Przekaźnik nadzorczy
MMR17-V1A-U230-108
Voltage monitoring 1-phase mains
MMR17-V1B-U230-108
Switching current range AC1
DC1
Supply voltage Un DC/ AC (50-60Hz) = measured voltage
Tolerance 0,8…1,2Un (40…276V)
Rated surge voltage V 1 000
Dielectric strength
Input – output
Open contact
Regulation range voltage min U
min
Regulation range voltage max U
max
Sampling frequency of the input process
Setting range of time off delay
smooth 0,05…1,0 x time range
Electrical life AC1 at 1000 VA resistive load
Dimensions (L x W x H) / Weight
Storage temperature / ambient temperature
Voltages can be adjusted to customer requirements
The supervisory relay is designed for
application in automation and control
systems, it controls single-phase AC/DC
voltage systems, and protects the receivers
from voltage drops and rushes beyond the set
thresholds.
Use of the universal power supply allows
correct operation of the measuring system in
a wide range of voltages. TrueRMS voltage
measurement is an innovative method in such
products group and provides the highest
accuracy regardless of the AC input
waveform, which is important in case of
voltage deviation from the ideal sine wave.
TrueRMS method also allows measurement of
the constant DC voltage.
The relay has an adjustable off delay time in a
range from 0.5s to 10s. Seven-position switch
allows selection of measurement functions
undervoltage or window and rated input
voltage range of 50, 125 or 230V.
Relay status is indicated by two LEDs.
Mounted on DIN-rail TS 35 according to EN
60715
Mounting position: any
IP rating IP20
Tightening torque: max. 1 Nm
Terminal capacity: 1 x 0.5 to 2.5 mm²
with/without multicore cable end 1 x 4 mm2
without multicore cable end 2 x 0.5 to 1.5
mm² with/without multicore cable end 2 x
2.5 mm2 flexible without multicore cable
end
Read and understand these instructions before installing, operating or
maintaining the equipment.
Never carry out work on live parts! Danger of fatal injury! The product must not
be used in case of obvious damage. To be installed by an authorized person.
Voltage monitoring 1-phase mains
Input voltage range of 50, 125, 230V AC/DC
TrueRMS voltage measurement
Function window and undervoltage
1 change over contact
Width 17.5mm
Installation design
MMR17-3146 v1.0
Dobry Czas Sp. z o.o. 51-315 Wrocław ul. Miłostowska 7/6; Poland
+48 71 729 95 90
marketing@dobry-czas.pl
Voltage monitoring 1-phase mains
MMR17-V1B-U230-108
Front panel view Connection diagram
Functions which are selected by the means of
rotary switch
50U, 125U, 230U – Undervoltage monitoring
50W, 125W, 230W – Monitoring the window between Min and Max
indication of relay R output.
Indicates the system status monitor.
The flashing green LED to fill out short pulses of about 10% of the mean value of the input voltage drop below the lower
threshold U
min
.
Slow flashing green LED pulses to fill out about 90% mean increase in input voltage above the upper threshold U
max
.
Flashing green LED pulses to fill out about 50% means that U
max
upper voltage threshold is set below the lower limit U
min
.
MW (window) – The output relay R switches into on-
position again after the measured voltage reenters the
acceptance region
MU (undervoltage) – The output relay R switches into
on-position again after the measured voltage exceed
the Max-value.
Connect one of the power cords to desired
full rated voltage range input, and the
second one to the common input. For
monitoring constant DC voltage connect the
positive pole (+) to the +/~ terminal.
MMR17-3146 v1.0