Thank you for choosing a DOMUSA TEKNIK heating boiler. From the range
of DOMUSA TEKNIK products you have chosen the Lignum NG model.
With a suitable hydraulic installation and with firewood for fuel, this highefficiency wood boiler will provide the ideal level of comfort for your
home.
This manual forms an essential part of the product and it must be given to
the user. We recommend you read the warnings and recommendations in
the manual carefully, as they contain important information on the safety,
use and maintenance of the installation.
These boilers must be installed by qualified personnel only, in accordance
with the legislation in force and following the manufacturer's instructions.
Incorrect installation of these boilers could result in damage to people,
animals or property, and the manufacturer will hold no liability in such
cases.
CONTENTS Page
1 LIST OF COMPONENTS ..................................................................................................................................................... 2
2 CONTROL COMPONENTS ................................................................................................................................................ 3
FUEL: PREPARING THE FIREWOOD ....................................................................................................................................................... 5
3.3
IGNITION AND POSITIONING OF THE FIREWOOD ................................................................................................................................ 7
DHW TANK ELECTRICAL CONNECTION (OPTIONAL). ..................................................................................................................... 9
3.7.1
EXAMPLE OF AN INSTALLATION WITH A BUFFER TANK .................................................................................................................... 10
3.8
EXAMPLE OF AN INSTALLATION WITH A BUFFER TANK AND DHW TANK....................................................................................... 11
3.9
4 ADJUSTING THE COMBUSTION AIR .......................................................................................................................... 12
5 TEMPERATURE RELIEF SAFETY VALVE ..................................................................................................................... 13
6 STARTING UP THE BOILER ............................................................................................................................................ 14
FILLING THE INSTALLATION ................................................................................................................................................................ 14
INSTALLATION HAND OVER ................................................................................................................................................................ 15
6.4
7 DIGITAL DISPLAY AND SELECTING PARAMETERS ............................................................................................... 16
8 BOILER MAINTENANCE AND CLEANING ................................................................................................................. 18
8.1
CLEANING THE BOILER ....................................................................................................................................................................... 18
TAR ................................................................................................................................................................................................... 18
DRAINING THE CONDENSATION WATER ........................................................................................................................................ 19
8.2.1
BOILER WATER CHARACTERISTICS .................................................................................................................................................. 19
SAFE HANDLING OF ASHES ............................................................................................................................................................. 20
8.3.1
HAZARDS RELATED TO THE DOOR OF THE FUEL LOADING CHAMBER. ........................................................................................ 20
8.3.2
9 SHUTTING DOWN THE BOILER ................................................................................................................................... 21
9.1
DETECTION OF LACK OF FUEL ............................................................................................................................................................ 21
14 SPARES LIST .................................................................................................................................................................... 26
Used to stop the fan and, as a result, the
combustion adjustment. Also used to reduce
the values of the selected Menu settings.
3. START button (and increase value):
Activates the fan and the combustion
adjustment. Also used to increase the values of
the selected Menu settings.
4. Main switch:
Turn on the controller.
5. Fuse carrier:
It protects the controller and the elements
dependent on the controller. It is recommended
that a porcelain, slow-blow, 5x20mm, 3.15A
nominal current fuse be used.
3
Lignum NG
3 INSTALLATION INSTRUCTIONS
The boiler must be installed by personnel authorised by the Ministry of Industry, in compliance with
the applicable laws and regulations.
This boiler is suitable for heating water to a temperature below boiling point at atmospheric pressure.
It must be connected to a heating buffer tank, which must always be compatible with its performance
and power.
This appliance must only be used for the purpose for which it has been expressly designed. Any other
use is considered unsuitable and therefore hazardous. The manufacturer shall not be considered liable
under any circumstances for damage caused by unsuitable, erroneous or irrational use.
Remove all the packaging and check the contents are complete. In case of doubt, do not use the
boiler. Contact your supplier. Keep the packaging elements out of reach of children, as they can be
dangerous.
When you no longer wish to use the boiler, disable the parts that could represent a potential hazard.
3.1 Location
The boiler must be installed in a sufficiently ventilated site, away from humidity. It must be located
so that the air grilles on the premises are not obstructed and normal boiler maintenance is possible.
It must be kept a minimum distance of 1 m from the fuel tank or install a radiation protection plate.
The boilers must not operate on flammable surfaces. The boiler must have an external combustion
air supply (minimum opening 300 cm2).
Generally, it is not recommended to install boilers of up to 50 kW in stairways, living areas, corridors
or garages. Similarly, installing boilers in locations with ventilation, fans, extractor fans, air
extraction systems, etc. should be avoided (e.g. tumble dryer extraction). It must be kept a
minimum distance of 0.4 m from flammable building materials so as to not reach surfaces
temperatures above 85°C.
3.2 Hydraulic installation
The hydraulic installation must be made by qualified personnel. The applicable installation
legislation (RITE) must be complied with, and the following recommendations should also be taken
into account:
- It is obligatory and essential to install a heating water buffer tank (see “
installation with buffer tank”).
based on Standard EN 303-5.
- It is obligatory and essential to install a device for raising the return temperature, to prevent
any water condensation in the heat exchanger. If this requirement is not complied with,
DOMUSA TEKNIK's guarantee of the appliance will automatically be null and void.
The minimum volume of the buffer tank must be calculated
Example of
- It is obligatory and essential to install the temperature relief valve supplied with the boiler.
To correctly install the boiler, carefully follow the instructions given in the section "Installing
the temperature relief valve" . If this requirement is not complied with, DOMUSA TEKNIK's
guarantee of the appliance will automatically be null and void.
- The inside of the installation piping should be thoroughly cleaned before switching on the
boiler.
- We recommend inserting cut-off valves between the installation piping and the boiler to
simplify maintenance tasks.
4
- Leave a free space around the boiler for carrying out any maintenance and repair operations.
- Drain valves and suitable devices for correctly bleeding the air from the circuit during the boiler
filling stage should be fitted.
- Install all the necessary safety elements (expansion vessel , safety valve, etc.) to comply with the
applicable regulations for the installation.
3.3 Fuel: preparing the firewood
Firewood is the fuel which must be used for the Lignum NG boiler. If this requirement is not
complied with, DOMUSA TEKNIK's guarantee of the appliance will automatically be null and void.
The quality of the fuel plays an important part in the performance and useful life of the boiler. The
firewood must have less than 20% water content (humidity). If the percentage of water is too high,
the corrosion inside the boiler increases and the boiler performance is drastically reduced.
"Green" wood (recently cut) may contain over 50% humidity. Its caloric power is approximately half
of that of "seasoned" wood with 15% humidity. The greater the humidity of the wood, the slower
the combustion and the lower the flame temperature. This abruptly increases the amount of soot
and tar in the fumes.
To reach dry levels in the air (<20%), the following drying times are recommended:
- Oak: 2.5 years
- Beech, ash, fruit trees: 2 years
- Linden, alder, birch: 1.5 years
- Pine, poplar, spruce: 1 year
If the wood is not cut (round wood), a minimum of 2 extra months are required.
In addition to the cutting, another important factor is the physical size of the firewood. In relation
to its mass, smaller firewood has a greater surface than larger pieces of wood. It is easier to ignite
and its combustion is quicker. Large firewood may slow down combustion due to an unfavourable
volume/surface area ratio. This, unavoidably, implies a lower flame temperature and greater
contaminant emissions.
The following sizes of firewood are those recommended for a perfect and homogeneous service in
the combustion chamber:
For Lignum NG 20, Lignum NG 30 and Lignum NG 40 boilers, the recommended log length is 50
cm. If the logs are short, it is recommended that they be placed lengthwise in the back part and
that the free space at the front be filled with logs placed obliquely.
5
Lignum NG
Make sure the logs in the fuel loading compartment do not get stuck (avoid logs which are too
long). If the logs are too long, they do not fall properly and can cause gaps, causing a drop in the
boiler power. In order to avoid this, it may be necessary to cut the total length in half.
Place the rounded part of the logs facing down, to avoid any wedging effect.
If using briquettes, they must have a diameter of 6 to 10 cm. Their use is only recommended in
combination with firewood.
Pay special attention to the energy density of the firewood, as a full load of pine wood is equivalent
to 2/3 of a load of beech wood and to ½ a load of briquettes.
6
3.4 Ignition and positioning of the firewood
How the firewood is loaded into the housing is very important for an optimised combustion
process. It is recommended that the firewood be inserted into the loading compartment as follows:
Insert thick pieces of wood or stumps in the top area
only
4th Layer: Medium firewood
- Load the necessary amount in the compartment
3rd Layer: Ignition material
- Thick chippings, small chippings
2nd Layer: Paper, cardboar d
Chippi
- Ignite evenly throughout the compartment
Ignition
tunnel
Grill
opening
1st Layer: Small firewood
- Do not place im me diately on top of the grill opening
- Place the chippings crosswi s e o n top of the first l aye r
IMPORTANT: If there is no charcoal from a previous firewood load, put the first layer (at the bottom
of the fireplace) with abundant wood, as dry as possible, to obtain the proper amount of charcoal
(approximately 10 zm).
3.4.1 Ignition tunnel
The ignition tunnel allows the combustion air to flow during ignition. Therefore, do not place any
combustion material on top of the opening of the grill during the ignition, leaving the ignition
tunnel free of obstacles.
3.4.2 Paper, cardboard and kindling
The fire should be lit with paper, cardboard and/or kindling. The cardboard should be placed
evenly on top of the ignition tunnel, across the entire surface of the first layer of small logs. If the
cardboard used is small, distribute it in paper ball shapes. The kindling must be placed crossways
under the cardboard.
The ignition process is manual and must be performed as follows:
- Partially load the combustion chamber with small dry logs and paper, cardboard or wood
chips.
- Turn the boiler on and press START to start up the induced draught fan.
- Light a paper ball using a match or a lighter.
- The lit paper is placed with the paper/cardboard on top of the ignition tunnel. The door can
be kept slightly open to ease ignition.
7
Lignum NG
- Once the fire has spread and embers have formed, distribute them evenly, add the rest of
the load on top and fully close the doors.
- The control automatically regulates the combustion process.
3.4.3 Sawn wood (planks)
Sawn wood can be used in a similar way to kindling to ease ignition above the tunnel. The
planks should not be placed too close to each other, so that air circulates during ignition. It is
recommended that at least 1 cm be left between planks.
3.4.4 Thick wood or stumps
Thick wood or tree stumps (part of the trunk joined to the root) can be placed on the top layer,
on top of several layers of firewood. Do not use more than one oversized piece of firewood or
stump in the same load.
3.4.5 Thick kindling and woodworking waste
Thick kindling (G100, > 100mm), small material, woodworking waste, etc. must only be placed in
the loading compartment on top of at least three layers of firewood (approximately half of the
combustion chamber).
3.5 Unsuitable fuel
- Wood with >20% humidity.
- Waste, plastics
- Paper and cardboard (only for ignition).
- Sawdust, wood shavings.
- Small kindling.
- Coal.
- Material generally forbidden by legislation regarding atmospheric contamination and air
quality, such as treated wood, beams, etc.
3.6 Combustion product removal
The Lignum NG boiler is a biomass boiler and it is essential for it to be connected to a flue, i.e. a
smoke duct able to create a pressure drop (which in this case should be between 0.10 and 0.20
mbar), in compliance with the applicable laws in this regard.
The combustion product exhaustion ducts must be installed by qualified personnel and must
comply with the regulations in force. For the flue to create a pressure drop, the following
recommendations should be taken into account:
- It should be suitably insulated.
- It should be independently located, with a separate flue for each boiler.
- It should be vertical, avoiding any angles greater than 45º.
8
- It should always have the same diameter. It is recommended that it be circular, and never any
narrower than the boiler outlet.
- It is obligatory to install a fume inspection plate with condensation collection, to remove the condensation generated in the flue. Otherwise, the condensation may reach the inside of
the boiler and cause irreparable damage, which would not be covered by DOMUSA TEKNIK's
guarantee. The condensation pipe should lead to a drain outlet, as a large amount of water
may be generated. This connection must be made in compliance with the regulations for
draining off condensation water to the drain system.
- It is recommended that a draught stabiliser be installed to prevent any pressure drop
variations in the flue due to atmospheric conditions, which could affect correct boiler
combustion. This draught stabiliser must be installed below the fume inspection plate to
prevent any leakage of combustion gases.
3.7 Electrical Connection
The Lignum NG boiler must be connected to 230 V~ ac 50 Hz by the connector labelled “220V AC”
on the back of the boiler. The socket should have an appropriate earth connection.
The circulating pump must be connected to the 3-pin connector “
”on the back of the boiler,
on the side opposite the connection to the mains electrical supply.
3.7.1 DHW tank electrical connection (optional).
If there is an optional DHW tank, connect the DHW 3-way diverter valve in the 3-pin connector
“
Diagram"
”. Connect the DHW temperature sensor in the controller, as indicated in the
.
The hydraulic installation for the 3-way DHW diverter valve should be made so that the heating
circuit (buffer tank) can flow through the valve when it is idle (not powered):
BOILER
HEATING
NA / NO
NC
V3V
"Electrical
DHW
9
Lignum NG
IMPORTANT: Before carrying out any work on the boiler's electrical installation, always ensure
it is disconnected from the mains.
IMPORTANT: Make sure that none of the mains cables come into contact with a hot surface
(e.g. flue).
3.8 Example of an installation with a buffer tank
The Lignum NG boiler is equipped with an electronic control that can govern a circuit with buffer
tank, with an external circulation kit to prevent condensation in the heat exchanger. The heating
circuit must be regulated and controlled with an external regulator (not included in the boiler
control).
The figure below shows an example of a hydraulic diagram of a buffer tank heating installation:
IMPORTANT: It is obligatory and essential to install a heating water buffer tank.
10
BT: Buffer tank VDT: Temperature relief
valve
VC: Heating expansion vessel
BCD: Direct circuit pump
BCM: Mixed circuit pump
P: Automatic air bleed valve
3.9 Example of an installation with a buffer tank and DHW tank
The Lignum NG boiler is equipped with an electronic control that can govern a buffer tank circuit,
with an external circulation kit to prevent condensation in the heat exchanger and, optionally, a
DHW tank loading circuit.
To control a DHW circuit, connect a DHW sensor from the hot water tank to the boiler (optionally
supplied by DOMUSA TEKNIK) and a 3-way diverter valve (see
"Electrical Diagram
”).
The figure below shows an example of a hydraulic diagram for a heating installation with radiators
and a DHW tank:
V3V: 3-way valve
VC: Heating expansion vessel
BCD: Direct circuit pump
BCM: Mixed circuit pump
P: Automatic air bleed valve
IMPORTANT: It is obligatory and essential to install a heating water buffer tank.
11
Lignum NG
4 ADJUSTING THE COMBUSTION AIR
The various stages of combustion (drying, pyrolysis, gasification and combustion) of the Lignum NG
wood boiler take place in a controlled manner in different parts of the boiler.
The wood dries and decomposes in the loading compartment via the technique known as "inverted
draught", generating a combustible gas. The heat required for the decomposition reactions (pyrolysis
and gasification) is provided by the partial combustion of the firewood. The air necessary for the
gasification is called primary air.
The gas produced in the housing is mixed with the preheated secondary air and generates an
extremely high temperature combustion in the refractory chamber, reducing emissions and
increasing the boiler efficiency.
The induced draught fan supplies the primary and secondary air to the boiler by suction.
The air regulators or the boilers are set by default to optimal conditions for obtaining suitable fume
temperatures and emissions. Therefore, the initial air setting of the boiler should not be modified.
12
5 TEMPERATURE RELIEF SAFETY VALVE
In order to avoid the temperature inside the boiler reaching damaging levels, this valve opens and lets
the mains water supply pass into the interior coil, thereby dispelling the heat in a fully reliable manner.
This occurs when, for hydraulic reasons or due to lack of electric current, the boiler cannot dispel the
heat it is generating. This valve is obligatory in Lignum NG boiler installations.
5.1 Operating principle
The valve is regulated by the hot water from the boiler. If the water temperature is greater than
95ºC, the valve opens and lets the mains water through. This water moving in the coil absorbs the
boiler temperature and this prevents overheating and any damage to the boiler. The boiler
protection system corresponds with Standard EN 303-5.
5.2 Valve assembly
The temperature relief valve must be connected with free discharge to the safety heat exchanger
(in accordance with Standard EN 12828). The connection must not be blocked manually.
Furthermore, access must be granted to the heat protection mechanism and to the cleaning
inspection, once assembled. The minimum connection pressure for the safety heat exchanger is 2
bars. The nominal pressure of the valve is 5 bars.
The temperature relief valve is installed up-current of the coil (placed respecting the flow direction
according to the arrow on the coil). The mains water supply must be connected directly to the
temperature relief valve. The connection is threaded, type Rp 3/4" (DIN EN 10226).
IMPORTANT: It should not be possible to close the supply pipe so as to avoid any accidental
blockage.
IMPORTANT: The cold water pressure should not depend on the electricity supply.
IMPORTANT: The pipe must be thoroughly washed before installation.
13
Lignum NG
6 STARTING UP THE BOILER
6.1 Prior warnings
Repair and maintenance of the boiler must be carried out by a qualified professional, authorised by
DOMUSA TEKNIK. For optimum functioning and conservation of the boiler, it should be serviced
annually.
Carefully read this instruction manual and keep it in a safe, easily-accessible place. DOMUSA TEKNIK will not be liable for any damages caused by failure to follow these instructions.
During some of the operating phases, a forced noise may be heard for a few minutes. This is normal
and does not affect the boiler's integrity in any way.
Before any servicing, disconnect the boiler from the mains.
6.2 Filling the installation
The hydraulic installation must include a fill valve, a manometer, a safety valve, drain valves and the
necessary hydraulic components for correctly filling the installation.
To fill the installation, open the fill valve until the installation manometer shows a pressure of 1 - 1.5
bars. The installation must be filled slowly, bleeding the air from the water circuit using the drain
valves provided for this purpose. Close the fill valve after filling.
IMPORTANT: Switching on the boiler with no water inside could result in serious damage.
6.3 Start-up
Before beginning the start-up process, the following must be complied with:
- The boiler must be connected to the mains.
- The installation must be filled with water (the pressure must be between 1 and 1.5 bar).
The following steps are obligatory in the start-up sequence:
- Remove the cleaning brush and the rake supplied with the boiler.
- Check the flue is correctly installed using the condensation inspection plate and a draught
stabiliser
- Check the external hydraulic anti-condensation kit is correctly installed.
- Check that the temperature relief valve is properly installed.
- If the installation has flow and return valves, check they are open.
- Set the installation type parameter (see “
The value is 04 if there is a buffer tank without a DHW tank.
The value is 02 if there is a buffer tank and a DHW tank.
- Set the boiler adjustment mode parameter (see “
The recommended value is 02.
14
Digital display and selecting parameters"
):
Digital display and selecting parameters"
):
6.4 Installation hand over
After the initial start-up, the installation engineer will explain to the user how the boiler works,
making any observations they consider relevant.
The installer is responsible for clearly explaining to the user the functioning of any control or
regulation device forming part of the installation but not supplied with the boiler.
15
Lignum NG
7 DIGITAL DISPLAY AND SELECTING PARAMETERS
The Lignum NG boiler is equipped with a digital touch display for viewing and adjusting the different
boiler settings. The various parameters displayed on the main screen are described below.
The various parameters displayed on the screen are described in the table below. You can browse
through the parameters by pressing the "F" button:
Selecting the boiler set-point temperature, T1.
Default value (recommended): 80ºC
If the DHW sensor is connected and the hydraulic installation type selected
includes a DHW tank, after selecting the boiler temperature and pressing the F
button, the DHW set-point temperature must be selected, T2 (only valid for
installation with DHW tank ).
Default value: 55ºC
After pressing the F button again, select the fume set-point temperature, T3 (only
valid for Adjustment Mode 03).
Recommended value: 180ºC
Ventilation time during periods with no heat demand.
Default value (recommended): 10 s
Ventilation interval during periods with no heat demand.
Default value (recommended): 5 min
Maximum fan speed.
Default value (recommended): 99%
16
Minimum fan speed.
Recommended value: 50%
Settings for hydraulic installation type.
When the Lignum NG boiler is installed with a buffer tank (see
installation with buffer tank
), the value of this parameter must be 04.
Example of
If there is a buffer tank and a DHW tank (see
tank and DHW tank
tank, a domestic hot water temperature sensor (see
way valve must be connected in the "
IMPORTANT: Hydraulic installation types 01 and 03 are not operational in
Lignum NG boilers.
Boiler adjustment mode. There are 3 options:
To select the parameters, press "F". Use the “+” and “-“ buttons to increase or reduce the value of the
selected parameter (the value will be flashing). Check that the value shown on the boiler temperature
set-point indicator is the one desired.
- Classic Adjustment. 01
- PID adjustment based on the boiler temperature adjustment. 02
- PID adjustment based on the fume temperature adjustment. 03.
Recommended parameter: 02 (PID adjustment based on boiler temperature)
Service menu symbol.
), the selected parameter is 02. In order to work with a DHW
Example of installation with buffer
Electrical Diagram
" connector (see
Electrical Connection
) and a 3-
).
IMPORTANT: If the fume temperature is selected as an adjustment parameter, it must be taken into
account that the real value is 10 times greater than that selected. For example 20ºC
means 200ºC.
17
Lignum NG
8 BOILER MAINTENANCE AND CLEANING
8.1 Cleaning the boiler
8.1.1 Ashes
The ashes must be cleaned out regularly and properly after every 3 or 5 loads of firewood,
depending on the type of wood. The ashes accumulate in both the loading compartment and
the refractory combustion chamber and in the flue. The ash could be deposited in the ash box.
To clean the boiler, follow these steps:
- The boiler must be cold before cleaning. Wait 2-3 hours after all the fuel has been finished.
- Open the top loading door, clean the ashes through the hole in the refractory burner using the
cleaning rake provided with the boiler. We recommend that you save part of the ashes and
carbonised wood to make it easier to light the next time. Avoid scraping the rake on the
middle refractory part in order to avoid abrasion of the part.
- Close the top loading door and open the bottom front door. Remove the ashes that have built
up inside the combustion chamber and surrounding areas.
- Clean the flue by moving the lever towards the boiler approximately 10 times. Perform full 90º
cycles.
NOTE: The flue cleaning lever can be placed on the opposite side of the boiler. To do so,
remove the sides, the back part of the roof and the flue lid, loosen the lever and the arm of
the cleaning axle, remove the axle and place it in the reverse position.
8.1.2 Tar
Clean the tar from the metal surface of the fuel loading chamber using the scraper. The
gasification process produces tar and the amount will depend on the type of wood, its humidity
and the water inlet and outlet temperatures. It is recommended that it be cleaned once a month,
although the frequency may vary depending on the type of wood used.
18
8.2 Boiler maintenance:
Various maintenance operations should be carried out at different intervals to keep the boiler in
perfect working order.
The most important aspects to be checked are as follows:
No. Operation Frequency
Clean ashes from the loading compartment, combustion chamber and
1.
flue.
2. Check the boiler visually. weekly
3. Clean tar from the loading compartment monthly
4. Clean the windows of the peep-holes with alcohol visual control
Clean all exchange surfaces: flue, fume chamber, etc. You can use the
5.
cleaning brush for scraping and descaling any embedded tar or ashes.
Check and clean the flue. The flue must be free of any obstacles and have
6.
no leaks.
7. Check the expansion vessel. It must be full, according to its reference plate. yearly
8. Check the air-tightness of the housing doors. yearly
Check the water pressure in the heating installation. In cool mode, it
9.
should be between 1 - 1.5 bars.
8.2.1 Draining the condensation water
3-5 loads of
firewood
yearly
yearly
yearly
Draining of condensation water from the flue should not be altered in any way and it must be
kept free of obstructions.
8.2.2 Boiler water characteristics
In areas with water hardness exceeding 25-30ºfH, treated water must be used in the heating
installation to avoid any scale deposits on the boiler. It should be noted that even a few
millimetres of lime-scale will greatly reduce the boiler's heat conductivity, causing a significant
decrease in its performance.
Treated water must be used in the heating circuit in the following cases:
- Very large circuits (containing a large amount of water).
- Frequent filling of the installation.
If repeated partial or total draining of the installation is necessary, we recommend filling it with
treated water.
19
Lignum NG
8.3 Safety warnings:
8.3.1 Safe handling of ashes
For safe handling of the ashes, you should take the necessary safety precautions and wear
suitable clothing to protect against possible injury. The following advice should be particularly
taken into account:
- Shut down the boiler operation before removing the ashes.
- It is recommended to wear heatproof "thermal gloves" to protect your hands from any burns
from hot parts of the drawer.
- It is recommended you wear a "protective mask" to avoid breathing in any ash particles,
particularly in the case of people with allergies or any type of respiratory trouble, who should
always wear a mask when carrying out ashes.
- As the ash to be removed may be burning or glowing, special precautions should be taken with
regard to the type of container it is emptied into. A metal container is recommended, or the ash should be totally put out at the time of handling, using water or another extinguishing
agent.
DOMUSA TEKNIK shall not be liable for any damage caused to people, animals or property as a
result of incorrect handling of the ash drawer or the ash itself.
IMPORTANT: The ash clearance must only be undertaken when the boiler is switched off.
8.3.2 Hazards related to the door of the fuel loading chamber.
To avoid hazards related to the door of the fuel loading chamber, take the following advice into
account:
- If opening the fuel load ing door when there is combustion in the housi ng, do so carefully. First
open very slightly. Keep your body and face away from the fuel loading door.
- Close the door of the fuel loading chamber immediately after performing the control of the
fuel load amounts or after having reloaded fuel.
- The danger of deflagration increases after uncontrolled conditions in the installation (power
cut).
- Let the installation cool down before opening it.
- Do not open the door of the combustion chamber during/after a power cut.
- The flames can cause damage to the control unit.
- Inspect the doors and joints of the installation in search of possible leaks.
20
9 SHUTTING DOWN THE BOILER
To stop the boiler, press the "STOP" button. In shut-down mode, the fan stops working. To shut down
boiler operation completely, unplug it from the mains.
9.1 Detection of lack of fuel
The controller automatically detects the lack of fuel. When the fuel runs out, the message AL1
appears on the screen.
After detecting the lack of fuel, the circulating pump and the fan are deactivated so as to avoid any
heat loss in the buffer tank. In this case, if no additional load of wood is desired, the controller can
be turned off. The “AL1” alarm can be cancelled by pressing the “START” button or after turning the
controller on and off.
NOTE: If the lack of fuel is detected too quickly or too slowly, call the Technical Support Service
to check and modify the controller values.
CO at maximum power (10% of O2)
NOx at maximum power (10% of O2)
mg/m
mg/m3
317 238 231
161 141 199
Classification (as per EN 303-5) - Class 5 Class 5 Class 5
Maximum operating pressure bar 3
Fume temperature ºC 150 - 200
Control temperature range ºC 65 - 80
Minimum return temperature ºC 55
Safety thermostat temperature ºC 97
Boiler water volume litres 90 104 114
Water pressure drop (∆T=10ºC) mbar 39 22 44
Water pressure drop (∆T=20ºC) mbar 11 6 11
mbar 0.01
Minimum flue draught
Pa 10
Electrical supply - 230 V~, 50 Hz
Average electrical consumption in nominal
power
W 57 64 70
Average electrical consumption in Standby W 3
Fume outlet diameter mm 125 -130 146-150
Weight (net)
Kg 385 425 450
22
11 DIAGRAMS AND MEASUREMENTS
Lignum NG
MODEL
Boiler height (A) mm 1060 1210 1310
Total height (B) mm 1165 1315 1415
Feeder connection height (C) mm 1137 1287 1387
Fumes outlet connection (D) mm 125-130 146-150
Chimney connection height (E) mm 715 865 955
Height of the Safety Heat Exchanger (F) mm 975 1125 1225
Lignum NG
20
Lignum NG
30
Lignum NG
40
23
Lignum NG
12 ELECTRICAL DIAGRAM
yellow-green
yellow-green
yellow-green
yellow-green
brown
Red
Lamp
DS
NO
C
blue
STB
NC
yellow-green
9 1011121314151617181920
ecoSTER200
D+
ecoMAX 200
1
2
C
blue
blue
blue
brown
Mains
STB
230 V~
230 V~
AN AL BN BL CN CL
LN12345678
yellow-green
yellow-green
blue
Male
L1
N
Female
blue
brown
FemaleMale
N
Black Socket
blue
MaleFemale
L1
N
Black Socket
brown
L
White Socket
°C
D-
+5V
red
T3 T2
GND
red
blue
MaleFemale
N
T1
2,7 μF
Capacitor
brown
L
White Socket
Central
blue
black
brown
M
Heating Pum p
Fan
LN
Mains
230 V~
clockwise seen from
the rotor side
L: Phase.
N: Neutral. C: Common.
GND: Earth.
T1: Boiler sensor.
T2: DHW sensor.
T3: Fume temperature sensor. : Room thermostat (not operative in the Lignum NG boilers).
STB: Safety thermostat (100ºC).
DS: Door switch.
NO: Normally open port.
NC: Normally closed port.
DHW Tank
Pump
24
13 SENSOR VALUES
The table below shows the electrical resistance values for each temperature on the sensors connected
to the boiler. To correctly measure these values, the sensors must be electrically disconnected from
their corresponding terminal block:
If there are significant differences with regard to the values in the table, the sensor must be changed.
25
Lignum NG
14 SPARES LIST
Boiler
No.CodeDescription
1
2
3
4
5
6
7
8
9
CLIG000163
10
CLIG000111
Top door
Bottom door
LIGNUM NG coil
Gas flue cleaning system
Fan
Controller
Bottom back part
Outside
Refractory parts
Air adjustment LIGNUM NG 20/30
Air adjustment LIGNUM NG 40
26
Top door
No.CodeDescription
LIGNUM NG 20 top door seal
LIGNUM NG 30 top door seal
LIGNUM NG 40 top door seal
LIGNUM NG door hinge
LIGNUM NG door handle assembly
LIGNUM NG Bakelite arm
LIGNUM NG door fixing
LIGNUM NG handle shaft
LIGNUM NG Door lock
LIGNUM NG door lock pin
LIGNUM NG upper front door with refractory LIGNUM NG 20
LIGNUM NG upper front door with refractory LIGNUM NG 30
LIGNUM NG upper front door with refractory LIGNUM NG 40
LIGNUM NG 20 bottom door seal
LIGNUM NG 30/40 bottom door seal
LIGNUM NG peep-hole
LIGNUM NG peep-hole casing
LIGNUM NG rake
LIGNUM NG ash box
LIGNUM NG 20 bottom front door with refractory
LIGNUM NG 30/40 bottom front door with refractory
28
Coil
No.CodeDescription
3.1
3.2
3.6
3.8
CLIG000016
CLIG000017
CLIG000019
CLIG000131
LIGNUM NG cooling heat exchanger
LIGNUM NG Temperature relief valve
LIGNUM NG Temperature relief valve casing
LIGNUM NG Temperature relief valve seal
29
Lignum NG
Gas flue cleaning system
No. Code Description
CLIG000132
4.1
CLIG000133
CLIG000134
4.2
CLIG000026
4.3
CLIG000135
4.4
CLIG000030
4.5
CLIG000031
LIGNUM NG 20 turbulator
LIGNUM NG 30 turbulator
LIGNUM NG 40 turbulator
LIGNUM NG turbulator axle
LIGNUM NG cleaning axle
LIGNUM NG cleaning arm
LIGNUM NG cleaning handle
No.Code Description
4.8
4.9
4.11
4.14
4.15
CLIG000032
CLIG000034
CLIG000136
CLIG000137
CLIG000042
LIGNUM NG cleaning axle arm
LIGNUM NG cleaning axle support
LIGNUM NG flue lid
LIGNUM NG flue lid insulation
LIGNUM NG cleaning brush
30
Fan
No.CodeDescription
5.1
5.4
RLIG000113
RLIG000114
CLIG000046
LIGNUM NG fan
LIGNUM NG fan cover box
LIGNUM NG fan gasket
31
Lignum NG
Controller
No.CodeDescription
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.11
6.12
6.13
CLIG000048
CLIG000049
CLIG000050
CLIG000051
CLIG000052
CLIG000053
CLIG000138
CFOV000151
CLIG000114
LIGNUM NG controller
LIGNUM NG safety thermostat
LIGNUM NG fumes sensor
LIGNUM NG boiler sensor
LIGNUM NG DHW sensor
LIGNUM NG controller light
LIGNUM NG controller housing
LIGNUM NG capacitor
LIGNUM NG capacitor terminal
LIGNUM NG door switch
32
Bottom back part
No.CodeDescription
7.1
CLIG000139
7.2
CLIG000140
LIGNUM NG back part
LIGNUM NG back door insulation
LIGNUM NG front roof
LIGNUM NG back roof
LIGNUM NG 20 left side
LIGNUM NG 30 left side
LIGNUM NG 40 left side
LIGNUM NG right side
LIGNUM NG right side
LIGNUM NG right side
LIGNUM NG top door
LIGNUM NG top door
LIGNUM NG top door
LIGNUM NG 20 bottom door
LIGNUM NG 30/40 bottom door
LIGNUM NG 20 bottom back
LIGNUM NG 30 bottom back
LIGNUM NG 40 bottom back
LIGNUM NG coil cover
3-pin socket connector LIGNUM NG
3-pin plug connector LIGNUM NG
LIGNUM NG top refractory element
LIGNUM NG top fibre seal
LIGNUM NG middle refractory element
LIGNUM NG bottom fibre seal
LIGNUM NG 20 bottom refractory element
LIGNUM NG 30/40 bottom refractory element
LIGNUM NG primary air duct
Rear anti-condensates sheet LIGNUM NG 20
Rear anti-condensates sheet LIGNUM NG 30
Rear anti-condensates sheet LIGNUM NG 40
Front left anti-condensates sheet LIGNUM NG 20
Front left anti-condensates sheet LIGNUM NG 30
Front left anti-condensates sheet LIGNUM NG 40
Front right anti-condensates sheet LIGNUM NG 20
Front right anti-condensates sheet LIGNUM NG 30
Front right anti-condensates sheet LIGNUM NG 40
37
Lignum NG
15 ALARM CODES
The Lignum NG boiler has an electronic control able to detect overheating or lack of fuel in the boiler.
When the electronic control detects an operating error, this is indicated by an alarm code on the
display. The table below shows a list of the alarm codes that may appear:
CODE ALARM CAUSE / ACTION
AL1
AL2
AL3
AL4
Lack of fuel alarm
Damage to the boiler
sensor alarm
Boiler overheating
alarm
Fume temperature
sensor alarm
Maximum fume
temperature overrun
Safety thermostat
alarm
When the fuel runs out, this message appears on the screen.
It does not emit an acoustic signal.
This alarm occurs when the boiler temperature sensor does not function
properly or after it has exceeded its measuring range. The alarm activates
the heating pump and an acoustic signal.
The alarm is deactivated once the temperature returns to its measurement
range and after the general switch on the controller is turned off and on.
The Technical Support Service must be called to check and replace the
sensor.
This alarm occurs when the boiler temperature exceeds 90ºC. If this
happens, the fan switches off and the pumps are activated. In addition, an
acoustic signal is emitted.
When the boiler temperature drops, the regulator which controls the boiler
will operate normally.
This alarm occurs when the electronic control detects a failure in the fume
temperature sensor.
The regulator warns the user that the fume temperature is too high when it
exceeds 450ºC. This temperature can be reached if the housing door is left
open or due to a malfunction of the fume temperature sensor.
The alarm is displayed visually and emits a short, acoustic signal.
When the boiler temperature exceeds 100ºC, the safety thermostat (manual
reset) deactivates the fan and the red light on the control panel turns on.
38
16 GUARANTEE CONDITIONS
DOMUSA TEKNIK's commercial guarantee covers normal operation of the products manufactured by
DOMUSA TEKNIK Calefacción S.Coop., in accordance with the following conditions and time periods:
1. This commercial guarantee is valid for the following periods, as from the start-up date:
2 Years for electric and hydraulic elements, pumps, valves, etc.
5 Years for heat exchangers.
During the 2-year period following the date of first start-up, DOMUSA TEKNIK will carry out any
repairs of original flaws or defects totally free of charge.
After these 2 years have elapsed and until the end of the guarantee period, labour costs and callout charges will be payable by the user.
2. The annual service is not included in the terms of this guarantee.
3. The commissioning and annual service are to be carried out by personnel authorised by DOMUSA
TEKNIK.
4. The commercial guarantee will be null and void in the following cases:
- If the annual service has not been carried out by personnel authorised by DOMUSA TEKNIK.
- If the boiler has not been installed in accordance with the applicable laws and regulations for this
type of appliance.
- If the boiler has not been commissioned immediately after its installation, by personnel authorised
by DOMUSA TEKNIK.
Failures due to misuse or incorrect installation, use of non-suitable power or fuel, water supply with
physical or chemical properties causing lime-scale or corrosion, incorrect handling of the appliance
and, in general, for any reason beyond DOMUSA TEKNIK's control, are excluded from this guarantee.
This guarantee does not affect the consumer's rights as stipulated by law.