Door-Gard 232i, 232w, 232r, 232se, 232m Features And Programming Manual

...
FEATURES AND PROGRAMMING GUIDE
SELF-CONTAINED ACCESS CONTROL SYSTEMS KEYPADS:
DOOR-GARD SELF-CONTAINED ACCESS CONTROL SYSTEMS offer field proven reliability and cost effective solutions for residential, commercial and industrial installations. Elegant yet durable, Door• Gard systems blend with virtually any decor. Designed for compatibility with virtually any electric locking device, Door Gards accept power from a 12 or 24V AC/ DC supply. No separate programmer is ever necessary.
FE ATURES :
LOCK RELEASE RELAY
LOCK RELEASE TIMER
FORCED DOOR ALARM RELAY
PROPPED DOOR ALARM RELAY
ALARM ZONE SHUNTING RELAY
TIMED EGRESS INPUT
120 USERS
FRONT PROGRAMMING
MEMORY Non-volatile EEPROM memory means your codes and instructions will be there whether you remove power for 5 minutes or 5 years.
CODES The Door-Gard Self-Contained Access Control Systems allow up to 120 individual user codes to be valid. Codes may be from 1-6 digits in length and digits may be repeated. The Master Code is always user one (1)
FORCED DOOR RELAY Assisted by the Door Positition Sensor Input, this 1 Amp Form-C relay will energize if the door is opened without a valid user entry or egress input. This output can be pro­grammed to energize for up to 15 minutes or latch. It can be reset by a valid code entry.
PROPPED DOOR RELAY Programming a 1 to 15 minute open door time allows the Door-Gard to alert you to a propped door by energizing a 1 Amp Form-C relay. Assisted by the Door Position Sensor Input, this relay will deenergize upon closure of the door.
ALARM ZONE SHUNT RELAY Assisted by the Door Position Sensor Input, this 1 Amp Form-C relay is energized simultaneously with the lock release relay providing an easy means of shunting existing door contacts. The relay will continue shunting until the Door Gard sees the door close; preventing nuisance alarms (annunciate with the Propped Door Relay instead).
LOCK RELEASE RELAY This is an 8 Amp (10 Amp surge) Form-C relay which can be toggled (by code) or timed from 1 to 90 seconds.
DOOR POSITION SENSOR INPUT By simple adding a normally closed magnetic door switch, the Door Gard system will monitor the position of the door and immediately relock it after valid access has been gained, preventing unwanted “tailgate” entries.
PROGRAMMING All programming is accomplished entirely from the front of the keypad. LED guidance makes programming easy, and changing codes a matter of seconds for an autho­rized user.
TIMED EGRESS INPUT Upon a momentary closure, this normally open loop will trigger the main relay for the same time period as the Master Code.
KEYPRESS FEEDBACK / Door-Gard Self Contained Access Control Systems
will acknowledge a keypress by momentarily illuminating the yellow LED on the indoor(i), weather resistant(w), mullion(m) styles or momentarily sounding the sounder in the ruggedized(r) and sealed environmental(se) styles. This can be turned off through programming.
KEYPAD ACTIVE OUTPUT Door-Gard Self Contained Access Control Systems can be programmed to energize a voltage output whenever a key is touched. This can be used to turn on lights, CCTV camera, or notify a guard. This output is not available if the IEI 250 Printer Interface is used.
AUDIT TRAIL An accurate real-time audit trail can be provided by any Access Control Series Door-Gard (except 233/ 234) with the addition of a model 250 Printer Interface (not includ­ed). Up to 8 keypads can be monitored simultaneously. The 250 comes with power supply and printer cable and easily connects to any parallel printer (not included).
AUDIBLE KEYPRESS
TESTING THE KEYPAD
1. Connect the positive (+) lead of your power supply to the terminal strip (TS1) +V input.
2. Connect the negative (-) lead of your power supply to the terminal strip (TS1) -V input.Turn on your power supply.
1
2
4. Press 7890#123456*. If all 12 keypresses have been verfied, the keypad will enter self test mode. Either the LED’s will flash or the sounder will beep 3 times,.then light or sound continuously for 3 seconds (except on the mullion). If these responses do not happen, try the test mode again and then call tech support. Note: self test mode can be used when trou­bleshooting a keypad in the field. If you do not get the continuous light or sound then the memory has been corrupt and should be re-programmed with the 46 command (see option #16).
5.
Enter the master code of 1234*. The relay will
energize. Refer to programming section to program your keypad.
NOTE: The keypad may be programmed in your shop or at the
installation site. Programmed information is stored in non­volatile memory so it will not be lost if power is removed.
ACCESS CONTROL DEFAULTS
Door-Gard Self-Contained Access Control Systems are designed for easy installation in a minimum amount of time. The following defaults have been fac­tory programmed.
Master Code (user 1) 1234 * Lock Release Relay will energize for 5 secs. Keypad Active Output Off Keypress Feedback On Propped door relay will energize after 30 secs. Forced door relay will energize for 10 secs.
If defaults must be changed or additional functions are desired, please refer to the PROGRAMMING OPTIONS Chart after you are familiar with the PROGRAMMING section.
PROGRAMMING
1. Enter programming mode Press 99 # (master code) * Flashes slow-
ly
1
Yellow LED
2. To Change master code Press 1 # (new master code) * Flashes fast Press (new master code) * Flashes slowly If main relay time must be changed, substitute option 2 from Programming Options chart for step 2 above.
3. To Add/change second code Press 2 # (new user code) * Flashes fast Press (new user code) * Flashes slowly
4. To Add/change third code Press 3 # (new user code) * Flashes fast Press (new user code) * Flashes slowly
5. Up to 120 codes may be added in this fashion
6. Exit programming mode Press * Out
3
NOTE:
1 Door•Gard Self-Contained Access Control Systems are factory programmed with a master code of 1234 *.
2 Some Door•Gard products contain a sounder in place of the yellow LED. In these products the flashing is replaced by a beeping.
• 3 The master code is always user 1.
The master code allows access to the
programming mode & activates the main relay.
All codes must be followed by the *.
Codes may be from 1-6 digits in length, and digits
may be repeated.
If the master code is forgotten or does not seem to
be working, momentarily remove the programming jumper (or push SW1 on the SE style, see wiring diagram for location) to enter programming mode and go to option #16 and default keypad.
If the yellow LED lights (or sounder sounds) solid
while in programming mode an error has occurred. Press * to clear (yellow LED should flash or sounder sound) and start over from step 2 or 3 above.
PROGRAMMING OPTIONS CHART
2
If the pre-programmed default values must be changed
or additional functions are desired, the following options may be programmed
3
.
1. Enter programming mode
Press
99 # (master code)
*
2. Change master code/set main relay time
1
Press
( time) # 1 # (new code) * (new code)
*
Example: Master code of 4321/relay time of 10 seconds Press 10 # 1 # 4321 * 4321 *
3. Add/change user code
Press
(user number) # (new code) * (new code)
*
4. Add/change user code to toggle main relay
1
Press
(00) # (user number) # (new code) * (new code)
*
5. Delete user codes
Press
(user number) #
* *
6. Turn keypress feedback/audible keypress on
Press
30 # 0 # 1 #
* *
7. Turn keypress feedback/audible keypress off
Press
30 # 0 # 0 #
* *
8. Turn yellow LED/sounder on with relay
Press
30 # 1 # 1 #
* *
9. Turn yellow LED/sounder off with relay
Press
30 # 1 # 0 #
* *
10. Turn auto entry on
Press
30 # 2 # 1 #
* *
11. Turn auto entry off
Press
30 # 2 # 0 #
* *
12. Turn keypad active on
2
Press
43 # 0 # 99 #
* *
13. Turn keypad active off
Press
43 # 0 # 00 #
* *
14. Set propped door time
3
Press
44 # (time) # 0 #
* *
15. Set forced door relay time
3
Press
45 # (time) # 0 #
* *
16. Erase keypad memory/reset defaults
Press
46 # 00000 # 00000 #
* *
NOTES:
1
Time must always be represented by 2 digits. Example: 5 seconds = 05. Latching /toggle is accomplished by entering a time of 00
2
Keypad active is a negative voltage output (sink) available on terminal (or wire) marked WB (see wiring diagrams for location).
3
Propped Door and Forced Door times must be programmed in intervals of 10 seconds. ie. 10, 30, 60, ... up to 900 seconds.Forced door time of 00 will latch output, until reset by code.
INTERNATIONAL ELECTRONICS, INC.
427 TURNPIKE STREET, CANTON, MA
02021
U.S.A.
800-343-9502 , 617-821-5566
617-821-4443 (FAX)
SELF CONTAINED ACCESS CONTROL SYSTEM STYLES:
232i-INDOOR STYLE
Flushmount indoor design. 232w-WEATHER RESISTANT STYLE
Flushmount outdoor design. 232r-RUGGEDIZED STYLE
Weatherproof self-contained metal housing.
Vandal resistant.
Cast metal housing suitable for wall, post or
gooseneck mounting.
Available in White or Black. 232se-SEALED ENVIRONMENTAL STYLE
Weatherproof self-contained metal housing.
Vandal resistant.
Small design suitable for residential, commercial
and industrial applications.
232m-MULLION STYLE
Weather resistant metal housing.
Two-piece design with secured electronics.
Narrow housing suitable for aluminum
door frame mounting.
Available in Bronze or Satin Aluminum. 233 CARD READER SYSTEM
Weatherproof metal housing.
Two-piece design with secured electronics.
Narrow style suitable for aluminum door frame mount-
ing.
Uses any ABA standard track II magstripe card.
120 users.
234 KEYPAD CARD READER SYSTEM
Weatherproof metal housing.
Uses any ABA standard track II magstripe card.
Access via card, keypad or both.
60 users.
ACCESSORIES:
DATA LOGGING
IEI-250 P tion
inputs and outputs for up to 8 Door•Gard
Keypads. Interfaces
with any parallel printer for user/door activity logging.
INSTALLATION
IEI-280 WEATHERPROOF SURFACE BACK BOX.
IEI-281 F
IEI-290 12 VDC
IEI-293 T
relays.
Converts transistor outputs to dry contacts (for use
with
Command and Control indoor, weather resistant and
mullion
styles).
OTHER DOOR-GARD PRODUCTS FROM IEI
CONTROL PANEL INTERFACE SERIES COMMAND & CONTROL SERIES KEYPADS Please call to request more information.
LIMITED WARRANTY
International Electronics, Inc. (IEI) warrants its products to be free from defects in material and workmanship, when they have been installed in accordance with the manufacturer’s instructions, and have not been modified or tampered with. IEI does not assume any responsibility for damage or injury to person or proper­ty due to improper care, storage, handling, abuse, misuse, normal wear and tear, or an act of God.
IEI’s sole liability is limited to the repair or (at IEI’s option) the replacement of
the defective product or part when sent to IEI’s facility (freight and insurance
RINTER INTERFACE
provides power, communica-
LUSH MOUNT BACK BOX
PLUG-IN POWER SUPPLY
HREE RELAY PLUG--IN BOARD
.
FAX INFORMATION CENTER 617-821-0734 (FROM YOUR FAX MACHINE)
. 300MA.
with FORM C, 1 Amp
MAGNETIC STRIPE CARDS – Track II encoded, low coercivity cards.
IEI-2010 Pack of 10 cards.
IEI-2025 Pack of 25 cards.
TAMPER PROTECTION
IEI-282 T
IEI-283 S
(included)
AMPER SWITCH ECURITY MODULE
detects faceplate removal.
responds to tamper switch
and cuts all in/out power to the door lock. Wires can’t
be
crossed to unlock door. Must be reset from inside the protected area.
IEI-289 T
IEI-267 1/4”
IEI-270
ADAPTER SOCKET
IEI-288 T
charges prepaid), after first obtaining IEI’s Return Merchandise Authorization.
IEI will not be liable to the purchaser or anyone else for incidental or conse-
quential damages arising from any defect in, or malfunction of, its products.
This warranty shall expire two years after shipping date for DOOR-GARD
keypads.
Except as stated above, IEI makes no warranties, either express or implied, as to any matter whatsoever, including, without limitation to, the condition of its products, their merchantability, or fitness for any particular purpose.