Dorby Czas MMR17-RTA-M048 Technical data

Temperature Monitoring Relay
MMR17-RTA-M048-108
Description
Output circuit
Contact arrangement
1CO
Rated/max contact voltage
V AC
250/400
Switching current In in category AC1 DC1
A/V AC A/V DC
8/250
8/24
Switching load range AC1
VA
2 000
Contact resistance
mΩ
≤ 100
Maximum rated current
A
8
Input circuit
Input contacts A1, A2, A3
Rated supply voltage Un
V
A1-A2: 48VAC (50/60Hz)
A1-A3: 24VACDC (50/60Hz)
Supply voltage tolerance
supply 48VAC supply 24VACDC
0,8…1,15Un (38,455,2V) 0,85…1,2Un (20,4…28,8V)
Rated consumption
supply 48VAC supply 24VDC
VA
W
1
0,5W
Rated frequency AC
Hz
47…63
Rated surge voltage V 1 000
Burst voltage V 2 000
Insulation
Insulation rated voltage
V AC
250
Rated surge voltage
V
4 000 1,2/50s
Overvoltage category III
Pollution degree 2
Flammability pcb: V0, housing: HB
Dielectric strength
input - output open contact
V AC 4 000
1 000
Measurement circuit
Response value > T
max
Ω
> 3300
Release value Ω 110 < R < 1800
Max PTC resistance in when cold
Ω
1500
PTC short circuit resistance
Ω
< 70
PTC galvanic isolation no
Tolerance % 5
PTC sensors type PTC, Sign A
Delay circuit
ON/OFF delay
s
~ 0,5
General data
Electrical life AC1 at 1000 VA resistive load
cycles
1,5 x 105
Mechanical life
cycles
≥ 1 x 107
Dimensions (a x b x h) / Weight
mm / g
90 x 17,5 x 66 / 52
Storage / ambient temperature
ºC
-40…+70 / -20…+45
IP rating IP20
Relative humidity % 85
Shock resistance g 15
Vibration resistance
mm
0,35 10…55Hz
Indicators 2 LED diodes
Temperature Monitoring Relay is designed for application in automation and control systems to protect devices (i.e. motors) against temperature rise above the limit.
Two LED diodes indicate state of the relay. Green LED diode indicates the presence of supply voltage. If the temperature of the monitoring unit exceeds the limit, when resistance of PTC circuit is higher than 3300Ω, the contact is opened and the red LED diode flashes. The relay is released when the resistance of PTC sensors drops below 1800Ω. When the PTC resistance is lower than 70Ω the short circuit is detected, the contact is opened and the red LED diode illuminates steadily.
Caution!!!
Input of the PTC sensor is not galvanically isolated from the input circuit. When powering from 48VAC mains, dangerous voltage can appear on PTC T1 and T2 inputs posing danger of electric shock, so PTC sensors must provide galvanic isolation between the PTC circuit and the monitoring device. The hazard does not exist when the monitoring relay is powered from 24VACDC voltage.
Mounting
1. Mounted on DIN-rail TS 35 according to EN
60715.
2. Mounting position: any.
3. IP Rating IP20.
4. Tightening torque: max. 1 Nm.
5. Terminal capacity: 1 x 0.5 to 2.5 mm²
with/without multicore cable end 1 x 4 mm2 without multicore cable end 2 x 0.5 to
1.5 mm² with/without multicore cable end
2 x 2.5 mm2 flexible without multicore cable end.
Ordering information
Read and understand these instructions before installing, operating or maintaining the equipment. Never carry out work on live parts! Danger of fatal injury! The product must not be used in case of obvious damage. To be installed by an authorized person.
MMR17-RTA-M048-108
Temperature Monitoring Relay of the motor winding Up to 6 PTC thermistor sensors Overheat detection Short circuit monitoring of the PTC line Supply voltage 48VAC or 24VACDC In accordance with PN-EN 60730-1, PN-EN 60947-8A
MMR17-3141 v1.0
Temperature Monitoring Relay
MMR17-RTA-M048-108
Dobry Czas Sp. z o.o. 51-315 Wrocław ul. Miłostowska 7/6
+48 71 729 95 90 marketing@dobry-czas.pl
www.dobry-czas.pl
Monitoring function
Dimensions
Connection diagram
For 24VACDC mains, the supply voltage connect between A1 and A3 (polarity is irrelevant).
Maximum 6 PTC sensors connect in series between T1 and T2 inputs.
RT – if the PTC resistance is above 80Ω the output relay switches into ON position. When the cumulative resistance of the PTC circuit exceeds 3300Ω (at least one of the PTCs has reached the cut-off temperature), the output relay switches into OFF position and the red LED flashes. The output relay switches into ON position, if the cumulative resistance drops below 1800Ω by cooling down of the PTC. In case of PTC short circuit detection (<70Ω) the output relay switches into OFF position and red LED illuminates steadily.
MMR17-3141 v1.0