Doug Fleenor Design DMX8DIM User Manual

DOUG FLEENOR DESIGN, Inc.
Model DMX8DIM Installation and
Operations Manual
Doug Fleenor Design, Inc. 396 Corbett Canyon Road Arroyo Grande, CA 93420
(805) 481-9599 Voice and FAX
Page 1 of 7
Product description
The DMX8DIM is an 8 channel, 250 Watt dimmer. It is fed by a single 120VAC 20A branch circuit. Each output is protected by a self-resetting poly-fuse. Each of the dimmers can be separately controlled using a typical DMX512-based lighting controller. The DMX8DIM is housed in a standard NEMA1 electrical enclosure. Knockouts are provided on the top and bottom of the enclosure for easy installation. Cables may enter the sides of the enclosure by using standard chassis punches.
Safety warnings
The DMX8DIM should only be installed by qualified personnel in accordance with local electrical codes.
There are no user serviceable parts in the DMX8DIM. Servicing should be referred to qualified service personnel.
Do not operate the DMX8DIM without the cover installed.
Turn off all power to the DMX8DIM before installing. Do not attempt to wire or install any part of the DMX8DIM with the power on.
Environmental
Operating temperature: 0-40º C Operating humidity: 10-90% non-condensing Indoor use only
Electrical ratings
Input: 120VAC, 60Hz, 20A Output: 8 outputs, 120VAC, 250W each. Self-resetting protection on each output.
Certification
The DMX8DIM is ETL Listed under safety Standard UL 508.
Mounting
The DMX8DIM can be mounted on any stable surface in compliance with local electrical codes. To mount the DMX8DIM:
Remove the cover by loosening the front panel screws
Select the desired mounting location
Locate the mounting holes using the DMX8DIM as a guide
Secure the DMX8DIM to the surface using appropriate fasteners
After all wiring is complete and switches have been configured (see below), install the cover and secure it in place.
General installation notes
If enclosure knock-outs are used or if holes are punched in the enclosure for wire entries, the holes must have appropriate bushings or conduit fittings installed to protect the wires from cuts and abrasion.
Page 2 of 7
Safety grounding must be maintained through this product. Metallic conduit may be used for grounding if it is appropriately bonded to the enclosure. The ground terminal on the line input and all output terminals may be used for grounding conductors. All such terminals are internally bonded to the enclosure.
Power input (line) wiring
Supply the DMX8DIM with a protected branch circuit of no more than 20A. The power input terminals on the DMX8DIM are rated for #12AWG copper wire (maximum). The torque rating for the terminals is 4.51 IN/LB.
Input power wiring must enter the enclosure and route directly to the input power terminals without crossing over the circuit board or any control wiring.
Line input terminal
Power output (load) wiring
Each output can supply a 250W (maximum) 120VAC load. The output terminals are rated for #12AWG copper wire (maximum). The torque rating for the terminals is 4.51 IN/LB.
Load wiring must enter the enclosure and route directly to the input power terminals without crossing over the circuit board or any control wiring.
Load terminal (1 of 8 shown)
Page 3 of 7