Dorby Czas MMR17-V1B-U230-108 Technical data

1
NOWOŚĆ
MMR17-V1A-U230-108
Voltage monitoring 1-phase mains
MMR17-V1B-U230-108
Technical data
Description
Output circuit
Contact arrangement
1 CO
Rated voltage
V AC
250/400
Switching current range AC1 DC1
A/V AC A/V DC
8/250
8/24
Switching load range AC1
VA
2 000
Contact resistance
mΩ
≤ 100
Max. rated current A 8
Input circuit
Supply voltage Un DC/ AC (50-60Hz) = measured voltage
V
50, 125, 230
Tolerance 0,8…1,2Un (40…276V)
Rated consumption AC DC
VA W
≤ 2.5
<2
Rated frequency
Hz
47…63
Rated surge voltage V 1 000
Insulation
Insulation rated voltage
V AC
250
Rated surge voltage
V
2500 1,2/50s
Overvoltage category III
Dielectric strength
Input – output Open contact
V AC 4 000
1 000
Measuring circuit
Regulation range voltage min U
min
%
70…110%
Regulation range voltage max U
max
%
80…120%
Functions MU, MW
Measurement accuracy
%
≤ 5
Setting accuracy % ≤ 5
Repeatability % ≤ 2
Temperature influence
%/ºC
≤ 0,05
Sampling frequency of the input process
Hz
2930
resolution converters
bits
9
Time module data
Setting range of time off delay
10s
Timing adjustment
smooth 0,05…1,0 x time range
Setting accuracy % 5
Repeatability % 0,5
Reset time
ms
≤ 500
General data
Electrical life AC1 at 1000 VA resistive load
cycles
≥ 1,5 x 105
Mechanical life
cycles
≥ 1 x 107
Dimensions (L x W x H) / Weight
mm / g
90 x 17,5 x 66 / 50g
Storage temperature / ambient temperature
ºC
-40…+70 / -20…+55
IP rating IP20
Relative humidity % 85
Shock resistance g 15
Vibration resistance
mm
0,35 10…55Hz
LED indicator 2 LED
Voltages can be adjusted to customer requirements
The supervisory relay is designed for application in automation and control systems, it controls single-phase AC/DC voltage systems, and protects the receivers from voltage drops and rushes beyond the set thresholds.
Use of the universal power supply allows correct operation of the measuring system in a wide range of voltages. TrueRMS voltage measurement is an innovative method in such products group and provides the highest accuracy regardless of the AC input waveform, which is important in case of voltage deviation from the ideal sine wave. TrueRMS method also allows measurement of the constant DC voltage.
The relay has an adjustable off delay time in a range from 0.5s to 10s. Seven-position switch allows selection of measurement functions undervoltage or window and rated input voltage range of 50, 125 or 230V.
Relay status is indicated by two LEDs.
Mounting
Mounted on DIN-rail TS 35 according to EN 60715 Mounting position: any IP rating IP20 Tightening torque: max. 1 Nm
Terminal capacity: 1 x 0.5 to 2.5 mm²
with/without multicore cable end 1 x 4 mm2 without multicore cable end 2 x 0.5 to 1.5
mm² with/without multicore cable end 2 x
2.5 mm2 flexible without multicore cable end
Danger!
Ordering information
Read and understand these instructions before installing, operating or maintaining the equipment. Never carry out work on live parts! Danger of fatal injury! The product must not be used in case of obvious damage. To be installed by an authorized person.
MMR17-V1B-U230-108
Voltage monitoring 1-phase mains Input voltage range of 50, 125, 230V AC/DC TrueRMS voltage measurement Function window and undervoltage 1 change over contact Width 17.5mm Installation design
MMR17-3146 v1.0
2
Dobry Czas Sp. z o.o. 51-315 Wrocław ul. Miłostowska 7/6; Poland
+48 71 729 95 90 marketing@dobry-czas.pl
www.dobry-czas.pl
Voltage monitoring 1-phase mains
MMR17-V1B-U230-108
Functions
Dimensions
Front panel view Connection diagram
Functions which are selected by the means of rotary switch
50U, 125U, 230U Undervoltage monitoring
50W, 125W, 230W – Monitoring the window between Min and Max
LED indicator
Yellow LED
indication of relay R output.
Green LED
Indicates the system status monitor.
The flashing green LED to fill out short pulses of about 10% of the mean value of the input voltage drop below the lower threshold U
min
.
Slow flashing green LED pulses to fill out about 90% mean increase in input voltage above the upper threshold U
max
.
Flashing green LED pulses to fill out about 50% means that U
max
upper voltage threshold is set below the lower limit U
min
.
MW (window) – The output relay R switches into on- position again after the measured voltage reenters the acceptance region
MU (undervoltage) – The output relay R switches into on-position again after the measured voltage exceed the Max-value.
Connect one of the power cords to desired full rated voltage range input, and the second one to the common input. For monitoring constant DC voltage connect the positive pole (+) to the +/~ terminal.
MMR17-3146 v1.0