DIMMERMASTER 624
DIGITAL DIMMER
OWNER'S MANUAL
DM624
Dove Lighting Systems, Inc.
3563 Sueldo Street Unit E
San Luis Obispo, Ca 93401
+1 805 541 8292 fax +1 805 541 8293
dove@dovesystems.com / www.dovesystems.com
1
TABLE OF CONTENTS
1 SETUP AND CONNECTION
A Mechanical Installation
B Rack Mounting
C Electrical Installation
D Grounding
E Load Connections
F Control Connections, Overtemp Sensing
G Channel Selection and Testing
H Indicators
2 TROUBLESHOOTING CHART
3 WARRANTY INFORMATION
2
SETUP AND CONNECTION
Remove all packing material from the unit. Make certain that all holes are free of obstruction on all sides
For portable use, set the Dimmermaster on a smooth, cool surface. Up to 2 packs may be stacked
vertically. Do not remove the feet when stacking. Do not block any vent holes. Make certain that the
vent holes all have at least 6 inches of free air around them. It is essential that this unit have adequate
cooling for safe, reliable performance. Maximum air temperature must not exceed 40 Centigrade (105
The Dimmermaster may be rack mounted in a standard EIA 19-inch equipment rack. The rubber feet
may be removed. Do not remove the top and bottom panels. The Dimmermaster occupies 5.25 inches
of space in the rack, or three rack units. For best cooling, an additional 1.75 inches, or one rack unit,
between packs is recommended. The rack should be ventilated from the top at a minimum of 120 CFM.
The dimmer must be supplied with an amount of current equal to the combined total current of the
lamps it controls. To calculate this current, use the formula amps = watts ÷ volts. For example, if six
2400-watt, 120 volt lighting units are connected to the dimmer, it would require 14,400 ÷ 120, or 120
amps total power. This is available from a three phase 4 wire 40 amp or a single phase 3 wire 60 amp
service. Usually this much power is not required and a 30 - 50 amp service may be used with lower
The Dimmermaster accepts either three phase or single phase power input and is factory configured
for three phase. Line to neutral voltage is always 120 volts. Line 1 to Line 2 voltage is 208 volts in three
phase service and 240 volts in single phase service. It is very important that the input voltages be
checked with a meter to insure that they are correct. A mistake can place 208 to 240 volts across a 120
volt lamp. The breakers will protect the unit but may not save the lamps. A double check of voltages
The power input connector is a terminal block. Each leg of the power feed connects to one terminal on
the dimmer pack. These are marked "L1", "L2", and "L3". The neutral connection is made on the neutral
bar, just to the left of the power block. The ground connection is made on the ground terminal, just to
the right of the power block. The pack has circuit breakers to protect each dimmer channel, but the
When single phase service is used switch S2, located near the center of the board, must be moved
from the "3 phase" position to the "1 phase" position. The power input terminal marked "L3" is not used.
The two blue wires wrapped with red tape must be moved to the terminal marked "L1" and the two
wrapped with black tape to "L2". The tiny blue wire stays in terminal "L3". Please refer to the diagrams
A Mechanical Installation
of the unit. Replace all packing material in the carton and store it for reuse.
Fahrenheit).
B Rack Mounting
C Electrical Installation
power loads plugged in.
before applying power can guard against such disaster.
primary circuit protection and disconnect is to be provided by the user.
at the rear of this manual.
3