Dorby Czas MMR17-V3A-M230 Technical data

1
NOWOŚĆ
MMR17-V3A-M230-108
Voltage monitoring in 3- and 1-phase mains
MMR17-V3A-M230-108
Technical data
Description
Output circuit
Contact arrangement
1 CO
Rated voltage
V AC
250/400
Switching current range AC1 DC1
A/V AC A/V DC
8/250
8/24
Switching load range AC1
VA
2 000
Contact resistance
mΩ
≤ 100
Max. rated current A 8
Input circuit
Supply voltage Un DC/ AC (50-60Hz) = measured voltage
V
L1, L2, L3, N
Tolerance 0,8…1,2Un (11,5…276V)
Rated consumption AC DC
VA W
≤ 2.5
<2
Rated frequency
Hz
47…63
Rated surge voltage V 1000
Insulation
Insulation rated voltage
V AC
400
Rated surge voltage
V
4 000 1,2/50s
Overvoltage category III
Dielectric strength
Input – output Open contact
V AC 4 000
1 000
Measuring circuit
Regulation range voltage min U
min
%
70…110% (161…253V)
Regulation range voltage max U
max
%
80…120% (184…276V)
Threshold voltage asymmetry U
asym
20 (46V)
Hysteresis voltage asymmetry
% 5 Functions MU, MW, MA, MS
Measurement accuracy
%
≤ 5
Setting accuracy % ≤ 5
Repeatability % ≤ 2
Temperature influence
%/ºC
≤ 0,05
Sampling frequency of the input process
Hz
2930
resolution converters
bits
9
Time module data
Setting range of time off delay
10s
Timing adjustment
smooth 0,05…1,0 x time range
Setting accuracy % 5
Repeatability % 0,5
Reset time
ms
≤ 500
General data
Electrical life AC1 at 1000 VA resistive load
cycles
≥ 1,5 x 105
Mechanical life
cycles
≥ 1 x 107
Dimensions (L x W x H) / Weight
mm / g
90 x 17,5 x 66 / 50g
Ambient temperature / storage temperature
ºC
-40…+70 / -20…+55
IP rating IP20
Relative humidity % 85
Shock resistance g 15
Vibration resistance
mm
0,35 10…55Hz
LED indicator 2 LED
The executive relay R is designed for applications in automation and control systems to control the voltage, asymmetry and phase sequence in three- phase AC networks or to control the AC/DC voltage in a one-phase networks. It is used to protect the receiver from voltage drop or rush beyond the set threshold. Use of an universal power supply powered from any input voltage (L1, L2, L3) allows correct operation of the measuring system in a wide range in the presence of voltage on one, whichever electric terminal. True RMS is an innovative method for such products group and it provides the highest accuracy regardless of the AC input waveform, which may be important in case of voltage deviation from the ideal sine wave- due to a presence of nonlinear loads in the circuit. The TrueRMS method also allows the measurement of constant DC voltages. The relay has an adjustable off delay time in a range from 0.5s to 10 s. Seven-position switch allows selection of measurement undervoltage or window functions and supplements them with voltage asymmetry and phase sequence control. Relay status is indicated by two LEDs.
Mounting
Mounted on DIN-rail TS 35 according to EN 60715 Mounting position: any IP rating IP20 Tightening torque: max. 1 Nm
Terminal capacity: 1 x 0.5 to 2.5 mm²
with/without multicore cable end 1 x 4 mm2 without multicore cable end 2 x 0.5 to 1.5
mm² with/without multicore cable end 2 x
2.5 mm2 flexible without multicore cable end.
Danger!
Ordering information
Read and understand these instructions before installing, operating or maintaining the equipment. Never carry out work on live parts! Danger of fatal injury! The product must not be used in case of obvious damage. To be installed by an authorized person.
MMR17-V3A-M230-108
Voltage monitoring in 3- and 1-phase mains Multifunction TrueRMS actual voltage measurement method has been used Function window, undervoltage, asymmetry, sequence 1 change over contact Width 17.5 mm Installation design
MMR17-3127 v1.0
2
Voltage monitoring in 3- and 1-phase mains
MMR17-V3A-M230-108
Functions
Dimensions Front panel view
Function - MS (sequence) – Phase sequence monitoring
When all the phases are connected in the correct sequence and the measured asymmetry is less than the set value, the output relay switches into on-position (yellow LED illuminated). When the phase sequence changes, the output relay switches into offposition (yellow LED not illuminated).
Functions - MA (asymmetry) – Asymmetry monitoring As soon as the asymmetry exceeds the value at the Uas ­regulator, the set interval of the tripping delay (DELAY) begins. After the interval has expired the output relay R switches into off-position (yellow LED not illuminated).
MW (window) The output relay R switches into on- position again after the measured voltage reenters the acceptance region
MU (undervoltage) – The output relay R switches into on-position again after the measured voltage exceed the Max-value.
The actual voltage measurement method- TrueRMS provides the highest accuracy regardless of the AC input waveform, which may be important in case of voltage deviation from the ideal sine wave- due to a presence of nonlinear loads in the circuit. The TrueRMS method also allows the measurement of constant DC voltages.