Dorma M6D Installation Manual

Page 1
DORMA
Installation Manual Terminal M6D
Page 2
Page 3
M6D
Table of Contents
Table of Contents
1. General .................................4
1.1 Preface.................................5
1.2 Intended use.............................5
1.3 Safety instructions and warnings ..............5
1.4 Further Source of Information . . . . . . . . . . . . . . . .6
1.5 Disposal ...............................6
1.6 Functional principle . . . . . . . . . . . . . . . . . . . . . . .6
1.7 Components supplied ......................7
1.8 Assembly accessories (optional) ...............7
2. Assembly ................................8
2.1 Terminal design ..........................8
2.2 Casing variants ...........................8
2.3 Dimensions..............................9
2.4 Opening and closing the terminal .............10
2.5 Assembly preparations .....................11
2.6 Assembly with flush cabling .................12
2.7 Inclined console .........................13
2.8 Inclined console with 230 V supply voltage ......14
3. Connection variants ........................15
3.1 External connections of the M6D .............15
3.2 Power supply ...........................15
3.3 Communication interfaces ..................15
3.3.1 RS485 bus ...........................15
4. Commissioning ...........................16
4.1 Settings ...............................16
4.1.1 Bus address...........................16
4.1.2 Connection resistor ......................17
4.2 Tampering protection ......................17
4.3 Reader settings .........................18
5. Maintenance ............................19
5.1. Fuses ................................19
EU Declaration of conformity ...................20
6. Technical data ...........................24
Page 4
M6D
1. General
The information provided in these assembly instructions may be modified without prior notification. All previous ver­sions cease to be valid with the publication of these instruc­tions.
The information in these assembly instructions has been compiled to the best of our knowledge and in good faith. DORMA accepts no liability for the correctness and com­pleteness of the details provided.
In particular, DORMA cannot accept liability for any conse­quential damages due to incorrect or incomplete informa­tion.
The recommendations for installation provided in this manu­al are based on favourable basic conditions being present. DORMA accepts no liability for the perfect functioning of the M6D in external, non-system environments.
Despite every effort to prevent mistakes, they can never be completely avoided. Therefore, we would be grateful to receive notification of any errors or omissions.
DORMA accepts no liability for the information included in this document being free of protected third party rights. DORMA does not provide any licences to its own or to third party patents or other protected rights with this document.
It is not permitted to print, reproduce or to pass this manual, or parts thereof, to third parties, other than for your own use, without the approval of DORMA.
All rights reserved.
DORMA Time + Access GmbH Postfach 21 01 85 53156 Bonn http://www.dorma-time-access.de E-Mail [email protected]
© Copyright 2011 by DORMA Time + Access GmbH
Diagram no.: 1053G-00-B1 Status: 10/13 V1.30
Page 5
M6D
1. General
1.1 Preface
This installation manual is intended to assist you in con­necting and commissioning the M6D.
1.2 Intended use
The device is used as a time recording and access control terminal. Further details are described in chapter 1.6. Any other use than that indicated is not permitted!
1.3 Safety instructions and warnings
This device has been constructed and tested in accordance with the relevant current technological regulations. It left the factory in perfect condition in terms of technological safety and reliability. To maintain this condition and to ensure risk­free operation, the instructions and warnings given in this assembly guide must be observed by the user.
• The device may only be used for the purpose intended by the manufacturer.
• The installation and assembly of electrical devices may only be carried out by an electrical engineer.
• Before opening the unit, always switch off the power supply and verify that the device is free of voltage by per­forming a measurement.
• During assembly, please ensure that the requirements laid down in the relevant device safety standard for the unit are not negatively affected, as this would reduce the safety level of the unit.
• Before switching on, ensure that the operating and con­trol voltages connected do not exceed the permissible values in accordance with the technical data.
• This unit conforms to EN 60950-1 protection class III
• The units must be operated with safety extra low voltage (SELV)!
Electromagnetic compatibility:
• The device is designed for use in residential, business and commercial areas and conforms to EN 61000-6-2 and 61000-6-3.
• The PCB is at risk from electrostatic discharge and the relevant precautionary measures should be observed (earthing, etc.).
Caution
• These devices may only be operated when fully assem­bled.
• The locking screws on unassigned connection terminals should be screwed in as far as they will go.
• If it has to be assumed that danger-free operation is no longer possible, take the unit out of operation and secure against accidental use.
• If the failure or malfunctioning of the unit may result in injury to persons or animals or in damage to works equip­ment, this must also be prevented by using additional safety measures (limit switch, safety devices, etc.).
• Switch off the power supply before opening the device.
Page 6
M6D
1. General
1.4 Further Sources of Information
Further documents are available on request.
General Installation Guidelines
Specifications for planning attendance recording and access control systems with our wired components.
Planner Manual
Examples of cross-system solutions
1.5 Disposal
The device was manufactured using recyclable materials and components. When disposing of the device and the packaging, please ensure environmentally friendly recycling.
Information for EU Countries
European Directive 2002/96 EC applies to this device. This means that this product must not be disposed of with normal household waste. We, the manufacturer, will take back our electric and electronic products and dispose of them for you free of charge. Correct disposal of your old equipment protects people and the environment from possible harmful consequences.
1.6 Functional principle
The M6D terminal serves as a display and operation station in an attendance recording system. It has a keyboard that can be used to operate various que­ries and functions in the system.
The identity and the rights of the user are determined using a badge and where applicable by entering a PIN. The badge data is queried by the integrated reader. The data recorded are sent via an RS485 bus to a host ter­minal for evaluation. After they have been processed in the host, the result is sent via the RS485 to the M6D terminal and shown visually on a two-line display.
DORMA
Algeme ne In tal tonsich linen
Z
Z
A
Page 7
M6D
1. General
1.7 Components supplied
A M6D B Assembly instructions C 1 x cable binder
D 2 x Spax screws (4.5 x 35 mm) E 2 x dowels (6 mm)
1 x drilling template
A
B
2x
E
D
2x
DORMA
Installation Manual Terminal M6D
C
1x
1.8 Assembly accessories (optional)
a Inclined console, art. no. 1900070400119 b Inclined console with 230V-supply voltage, art. no. 1900070400120 c Front lock, art. no. 1900004912571
c
b
a
Page 8
M6D
2. Assembly
2.1 Terminal design
The terminal consists of the top casing section and the bottom casing section. The models are explained in the next chapter.
Top section
Bottom section
Contactless reader (PXL) Swipe reader (DZL)
2.2 Casing variants
Page 9
M6D
2. Assembly
176,3 mm
59,3 mm
176,3 mm
2.3 Dimensions
Page 10
M6D
2. Assembly
10
2.4 Opening and closing the terminal
The unlocking mechanism is accessed through the hole on the underside of the terminal. If there is a lock in this hole, remove the lock first. To open the casing you need a rod-shaped tool (such as a screwdriver) which you insert through the unlocking hole.
Using strong pressure, increasing in force on the unlocking piece on the inside, the casing will spring open. (See right.) Then pull the top casing section vertically towards the wall as far as it will go to remove it from the lower casing sec­tion. Then swivel the top casing section to the left.
To close the unit, follow the same steps in the reverse order.
When working on the open casing, it is advisable to lock the front using the front locking catch. This tool can also be used to open the terminal.
Please note the following points:
• Do not allow the flat-band cable between the top and bottom casing sections to be trapped when closing.
• The unlocking piece must be positioned to fit the guide.
• The top casing section can only be positioned parallel to the bottom section based on the design.
When the top casing section is positioned on the bottom casing section, the unit can be closed using even pressure on the right and left-hand sides of the top casing section. This means that an audible "click" can be heard when the unit is closed correctly.
d
Page 11
M6D
2. Assembly
11
2.5 Assembly preparations General
General
When planning the installation site for the terminal, the required space specified in the diagram opposite must be provided. This space is necessary to ensure problem-free operation and sufficient room for servicing work.
The installation height specified is recommended to provide persons of average height the optimum operation and view of the display.
If it is necessary, or desired, that a different height is used, an assembly wedge piece should be used.
Once the installation site has been determined, the cables should be laid first of all. Specifications on the planning and installation of time systems and access systems using our components are described in the General Installation Guidelines.
The following assembly types are possible:
• Flush cabling (standard)
• Inclined console assembly with flush cabling or surface wiring
For each installation type, the relevant specifications on the position of the cable infeed and cable length must be observed.
M6D terminal with contactless readers
To prevent interference from both sides, the two devices with contactless readers may not be installed closer to each other than the minimum specified distance. This minimum distance depends on local speci­fications. It should always be greater than 50 cm.
min.
165 mm
Top edge of finished floor
min.
165 mm
15000 mm
Inclined console
Page 12
M6D
2. Assembly
12
2.6 Assembly with flush cabling
For the cable outlet, use a flush box with a maximum width of 40 mm. We recommend wall lighting connection boxes. Refer to the illustration so that the cable emerges from the wall correctly at the knock-out section on the back side of the M6D. The box may not protrude above the contour of the underside of the casing.
Then use the attached drilling template to draw the two mounting holes required for fixing and drill them with a 6 mm drill bit.
Before drilling, ensure that you will not be able to damage any cables or similar located underneath the plaster. Now insert the dow­els included with delivery into the drill holes.
Cable packaging
The data cable should be cut to a length of 120 mm so that it can be easily connected after the terminal is installed. Strip the cable completely from approx. 10 mm after the wall opening.
Final assembly
Before the M6D is firmly attached, pull the connecting cables through the opening in the rear panel. Finally, the device can be screwed onto the wall with the screws includ­ed with delivery and aligned properly.
94mm
79mm
max. 40mmmin. 10mm
Underside of the casing
Casing contour
Page 13
M6D
2. Assembly
13
2.7 Inclined console
If the terminal needs to be installed underneath the recom­mended installation height of 1,500 mm, the poor viewing angle should be adjusted using the inclined console.
There are two holes on the underside on the right. These must be closed using the blind plugs from the accessories kit. If the cables are being laid directly against the wall, these need to be punched out.
First the two mounting holes required for fixing are drawn in accordance with the illustration below and drilled using a 6 mm drill bit.
Before drilling, ensure that you will not be able to damage any cables or similar located underneath the plaster.
Now insert the dowels included with delivery into the drill holes, but do not mount the inclined console yet.
Cable packaging
The data cable should be cut to a length of 130 mm so that it can be easily connected after the terminal is installed. Strip the cable completely from approx. 60 mm after the wall opening.
Final assembly
First pull the connecting cables through the opening in the rear panel. Now the inclined console can be screwed onto the wall. Afterward, insert the cables into the opening in the rear panel of the terminal. Finally, the M6D can be screwed onto the inclined console with the screws included with delivery.
3116
6
284215
120
79
83
105
9
range of cable exit
Page 14
M6D
2. Assembly
14
2.8 Inclined console with 230 V
supply voltage
To power the M6D with 230 V supply voltage, the inclined console can be ordered with a built-in power supply unit.
To create the connection, connect the phase and the neutral wire directly to the power supply unit. Connect the protec­tive conductor to the earthing screw in the inclined console.
The power supply is designed for a perma­nent connection to the power supply circuit only. It must be connected by a qualified electrician only.
The power supply circuit for this power sup
­ply requires a suitable, easily accessible power isolating device with a minimum contact gap of 3 mm and a fuse element to protect against short circuits, both already provided on site.
The earth conductor must be connected.
If the M6D-terminal is supplied with alternating current (AC) it must not be used for the power supply of sub-devices.
Sub-devices may only be supplied with direct current (DC)!
Page 15
M6D
3. Connection variants
15
3.1 External connections of the M6D
All external connections are on the basic card.
ST103
24V
A(+) B(-) 0V
24V
A(+) B(-) 0V
ST102
3.2 Power supply
The power supply for the M6D is connected to terminal 24 V and 0 V of the ST102. ST103 serves as the connec­tion for other bus devices. The pin assignment of ST103 is identical with ST102. The voltage must lie in the range of 16 V to 36 VDC or 24 VAC.
3.3 Communication interfaces
3.3.1 RS485 bus
The RS485 bus line is connected to the connection terminals ST101 and ST102, signals A(+) and B(-). The pin assignment of ST103 is identical with ST102.
3
1
B A
1
A
B
3
ST102
ST103
0V
24V
B(-) A(+)
0V
24V
B(-) A(+)
RS485 bus
further bus
If the M6D-terminal is supplied with alternating current (AC) it must not be used for the power supply of sub-devices.
Sub-devices may only be supplied with direct current (DC)!
Page 16
M6D
4. Commissioning
16
4.1 Settings
4.1.1 Bus address
The bus address can be set with the 8-pin DIP switch SW201. 31 addresses are available. The address 00 is reserved for the control unit.
SW201 1 2 3 4 5 6 7 8
Functionality
Bus address Test mode
RS485
Bus connection resistor
Bit0 Bit1 Bit2 Bit3 Bit4 on/off on/off on/off
Binary value 2
0
2
1
2
2
2
3
2
4
SW201 / 6 Funktion
off (factory setting) Normal mode: If switch SW201/6 = off, the M6D functions in normal mode.
on on test mode:
If switch SW201/6 = on, the test mode is activated if no communication occurs at the RS485 interface after the M6D is switched on. If the M6D recognises communication at the RS485 interface, it switches into normal mode.
SW201
Page 17
M6D
4. Commissioning
17
*) The address 00 is reserved for the control unit.
4.1.2 Connection resistor
The bus connection resistors must be switched on if the M6D is the first or last bus device.
4.2 Tampering protection
A light barrier for tampering protection is integrated into the M6D, which sends a signal to the higher level terminal if the casing is opened.
Switch SW201
Address
(decimal)
1 2 3 4 5
off off off off off 00* on off off off off 01 off on off off off 02 on on off off off 03 off off on off off 04 on off on off off 05 off on on off off 06 on on on off off 07 off off off on off 08 on off off on off 09 off on off on off 10 on on off on off 11 off off on on off 12 on off on on off 13 off on on on off 14 on on on on off 15
Switch SW201
Address
(decimal)
1 2 3 4 5
off off off off on 16 on off off off on 17 off on off off on 18 on on off off on 19 off off on off on 20 on off on off on 21 off on on off on 22 on on on off on 23 off off off on on 24 on off off on on 25 off on off on on 26 on on off on on 27 off off on on on 28 on off on on on 29 off on on on on 30 on on on on on 31
Page 18
M6D
4. Commissioning
18
SW101
6
Configuration protection
off off
on active
4.2 Reader settings
Hitag (PX10) Legic advant-Leser (PX51) Mifare DESfire-Leser (PX71)
SW101
1 2 3 4 5 6 7 8
Function
unused 1) 2) 3)
1)
Configuration protection
When configuration protection is activated, the configuration cannot be changed or deleted
.
SW101
1 2 3 4 5 6 7 8
Function
unused Reader Function unused
SW101
Reader Function
4 5 6
off off off Indala-Trovan (Kombi)
off off on Indala (Flexpass)
off on off Trovan (TIMAC)
off on on free
on off off Trovan current customer (TIMAC)
on off on free
on on off Trovan (IPEV)
on on on free
XX
XX
XXXXXXXXX
3801###
SW101
Number Reader
3801415
HITAG (PX10)
3801400
Legic advant (PX51)
3801202
Mifare DESFire (PX71)
Indala-Trovan (PX15)
3801261
########
## ##
SW101
Number Reader
3801261
Indala-Trovan (PX15)
The configuration protection function is only available with firmware V3.30 or later.
2)
Interface
3)
unused
Switch 6 is set ex works, and its position should not be changed. An incorrect setting can make the reader unusable!
Configuration protection may only be deactivated if the "Load IdendAssembler" system parameter is activated in DORMA MATRIX.
SW101
7
Interface
off OMRON operation
on RENA operation
Page 19
M6D
5. Maintenance
19
5.1 Fuses
In the event that the fuse (SI101 basic card) needs to be replaced, there is a spare fuse at the bottom right of the basic module. The fuse can be re-ordered using art. no.1900001797488 (Littlefuse 0154.750 DRT, 750mA). The use of other fuses is not permissible.
SI101
Page 20
M6D
20
EG Konformitätserklärung EC Declaration of Conformity CE Déclaration de conformité
Page 21
M6D
EG Konformitätserklärung EC Declaration of Conformity CE Déclaration de conformité
21
Page 22
M6D
22
EG Konformitätserklärung EC Declaration of Conformity CE Déclaration de conformité
Page 23
23
M6D
Notes
Page 24
M6D
6. Technical data
Technical data for M6D
Power supply
16 V bis 36 VDC (SELV) 16 V bis 24 VAC (SELV)
Power consumption
max. 2.4 W (approx. 100 mA at 24 V)
Read procedure
The following readers can be fitted:
• Swipe reader
• Indala-Trovan Frequency: 125 kHz Read distance: up to 8 cm
• Hitag (HITAG1, HITAG2, EM4102, EM4450) Frequency: 125 kHz Read distance: up to 4 cm
• Legic prime, Legic advant Frequency: 13,56 MHz Read distance: up to 4 cm
• Mifare Classic, Mifare DESFire Frequency: 13,56 MHz Read distance: up to 4 cm
Anti-tamper monitoring
available
Interfaces:
RS485
Protocols:
DP1
Display and operating elements
1x LC display with 2x 16 characters, back-lit 1x LED 1x acoustic signal transmitter 1x keyboard (various models possible)
Connection cable
Due to the connection terminals, only lines with a max. cross-section of 1
mm²
can be connected.
Ambient conditions
Operating temperature range: –20°C bis +50°C Storage temperature range: –20°C bis +70°C Humidity range: 0 bis 80%, non-condensing
General design
EN 60 950-1, protection class III
Protection rating
IP30
Resistance to interference
EN 61000-6-2 Immunity of devices in industrial operation
Interference emissions
EN 61000-6-3 Emission standard for residential, commercial and light­industrial environments
Dimensions
176 x 176 x 55 mm (WxHxD)
Casing colour
Grey/blue RAL2208005
Weight: approximately 600 g
We reserve the right to make technical modifications and improvements to promote the progress of our equipment.
DORMA Time + Access GmbH Postfach 21 01 85 • D-53156 Bonn • Mainzer Straße 36-52 • D-53179 Bonn Tel. +49 (0) 2 28/85 54-0 • Fax +49 (0) 2 28/85 84-1 75 • www.dorma-time-access.de
DORMA GmbH + Co. KG Postfach 40 09 • D-58247 Ennepetal • DORMA Platz 1 • D-58256 Ennepetal Tel. +49 (0) 23 33 / 793-0 • Fax +49 (0) 23 33 / 79 34 95 • www.dorma.com
Loading...