This manual describes how to install, service and use an DR-LA-water heater.
An DR-LA water heater is a gas-fired open water heater without a fan. DR-LA
water heaters are fitted with a combustion products discharge safety device.
The DR-LA belongs to water heater category B
manual is applicable to types: DR-LA 30, DR-LA 40, DR-LA 45, DR-LA 60, DRLA 75, DR-LA 95 and DR-LA 110.
The manner of construction and features of the water heater are in conformance
with the European standard for gas-fired storage water heaters for the
production of domestic hot water (EN 89). The water heaters are therefore
compliant with the European Directive for Gas Appliances and have the right to
bear the CE mark.
Warning
Read this manual carefully before starting up the water heater. Failure to
read the manual and to follow the printed instructions may lead to personal
injury and damage to the water heater.
Warning
Whenever there is a smell of gas:
No naked flames! No smoking!
Avoid causing sparks! Do not use any electrical equipment or switch, i.e. no
telephones, plugs or bells!
. The information in this
11B S
1.3Regulations and
documents
Shut off the mains gas supply!
Open windows and doors!
Warn occupants and leave the building!
After leaving the building, alert the gas distribution company or installation
engineer.
Gas Safety Installations and Use Regulations 1998, (As amended). It is law
that all gas appliances are installed by competent persons, in accordance with
the above regulations. Failure to install appliances correctly could lead to
prosecution. It is in your own interest, and that of safety, to ensure that this law
is complied with.
The installation of the boiler MUST be in accordance with the relevant
requirements of the Gas Safety Regulations, Building Regulations, IEE
Regulations and the Water Supply (water fittings) Regulations.
The installation should also be in accordance with any relevant requirements of
the HSE, local gas region and local authority and the relevant recommendations
of the following documents:
Instruction manual DR-LA7
1
Introduction
gis
British Standards
•BS 6891: Specification for installation of low pressure gas pipework of up to
28 mm (R1) in domestic premises (2nd family gas). For larger installations
see IGE/UP/2 below.
•BS 6798: Specification for installation of gas-fired boilers of rated input not
exceeding 70 kW net.
•BS 6644: Specification for installation of gas-fired hot water boilers of rated
inputs between 60 kW and 2 MW (2nd and 3rd family gases).
•BS 6700: Specification for design, installation, testing and maintenance of
services supplying water for domestic use within buildings and their
curtilages.
•BS EN 806-2: Specification for installations inside buildings conveying water
for human consumption. Part 2: Design.
•BS 5546: Specification for installation of hot water supplies for domestic
purposes, using gas-fired appliances of rated input not exceeding 70 kW.
•BS 5440: Installation and maintenance of flues and ventilation for gas
appliances of rated input not exceeding 70 kW net (1st, 2nd and 3rd family
gases). Part 1: Flues. Part 2: Ventilation.
Institute of Gas Engineers and Managers Publications
•IGE/UP/1 Soundness testing and purging of industrial and commercial gas
installations.
•IGE/UP/1A Soundness testing and direct purging of small low pressure
industrial and commercial natural gas installations.
•IGE/UP/2 Gas installation pipework, boosters and compressors on industrial
and commercial premises.
•IGE/UP/10 Installation of gas appliances in industrial and commercial
premises. Part 1: flued appliances.
CIBSE Publications:- "CIBSE Guide"
Section B4 : Water Service Systems.
1.4Target groupsThe three target groups for this manual are:
•(end) users;
•installation engineers;
•service and maintenance engineers.
Symbols on each page indicate the target groups for whom the information is
intended. See Table 1.1.
Table 1. 1 Target group symbols
SymbolTarget group
(End) user
g
installation engineer
i
Service and maintenance engineer
s
8Instruction manual DR-LA
Maintenance
gis
1.5MaintenanceA service should be carried out at least once a year, both on the water side and
on the gas side. Maintenance frequency depends, among other things, on the
water quality, the average burning time per day and the set water temperature.
n Caution
To determine the correct maintenance frequency, it is recommended to
arrange for the service and maintenance engineer to check the water heater
on both the water and gas side, three months after installation. Based on this
check, the best maintenance frequency can be determined.
n Caution
Regular maintenance extends the service life of the water heater.
Both the end user and the service and maintenance engineer are responsible
for regular maintenance. They will need to establish clear agreements on this.
n Caution
If the water heater is not regularly maintained, the warranty will become void.
1.6Forms of notationThe following notation is used in this manual:
n Caution
Important information
cNote
Ignoring this information can lead to the water heater being damaged.
Warning
Failure to carefully read this information may lead to danger of personal
injury and serious damage to the water heater.
Instruction manual DR-LA9
1
Introduction
gis
1.7Overview of this
document
Table 1. 2 Contents of document
ChapterTarget groupsDescription
2 Functioning of the water
heater
3Installation
4 Filling and draining
Table 1.2 provides an overview of the contents of this document.
This chapter describes how the water heater functions.
gis
This chapter describes the installation activity to be completed
is
before you actually start up the water heater.
This chapter describes how to fill and drain the water heater.
gis
5 Controls
6 Status of the water heater
7 Starting up and shutting
down
8 Troubleshooting
gis
gis
gis
gis
This chapter describes the water heater’s control panel and
how to use it.
This chapter describes each status (state) that the water
heater may be in and how to respond, if necessary.
This chapter describes how to start up the water heater and
how to shut it down for a brief or long period of time. The
general heating cycle of the water heater is also described.
This chapter is mainly intended for the installation engineer
and the service and maintenance engineer. It describes water
heater errors. These errors are indicated on the display. A
table of possible causes and solutions is provided. End users
may also refer to this chapter for additional information about
the water heater.
9 Maintenance
s
This chapter sets out the maintenance tasks to be carried out
during a service.
10Instruction manual DR-LA
gis
gis
2Functioning of the
water heater
2.1IntroductionTopics covered in this chapter:
•Functional description of the water heater;
•The water heater’s heating cycle;
•Protection for the water heater;
•Safety of the installation.
Introduction
Instruction manual DR-LA11
2
Functioning of the water heater
gis
2.2Functional
description of the
water heater
Legend
a flue gas discharge
b draught diverter
c anodes
d flue tubes
e flue baffles
f flue gas thermostat
g flue gas thermostat sensor
h insulation layer
i hot water tank
j cleaning opening
k drain valve
l combustion chamber
m radiation shield/condensation
tray
n gas control
o safety thermostat sensor
p high-limit thermostat sensor
q burner control
r hot water outlet
s control panel
t control thermostat
u high-limit thermostat
v safety thermostat
w frost thermostat
x control thermostat sensor
y frost thermostat sensor
z hot surface igniter
A flame probe
B cold water inlet
C bar burners/burner tray
Figure 2.1 shows a cut-away view of the water heater.
a
b
c
d
e
f
g
h
i
j
k
l
m
n
Figure 2.1 Cut-away view of the water heater
o
p
q
r
s
t
u
v
w
x
y
z
A
B
C
IMD-0133
In this water heater the cold water enters the bottom of the it via the cold water
inlet B. The heat of combustion is transferred to the water through the
combustion chamber l and flue tubes d. The heated tap water leaves the
heater through the hot water outlet r. Once the water heater is completely filled
with water, it remains constantly under water supply pressure. As hot water from
the water heater is consumed, it is continuously replenished with cold water.
The gas required for combustion flows into the manifold via the gas control n.
Orifices are located within the manifold. Via these orifices, the gas enters the
bar burners C. Together, the bar burners constitute the burner tray. As the gas
is injected into the bar burners, the primary air required for combustion is also
drawn in
1. The narrow opening in the orifices accelerates the gas flow. This causes a partial vacuum. The
(1)
. Additional air is drawn through the openings in the burner tray. The
effect of this partial vacuum is to draw the air into the flow (the Venturi effect).
12Instruction manual DR-LA
gis
The water heater’s heating cycle
hot surface igniter z ensures the ignition of the gas/air mixture. The flue gases
generated by this combustion are led through the flue tubes d. There are flue
baffles e located in the flue tubes. These slow down the flue gas exhaust,
improving the heat transfer efficiency. The flue gases leave the water heater via
the draught diverter b. A radiation shield/condensation tray m is mounted under
the burner tray. This prevents overheating of the floor surface under the water
heater and serves as a collection tray for condensate.
The insulation layer h prevents heat loss. The inside of the hot water tank is
enamelled to protect against corrosion. The anodes c provide additional
protection.
2.3The water heater’s
heating cycle
2.4Protection for the
water heater
2.4.1Water temperature protection
The water heater is controlled by the burner control q and the control
thermostat t or frost thermostat w. The control thermostat and frost thermostat
both independently measure the water temperature (T
heating cycle is activated as soon as T
value (T
heater, see paragraph 6.2 Operating states. If the water heater is in the 'OFF
mode' (frost protection), then this value is determined by the frost thermostat
(threshold value = 20°C). If the water heater is in the 'ON mode', then the
threshold value is selectable via the control thermostat (40°C - 70°C).
As soon as T
close and the burner control will register a heat demand. The gas control n will
open and the gas will mix with the air it draws in. This mixture is ignited by the
hot surface igniter z and the water becomes heated. A soon as T
T
set
burner control will stop the heating cycle.
The thermostats have a certain margin both when closing and opening. We refer
to this margin as the hysteresis. The hysteresis cannot be adjusted.
The burner control monitors the water temperature by means of thermostats
and ensures a safe combustion. This is achieved by:
•the Water temperature protection;
•the Combustion products discharge safety device;
•the flame probe.
By means of the frost, high-limit and safety thermostats, the burner control
monitors three temperatures related to safety. Tab le 2 . 1 explains the operation
of the thermostats with sensors.
). The value for T
set
falls below T
water
, the thermostat will open once more. The heat demand will cease and the
depends on the status chosen for the water
set
, the relevant thermostat (control or frost) will
set
falls below the specified threshold
water
). The water heater’s
water
water
exceeds
Tab le 2.1 Temperature protection
ProtectionDescription
Frost thermostatIf the frost thermostat sensor y detects a temperature of 20°C or lower, the
water heater’s heating cycle will start. See paragraph 2.3 The water heater’s
heating cycle.
High-limit thermostatIf the high-limit thermostat sensor p detects a temperature greater than 84°C,
the high-limit thermostat will open. The heat demand will be stopped and the
burner control will stop the heating cycle until the high-limit thermostat closes
again. At that moment, the burner control resets the water heater and the
heating cycle resumes. The high-limit safeguard serves to prevent
overheating and/or excessive formation of scale in the water heater.
Safety thermostatIf the safety thermostat sensor o detects a temperature greater than 93°C, the
safety thermostat will open. The heat demand will be ended and the burner
control immediately stops the heating cycle. A lockout error will occur in the
burner control. This must be manually reset, before the water heater can be
put back into operation.
Instruction manual DR-LA13
2
2.4.2Combustion products discharge safety device
2.4.3flame probe
2.5Safety of the installation
Functioning of the water heater
gis
The flue gases are channelled to the outside via the draught diverter b and the
flue gas discharge a. To prevent the flue gases from flowing back into the boiler
room, the discharge ducting is monitored by a feature called the combustion
products discharge safety device. This uses a flue gas thermostat f with flue
gas thermostat sensor g which are located in the draught diverter. Under
normal circumstances this sensor will register the ambient temperature.
However, if the chimney is not drawing sufficiently (for example, due to a
blockage in the chimney), the flue gases will flow back past the flue gas
thermostat sensor. The sensor will then detect an excessive temperature and
the flue gas thermostat will open. The heat demand will be ended and the burner
control immediately stops the heating cycle. The flue gas thermostat will also
lock out. This must be manually reset, before the water heater can be put back
into operation.
To ensure that no gas can flow when there is no combustion, an flame probe A
has been fitted. The burner control uses this rod for flame detection, by means
of ionisation sensing. The burner control closes the gas valve as soon it detects
that gas is flowing and there is no flame.
2.5.1Unvented installation
With an unvented installation, an expension valve and expansion vessel prevent
excessive pressure in the water heather. This prevents damage of the water
heater. A non-return valve prevents excessive pressure in the water supply
system. This valve also prevents water from flowing backwards from the heater
into the cold water supply system. The pressure reducing regulates the water
supply pressure to a normal operating pressure of 3.5 bar. The components are
fitted to the cold water pipe. See paragraph 3.6.1 Cold water side.
2.5.2Vented installation
With a vented installation, excess pressure is taken up by the open water tank.
The level of the water determines the working pressure which may not exceed
8 bar.The installation must also be fitted with an open vent from the hot water
pipe. Ideally the vent pipe should be linked to a separate tundish/drain or else
to the cold water storage tank. A safety valve should also be fitted to the water
heather. See paragraph 3.6.3 Hot water side.
2.5.3Temparature and Pressure valve (T&P valve)
A T&P valve is mandatory in an 'unvented' installation.
A T&P valve monitors the water pressure in the water heater and the water
temperature at the top of it. If the pressure in the water heater becomes
excessive (> 7 bar) or the water temperature is too high (>97°C), the valve will
open. The hot water will immediately flow out of the heater. Because the water
heater is under water supply pressure, cold water will automatically flow into it.
The valve remains open until the unsafe situation has been averted. A
connecting point for a T&P valve is standard on the water heater. See paragraph
3.6.3 Hot water side.
2.6Indicators and
Alarms
2.6.1Volt Free Contacts
Volt free contacts are supplied as standard to give remote indication/alarm of
'normal run' and 'lockout'. The 'lockout' indication includes shut down due to
operation of the safety thermostat, loss of flame and failure to ignite.
14Instruction manual DR-LA
Options
gis
2.7OptionsThe heaters can be supplied with the following additional variations, either
ready fitted or for site fitting:
2.7.1LPG
The heaters can be supplied adjusted for use on propane or butane, see section
3.12. It is most important that the heater is correctly adjusted for the gas to be
fired.
2.7.2Unvented Supply
The heaters can be supplied with a purpose designed and sized unvented kit
comprising pressure reducing valve, non-return valve, expansion vessel,
expansion relief valve and pressure/temperature relief valve, to enable the
heater to be coupled directly to the mains water. For details see 2.5.1, 2.5.3 and
3.6.
2.7.3Top to Bottom Circulation
In order to give enhanced temperature control to aid compliance with the HSE
guidance and the DHss Code of Practice for 'The Control of Legionellae in
Health Care Premises', a pump circulation kit can be supplied comprising 230
volt single phase pump, non-return valve, pipe work and sufficient fittings to
contact between the hot water flow and the bottom connection. For details see
section 3.5 of this manual.
Instruction manual DR-LA15
2
Functioning of the water heater
gis
16Instruction manual DR-LA
Introduction
is
is
3Installation
Warning
The installation should be carried out by an approved installation engineer
in compliance with the general and local regulations imposed by the gas,
water and power supply companies and the fire service.
The water heater may only be installed in a room which complies with the
requirements stated in national and local ventilation regulations.
Refer also to paragraph 1.3 Regulations and documents.
3.1IntroductionThis chapter describes the installation activities to be carried out before the
water heater may be started up, namely:
•Packaging;
•Environmental conditions;
•Technical specifications;
•Water connections, Unvented;
•Water connections, Vented;
•Gas connection;
•Flue gas discharge;
•Electrical connection;
•Checking the supply pressure and burner pressure;
•Conversion to a different gas category.
n Caution
Starting up the water heater is described in chapter 7 Starting up and
shutting down.
3.2PackagingTo avoid damaging the water heater, remove the packaging carefully. We
recommend unpacking the water heater at or near its intended location.
cNote
The water heater may only be manoeuvred in an upright position. Take care
that the water heater is not damaged after unpacking.
3.3Environmental
conditions
cNote
The water heater may not be used in rooms where chemical substances are
stored or used due to the risk of explosion and corrosion to the water heater.
Some propellants, bleaching agents, degreasing agents etc. disperse
vapours which are explosive and/or which cause accelerated corrosion. If
the water heater is used in a room in which such substances are present,
the warranty will be void.
DR-LA water heaters are open water heaters and may only be placed in an
open boiler room. They fall under category B
11B S
.
Instruction manual DR-LA17
3
Installation
is
3.3.1Humidity and ambient temperature
The boiler room must be frost-free or be protected against frost. Ta bl e 3 .1
shows the environmental conditions that must be adhered to, for correct
functioning of the electronics present in the water heater to be guaranteed.
Table 3 .1 Humidity and ambient temperature specifications
Humidity and
Humiditymax. 93% RH at +25°C
Ambient temperatureFunctional: 0 ≤ t ≤ 60°C
3.3.2Maximum floor loading
In connection with the water heater’s weight, take account of the maximum floor
loading, see Tab le 3 . 2.
Table 3 .2 Weight specifications related to maximum floor loading
For access to the water heater it is recommended that the following
clearances are observed (see Figure 3.2):
•AA: around the water heater’s control column and cleaning openings:
100 cm.
•BB: around the water heater itself: 50 cm.
•Above the water heater (room to replace the anodes):
-100 cm if using fixed anodes or
-50 cm if using flexible anodes.
ambient temperature
18Instruction manual DR-LA
is
Environmental conditions
If the available clearance is less than 100 cm, flexible magnesium anodes
may be ordered from Hamworthy, the installation engineer / supplier.
n Caution
When installing the water heater, be aware that any leakage from the it and/
or connections can cause damage to the immediate environment or floors
below the level of the boiler room. If this is the case, then the water heater
should be installed above a wastewater drain or in a suitable metal leak tray.
The leak tray must have an appropriate wastewater drain and must be at
least 5 cm deep with a length and width at least 5 cm greater than the
diameter of the water heater.
Figure 3.1 Working clearances
IMD-0135a
Instruction manual DR-LA19
3
Installation
is
3.4Technical specifications
The water heater is supplied without accessories. Check the dimensions and
other specifications for the accessories to be used, based on Figure 3.2 and
(1) Based on 1013.25 mbar and 15oC.
(2) If using a blank plate or high-low control program, instead of a burner pressure regulator, it is assumed that the burner pressure is equal
to the supply pressure. In practice however, the burner pressure will be lower.
(2)
(2)
(1)
(1)
mbar30303030303030
kg/h3.04.05.05.87.09.010.1
1,2, or 31111113
mbar37373737373737
kg/h2.73.74.55.36.48.19.3
Instruction manual DR-LA23
3
Installation
is
3.5Installation diagramFigure 3.3 shows the water and gas connection diagrams for unvented and
vented installations. The following paragraphs, describing the connections in
detail, make reference to these diagrams
Legend
a pressure-reducing valve
(mandatory )
b expansion vessel (mandatory)
c T&P valve (mandatory)
ca) safety valve
d stop valve (recommended)
e non-return valve (mandatory)
ea) non-return valve
f circulation pump (optional)
g drain valve
h manual gas valve (mandatory)
i stop valve (mandatory)
j temperature
gauge (recommended)
k top to bottom recirculation
pump (optional)
l draught diverter
m hot water draw-off points
n expension valve (mandatory)
o water tank
p float valve
q 3-way venting valve (optional)
r overflow pipe
a cold water supply
b hot water outlet
c circulation pipe
d gas supply
e flue gas discharge
UNVENTED
4
6
5a
4
C
7
D
VENTED
13
E
12
3
8
4
11
5a
4
14
12
3a
10
T
9
2
5
1
E
10
T
4
11
5a
4
B
4
A
IMD-0142
16
18
17
B
9
13
C
4
15
5a
6
4
C
4
7
D
8
4
IMD-0141
Figure 3.3 Installation diagrams
24Instruction manual DR-LA
is
3.6Water connections,
Unvented
3.6.1Cold water side
3.6.2Top to bottom recirculating pump
Water connections, Unvented
See a in Figure 3.3.
1. Fit an approved stop valve
regulations.
Refer also to paragraph 1.3 Regulations and documents.
2. The maximum working pressure of the water heater is 8 bar. The expansion
valve regulates the pressure to 5.5 bar. The operatiing pressure is 3.5 bar.
Fit an approved pressure-reducing valve
3. Fit a non-return valve
4. Fit an expension valve
You can connect a top to bottom recirculation pump to prevent stratification of
the water in the water heater.
1. Fit a pipe (Ø 22 mm), a stop valve
k.
pump
2. Fit non-return valve
3. Fit stop valves
i.
i on the cold water side as required by
a.
e and an expansion vessel b.
n and connect the discharge to a drain via tundish.
d and a top to bottom recirculation
e.
3.6.3Hot water side
See b in Figure 3.3.
n Caution
Insulating long hot water pipes prevents unnecessary energy loss.
1. Optional: fit a temperature gauge
the tap water.
2. Fit the T&P valve
3. Fit a stop valve
c.
i in the hot water outlet pipe, for use when servicing.
3.6.4Drain valve
1. Fit the standard drain valve supplied g.
2. If a circulation pipe is to be fitted, then refer to paragraph 3.6.5. Otherwise,
fit the sealing nut and gasket supplied with the drain valve. See Figure 3.4.
3.6.5Circulation pipe
See c in Figure 3.3. and Figure 3.4.
c
If an immediate flow of hot water is required at draw-off points, a circulation
pump can be installed. This improves comfort and reduces water wastage.
1. Fit a circulation pump
of the circulation system.
2. Fit a non-return valve
direction of circulation.
3. Fit two stop valves for servicing
4. Connect the circulation pipe to the T-piece on the drain valve
Figure 3.4.
f of the correct capacity for the length and resistance
ea downstream the circulation pump to guarantee the
j to be able to check the temperature of
d.
g. See
IMD-0122
Figure 3.4 Drain valve
Instruction manual DR-LA25
3
3.7Water connections,
Vented
3.7.1Cold water side
3.7.2Top to bottom recirculating pump
3.7.3Hot water side
Installation
is
See a in Figure 3.3.
•Fit an approved stop valve
tank o and the water heater, as required by regulations. Ideally the vent
pipe should be linked to a separate tundish/drain or else to the cold water
storage tank. Refer also to paragraph 1.3 Regulations and documents.
You can connect a top to bottom recirculation pump to prevent stratification of
the water in the water heater.
1. Fit a pipe (Ø 22 mm), a stop valve
pump
k.
2. Fit non-return valve
3. Fit stop valves
See b in Figure 3.3.
i.
i on the cold water side between the water
d and a top to bottom recirculation
e.
3.8Gas connection
n Caution
Insulating long hot water pipes prevents unnecessary energy loss.
1. Fit a safety valve
2. Optional: fit a temperature gauge
the tap water.
3. Fit a stop valve
4. If a circulation pipe is to be fitted, then refer to paragraph 3.7.4.
3.7.4Circulation pipe
See c in Figure 3.3.
If an immediate flow of hot water is required at draw-off points, a circulation
pump can be installed. This improves comfort and reduces water wastage.
1. Fit a circulation pump
of the circulation system.
2. Fit a non-return valve
direction of circulation.
3. Fit two stop valves for servicing
4. Connect the circulation pipe to the T-piece on the drain valve
Figure 3.4.
Warning
Gas installation may only be carried out by an authorised installation
engineer in compliance with the general regulations imposed by the gas
company.
Refer also to paragraph 1.3 Regulations and documents.
ca.
j to be able to check the temperature of
i in the hot water outlet pipe, for use when servicing.
f of the correct capacity for the length and resistance
ea downstream the circulation pump to guarantee the
d.
g. See
cNote
Make sure that the diameter and length of the gas supply pipe are large
enough to supply sufficient capacity to the water heater.
26Instruction manual DR-LA
is
3.9Flue gas discharge
3.9.1Introduction
Flue gas discharge
See d in Figure 3.3.
1. Fit a gas valve
2. Blow the gas pipe through before use, to be sure it is clean.
3. Close the gas valve.
4. Fit the gas supply pipe to the gas control.
h in the gas supply pipe.
Warning
Check for leaks after fitting.
Warning
The installation should be carried out by an authorised installation engineer,
in compliance with the general and local regulations imposed by gas, water
supply and power supply companies and the fire service. Refer also to
paragraph 1.3 Regulations and documents.
When connecting the water heater to the chimney, the draught diverter l
supplied with the water heater must be used. The standard flue gas thermostat
and sensor that are supplied must be fitted in the draught diverter.
3.9.2Fitting the draught diverter
Legend
a sealing ring
b fastening screws
c chimney pipe
d 45° bend
e holes to attach support bracket
f support bracket
n Caution
To guarantee draught a
chimney pipe with a lenght of at
least 0.5 m should be fitted to
the 45o bend.
The draught diverter can be positioned according to preference. After
positioning, the draught diverter is secured using two screws b to the top
surface of the water heater and also sits on a support bracket
side of the water heater. The assembly procedure is as follows:
> 0.5 m
f attached to the
a
b
Figure 3.5 Placing the draught diverter
c
d
e
f
IMD-0123
1. Take the support bracket out of the bag.
2. Fit the support bracket
diverter.
3. Drill two holes
4. Screw the support bracket tightly to the water heater.
e (3.2 mm drill) for the support bracket screws.
f in such a way that it properly supports the draught
Instruction manual DR-LA27
3
Installation
is
5. Place the draught diverter in the support bracket and mark the centres for
the two drill holes on the top surface of the water heater. Remove the
draught diverter from the water heater.
6. Now drill two holes
7. Place the sealing ring
8. Screw the draught diverter tightly in place.
9. Fit:
-a 45° bend
-a corrosion-resistant vertical chimney pipe
-the remaining flue components.
n Caution
Use flue gas discharge materials that comply with the regulations. See
paragraph 1.3 Regulations and documents.
n Caution
Make sure that the chimney discharges into an area where this is permitted
for this category of water heater.
b into the top of the water heater (3.2 mm drill).
a on the water heater.
d onto the outlet of the draught diverter, followed by:
c of at least 0.5 metre,
3.9.3Flue gas thermostat assembly
Attached to the control column is a plastic bag containing the flue gas
thermostat with sensor and related attachment materials. The cable from the
sensor is already connected in the control column. The thermostat/bracket and
sensor have yet to be fitted inside the draught diverter. See Figure 3.6.
Warning
If the flue gas thermostat is not (or is incorrectly) fitted/connected, the flue
gas discharge will not be protected. An incorrectly fitted chimney can cause
flue gases to backflow into the boiler room.
1
4
2
2
3
Figure 3.6 Flue gas thermostat assembly
Fit the flue gas thermostat as follows:
1. Take the bracket 1 with thermostat and sensor 2 from the packaging.
2. Place the bracket in the draught diverter and screw the bracket and the
sensor firmly in place.
3. Bend the cable clips 3 around the cable 4 of the flue gas thermostat.
28Instruction manual DR-LA
IMD-0137.
is
3.10 Electrical
connection
4. Screw the cable clips 3 in place in the draught diverter and the water heater.
Warning
The installation should be carried out by an approved installation engineer
in compliance with the general and local regulations imposed by the gas,
water and power supply companies and the fire service.
Refer also to paragraph 1.3 Regulations and documents.
3.10.1Introduction
Topics covered in this paragraph:
•3.10.2 Preparation;
•3.10.3 Mains power;
3.10.2Preparation
cNote
The water heater is phase-sensitive. It is absolutely essential to connect
the phase (L) from the mains to the phase of the water heater and the neutral
(N) of the mains to the neutral of the water heater.
There should also be no potential difference present between neutral (N)
and earth (
applied in the supply circuit. For more information or to order this isolating
transformer, please contact Hamworthy.
Electrical connection
A). If this is the case, then an isolating transformer must be
Figure 3.7 shows a front view of the electrical connection block. Ta bl e 3 . 6
shows the associated connections.
Tab le 3.6 Electrical connection block DR-LA
Mains powerCombustion products
discharge safety device
NL
1234 56789101112
Close Control
Thermostat
1
AL
2
Time clock powerCorex Anode
L
3
Volt Free contact
Lock Out
NOPNCNOPNC
power
Volt Free contact
Normal Run
Time clock
connection
ANLNLNLNLL LL
131415161718192021222324
Instruction manual DR-LA29
3
Installation
is
3
2
1
Figure 3.7 Connection block (connections 1 through 6 explained in Ta bl e 3 .6 )
In preparation, first remove the protective cover from the control column:
•Undo the 4 screws 1 and remove the protective cover 2 from the electrical
section. The connection block 3 is now visible.
6
1
IMD-0134
n Caution
Refer to 1.2 Electrical diagram DR-LA for the connection of electrical
components.
3.10.3Mains power
The water heater is supplied without a power cable and isolator.
n Caution
In order to receive electrical power, the water heater has to be connected to
the mains voltage by means of a permanent electrical connection. A double
pole isolator with contacts gaps of at least 3 mm must be fitted local to the
water heater. The power cable must have cores of at least 3 x 1.0 mm2.
1. Feed the power cable through the metric strain relief on the top of the control
column.
2. Connect earth (A), phase (L1) and neutral (N) on the power cable to
terminals 1 to 3 of the connection block as set out in Table 3.6.
3. Tighten the strain relief so that the cable is clamped.
4. If you do not need to make any more connections, then fit the protective
cover back on the control column.
30Instruction manual DR-LA
is
3.11 Checking the supply
pressure and burner
pressure
Checking the supply pressure and burner pressure
5. Connect the power cable to the isolator.
Warning
Leave the water heater disconnected until you are ready to start it up.
cNote
Before you start up the water heater and/or begin to check the supply
pressure and burner pressure, you must first fill the water heater.
Please refer to paragraph 4.2 Filling the water heater for filling
instructions.
cNote
Before starting-up for the first time and following conversion, you
must always check the supply pressure and burner pressure. If
necessary, adjust these to be certain of optimum performance of the
water heater.
cNote
The easiest way to check the gas pressures is by using two pressure
gauges. This procedure assumes that these two gauges are available.
Legend
a burner pressure regulator
b burner pressure regulator
cap
c burner pressure regulator
adjusting screw
d gas control connector
e blank plate
f supply pressure test nipple
g gas control
h manifold test nipple
i high-low control
Gas control valve for DR-LA 30 to 95
e
g
c
e
d
h
a
Figure 3.8 Gas control valve for DR-LA 30 through 95 and DR-LA 110
Instruction manual DR-LA31
b
IMD-0127
3
Installation
is
Gas control valve for DR-LA 110
b
c
ai
f
g
h
IMD-0129
Figure 3.8 Gas control valve for DR-LA 30 through 95 and DR-LA
To check the supply pressure and burner pressure, proceed as follows:
1. Disconnect the water heater from the power supply. See paragraph
7.3.2 Isolate the water heater from the power supply.
2. On the gas control (Figure 3.8) there are two test nipples. To check the
supply pressure, test nipple
control is not used. The manifold test nipple h is used for measuring the
burner pressure.
Sealing screws are located inside the test nipples. Loosen both sealing
screws by a few turns. Do not loosen them completely; this makes them
difficult to tighten again.
3. Connect a pressure gauge to the manifold test nipple
f is used. The other test nipple on the gas
h.
n Caution
All gas pipes should be bleeded and free of leakage.
4. Connect a pressure gauge to test nipple.
5. Open the gas supply .
6. Switch on the power to the water heater using the isolator on the water
heater.
7. Set the control thermostat to the highest position and start the water heater
running by putting the On/Off-switch to position I.
8. The heating cycle will start and the burner tray will ignite after a short time.
9. After the burner tray has ignited, wait for approximately 1 minute before you
start reading the dynamic pressures.
10. Use the pressure gauge to read the supply pressure at the test nipple
Refer to Tabel 3.5.
f.
n Caution
Consult the mains gas supply company if the supply pressure is not correct.
32Instruction manual DR-LA
is
Conversion to a different gas category
11. Use the pressure gauge to read the burner pressure at test nipple h. Refer
to Ta be l 3 .5 .
n Caution
If the burner pressure is not correct and the water heater is fitted with a blank
plate or high-low control, you will not be able to adjust the pressure. In this
case, consult your installation engineer or supplier.
If the water heater is fitted with a burner pressure regulator, then the
pressure can be adjusted by following steps 12 through 17.
3.12 Conversion to a
different gas
category
12. Remove the cap
13. Adjust the burner pressure by turning the adjusting screw
the correction required:
14. Cover the opening of the adjusting screw and check the burner pressure
against the target value from Tabel 3.5.
15. If the pressure reading is not correct, repeat steps 13 and 14 until the correct
pressure is attained.
16. Fit the cap
17. Shut down the water heater by putting the On/Off -switch to position 0.
18. Shut off the gas supply.
19. Disconnect the two pressure gauges and re-tighten the sealing screws in the
test nipples.
cNote
The conversion may only by carried out by an authorised installation
engineer.
3.12.1Introduction
If the water heater must operate on a family of gas (LP-gas or natural gas)
other than the category of gas for which the water heater has been set up at
the factory, the water heater will have be adapted using a special conversion
kit.
b from the burner pressure regulator a.
c, depending on
b on the burner pressure regulator.
cNote
After conversion, check the supply pressure and the burner pressure.
There are differences between the conversions for the DR-LA 110 and the DRLA 30 through 95. The conversion procedures are described in paragraphs:
•3.12.2 Conversion to a different gas category DR-LA 30 through 95
•3.12.3 Conversion to a different gas category, DR-LA110.
Instruction manual DR-LA33
3
6
Legend
a cover plate
b locking strips
c orifice with stamped figures
Installation
is
a
b
3.12.2Conversion to a different gas category DR-LA 30 through 95
Take care
The burner may be
hot.
c
IMD-012
Figure 3.9 Exchanging orifices
1. Disconnect the water heater from the power supply. See paragraph
7.3.2 Isolate the water heater from the power supply.
2. Shut off the gas supply.
3. Unscrew the cover plate
4. Use a suitable tool to remove the locking strips
have very sharp edges.
Withdraw the locking strips straight upwards.
5. The radiation shield / the condensation tray can be temporarily loosened to
simplify assembly of the burner.
6. Remove the burners one by one from their brackets at the front. To do this,
you first move them away from you and then downwards. The orifices will
now be accessible.
7. Remove the orifices.
8. Select and fit the correct orifices from the conversion kit, based on Tabel 3.5.
The orifice diameter is indicated by figures stamped on the orifice, see
9. Refit the burners back in their original position.
10. Re-fit the locking strips.
11. If the radiation shield / the condensation tray was loosened, re-tighten it.
a from the burner support.
b. Note: the locking strips
c.
34Instruction manual DR-LA
is
Legend
See Figure 3.9 for
d burner pressure regulator
e gas control connector
f blank plate
g supply pressure test nipple
h gas control valve
a through c.
Conversion to a different gas category
g
f
h
e
Figure 3.10 Conversion of gas control
12. Check whether there is a burner pressure regulator d fitted to the gas
n Caution
13. If the blank plate or burner pressure regulator need to be replaced:
cNote
14. Check the burner pressure and supply pressure (see paragraph 3.11).
15. Remove the sticker showing the new gas category from the conversion kit
d
control or simply a blank plate
In the event the supply pressure for a gas category is the same as the burner
pressure (see Tabel 3.5) then the gas control must be fitted with a blank
plate with cork gasket. A burner pressure that deviates in comparison to the
supply pressure requires the use of a burner pressure regulator with rubber
gasket. Each conversion kit contains all the necessary components.
-Unscrew the connector
-Either, remove the blank plate
-Either, fit the blank plate or burner pressure regulator supplied with the
conversion kit.
-Refit the connector
and attach it below the water heater’s rating plate. This clearly indicates that
the water heater may no longer be run on the gas for which it was originally
supplied.
f.
e from the gas control.
f or burner pressure regulator d.
e to the gas control.
IMD-0131
Instruction manual DR-LA35
3
3.12.3Conversion to a different gas category, DR-LA110
Legend
a burner pressure regulator
b high-low control
c gas control valve
Installation
is
16. Start the water heater (see paragraph 7.2).
Introduction
This paragraph describes the:
•Conversion from LP gas to natural gas.
•Conversion from natural gas to LP gas.
12
3
Figure 3.11 Conversion of gas control DR-LA110
Conversion from LP gas to natural gas
1. Perform steps 1 through 9 of paragraph 3.12.2 Conversion to a different gas
category DR-LA 30 through 95.
2. Detach the high-low control
3. Fit the burner pressure regulator a including the sealing gasket from the
conversion kit. Attach the burner pressure regulator to the gas control
c using the two small screws supplied.
valve
IMD-0132
b
36Instruction manual DR-LA
is
Legend
Conversion to a different gas category
See Figure 3.11 for numbers 1
through 3.
d timers
e bracket
f 6-terminal connector strip
g pull reliefs
h 9-terminal connector strip
i metric strain relief
j high-low control cable
4
5
6
7
8
9
0
IMD-0130
Figure 3.12 Fitting and removal of conversion components
4. Detach the cables between the 6-terminal connector strip 6 and the
9-terminal connector strip 9. These are the cables for the timers, high-low
control, gas control, hot surface igniter and flame probe.
5. Remove the timers 4, bracket 5, cable harness (not shown) and 9-terminal
connector strip 8.
6. Turn the metric strain relief 9 with the high-low control cable 0 to loosen it.
Remove this cable.
7. Fit the stop plug from the conversion set in the place of the metric strain
relief.
8. Connect the cables of the gas control valve, the hot surface igniter and flame
probe to the 6-terminal connector strip as shown in the electrical diagram.
See appendices 1.2.1 Electrical diagram DR-LA 30 through 95 and 110
(natural gas) and 1.2.2 Electrical diagram DR-LA 110 (LP gas).
Instruction manual DR-LA37
3
Installation
is
9. Clamp the gas control cable in one of the pull reliefs supplied 7. Do the
same for the cables from the hot surface igniter and flame probe.
cNote
10. Check the burner pressure and supply pressure (see paragraph 3.11).
11. Remove the sticker showing the new gas category from the conversion kit
and attach it below the water heater’s rating plate. This clearly indicates that
the water heater may no longer be run on the gas for which it was originally
supplied.
12. Start the water heater (see paragraph 7.2)
Conversion from natural gas to LP gas
1. Perform steps 1 through 9 of paragraph 3.12.2 Conversion to a different gas
category DR-LA 30 through 95.
2. Detach the burner pressure regulator
3. Fit the high-low control
kit. Attach the high-low control to the gas control using two small screws.
4. Detach the cables from the gas control valve, the hot surface igniter and the
flame probe from the 6-terminal connector strip 6 and the strain relief 7.
5. Fit the timers 4 including cable harness plus 9-terminal connector strip 6
from the conversion kit, to the control column.
6. Remove the stop plug (not shown) from the underside of the control column
and replace this with the metric strain relief 9 from the conversion kit.
7. Draw the high-low control cable 0 through the strain relief and tighten the
strain relief by turning it until the cable is clamped.
8. Connect the high-low control cable 0 plug to the high-low control
9. Connect the cables from the timers, high-low control, gas control, flame
probe and the hot surface igniter as shown in the electrical diagram. See
appendix 1.2 Electrical diagram DR-LA.
b including the sealing gasket from the conversion
a.
b.
cNote
10. Check the burner and supply pressure (see paragraph 3.11).
11. Remove the sticker showing the new gas category from the conversion kit
and attach it below the water heater’s rating plate. This clearly indicates that
the water heater may no longer be run on the gas for which it was originally
supplied.
12. Start the water heater (see paragraph 7.2).
38Instruction manual DR-LA
gis
gis
4Filling and draining
4.1IntroductionTopics covered in this chapter:
•Filling the water heater.
•Draining the water heater.
The components referred to in these paragraphs are illustrated in Figure 4.1.
Legend
a pressure-reducing valve
(mandatory )
b expansion vessel (mandatory)
c T&P valve (mandatory)
ca) safety valve
d stop valve (recommended)
e non-return valve (mandatory)
ea) non-return valve
f circulation pump (optional)
g drain valve
h manual gas valve (mandatory)
i stop valve (mandatory)
j temperature
gauge (recommended)
k top to bottom recirculation
pump (optional)
l draught diverter
m hot water draw-off points
n expension valve (mandatory)
o water tank
p float valve
q 3-way venting valve (optional)
r overflow pipe
a cold water supply
b hot water outlet
c circulation pipe
d gas supply
e flue gas discharge
UNVENTED
4
6
5a
4
C
7
D
8
VENTED
13
12
3
Introduction
E
10
T
4
11
2
5a
4
5
1
14
E
12
3a
4
11
5a
4
B
9
4
A
IMD-0142
16
18
17
10
T
B
9
13
C
15
A
4
C
7
D
8
4
IMD-0142
5a
6
4
4
Figure 4.1 Installation diagrams
Instruction manual DR-LA39
4
4.2Filling the water
heater
Filling and draining
gis
4.2.1Filling unvented installations
To fill the water heater, proceed as follows.
1. Open the stop valve i in the hot water pipe and, if present, the stop
valves d for the circulation pump.
2. Shut drain valve g.
3. Open the nearest hot water draw-off point m.
4. Open the supply valve i on the cold water side a so that cold water flows
into the water heater.
5. Completely fill the water heater (when cold water flows at normal pressure
from the nearest hot water draw-off point, the water heater is full).
6. Vent the entire installation of air, for example by opening all hot water drawoff points.
7. The water heater is now under water supply pressure. There should be no
water coming out of the expansion valve n nor the T&P-valve c. If this does
happen, the cause might be:
-The water supply pressure is greater than the specified 3.5bar.
Check the correct pressure.
-The expansion valve in the protected cold supply setup is defective or
incorrectly fitted.
4.2.2Filling vented installations
4.3Draining the water
heater
4.3.1Draining unvented installations
To fill the water heater, proceed as follows.
1. Open the stop valve i in the hot water pipe and, if present, the stop
valves d for the circulation pump.
2. Shut drain valve g.
3. Open the nearest hot water draw-off point m.
4. Open the supply valve i on the cold water side a so that cold water flows
into the water heater.
5. Completely fill the water heater (when cold water flows at normal pressure
from the nearest hot water draw-off point, the water heater is full).
6. Vent the entire installation of air, for example by opening all hot water drawoff points.
7. The water heater is now under water supply pressure. There should be no
water coming out of the T&P-valve ca. If this does happen, the safety valve
might be defective or incorrectly fitted.
Some service activities require the water heater to be drained. The procedure is
as follows:
1. Shut the water heater down by putting the On/Off switch to position 0.
2. Disconnect the water heater by putting switching the mains isolator off.
3. Shut off the gas supply h.
4. Close the stop valve i in the hot water pipe.
5. Close the supply valve in the cold water supply a.
6. Open the drain valve g.
40Instruction manual DR-LA
gis
Draining the water heater
7. Vent the water heater (or installation) so that it drains completely.
4.3.2Draining vented installations
Some service activities require the water heater to be drained. The procedure
is as follows:
1. Shut the water heater down by putting the On/Off switch to position 0.
2. Switch the mains isolation off.
3. Shut off the gas supply h.
4. Close the stop valve i in the hot water pipe.
5. Close the stop valve between the water tank and the cold water inlet.
6. Open the drain valve g.
Instruction manual DR-LA41
4
Filling and draining
gis
42Instruction manual DR-LA
gis
gis
5Controls
5.1IntroductionTopics covered in this chapter:
•5.2 Control panel;
•5.3 Explanation of the symbols;
•5.4 ON/OFF switch;
•5.5 Control thermostat;
•5.6 Burner control reset button;
•5.7 Flue gas thermostat reset button.
5.2Control panelFigure 5.1 shows the control panel The panel consists of:
•an ON/OFF switch;
•a reset button;
•a control thermostat with rotary knob;
•two status LEDs.
Introduction
IMD-0361
Figure 5.1 The control panel
Instruction manual DR-LA43
5
Controls
gis
5.3Explanation of the
symbols
5.4ON/OFF switchThe ON/OFF switch is used to put the water heater in the ON mode or OFF
Table 5.1 shows the meanings of thesymbol s on the control panel.
Table 5 .1 Icons and their meaning
SymbolNameExplanation
ON/OFF switch'ON mode' / 'OFF mode'
Reset buttonReset burner control
Power LEDIndicates power to burner control
Error LEDBurner control lockout
Temperature controlTo set water temperature (T
mode. The water heater remains live, even when in the OFF mode. This
ensures the frost protection remains activated.
set
)
n Caution
To electrically disconnect the appliance, you must use the main switch
between the appliance and the mains power supply.
5.5Control thermostatUse the rotary knob of the control thermostat to set the desired water
temperature to between 40°C and 70°C. The knob rotates over a scale of 1 to
4. Ta bl e 5 . 2 shows the temperatures corresponding to each position.
Table 5 .2 Temperature setting
PositionTemperature
5.6Burner control reset
button
1
2
3
4
An error can cause the burner control to lock out. When this happens, the red
LED on the control panel will illuminate. After eliminating the cause of the error,
you can reset the water heater using the reset button.
≈ 40°C
≈ 50°C
≈ 60°C
≈ 70°C
n Caution
Before resetting, always eliminate the cause of the error.
To identify the various errors, refer to chapter 6 Status of the water heater.
Chapter 8 Troubleshooting describes how to troubleshoot errors and problems.
5.7Flue gas thermostat
reset button
44Instruction manual DR-LA
A malfunction in the flue gas discharge, e.g. a blockage in the chimney, can lead
to the flue gas thermostat locking out. This state is evident when the push button
on the flue gas thermostat has been activated, see Figure 5.2. Once the cause
has been removed and the sensor has cooled down sufficiently, press this push
gis
Take care
The draught diverter
can be hot.
Flue gas thermostat reset button
button to reset (if the sensor is not sufficiently cooled down, the flue gas
thermostat will immediately lock out again). The water heater will then
automatically start up again, if there is a demand. If this does not happen, refer
to chapter 8 Troubleshooting for a complete troubleshooting guide.
Figure 5.2 Flue gas thermostat reset button
IMD-0140
Instruction manual DR-LA45
5
Controls
gis
46Instruction manual DR-LA
gis
gis
6Status of the water
heater
6.1IntroductionTopics covered in this chapter:
•6.2 Operating states;
•6.3 Error states;
6.2Operating statesThe water heater has three operating states, namely:
•ISOLATED
In this state the water heater is off and all components are electrically dead.
The isolator (switch between the water heater and the power supply) is
turned off. On the control panel:
-the ON/OFF switch is at position 0;
-the green LED is off.
•OFF
In this state, the frost protection is activated. The isolator is set to position I.
On the control panel:
-the ON/OFF switch is at position 0;
-the green LED is illuminated.
•ON
In this state the water heater continuously fulfils the demand for heat. On the
control panel:
-the ON/OFF switch is at position I;
-The water temperature can be set by turning the rotary knob on the
control thermostat, see paragraph5.5 Control thermostat;
-the green LED is illuminated.
Introduction
6.3Error statesIf the water heater has an error the heater will not operate. The frost protection
will also be out of operation.
If the water heater should go into an "error" state, you will be unable to
continuosly draw hot water. These error conditions are divided into three
groups:
•Lockout error due to the flue gas thermostat
The lockout (push button) of the flue gas thermostat in the draught diverter
has been activated. See paragraph 5.7 Flue gas thermostat reset button.
After removing the cause, the push button must be pressed to re-start the
water heater.
•Lockout errors of the burner control
In this event, the red error LED on the control panel will be illuminated. The
burner control is locked out.
After eliminating the cause. the water heater must be returned to service by
pressing the reset button (see 5.6 Burner control reset button).
•Blocking error due to high limit thermostats
You can recognise this status by the fact that the water heater will not start
operation, despite the water temperature being lower than you have set with
the control thermostat (see 5.5 Control thermostat).
This error disappears automatically once the high limit thermostat resets
itself, after which the water heater re-starts.
Instruction manual DR-LA47
6
Status of the water heater
gis
The cause of the error cannot be seen on the control panel. For a detailed
overview of error states, please refer to chapter 8 Troubleshooting.
If, as end-user, you find the water heater in an error status, you may attempt to
re-start the water heater by pressing the reset button once. However, should the
error return or become persistent, you should contact your service and
maintenance engineer.
48Instruction manual DR-LA
gis
gis
7Starting up and
shutting down
7.1IntroductionTopics covered in this chapter:
•Starting up;
•Shutting down;
•Heating cycle.
7.2Starting upStart-up the water heater as follows:
1. Fill the water heater. See chapter 4 Filling and draining.
2. Open the manual gas valve (see Figure 4.1 Installation diagrams).
3. Switch on the power to the water heater using the isolator between the water
heater and the power supply.
4. Switch the water heater to "ON mode" by switching the ON/OFF switch on
the control panel to position I.
5. Set the desired water temperature using the control thermostat. See
paragraph 5.5 Control thermostat
If there is a heat demand, the water heater will run through a heating cycle. See
paragraph 7.4 Heating cycle.
Introduction
7.3Shutting downYou can:
•Shut the water heater down for brief periods ("OFF mode").
•Isolate the water heater from the power supply.
•Shut the water heater down for a longer period.
7.3.1Shut the water heater down for brief periods ("OFF mode")
To shut the water heater down for a brief period, you must activate the frost
protection. Refer also to paragraph 2.3 The water heater’s heating cycle
With the frost protection you can prevent water freezing in the water heater.
Activate the frost protection by switching the ON/OFF switch on the control
panel to position 0.
7.3.2Isolate the water heater from the power supply
The water heater should only be isolated from mains power in the correct way.
The correct procedure is as follows:
1. Shut the water heater down by switching the ON/OFF switch to position 0.
2. Disconnect the water heater by switching the isolator between the water
heater and the mains power supply to position 0.
7.3.3Shut the water heater down for a longer period
Drain the water heater, if you are shutting it down for a longer period of time.
Proceed as described in paragraph 4.3 Draining the water heater.
Instruction manual DR-LA49
7
Starting up and shutting down
gis
7.4Heating cycleThe heating cycle is activated as soon as the measured water temperature
) falls below the threshold value (T
(T
water
the state in which you want to place the water heater. For example, if the water
heater is in the "OFF mode" (frost protection), then this value is 20°C. If the
water heater is in the "ON mode", then this threshold value is selectable, for
example, position 3 (60°C).
The heating cycle runs in turn through the following states:
1. HEAT DEMAND;
2. WAITING TIME;
3. PRE-GLOW;
4. IGNITION;
5. RUNNING;
6. WAITING TIME.
The complete cycle is explained in the example set out below.
n Caution
The water heater runs through an identical cycle when frost protection is
activated.
). This threshold value depends on
set
1. The control thermostat sensor measures the water temperature. The water
temperature falls below the set temperature, e.g. 60°C, causing the control
thermostat to close. The burner control now detects a heat demand and
starts the heating cycle.
2. After heat demand is detected, the waiting time begins. This waiting time
ensures the ignition takes place safely. The waiting time lasts about 15
seconds.
3. Once the waiting time is over (audible ’clicking’ of the relay in the burner
control) the pre-glowing of the hot surface igniter is started
4. After about 12 seconds (pre-)glowing, the gas control is opened and ignition
can take place.
5. After ignition, the flame is detected and the water heater will be running. This
means that actual heating has started.
6. When the water is up to temperature, the heat demand cuts out. The gas
control closes and the burner tray is extinguished. A new waiting time
begins, of about 10 seconds.
7. After this waiting time, the water heater enters a state of rest and waits until
the water temperature again falls below the set temperature.
With any subsequent heat demand, the heating cycle will resume from step 1.
50Instruction manual DR-LA
gis
8Troubleshooting
8.1IntroductionThis chapter covers the following errors:
•Gas smell.
•Water leakage.
•Explosive ignition.
•Poor flame profile.
•No hot water
•Insufficient hot water.
If the water heater should go into an "error" state, you will be unable to draw hot
water. These error conditions are divided into three groups:
•Lockout error due to flue gas thermostat
The lockout (push button) of the flue gas thermostat in the draught diverter
has been activated. See paragraph 5.7 Flue gas thermostat reset button.
After removing the cause, the push button must be pressed to re-start the
water heater.
•Lockout errors of the burner control
In this event, the red error LED on the control panel will be illuminated. The
burner control is locked out.
After eliminating the cause. the water heater must be returned to service by
pressing the reset button (see 5.6 Burner control reset button).
•Blocking errors
You can recognise this status by the fact that the water heater will not start
operation, despite the water temperature being lower than you have set with
the control thermostat (see 5.5 Control thermostat).
These errors disappear automatically once the cause of the error has been
removed, after which the water heater re-starts itself.
The following pages provide troubleshooting tables for each type of error.
n Caution
Footnotes referred to from within the tables are shown at the bottom of the
last page of the table in question.
Instruction manual DR-LA51
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
8.2Troubleshooting table for general errors
Table 8 .1 General errors Page 1 of 2
SymptomCauseSolutionRemark
is
Gas smellGas leak
Water leakageLeakage from one of
the water connections
(threaded).
Leakage from another
nearby water heater or
pipe segment.
Leakage from the
water heater’s hot
water tank.
Warning
Immediately close the main gas valve.
Warning
Do not operate any switches.
Warning
No naked flames.
Warning
Ventilate the boiler room.
Tighten the threaded connection. If the leak persists, consult your installer.
Trace the leak.
Consult the supplier and/or manufacturer.
n Caution
Immediately contact your installer or local gas company.
CondensationBefore drawing off (too much) hot tap water, wait until the water in
the heater has reached the set temperature.
Instruction manual DR-LA52
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Table 8 .1 General errors Page 2 of 2
SymptomCauseSolutionRemark
is
Explosive ignition
Poor flame profile
Incorrect supply
pressure and/or burner
pressure.
Contaminated burnerClean the burner. See 9.4.2 Cleaning the burners
Contaminated orifice.Clean the orifice. See 9.4.3 Cleaning the orifices
Inadequate air supplyImprove the air supply by better ventilating the boiler room.
Set the correct supply pressure and/or burner pressure, see
3.11 Checking the supply pressure and burner pressure.
If ignition is not improved, consult your installer.
8.3Troubleshooting table "no hot water"
If the water heater fails to supply any hot water, there are several possible causes.
Refer to table Table 8.2 No hot water.
Table 8.2 No hot waterPage 1 of 2
SymptomCauseSolutionRemark
Green LED OFF
and
Red LED OFF
Green LED ON
and
Red LED OFF.
No voltage from power
supply
Blockage in the flue
gas discharge (the
combustion products
discharge safety
device has cut out)
1. Check that the isolator is ON.
2. Check the voltage across the isolator.
3. Check the voltage on the electrical connector block.
4. Check the voltage on the burner control.
5. Check the fuse in the burner control.
The measured voltage must be 230V AC +15% -10%.
1. Trace the blockage.
2. Remove the blockage.
3. Reset combustion products discharge safety device. See
paragraph 5.7 Flue gas thermostat reset button.
See appendix 1.2 Electrical diagram DR-LA. If you cannot resolve
the error, contact your installation engineer.
When heat demand is detected, the water heater will re-start.
Instruction manual DR-LA53
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Table 8.2 No hot waterPage 2 of 2
SymptomCauseSolutionRemark
is
Green LED ON
and
Red LED ON.
There are three possible causes for this error. To determine the cause, the error must be
made to recur:
1. Reset the water heater by pressing the reset button once;
2. Should nothing happen, then the reset button has already been pressed too often
(maximum 5 times in a single heating cycle) and you will have to first electrically isolate
the water heater, then start it again. See paragraph 7.3.2 Isolate the water heater from
the power supply and steps 3 through 5 of paragraph 7.2 Starting up.
3. Decide which type of cause (a) or (b) describes the situation.
(a) three unsuccessful
start attempts in a row
(b) The safety
thermostat has cut out
1. No gas:
•Check that the gas valve is open.
•Check that gas control opens (clicking of the gas control).
•Check the gas control wiring.
2. No ignition:
•Check whether the hot surface igniter lights up.
•Check the power supply to the hot surface igniter.
•Check the wiring of the hot surface igniter.
3. No flame detection:
•Check that the Phase (L) and Neutral (N) are correctly
connected (from the power supply) to the water heater
•Check that the flame probe is not defective.
•Check that the wiring to the flame probe is correctly
connected.
1. The safety thermostat has cut out correctly:
•Reset the water heater.
•Check whether the control thermostat is working.
•Check whether the high-limit thermostat is working.
•Check that the circulation pump (if present) is working.
2. The safety thermostat has cut out without apparent reason:
•Check whether the thermostat may be broken.
•Check whether the thermostat sensor may be broken.
If the error cannot be resolved or is persistent, contact your
installer.
If the error cannot be resolved or is persistent, contact your
installer.
Instruction manual DR-LA54
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
8.4Troubleshooting table "insufficient hot water’"
If the water heater fails to supply any hot water, there are several possible causes.
Refer to Table 8.3 Insufficient hot water
Table 8.3 Insufficient hot water
SymptomCauseSolutionRemark
is
Insufficient hot waterThe water temperature
setting (T
Hot water supply used
up.
) is too low
set
Set the control thermostat to a higher setting. See paragraph
5.5 Control thermostat.
1. Reduce the rate of hot water consumption. Allow the water
heater enough time to heat up the water.
2. If this error occurs regularly, check whether the high-limit
thermostat is cutting in/out. If so, check that the circulationand/or top to bottom recirculation pump are working properly.
If the error has not been rectified and no other cause can be found,
isolate the water heater from the power supply, shut off the gas
valve and alert your installer.
Instruction manual DR-LA55
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
is
Instruction manual DR-LA56
s
s
9Maintenance
9.1Introduction
Introduction
cNote
Maintenance may only by carried out by an approved service and
maintenance engineer.
At each service, the water heater undergoes maintenance both on the water
side and on the gas side. The maintenance should be carried out in the following
order.
1. Preparing for maintenance;
2. Water-side maintenance;
3. Gas-side maintenance;
4. Finalising maintenance.
9.2Preparing for
maintenance
n Caution
Before ordering spare parts, take a moment to write down the water heater
type and model and the full serial number of the water heater. Only by
ordering with this information can you be sure to receive the correct spare
parts. These details can be found on the rating plate.
To test whether all components are still working properly, you should complete
the following steps:
1. Put the ON/OFF switch on the control panel to position 0.
2. Set the control thermostat (note the original setting) to the highest position
and put the ON/OFF switch back to position I.
3. If there is no heat demand, draw some hot water off to initiate a heat
demand.
4. Check whether the heating cycle runs correctly. See paragraph 7.4 Heating
cycle.
5. Set the control thermostat back to the original setting and put the ON/OFF
switch back to position I.
6. Check the supply and burner pressures and adjust these, where necessary.
See paragraph 3.11 Checking the supply pressure and burner pressure.
7. Check that all components of the flue gas system are properly attached.
8. Test the operation of the expansion valve of the cold supply setup. The water
should spurt out.
9. Test the overflow operation of the T&P valve. The water should spurt out.
10. Check the drain pipes from the discahrge points of any valve and remove
any lime buildup that may be present.
11. Drain the water heater. See paragraph 4.3 Draining the water heater.
Instruction manual DR-LA57
9
9.3Water-side maintenance
9.3.1Introduction
9.3.2Checking the anodes
Take care
The draught diverter
and the cover may be
hot.
Maintenance
s
The following steps should be carried out on the water side:
1. Checking the anodes.
2. Descaling and cleaning the heater.
Timely replacement of the anodes extends the service life of the water heater.
The anodes that are present must be replaced as soon as they are 60% or more
used up (take this into consideration when determining the maintenance
frequency).
1. Remove the protective cover from the control column by unscrewing the 4
screws in the cover.
2. Detach the wiring for the flue gas thermostat from the connector block and
remove the cable from the strain relief.
3. Remove the cable clamps holding the flue gas thermostat cable.
4. Disconnect the draught diverter from the flue gas discharge.
5. Undo the screws on the draught diverter.
6. Remove the draught diverter from the water heater.
7. Undo the screws of the cover on the top of the water heater.
8. Remove the cover from the water heater.
9. Remove the sealing ring from the hot water tank.
10. Loosen the anodes using suitable tools (27 mm A/F).
11. Check the anodes and if necessary, replace them.
12. Now also check the flue baffles. Replace them, if necessary. See paragraph
9.4.4 Checking the flue baffles.
13. Fit a new sealing ring around the edge of the hot water tank and replace the
cover.
14. Fit the draught diverter. See paragraph 3.9.2 Fitting the draught diverter.
15. Feed the cable of the flue gas thermostat through the strain relief and attach
the wiring to the connector block. See appendix 1.2 Electrical diagram DR-
LA or 1.2.2 Electrical diagram DR-LA 110 (LP gas).
16. Refit the cable clamps to the water heater and draught diverter.
17. Refit the protective cover.
9.3.3Descaling and cleaning the heater
Scale and lime buildup prevent effective conduction of the heat to the water.
Periodic cleaning and descaling prevents buildup of these deposits. This
increases the service life of the appliance, and also improves the heating
process.
Take the rate of scale formation into account when deciding on maintenance
frequency. Scale formation depends on the local water composition, the water
consumption and the water temperature setting. A water temperature setting of
maximum 60
To guarantee a good, watertight seal around the cleaning opening, the gasket ,
O-ring g, spring washers, bolts and if necessary, the lid c should be replaced
with new parts before reassembly. See Figure 9.1. A special set is obtainable
from Hamworthy for this purpose.
58Instruction manual DR-LA
O
c is recommended for prevention of excessive scale buildup.
s
Gas-side maintenance
To simplify descaling and cleaning of the tank, the appliance is equipped with
two cleaning openings.
1
2
5
6
3
4
7
IMD-0235
Figure 9.1 Cleaning opening
1. Remove the cover plate a on the outer jacket. See Figure 9.1.
2. Carefully remove the insulation b and set it to one side. This will be needed
again later.
3. Undo the bolts.
4. Remove the lid, the gasket and the O-ring.
5. Inspect the tank and remove the loose scale deposits and contamination.
6. If the scale cannot be removed by hand, then the appliance will need to be
descaled using a suitable cleaner.
9.4Gas-side maintenance
Take care
The burners may be
hot.
5
4
Figure 9.2 Bolt tightening sequence
7. Close the cleaning opening. To avoid damage to the tank, the bolts that
fasten the lid should be tightened with a torque no greater than 50 Nm. Use
suitable tools for this. To properly seal the cleaning opening, we recommend
tightening the bolts in the sequence shown in Figure 9.2.
9.4.1Introduction
On the gas side the following steps should be carried out:
1. Cleaning the burners.
2. Cleaning the orifices.
3. Checking the flue baffles.
1
3
6
2
IMD-0282
9.4.2Cleaning the burners
1. Detach the burners.
2. Carefully remove any contamination present on the burners.
Instruction manual DR-LA59
9
9.4.3Cleaning the orifices
9.4.4Checking the flue baffles
Take care
The flue baffles may
be hot.
Maintenance
s
3. Re-attach the burners.
1. Remove the orifices.
2. Remove any contamination present in the orifices.
3. Re-attach the orifices.
1. Complete steps 1 through 9 of paragraph 9.3.2 Checking the anodes.
2. Remove the flue baffles from the water heater.
3. Check the flue baffles for rust and remove any which is present.
4. Check the flue baffles for wear and replace any worn flue baffles.
5. Complete steps 13 through 17 of paragraph 9.3.2 Checking the anodes
9.5Finalising maintenance
To finalise the maintenance carry out the following steps:
1. Fill the water heater. See paragraph 4.2 Filling the water heater.
2. Re-start the water heater. See 7.2 Starting up.
60Instruction manual DR-LA
is
AAppendices
1.1IntroductionThis appendix contains:
•The Electrical diagram DR-LA.
Instruction manual DR-LA61
A
1.2Electrical diagram
DR-LA
1.2.1Electrical diagram DR-LA 30 through 95 and 110 (natural gas)
1 = brown
2 = blue
3 = yel./green
4 = black
5 = white
Q
R
3
Appendices
N
22
2
NN
N
LLL
16151413
2
1
2
1
111
N
1817
12 1
2
230V AC
50Hz
L
N
1
L
2 143444 4
44
4
LL
L
L
2419 20 21 22 23
444
4
is
P
4
2L3
L
NO P NC
N
65432198710
L
K
FUSE
F1
NONCP
1211
4
444
3
4
4
M
4
4
2
4
24
1
5
O
A
B
0
D
11
4
E
11
4
F
TERMINAL STRIP CONNECTIONS:
A Earth
N Neutral
L1 Phase
L2 Phase input of controller
L3 Phase input of combustion products discharge safety device
LPhase input safety ciruit of thermostat circuit
NO Normally open
PPVC power supply
NC Normally closed
PARTS:
ABurner control
NNeutral
AEarth
L'Phase input of controller
L"Phase output
THPhase input of thermostat circuit
GV1 Phase output of gas control
MAX Phase input of safety thermostat
LGPhase input of hot surface igniter
IIonisatiion detection = output
NONormally open
PPhase input alarm
NCNormally closed
F1Fuse (T5A)
R1Relay (Max. 250V, 10A)
4
1
11
12
3
I
4
1
12
1
3
12
4
3
4
C
11
12
G
TV
L"N
HN1
3
BFrost thermostat
C Control thermostat
DOn/Off switch
ESafety thermostat
FHigh-limit thermostat
G Gas valve
H Hot surface igniter
JFlame probe
KError detection
LOn detection
M Reset button
NCombustion products discharge safety device
O Relay (Max. 250V, 10A)
OPTIONAL PARTS:
PMain switch control
Q potentiostat (for power anodes)
RWeek timer
L’
4212144433343
1
4
Figure 1.1 Electrical diagram DR-LA 30 through 95 and 110 (natural gas)
HOT
R1
SURFACE
M
LA
N
NX
G
4
23
1
N
LLI
NN
O
CP
I
4 4 4
44
4
N
302725 2628 29
32
1
GJ
544
H
62Instruction manual DR-LA
is
1 = brown
2 = blue
3 = yel./green
4 = black
5 = white
T
1.2.2Electrical diagram DR-LA 110 (LP gas)
230V AC
50Hz
L
N
R
4
2L3
1
L
N
L
65432198710
K
FUSE
F1
HOT
SURFACE
G
M
LA
TV
G
N
HN1
NX
L"N
L’
42121444333 43
1
S
22
3
2
NN
N
LLL
16151413
2
1
N
2
1
111
N
1817
2
12 1
4
1
B
11
12
3
0
D
I
4
1
2 143444 4
44
4
LL
L
L
2419 20 21 22 23
444
4
4
4
C
11
12
3
NO P NC
L
M
R1
I
Electrical diagram DR-LA
NONCP
4
1211
444
3
4
4
4
4
2
4
24
1
5
O
A
NN
O
CP
4 4 4
12
11
4
E
4
F
TERMINAL STRIP CONNECTIONS:
AEarth
NNeutral
LPhase
L1Phase input of controller
2
Phase input of combustion products discharge safety device
L
3
L
Phase input safety ciruit of thermostat circuit
NO Normally open
PPVC power supply
NC Normally closed
PARTS:
A Burner control
N Neutral
A Earth
L'Phase input of controller
L"Phase output
THPhase input of thermostat circuit
GV1 Phase output of gas control
MAX Phase input of safety thermostat
LGPhase input of hot surface igniter
IIonisatiion detection = output
NONormally open
PPhase input alarm
NC Normally closed
F1Fuse (T5A)
R1Relay (Max. 250V, 10A)
1
3
12
11
4
3
Figure 1.2 Electrical diagram DR-LA 110 (LP gas)
23
4
1
N
LLI
1
3
2
N
2
G
LHigh-limit thermostat
BFrost thermostat
CControl thermostat
DOn/Off switch
ESafety thermostat
FHigh-limit thermostat
G Gas valve
H Hot surface igniter
J Flame probe
KError detection
LOn detection
M Reset button
N Combustion products discharge safety device
O Relay (Max. 250V, 10A)
PHigh-low control
QTimer
OPTIONAL PARTS:
RMain switch control
SPotentiostat (for power anodes)
TWeek timer
44
4
N
32
13454243
302725 2628 29
444
41 44 2
N
L
N
IL
373331 3234 354038 39
HJP
3 4
11
A
1
15
1
L
L
2
L
16Q18
’’
L
4 4
A
1
15
2
2
L1L
3
LN
N
A
A
2
2
1618
Q
2424
Instruction manual DR-LA63
A
Appendices
is
64Instruction manual DR-LA
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.