 3 feet higher than the highest point where it passes through the roof and at least 2 feet higher than the highest part of the roof or structure that is within 10 feet of the chimney, measured horizontally. See Figure 6.
These are safety requirements and are not meant to assure proper flue draft.
We recommend using a minimum total system height of 12 feet/3657 mm when using single wall connec­tor, not including the chimney cap, measured from the stove flue collar to the top of the chimney. For a listed connector pipe, use a minimum total system height of 9 feet/2743 mm.
MODEL 400 WOODSTOVE
4. FLUE SYSTEMS.
There are two separate and different parts to a flue system: the chimney connector and the chimney itself.
Chimney Connector.
The chimney connector connects the stove to the chimney. The connector must be the same size as the flue outlet of the stove. There are two types of chimney connectors.
A. Single wall connector or stovepipe. This must be
at least 24 gauge mild steel or 26 gauge blue steel. The sections must be attached to the stove and to each other with the crimped (male) end pointing toward the stove. See Figure 7. All joints, including the connection at the stove collar, should be secured with three sheet metal screws. Make sure to follow the minimum clearances in Table 1, page 5.
B. Factory-built listed chimney connector (vented).
The listed connectors must be the same brand at the listed chimney.
Figure 6
Chimney Height
5-98 8 72308B
NOTE: The chimney connector must be attached to either an approved masonry chimney or any safety listed factory-built chimney.
5-98 9 72308B
MODEL 400 WOODSTOVE
5. MASONRY CHIMNEY.
Be sure a masonry chimney meets the minimum standards of the National Fire Protection Association (NFPA) Standard 211. It must have at least a 5/8 inch/16 mm fire clay liner or a listed chimney liner system. Make sure there are no cracks, loose mortar or other signs of deterioration and blockage. It is best to have the chimney inspected by a professional and be sure to have the chimney cleaned before the stove is installed and operated.
The flue should be checked to determine that it is not too large for the stove. NFPA211 allows the cross-sectional area of the flue to be no more than 3 times the cross-sectional area of the flue collar of the stove (28 x 3 = 84). It is recommended that a chimney with a larger diameter be relined, since the oversized flue can cause poor performance and contribute to the accumulation of creosote. (See page 16 for more information about draft.)
When connecting the stove through a combustible wall to a masonry chimney, special methods are needed. There are several ways to make this connection, including the construction of a masonry thimble. Check with your local building authorities or consult the National Fire Protection Association (NFPA211). Refer to Figure 8.
NOTE: Never install more than one appli­ance to any Chimney.
Figure 8
Masonry Thimble
Loading...
+ 19 hidden pages