Dormont Supr-Safe® Flexible Gas Appliance Connectors
The flexible connection between the gas supply and the gas inlet of a Generac
Features
• Operating Temperature -40°F to 150°F (-40°C to 65.6°C)
• Operating Pressure MAX 0.5psi (3.45 kPa)
• Hydrostatic Burst Pressure MIN 250psi (1725 kPa)
• Flare Nut Material Carbon Steel with Zinc Trivalent
• Flare Adapter Material Carbon Steel with Zinc Trivalent
CSA Group Certificate of Compliance to Product Standards
ANSI Z21.75/CSA 6.27 – Connectors for Outdoor Gas Appliances
Scope states “…intended for exterior use above ground for making non-rigid connections…between the gas supply and the gas inlet of an appliance for outdoor installation that is not frequently moved after installation.” In addition section 1.5.4 states the connector is designed for occasional movement after installation. Repeated bend­ing, flexing or extreme vibration must be avoided. Normal opera­tion of a clothes dryer, rooftop HVAC unit or SIMILAR OUTDOOR APPLIANCE DOES NOT constitute extreme vibration or movement.
ANSI Z21.24/CSA 6.10 – Connectors for Gas Appliances
®
Stationary Outdoor Backup/Standby Generator.
Chromate Plating
Chromate Plating
and Manufactured Homes
(Excluding 60/61 Series)
Applicable Codes
ANSI Z223.1/NFPA 54 National Fuel Gas Code Section 9.6 International Fuel Gas Code (IFGC) Section 411.1 B149.1 – Natural Gas and Propane Installation Code
Uniform Mechanical Code (UMC) Section 1313.0 Uniform Plumbing Code (UPC) Section 1212.0
Additional Approvals
Commonwealth of Massachusetts Board of State Examiners of Plumbers and Gas Fitters
Additional Testing
UL2200-2015: Stationary Engine Generator Assemblies Section 66B Vibration Test.
For use with Generac
stationary outdoor backup/
standby generators.
Series 30, 40 and 60
(CSA Group) Section 6.21
Product Configurations
Part Number SerIeS NomINal ID NomINal oD
in in in in
CAN30-3131-14GL 30 CAN40-4141-14GL 40 CAN60-6161-15GL 60 1-
“CAN” prefix indicates product supplied with both English and French instructions for Canada
1
2
3
4 1
4
WARNING
All installations must completely comply with all Dormont manufacturing company warnings and instructions, national, state and local codes and all applicable ansi standards.
Dormont product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measure­ments, please contact Dormont Technical Service. Dormont reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Dormont products previously or subsequently sold. Refer to the owner's manual for warranty information.
5
8
1 ¾ 14
1-1⁄
2
Flare aDaPter threaDS
(male NPt)
½ 14
1-1⁄
4
NomINal leNgth
15
Minimum Flow Capacity at Specified Pressure Drop
(Straight Length BTU/hr. NATURAL GAS, 0.64 SG, 1000 BTU/cu.ft.)
CoNFIguratIoN PreSSure DroP [INCheS water ColumN]
Part Number SERIES Nominal ID Nominal Length
in in
CAN30-3131-14GL 30 CAN40-4141-14GL 40 CAN60-6161-15GL 60 1-
1
2
3
4
1
4
14 174,500 213,500 246,500 275,500 302,000 326,000 349,000 14 338,500 414,500 478,500 535,000 586,000 633,000 677,000 15 1,171,500 1,434,500 1,656,500 1,852,000 2,029,000 2,191,000 2,343,000
(Straight Length BTU/hr. LP GAS, 1.55 SG, 2500 BTU/cu.ft.)
CoNFIguratIoN PreSSure DroP [INCheS water ColumN]
Part Number SERIES Nominal ID Nominal Length
CAN30-3131-14GL 30 CAN40-4141-14GL 40 CAN60-6161-15GL 60 1-
in in 0.50 in 0.75 in 1.00 in 1.25 in 1.50 in 1.75 in 2.00 in
1
2
3
4 1
4
14 279,200 341,600 394,400 440,800 483,200 521,600 558,400 14 541,600 663,200 765,600 856,000 937,600 1,012,800 1,083,200 15 1,874,400 2,295,200 2,650,400 2,963,200 3,246,400 3,505,600 3,748,800
EXAMPLE
Dormont part number CAN30-3131-14GL can supply a minimum of 349,000 BTU/hr. of natural gas @ 2.00 in. water column pressure drop to the generator.
0.50 in 0.75 in 1.00 in 1.25 in 1.50 in 1.75 in 2.00 in