For Commercial Applications
ES-D-R325N32-0509-06
Job Name
Job Location
Engineer
Approval
–––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
Contractor
Approval
Contractor’s P.O. No.
Representative
SKU
––––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––
Natural Gas
Appliance Regulator
R325N32-0509-06 (2 PSIG Gas System)
½" NPT Female X ½" NPT Female
Gas appliance pressure regulators for 2 psi piping systems for use on
residential, commercial and industrial applications. Features a high leverage
linkage assembly to deliver positive dead-end lock-up. The regulators are
capable of precise regulating control from full flow down to pilot flow. Housings
are high strength aluminum castings and all models are suitable for multipositional mounting. If ball check vent limiting device is installed, mount in an
upright position only.
R325N32-0509-06 (2 PSIG Gas System)
Technical Data
Item CapaCIty maX IND. LOaD maX INLet pressure TemperaTure LimiTs sprING raNGe sprING set pOINt DesIGN CertIfICatIONs
R325N32-0509-06 150,000 100,000
(BTU/HR) (BTU/HR) PSI (kPa) Degrees Fahrenheit " WC " WC CSA (C and US)
2 (13.8)
-40 to 205 5 - 9 6 ANSI Z21.18/CSA 6.3
Vent Limiting Device #12A09
1
⁄8" NPT
1
⁄2" NPT (TYP.)
R325N32-0509-06 (2 PSIG Gas System)
NOTICE
Vent limiting devices are designed for use indoors and in spaces
where limiting the amount of gas escapement due to diaphragm
failure is critical. Vent limiting devices should not be used out-
doors if they are exposed to the environment. Vent protectors
are available for all outdoor applications to ensure proper vent
protection. 13A15 (
Maxitrol Regulator distributed by Dormont. Model 325-3 Series Lever Acting Design.
Dormont product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Dormont Technical Service. Dormont reserves the
right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Dormont products previously
or subsequently sold. Refer to the owner's manual for warranty information.
1
⁄8" NPT) and 13A15-5 (3⁄8" NPT).
USA: Tel: (800) 367-6668 • Fax: (724) 733-4808 • Dormont.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • Dormont.ca
Latin America: Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • Dormont.com
ES-D-R325N32-0509-06 1610 © 2016 Dormont