Dorman Smith LOADLINE YB3 Installation Instructions

Page 1
Packaged Items/Assembly Tools
Operating Instructions
Fitting Internal Accessories
Breaker
uct
ion
1
233P:
4P:
Instruction Manual (This document)
Interpole Barrier
(Only FC)
17
65
RESET
TRIPPED
YBAL
Alarm Switch
YBAUX1
Auxiliary Switch
YBST** YBUVR**
Shunt Trip Undervoltage Trip
Ring Mark
10 mm
Auxiliary Switch Alarm Switch
a contact b contact
a contact
b contact
11/AXc-14/AXa 11/AXc-12/AXb
91 /ALc -
21/AXc-24/AXa 21/AXc-22/AXb 31/AXc-34/AXa 31/AXc-32/AXb 41/AXc-44/AXa 41/AXc-42/AXb
Shunt Trip
power source
C1-C2
Undervoltage Trip
power source
D1-D2
94 /ALa
91 /ALc ­92 /ALb
Symbols of Accessories
Symbols of Accessories
Dummy unit
After fitting, verify the function of the Accessory.
ON
Handle
OFF
Trip Button
AX AL SH UV
V
Form the cable
Pull Out Leads on Load Side
Combination
Removal
In case of fiting one (or two) auxiliary switch, fit in an order from a left side-slot.
3 pole
4 pole
Please retain this manual for future reference.The Manufacturer assumes no responsibility for damages resulting from non-application or incorrect application of the instructions provided herein.
Operation effortOperation
(OFF) (ON)
53N
(ON) (OFF)
57N
TRIP (OFF)
91N
Connections/Poles
YB3
Front Connection
M4 55
3P
2
4P
4
M8 18
6 8
Qty Mounting screw Qty
Type
Connecting screw
3P 4P
Rear Connection
M4 55 M8 25
3P
2
3P
6
4P
4
4P
8
Plug-in Connection
M4 65
M83P
2
3P
6
4P
4
4P
8
DORMAN SMITH
A49914
LOADLINE YB3 FRAME
Instruction Manual for Moulded Case Circuit Breakers
Fixed Type YB3***TF
Adjustable Thermal Magnetic Type YB3***T
Dorman Smith Switchgear Limited
8 Swinbourne Drive Springwood Industrial Estate Braintree Essex CM7 2YG UK Tel: +44 (0) 844 225 1063 Fax: +44 (0) 844 225 1064
Safety Notices
Be sure to read these instructions and other documents accompanying this product. Please familiarise yourself with handling of this product, safety information, and all other precautions before mounting, using, servicing or inspection. In these instructions, safety notices are divided into "Warning" and "Caution" according to the hazard level.
WARNING
A warning notice with this symbol indicates that neglecting the suggested procedure or practice could result in lethal or serious personal injury.
CAUTION
A caution notice with this symbol indicates that neglecting the suggested procedure or practice could result in moderate or slight personal injury and/or property damage.
Note that failing to observe
CAUTION
notices could result in serious results in some cases. Because safety notices contain important information, be sure to read and observe them.
Mounting Precautions
For detailed mounting dimensions, refer to either the Loadline or System Loadbank catalogues.
CAUTION
Electrical work should only be undertaken by suitably qualified persons.
Do not place the product an an area that is subject to high temperature, high humidity, excessive dust air, corrosive gas, strong vibration and shock, or other unusual conditions. Mounting in such areas could cause a fire or malfunction.
Be careful to prevent foreign objects (debris, concrete, iron powder etc) and rainwater from entering product. These materials inside the product could cause a fire or malfunction.
Prior to commencing any work on the product, open an upstream circuit breaker or isolator to ensure that no voltage is applied to the product otherwise electrical shock may result.
For 4 pole breakers, be sure to connect a neutral conductor to the N-phase pole, otherwise an overcurrent may hinder the product from tripping thus resulting in a fire.
When connecting cable or busbar to the product, tighten terminal screws to the torque specified in this manual, otherwise, a fire could result.
After conductor connection, do not apply excessive force to the terminals. Otherwise, a fire may result.
For front-connected breakers, insulate all bare conductors of the line side until the breaker end. If interpole barriers are packed, be sure to use the barriers; moreover, insulate all bare conductors by insulting tape or the like so that the tape overlaps with the barriers. Insufficient insulation may result in short-circuit.
Do not block the arc gas vents of the product to ensure adequate arc space. Blocking these vents could result in failure of circuit interruption.
Handling Precautions
WARNING
Never touch terminals. Otherwise, electric shock may result
CAUTION
When the breaker trips open automatically, remove the cause, then return the handle to the ON position. Should a fault be interrupted, the breaker must be inspected, otherwise, a fire may result.
Maintenance Precautions
CAUTION
Service and/or inspection of the product must be done by persons having expert knowledge.
Before servicing or inspecting the product, open an upstream circuit breaker or the like to isolate all sources of power. Otherwise, electric shock may result.
Regularly check that the breaker terminal screws are tightened to torque values shown within this manual, failure to do so may result in fire.
Other Precautions
Do not carry this product by accessory leads, as this may cause damage to the product.
Unauthorised opening of the breaker cover will invalidate product warranty.
When installing the product, use wires or conductors, the cross sectional areas of which accommodate the rated current of the product. Using wires or conductors with inadequate cross sectional areas may cause false tripping and overheat.
Page 2
Breaker Mounting
Conductor Connection Procedure for RC/F.P (where applicable)
Procedure for FC / RC
Interpole Barrier Terminal Cover Mounting Procedure
Time/Current Characteristic Curves
Mounting Procedure
M4 55 mm
1.3 1.7N m
Adjustable Thermal Magnetic Type
Conductor Connection Procedure for FC
OFF
11
9
5
7
0.63
0.8
1
l
i
(
x
l
n
)
l
R
(
x
l
n
)
Insulate all bare conductors of the line side until the breaker end.
When removing, remove the items in
reverse order of mounting.
When removing, remove the items in
reverse order of mounting.
0.63 0.8 1
11975
I
T
/R Adjustment Range
/
i Adjustment Range
I
n
x
I
n
0.63 0.8 1
1086 13
I
T
/RAdjustment Range
/iAdjustment Range
I
n
x
I
n
( =100, 125, 160, 200A)
I
n
( =250A)
I
n
L
L
M
13
N
Solderless Terminals Mounting Procedure for FC
A
J
C
22mm
D
11mm
E
8.4mm
F
25mm
G
11mm
H
7mm
I
9mm
L
M6 18 mm
11.8 18.6N m
7.8 11.8N m
M
9mm
N
M8 25 mm
Flat Bar Stud
YB3RT*P
M8 18
7.8 12.7N m M10 25
22.5 37.2N m
K
J
J
K
6
17
Flat Bar
YB3XT*P YB3XTS*P
Interpole Barrier
YB3TB
Terminal Cover Lock
Rear/Plug-in Connected
(RC / PM)
Connection
Front Connected
(FC)
YB3TS*P
Terminal Cover
YB3TC*P
YB3TS*PS
End cap
Solderless Terminal
YB3CC*P
P
120mm
2
Q
19N m
R
M6 20mm
6.9 9.3N m
R2
T2FW25LS
O
23mm
10
6
Handle Lock Mounting Procedure
Handle Lock
YBDL1
Handle lock can be fitted in any position of I (ON) and O (OFF).
When removing, remove the items in reverse order of mounting.