DOMUSA TEKNIK JAKA 20 HFD CONDENS, JAKA 30 HFD CONDENS Installation And Operation Instruction Manual

INSTALLATION AND OPERATING INSTRUCTIONS
JAKA HFD CONDENS
JAKA HFD CONDENS
JAKA HFD CONDENSJAKA HFD CONDENS
Thank you for choosing a DOMUSA TEKNIK chosen a boiler that, with a suitable hydraulic installation and using oil for fuel, will provide the ideal level of comfort for your home.
This manual forms an essential part of the product and it must be given to the user. Read the warnings and recommendations in the manual carefully, as they contain important information on the safety, use and maintenance of the installation.
These boilers must be installed by qualified personnel only, in accordance with the legislation in force and following the manufacturer's instructions.
The start-up of these boilers and any maintenance operations must only be carried out by Official Technical Assistance Services of DOMUSA TEKNIK
TEKNIK.
TEKNIKTEKNIK
Incorrect installation of these boilers could result in damage to people, animals or property, and the manufacturer will hold no liability in such cases.
DOMUSA TEKNIK
DOMUSA TEKNIK informs all parties concerned that, in compliance with
DOMUSA TEKNIKDOMUSA TEKNIK section 1 of the first additional provision of Law 11/1997, the responsibility for delivering packaging waste or used packaging for its proper environmental management will be that of the final owner of the product (Article 18.1 Royal Decree 782/1998). At the end of its useful life, the product must be taken to a selected collection point for electrical and electronic equipment or must be returned to the distributor at the time of purchasing a new equivalent appliance. For more detailed information on the collection schemes available, contact either the collection facilities of the local authority or the distributor where the purchase was made.
DOMUSA TEKNIK heating boiler. You have
DOMUSA TEKNIKDOMUSA TEKNIK
DOMUSA
DOMUSA DOMUSA
CONTENTS
CONTENTS Page
CONTENTSCONTENTS
Page
PagePage
1 LIST OF COMPONENTS .............................................................................................................................................................................................. 2
2 CONTROL COMPONENTS ......................................................................................................................................................................................... 3
3 INSTALLATION INSTRUCTIONS............................................................................................................................................................................... 4
3.1 L
OCATION
3.2 I
NSTALLATION AND ELECTRICAL CONNECTION OF THE BOILER
3.3 H
3.4 E
LECTRICAL CONNECTION
3.5 F
UEL INSTALLATION
3.6 D
3.7 P
RECAUTIONS FOR PREVENTING NOISE DURING OPERATION
3.8 F
ILLING AND BLEEDING THE INSTALLATION
....................................................................................................................................................................................................................... 4
. .................................................................................................................................. 4
YDRAULIC INSTALLATION
........................................................................................................................................................................................... 4
............................................................................................................................................................................................. 5
....................................................................................................................................................................................................... 5
RAINING THE BOILER
.................................................................................................................................................................................................... 5
...................................................................................................................................... 5
................................................................................................................................................................. 5
4 COMBUSTION PRODUCT REMOVAL ..................................................................................................................................................................... 6
4.1 C
OMBUSTION PRODUCT REMOVAL
4.2 Ø80 / Ø100 (
4.3 C
HANGING FROM DUAL DUCT FUME REMOVAL TO COAXIAL FUME REMOVAL
4.4 C
ONCENTRIC HORIZONTAL DUCT FOR COMBUSTION PRODUCT REMOVAL AND AIR INTAKE Ø
4.5 C
ONCENTRIC VERTICAL DUCT FOR COMBUSTION PRODUCT REMOVAL AND AIR INTAKE Ø
TYPE
C53)
DUAL DUCT SYSTEM FOR COMBUSTION PRODUCT REMOVAL AND AIR INTAKE
............................................................................................................................................................................... 6
................................................................. 7
.......................................................................................................... 8
80-125 (
80-125 (
TYPE
C13) ............................................... 9
TYPE
C33) ................................................... 10
5 OPERATION .................................................................................................................................................................................................................. 11
5.1 B
OILER FUNCTIONING
5.2 O
PERATING WITH A SANIT HOT WATER TANK (OPTIONAL
.................................................................................................................................................................................................. 11
) ....................................................................................................................................... 11
6 SAFETY CUT-OUTS..................................................................................................................................................................................................... 11
6.1 E
XCESSIVE TEMPERATURE SAFETY CUT-OUTS (THERMOSTAT
6.2 E
XCESSIVE FUME TEMPERATURE SAFETY CUT-OUT (THERMOSTAT
6.3 B
URNER CUT-OUT
......................................................................................................................................................................................................... 11
TS) ............................................................................................................................. 11
TH) .................................................................................................................... 11
7 CLIMATE CONTROL (OPTIONAL) : ....................................................................................................................................................................... 12
8 SHUTTING DOWN THE BOILER ............................................................................................................................................................................. 12
9 START-UP ...................................................................................................................................................................................................................... 12
10 FIRST START-UP ....................................................................................................................................................................................................... 12
11 DELIVERY OF THE SYSTEM ................................................................................................................................................................................... 12
12 BOILER MAINTENANCE ......................................................................................................................................................................................... 13
12.1 C
LEANING THE BOILER
12.2 B
OILER WATER CHARACTERISTICS
12.3 C
ONDENSATE DRAIN-OFF
............................................................................................................................................................................................... 13
............................................................................................................................................................................ 14
......................................................................................................................................................................................... 14
13 TECHNICAL CHARACTERISTICS .......................................................................................................................................................................... 15
14 ELECTRICAL DIAGRAM .......................................................................................................................................................................................... 16
15 DIAGRAMS AND MEASUREMENTS ................................................................................................................................................................... 17
16 BURNER ....................................................................................................................................................................................................................... 18
16.1 A
SSEMBLY
16.2 B
URNER START-UP
16.3 A
DJUSTING THE COMBUSTION CONDITIONS
16.4 P
RIMARY AIR ADJUSTMENT
16.5 C
OMBUSTION LINE ADJUSTMENT
16.6 C
ORRECT POSITION OF ELECTRODES
16.7 O
IL PRESSURE ADJUSTMENT
16.8 O
IL SUPPLY PIPING DIAGRAMS
16.9 R
ECOMMENDED NOZZLE AND PUMP PRESSURE
16.10 E
16.11 Q
16.12 B
.................................................................................................................................................................................................................. 18
..................................................................................................................................................................................................... 18
........................................................................................................................................................... 18
....................................................................................................................................................................................... 19
............................................................................................................................................................................. 19
........................................................................................................................................................................ 19
..................................................................................................................................................................................... 20
................................................................................................................................................................................. 20
...................................................................................................................................................... 21
LECTRICAL CONNECTION DIAGRAM
UICK CONNECTOR
URNER CONTROL OPERATING SEQUENCE
................................................................................................................................................................................................ 22
..................................................................................................................................................................... 21
............................................................................................................................................................ 23
17 . TROUBLESHOOTING ............................................................................................................................................................................................ 24
17.1 B
URNER ERROR CODE
17.2 B
OILER FAILURES
17.3 T
HERMOSTAT
................................................................................................................................................................................................ 24
....................................................................................................................................................................................................... 24
............................................................................................................................................................................................................. 24
18 SPARES LIST ............................................................................................................................................................................................................... 25
18.1 B
URNER
...................................................................................................................................................................................................................... 25
18.2 BOILER ...................................................................................................................................................................................................................... 26
18.3 FRONT ELECTRICS ................................................................................................................................................................................................ 27
1111
Jaka HFD Condens
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
1
1 LIST OF COMPONENTS
LIST OF COMPONENTS
11
LIST OF COMPONENTSLIST OF COMPONENTS
5555
4444
2222
3333
6666
7777
8888
1111
1. Blow-off valve.
2. Domestic sealed oil burner.
3. Bulb-holder sheath.
4. Automatic air bleed valve.
2222
5. INOX Condenser output diam. 100.
6. Automatic air bleed valve.
7. Condensate siphon.
8. Cast body.
2
2 CONTROL COMPONENTS
CONTROL COMPONENTS
22
CONTROL COMPONENTSCONTROL COMPONENTS
8888 9999 10
17
1717
8. Climate control (optional)
8. Climate control (optional) ::::
8. Climate control (optional)8. Climate control (optional)
It is an optional element which allows us to regulate the temperature of the installation according to the needs of the household and the outside temperature.
9. Thermometer:
9. Thermometer:
9. Thermometer:9. Thermometer:
Indicates the water temperature of the boiler.
10. Control thermostat.
10. Control thermostat.
10. Control thermostat.10. Control thermostat.
With this we can select the operating temperature of the central heating, stopping the burner when the boiler temperature is equal to that selected or keeping it going when it is less.
1617
1616
10 11
1010
1516
1515
13. Burner blocked pilot light:
13. Burner blocked pilot light:
13. Burner blocked pilot light:13. Burner blocked pilot light:
When lit, it indicates that the boiler operation has been blocked due to blocking of the burner.
14. Blocked due to temperature pilot light:
14. Blocked due to temperature pilot light:
14. Blocked due to temperature pilot light:14. Blocked due to temperature pilot light:
When lit, it indicates that the boiler operation has been blocked due to excessive temperature (higher than 110ºC).
15. ON position pilot light:
15. ON position pilot light:
15. ON position pilot light:15. ON position pilot light:
When lit, it indicates that the boiler is in "normal operation (ON)" mode.
16. Master switch:
16. Master switch:
16. Master switch:16. Master switch:
11 12
1111
14
1415
1414
12
1212
13
13
1313
11. Boiler safety thermostat:
11. Boiler safety thermostat:
11. Boiler safety thermostat:11. Boiler safety thermostat:
This is a cut-out mechanism to ensure the boiler temperature does not exceed 110ºC.
12. Fume safety thermostat:
12. Fume safety thermostat:
12. Fume safety thermostat:12. Fume safety thermostat:
This safety thermostat operates when the temperature of the combustion products exceeds 110ºC, in order to protect the polypropylene duct.
3333
This lets us turn the boiler on and off by pressing the "O/I" switch. By pressing the
"
/
" switch, we can select either summer service (DHW only) or Winter service (heating + DHW).
17. Manometer:
17. Manometer:
17. Manometer:17. Manometer:
Indicates the water pressure of the installation.
Jaka HFD Condens
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
3
3 INSTALLATION INSTRUC
INSTALLATION INSTRUCTIONS
33
INSTALLATION INSTRUCINSTALLATION INSTRUC
The boiler must be installed by personnel authorised by the Department of Industry in accordance with the applicable regulations and standards in force. However, the following recommendations must be complied with when installing the boiler:
3.1
3.1 Location
Location
3.13.1
LocationLocation
The boiler must be installed in a enough ventilated room and sufficient access space must be maintained to carry out preventive or corrective maintenance operations.
3.2
3.2 Installation and electrical connection of the boiler.
Installation and electrical connection of the boiler.
3.23.2
Installation and electrical connection of the boiler.Installation and electrical connection of the boiler.
The pictures below show the two burner assembly operations:
TIONS
TIONSTIONS
3.3
3.3 Hydraulic Installation
Hydraulic Installation
3.33.3
Hydraulic InstallationHydraulic Installation
Fit the flexible pipe.
Tighten the bracket.
Connect the electrical
connector.
The hydraulic installation must be made by qualified personnel. The applicable installation legislation is to be complied with, and the following recommendations should also be taken into account:
- The inside of the installation piping should be thoroughly cleaned before switching on the boiler.
- We recommend inserting cut-off valves between the installation piping and the boiler to simplify maintenance tasks.
- Before starting up the unit, it is essential to install the condensation siphon supplied with the boiler documentation, in the condensation drain tube on the back of the boiler.
- When the pressure of the domestic water supply exceeds 7 bars, a pressure reducer must be fitted.
4444
- The condensation pipe must lead to a drain outlet
The condensation pipe must lead to a drain outlet, as the Jaka HFD Condens is a condensing
The condensation pipe must lead to a drain outletThe condensation pipe must lead to a drain outlet boiler and a large amount of water may be generated. This connection must be made in compliance with the regulations for draining off condensation water to the drainage system.
- Fill the siphon with water before starting up the unit, to prevent fumes coming out of it.
3.4
3.4 Electrical Connection
Electrical Connection
3.43.4
Electrical ConnectionElectrical Connection
The boiler is equipped for connection to 230 V in pins 1 and 2. Remember to earth the appliance.
The boiler has two terminals prepared for connecting the room thermostat (see wiring diagram). The bridge that joins the terminals must therefore be removed and the room thermostat connected there.
3.5
3.5 Fuel installation
Fuel installation
3.53.5
Fuel installationFuel installation
The Jaka HFD Condens
Jaka HFD Condens boiler is supplied with a Domestic
Jaka HFD CondensJaka HFD Condens
Characteristics"). For the fuel installation, proceed in accordance with the burner instructions enclosed with this manual (see "Burner" section). The oil line installation and start-up of the burner must be carried out by qualified, authorised personnel.
3.6
3.6 Draining the boiler
Draining the boiler
3.63.6
Draining the boilerDraining the boiler
The boiler is emptied by opening the drain tap located in the rear of the boiler. A flexible hose must be attached to this tap to direct it to a water outlet. After draining the boiler, the valve must be closed and the flexible tube removed.
3.7
3.7 Precautions for preventing noise during ope
Precautions for preventing noise during operation
3.73.7
Precautions for preventing noise during opePrecautions for preventing noise during ope
Ensure the flow and return pipes are not touching each other, or insulate them to prevent any vibration noise. The boiler must be correctly seated on its base and levelled. Before start-up, make sure that the boiler and the system have been properly bled.
Domestic oil burner (see model in "Technical
DomesticDomestic
ration
rationration
Remember to earth the appliance.
Remember to earth the appliance.Remember to earth the appliance.
3.8
3.8 Filling and bleeding the installation
Filling and bleeding the installation
3.83.8
Filling and bleeding the installationFilling and bleeding the installation
To fill the installation, open the fill valve until the manometer shows a pressure of 1 - 1.5 bars. The circuit should be filled slowly and with the automatic air bleed valve cap loose, to let the air out of the installation. The air should also be bled from the rest of the installation using the air bleed valves provided. Close the fill valve after filling.
NOTE: Switching on the boiler with no water inside could result in serious damage.
NOTE: Switching on the boiler with no water inside could result in serious damage.
NOTE: Switching on the boiler with no water inside could result in serious damage.NOTE: Switching on the boiler with no water inside could result in serious damage.
5555
Jaka HFD Condens
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
4
4 COMBUSTION PRODUCT R
COMBUSTION PRODUCT REMO
44
COMBUSTION PRODUCT RCOMBUSTION PRODUCT R
4.1
4.1 Combustion product removal
Combustion product removal
4.14.1
Combustion product removalCombustion product removal
EMOVAL
VAL
EMOEMO
VALVAL
The combustion product exhaust ducts must be installed by qualified personnel and must comply with current legislation and standards.
The Jaka HFD Condens
Jaka HFD Condens boilers are sealed oil-fired boilers, and the combustion products are
Jaka HFD CondensJaka HFD Condens
therefore removed through an outlet pipe, with a separate air intake from outside. We recommend that the position of the outside exhaust duct is as shown in the figures and in the table below:
Minimum distance
Minimum distance
Removal pipe position
Removal pipe position
Removal pipe positionRemoval pipe position
AAAA under a cornice 300 BBBB between two horizontal ducts 1000 CCCC from an adjacent window 400 DDDD between two vertical ducts 1500 EEEE from an adjacent ventilation grille 600 FFFF under a balcony (*) 300 GGGG under a window 600 HHHH under a ventilation grille 600 IIII from a recess in the building 300 JJJJ from a corner of the building 300 KKKK from the ground 2500 LLLL from a vertical or horizontal duct or outlet (**) 300 MMMM from a frontal surface at a distance of 3 metres from the fume outlet 2000 NNNN as above, but with an opening 3000
Minimum distanceMinimum distance
mm
mm
mmmm
(*)
(*) Providing the width of the balcony is not over 2000 mm.
(*)(*) (**)
(**) If the pipe is made of materials sensitive to the action of the flue gases, this distance should be over 500 mm.
(**)(**) Note:
Note: Spanish law also stipulates that the end of the exhaust duct must be at a distance of at least 400 mm from any air intake
Note: Note:
opening, and from the wall.
IMPORTANT: All accessories used for combustion product removal and air intake should be
IMPORTANT: All accessories used for combustion product removal and air intake should be
IMPORTANT: All accessories used for combustion product removal and air intake should be IMPORTANT: All accessories used for combustion product removal and air intake should be
those supplied by
those supplied by DOMUSA TEKNIK
those supplied by those supplied by
DOMUSA TEKNIK....
DOMUSA TEKNIKDOMUSA TEKNIK
6666
4.2
45º bend
80 Code CGAS000148
4.2 ø80 / ø100 (type C
ø80 / ø100 (type C
4.24.2
ø80 / ø100 (type Cø80 / ø100 (type C
intake
intake
intakeintake
) dual duct system for combu
) dual duct system for combustion product removal and air
) dual duct system for combu) dual duct system for combu
53
53
5353
stion product removal and air
stion product removal and air stion product removal and air
For this type of boiler, combustion product removal and air intake take place through separate Ø80/100 mm mm ducts, using the Ø80/100 Kit, code CGAS000265. Jaka HFD Condens
Jaka HFD Condens boilers
Jaka HFD CondensJaka HFD Condens
come equipped with this type of extraction, by default.
15 metres is the maximum length
maximum length of pipe that can be installed in the Jaka HFD Condens
maximum lengthmaximum length
Jaka HFD Condens model,
Jaka HFD CondensJaka HFD Condens which is the maximum when adding up the metres of the air intake duct and the metres of the combustion product removal duct. For every horizontal metre, the available length is reduced by 2 metres and for every 90° bend, or two 45º bends, it is reduced by 1m.
It is recommended to fit the removal pipe in a slightly upwardly-inclined direction, at around 2º - 3º, thus preventing any water and condensation from dripping out.
90º bend ∅80 Code CGAS000147
90º bend ∅100 Code CGAS000267
Double outlet duct kit ∅80/100
Code CGAS000265
1m pipe ∅80 Code CGAS000145
1m pipe ∅100 Code CGAS000268
NOTE: For this configuration the pipes and elbows of ∅80 are only for the intake of air.
45º bend ∅100 Code CGAS000266
Examples of installation:
7777
Jaka HFD Condens
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
4.3
4.3 Changing from dual duct fume removal to coaxial fume removal
Changing from dual duct fume removal to coaxial fume removal
4.34.3
Changing from dual duct fume removal to coaxial fume removal Changing from dual duct fume removal to coaxial fume removal
The Jaka HFD Condens
Jaka HFD Condens boiler has a Ø80 dual duct system for combustion product removal and air
Jaka HFD CondensJaka HFD Condens intake. If you prefer the combustion products to be removed by means of a Ø80/125 coaxial tube, you may use the Ø80/125 coaxial tube adaptor kit (supplied to order), code CGAS000213 + Code CGAS000222.
Adapter for coaxial pipe 80/125
The changeover may be made with two different assembly configurations:
1. Output towards the back: simply remove the combustion air intake from the boiler, unscrewing the three screws holding it in place, mount the adaptor on the fume outlet towards the rear, and use the flexible air inlet tube to connect it to the adaptor T.
2. Side or top output: the procedure is the same, but for side mounting of the adaptor kit a 90º Ø80 elbow (code CGAS000147) needs to be fitted before the adaptor at the fume outlet.
The two configurations are shown in the figures below:
Combustion air intake
Rear outlet
Side outlet
90º Ø100 elbow
8888
Code CGAS000267
4.4
1m Horizontal duct kit
80/125 PP Cod
e CGAS000188
1m coaxial tube
80/125 PP Cod
e CGAS000082
≤≤≤≤
4.4 Concentric horizontal duct for combustion product removal and air intake
Concentric horizontal duct for combustion product removal and air intake
4.44.4
Concentric horizontal duct for combustion product removal and air intake Concentric horizontal duct for combustion product removal and air intake
ø80
ø80----125 (type C
125 (type C
ø80ø80
125 (type C125 (type C
13
13
1313
)
)
) )
Combustion product removal and air intake can be made using concentric Ø80 mm pipes for combustion product removal and Ø125 mm pipes for air intake, using the 1m Ø80-125 horizontal outlet kit, code CGAS000189.
The maximum length
maximum length in a horizontal direction from the boiler, including the kit terminal, is 8
maximum lengthmaximum length metres (20 HFD) and 6 metres (30 HFD). Each 90° elbow, or two 45° elbows, will reduce the available length by 1 metre.
It is recommended to fit the pipe in a slightly upwardly-inclined direction, at around 2º - 3º, to prevent any water or condensation from dripping out.
1m Horizontal duct kit 80/125 inox Code CGAS000189
1m coaxial tube ∅80/125 inox Code CGAS000184
Examples of installation:
Coaxial 90º bend 80/125 inox
Code CGAS000182
Coaxial 90º bend 80/125 PP
Code CGAS000080
Coaxial 45º bend 80/125 inox
Code CGAS000183
Coaxial 45º bend 80/125 PP
Code CGAS000081
L
L
8 mts. (20 HFD)
8 mts. (20 HFD)
L L
8 mts. (20 HFD) 8 mts. (20 HFD)
L
L ≤≤≤ 6 mts.
6 mts. (30 HFD)
6 mts. 6 mts.
(30 HFD)
(30 HFD)(30 HFD)
L L
9999
Jaka HFD Condens
80/125
80/125
Cód. CGAS000074
90º bend
∅80/125 PP Code CGAS000080
Cód. CGAS000075
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
4.5
4.5 Concentric vertical duct for combustion product removal and air intake
Concentric vertical duct for combustion product removal and air intake
4.54.5
Concentric vertical duct for combustion product removal and air intake Concentric vertical duct for combustion product removal and air intake
ø80
ø80----125 (type C
125 (type C
ø80ø80
125 (type C125 (type C
33
33
3333
)
)
) )
The evacuation of the combustion products and the air intake may be accomplished by using Ø80 mm concentric tubes for the evacuation of combustion products and Ø125 mm for the air intake, using the vertical output Ø80-125 Kit, code CGAS000231.
The maximum length
maximum length in a vertical direction from the boiler, including the kit terminal, is 10 metres
maximum lengthmaximum length (20 HFD) and 7 metres (30 HFD). Each 90° elbow, or two 45° elbows, will reduce the available length by 1 metre.
Vertical duct kit
inox Code. CGAS000181
Vertical duct kit
PP Code. CGAS000360
Examples of installation:
45ºbend ∅80/125 inox Code. CGAS000183
45ºbend 80/125 PP Code. CGAS000081
90º bend ∅80/125 inox Code CGAS000182
1m coaxial tube ∅80/125
inox Code CGAS000184
1m coaxial tube 80/125
PP Code CGAS000082
Black tile ∅80/125
Black tile ∅80/125
10
10
1010
L
L ≤≤≤ 1 0 mts. 20 HFD
10 mts. 20 HFD
L L
10 mts. 20 HFD 10 mts. 20 H FD
L
L ≤≤≤ 7 mts . 30 HFD
7 mts. 30 HFD
L L
7 mts. 30 HFD 7 mts. 30 HFD
5
5 OPERATION
OPERATION
55
OPERATIONOPERATION
5.1
5.1 Boiler functioning
Boiler functioning
5.15.1
Boiler functioningBoiler functioning
Set the control thermostat and the room thermostat (if applicable) to the desired temperature. Move the main switch to the
burner and the pump will begin to function until the installation reaches the pre-selected temperature of the control thermostat (or the room thermostat, if the unit has one). When the temperature in the installation drops, the burner will start up again, running the heating cycle.
5.2
5.2 Operating with a Sanit hot water tank (optional)
Operating with a Sanit hot water tank (optional)
5.25.2
Operating with a Sanit hot water tank (optional)Operating with a Sanit hot water tank (optional)
The Jaka HFD
Jaka HFD Condens
Jaka HFDJaka HFD
TEKNIK
TEKNIK Sanit
TEKNIKTEKNIK the assembly and connection instructions enclosed with the hot water tank.
The boiler is provided with a switch to select summer position or winter position. Using this switch we may choose:
6
6 SAFETY CUT
SAFETY CUT----OUTS
66
SAFETY CUTSAFETY CUT
Sanit range, to obtain domestic hot water. For correct hydraulic installation, carefully follow
SanitSanit
- Summer Position
Summer Position ☼: in this position, the boiler only attends to the needs of DHW production,
Summer PositionSummer Position lighting the burner and the hot water tank loading pump (summer pump) until the accumulated DHW temperature reaches the regulated temperature in the thermostat of the hot water tank. When the DHW temperature is reached, the burner and the summer pump will stop.
- Winter Position : in this position, the boiler attends to the needs of DHW and the heating system, giving priority to DHW.
"I"
"I"
position and the summer-winter switch to the Winter position "". The
"I" "I"
Condens boiler may be installed together with a hot water tank from the DOMUSA
CondensCondens
OUTS
OUTSOUTS
DOMUSA
DOMUSA DOMUSA
The boiler has three types of safety cut-outs:
6.1
6.1 Excessive temperature safety cut
Excessive temperature safety cut----outs (Thermostat T
6.16.1
Excessive temperature safety cutExcessive temperature safety cut
This cut-out is indicated by the pilot light for blocking due to temperature. This occurs when the boiler exceeds a temperature of 110ºC. To restart, press the button on the safety thermostat after first removing the button cover.
6.2
6.2 Excessive fume temperature safety cut
Excessive fume temperature safety cut----out (Thermostat T
6.26.2
Excessive fume temperature safety cutExcessive fume temperature safety cut
This cut-out is indicated by the pilot light for blocking due to temperature. This occurs whenever the temperature of the fumes exceeds 110ºC. To restart, press the button on the safety thermostat after first removing the button cover.
6.3
6.3 Burner cut
Burner cut----out
6.36.3
Burner cutBurner cut
This cut-out is indicated by the pilot light for blocking of the burner. This occurs as a result of an anomaly in the burner or in the fuel installation. To unblock it, press the illuminated button that lights up on the burner.
NOTE: If any of these cut
NOTE: If any of these cut----outs occur repeatedly, call your nearest official Technical Assistance
NOTE: If any of these cutNOTE: If any of these cut Service.
Service.
Service.Service.
out
outout
outs occur repeatedly, call your nearest official Technical Assistance
outs occur repeatedly, call your nearest official Technical Assistance outs occur repeatedly, call your nearest official Technical Assistance
outs (Thermostat T
outs (Thermostat Touts (Thermostat T
out (Thermostat T
out (Thermostat Tout (Thermostat T
))))
SSSS
))))
HHHH
11
11
1111
Jaka HFD Condens
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
7
7 CLIMATE CONTROL (OPT
CLIMATE CONTROL (OPTIONAL)
77
CLIMATE CONTROL (OPTCLIMATE CONTROL (OPT
The Jaka HFD Condens
Jaka HFD Condens boiler comes prepared for the installation of a Lago BVS
Jaka HFD CondensJaka HFD Condens
system.
BBBB:::: Action on burner.
VVVV:::: Action on mixing valve.
SSSS:::: Action on domestic water.
The operating instructions and electrical connections are found in the packaging of the boiler.
8
8 SHUTTING DOWN THE BO
SHUTTING DOWN THE BOILER
88
SHUTTING DOWN THE BOSHUTTING DOWN THE BO
To stop the boiler, simply turn the master switch to "OOOO". To stop the central heating mode and leave only the DHW mode running, set the general switch to
the summer position "☼".
9
9 START
START----UP
99
STARTSTART
UP
UPUP
IONAL) ::::
IONAL)IONAL)
ILER
ILERILER
Lago BVS climate control
Lago BVSLago BVS
Before beginning the start-up process of the boiler, check that:
- The boiler is connected to the mains.
- The installation has been filled with water (the manometer should indicate a pressure of 1 - 5 bar).
- The fuel reaches the burner.
- The isolation valves are open, if there are any installed.
- The room thermostat is set to the desired temperature.
- The boiler room has effective and free ventilation (ventilation based on 0.5 dm2 minimum).
To start-up the boiler, position the main switch and the room thermostat to the desired temperature.
10
10 FIRST START
FIRST START----UP
1010
FIRST STARTFIRST START
For the guarantee TEKNIK
TEKNIK Technical Assistance Service
TEKNIKTEKNIK complied with:
guarantee to be valid
guarantee guarantee
Technical Assistance Service. Before beginning the start-up process, the following must be
Technical Assistance ServiceTechnical Assistance Service
- The boiler must be connected to the mains.
- The installation must have been filled with water (the manometer should indicate a pressure of 1 - 5 bar).
UP
UPUP
to be valid, the boiler must be started up for the first time by an official
to be validto be valid
official DOMUSA
official official
DOMUSA
DOMUSA DOMUSA
- The fuel must be reaching the burner at a pressure of no more than 0.5 bar.
11
11 DELIVERY OF THE SYST
DELIVERY OF THE SYSTEM
1111
DELIVERY OF THE SYSTDELIVERY OF THE SYST
After the initial start-up, the Technical Assistance Service will explain to the user how the boiler functions, making any observations they consider relevant.
The installer is responsible for clearly explaining to the user the functioning of any control or regulation device forming part of the installation but not supplied with the boiler.
12
12
1212
EM
EMEM
12
12 BOILER MAINTENANCE
BOILER MAINTENANCE
1212
BOILER MAINTENANCEBOILER MAINTENANCE
To maintain the boiler in perfect working order, a yearly service should be performed by personnel authorised by DOMUSA TEKNIK
12.1
12.1 Cleaning the boiler
Cleaning the boiler
12.112.1
Cleaning the boilerCleaning the boiler
To maintain the boiler in optimal operating conditions it is recommended that an annual cleaning be undertaken of the combustion chamber, the fume outlets and the condenser. A cleaning brush of a suitable size for cleaning the inside of the exhaust ducts is supplied with the boiler for this purpose. This brush is located at the rear of the boiler, beside the condenser.
The combustion chamber and exhaust ducts should not be cleaned using chemical products
The combustion chamber and exhaust ducts should not be cleaned using chemical products
The combustion chamber and exhaust ducts should not be cleaned using chemical products The combustion chamber and exhaust ducts should not be cleaned using chemical products or hard steel brushes.
or hard steel brushes. After any cleaning operation has been carried out, it is important to run
or hard steel brushes.or hard steel brushes.
several ignition cycles to check all the elements are functioning correctly.
For correct cleaning, the following recommendations should be carefully observed:
Cleaning the boiler body
Cleaning the boiler body
Cleaning the boiler bodyCleaning the boiler body
- Open and remove the outer door of the boiler.
DOMUSA TEKNIK.
DOMUSA TEKNIKDOMUSA TEKNIK
- Remove the burner by unscrewing the fixing nut on the top of the burner.
- Remove the combustion chamber door and the exhaust duct cover, unscrewing the six fixing nuts around them.
- Clean the exhaust ducts on the cast body, using the cleaning brush supplied with the boiler.
- Clean the boiler combustion chamber. We recommend using a soft brush for scrubbing the combustion chamber surfaces, and a blower to remove the flakes.
- After cleaning, replace the combustion chamber door, the exhaust duct cover, the burner and the outer door of the boiler.
Cleaning the condenser
Cleaning the condenser
Cleaning the condenserCleaning the condenser
- Open and remove the top cover of the boiler to access the condenser on the rear of the boiler body.
- Open the top cover of the condenser to access its exhaust ducts. To open this cover, release the two side closures, turn the locking plate anti-clockwise and pull the cover upwards to remove it.
- Remove the exhaust deflectors inside the exhaust outlets.
- Clean the exhaust ducts using the cleaning brush supplied with the boiler. Any scale will fall through the condensation drain and onto the lower condenser cover. It is advisable to pour water into the top of the condenser for a more effective cleaning. This water will be automatically discharged through the condensation drain.
- To clean the outer part of the condenser cylinder, remove the three screws and then remove the metal ring. Take out the seal and use the brush to clean it. Next, put the components back in place again and replace and tighten the three screws and the metal ring.
- If the lower condenser cover needs cleaning, remove the side cover of the boiler to access it. Firstly remove the bracket holding it in place and pull on it to open it. Then pull the lower cover down to open and clean it.
- After cleaning, replace the fume deflectors, the top condenser cover and the top outer cover of the boiler. Then put the cleaning brush back inside the boiler.
13
13
1313
Jaka HFD Condens
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
- The condensation siphon should be cleaned once a year. To do this, remove it and wash it in soapy water. Replace the siphon after cleaning.
1111
2222
3333
4444
5555
6666
7777
8888
9999
Cleaning brush
12.2
12.2 Boiler water characteristics
Boiler water characteristics
12.212.2
Boiler water characteristicsBoiler water characteristics
In areas with water hardness over 25-30ºF, treated water must be used in the heating installation to avoid any lime scale deposits on the boiler. It should be noted that even a few millimetres of scale will greatly reduce the boiler's heat conductivity, causing a major drop in performance.
Treated water must be used in the heating circuit in the following cases:
- Very large circuits (containing a large amount of water).
- Frequent filling of the installation.
If repeated partial or total draining of the installation is necessary, we recommend filling it with treated water.
12.3
12.3 Condensate drain
Condensate drain----off
12.312.3
Condensate drainCondensate drain
off
offoff
The drain for boiler condensate must not be altered and must be kept clear of obstructions. Annual maintenance of the condensate trap is recommended to avoid obstructions that hinder the discharge.
If a neutralisation system is installed in the condensate drain, it is essential to conduct annual maintenance of the system, following the instructions of the manufacturer of the neutralisation system.
Fit the siphon, supplied in the documentation bag, as per the image
14
14
1414
13
13 TECHNICAL CHARACTERI
TECHNICAL CHARACTERISTICS
1313
TECHNICAL CHARACTERITECHNICAL CHARACTERI
JAKA HFD CONDENS
JAKA HFD CONDENS
JAKA HFD CONDENSJAKA HFD CONDENS
STICS
STICSSTICS
Boiler type -
20 HFD
20 HFD 30 HFD
20 HFD20 HFD
condensing
condensing
condensingcondensing
30 HFD
30 HFD30 HFD
Heating only
Rated heat output P
rated
Useful heat output P4
Useful heat output (30%) P1
Seasonal energy efficiency of heating
Useful efficiency
Useful efficiency (30%)
Auxiliary electricity consumption at full load el
Auxiliary electricity consumption at part load el
ȠS
Ƞ4
Ƞ1
max
min
Auxiliary electricity consumption in standby mode PSB
Heat loss in standby mode P
stby
Emissions of nitrogen oxides NOx
kW 19 30
% (PCI)
% (PCS)
% (PCI)
% (PCS)
kW
kW
%
kW
kW
19.0 28.7
6.1 8.5
90 91
96.55 97.96
91.04 92.38
103.82 103.45
97.90 97.55
kW
kW
mg/kWh
0.127 0.135
86 84
0.226
0.078
0.001
Heating temperature regulation ºC 60 - 85
Maximum safety temperature ºC 110
Maximum operating pressure of heating bar 3
Heating expansion vessel capacity Lts 8 8
Heating water volume Lts 14 19.2
Water pressure drop mbar 96 163
Fume temperature ºC
Volume on fume side m3
Maximum fume flow Kg/s
Pressure drop of the fumes mbar
Combustion chamber length mm
Combustion chamber type -
69
0.094
0.0085
0.20
220
67
0.114
0.0132
0.20
300
wet + three exhaust ducts
Type of burner adjustment - ON/OFF
Electrical supply - ~220-230 V - 50 Hz - 200 W
Gross weight Kg 122 155
15
15
1515
Jaka HFD Condens
cs
NC
N
+
-
Brown
Grey
Pink
Orange
Black
Purple
Blue
White
Red
V
1
1
White
1
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
14
14 ELECTRICAL DIAGRAM
ELECTRICAL DIAGRAM
1414
ELECTRICAL DIAGRAMELECTRICAL DIAGRAM
Grey
X12
1
2
3
4
5
6
7
8
9
10
11
12
C
PON
1a
O/I
1
PT
TC
1
C
TS
2
2b
2a
I
2
PB
C
T
HUM
2
C
TF3
2
1 2 3 4 5 6 7 8 9 10 11
TA
220 V
Ph N
B:
B: Burner.
B:B:
BV:
BV: Summer pump.
BV:BV:
BCM:
BCM: Mixed circuit pump.
BCM:BCM:
BCD:
BCD: Direct circuit pump
BCD:BCD:
M:
M: Motor valve.
M:M:
O/I:
O/I: Main on/off switch.
O/I:O/I:
V/I:
V/I: Summer-Winter switch
V/I:V/I:
TA:
TA: Air thermostat.
TA:TA:
TC:
TC: Control thermostat (in boiler).
TC:TC:
TTTT
:::: Fume safety thermostat
HUM
HUM
HUMHUM
Q
bc7
BV
BCD
12 13 14 15 16 17 18 19 20
Black Black
BCM
C
NO
Ta
TS:
TS: Safety thermostat (in boiler).
TS:TS:
TF3:
TF3: 93º Anti-inertia thermostat
TF3:TF3:
M
(in boiler). Tacs:
Tacs: DHW thermostat.
Tacs:Tacs:
PON:
PON: "ON" pilot light.
PON:PON:
PB:
PB: Burner blocked pilot light.
PB:PB:
PT:
PT: Temp blocking pilot light.
PT:PT:
X12:
X12: 12 pole connector for climate control
X12:X12:
(optional).
bc7:
bc7: Terminal no.7 burner control.
bc7:bc7:
16
16
1616
15
15 DIAGRAMS AND MEASURE
DIAGRAMS AND MEASUREMENTS
1515
DIAGRAMS AND MEASUREDIAGRAMS AND MEASURE
MENTS
MENTSMENTS
IC:
IC: Heating flow. MODEL
IC:IC: RC:
RC: Heating Return.
RC:RC: V:
V: Drain valve
V: V: SH:
SH: Fume exhaust duct, Ø100.
SH:SH: SC:
SC: Condensate outlet, 1" H.
SC:SC:
EA:
EA: Combustion air intake, Ø80.
EA:EA:
MODEL
MODELMODEL
JAKA 20 HFD
JAKA 20 HFD
JAKA 20 HFD JAKA 20 HFD
CONDENS
CONDENS
CONDENSCONDENS
JAKA 30 HFD
JAKA 30 HFD
JAKA 30 HFD JAKA 30 HFD
CONDENS
CONDENS
CONDENSCONDENS
DC, RC
DC, RC LLLL
DC, RCDC, RC
3/4”M 540
1”M 640
17
17
1717
Jaka HFD Condens
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
16
16 BURNER
BURNER
1616
BURNERBURNER
16.1
16.1 Assembly
Assembly
16.116.1
AssemblyAssembly
Secure the burner support to the boiler. then fix the burner to the support. This will allow the correct tilt of the flame tube towards the combustion chamber. Fit the intake and return pipes.
16.2
16.2 Burner start
Burner start----up
16.216.2
Burner startBurner start
First place a manometer and a vacuum gauge and prepare the combustion analyser.
The "Domestic" burner is equipped with a self-priming pump, which allows the aspiration of fuel from a tank installed at a lower level than the burner, as long as the vacuum measured with the vacuum gauge in the pump does not exceed 0,4 bat (30cmHg).
The suction of fuel must never reach the bottom of the tank, always leaving a minimum distance of 10 cm to the bottom, if possible, the suction kit with float is recommended.
In installations that allow it, the fuel returns must be made to a recirculation filter with air purge, thus avoiding oxidations in the diesel pump.
up
upup
Make sure there is fuel in the tank, that the oil valves are open and that voltage is reaching the burner. Turn on the master switch. Unscrew the air bleed screw (manometer point). Then, when the valve opens, remove the photocell sensor and move it towards a light source until the oil comes out. Disconnect the burner and screw the bleed screw back in.
16.3
16.3 Adjusting the combustion conditions
Adjusting the combustion conditions
16.316.3
Adjusting the combustion conditionsAdjusting the combustion conditions
As each particular installation has a different combustion circuit, it is essential to adjust the combustion conditions of each boiler. In order for the guarantee to be valid adjusted by an official
Observe the flame. If there is insufficient combustion air, it will be dark in colour and will produce smoke, rapidly obstructing the flue outlet.
On the contrary, if there is an excess of combustion air, the flame will be whitish or bluish-white in colour. This will reduce the performance of the boiler and it will fail to comply with anti-pollution standards, and the excess air may also hinder the ignition process.
The flame should be orange in colour.
If the shape of the boiler makes it difficult or impossible to observe the flame, the combustion air flow can be regulated by observing the smoke coming out of the flue. If the smoke is dark in colour, more air will need to be provided to the burner, or if it is a very whitish colour, the air in the burner will need to be decreased until no smoke at all is observed.
official DOMUSA TEKNIK
official official
DOMUSA TEKNIK Technical Assistance Service
DOMUSA TEKNIKDOMUSA TEKNIK
Technical Assistance Service.
Technical Assistance ServiceTechnical Assistance Service
guarantee to be valid, the burner must be
guarantee to be validguarantee to be valid
If you have a device for determining the composition of the combustion gases, this will be the best guide for flame adjustment. If not, simply follow the above indications.
To adjust the air and burner line conditions, carefully follow the instructions given below.
18
18
1818
16.4
BL
BLBL
BL
RL
RLRL
RL
-
3 m m
3 m m3 m m
3 m m
0 1
2/3 mm
2/3 mm2/3 mm
2/3 mm
3 m m
3 m m3 mm
3 m m
16.4
Primary air adjustment
Primary air adjustment
16.416.4
Primary air adjustmentPrimary air adjustment
To adjust the primary combustion air, turn
0
10
the screw using a 6 mm. Allen key, as shown in the diagram. Turn it clockwise to increase the airflow, and anticlockwise to decrease it.
16.5
16.5
Combustion lin
16.516.5
Combustion line adjustment
Combustion linCombustion lin
e adjustment
e adjustmente adjustment
To adjust the combustion line, loosen the combustion line blocking screw "BL regulator "RL tighten the combustion line blocking screw "BL
RL" clockwise to increase the airflow and anticlockwise to decrease it. After adjustment,
RLRL
BL".
BLBL
+
BL". Turn the line
BLBL
16.6
16.6 Correct position of electrodes
Correct position of electrodes
16.616.6
Correct position of electrodesCorrect position of electrodes
To ensure correct ignition of the "Domestic
Domestic" burner, the measurements shown in the diagram must
DomesticDomestic be observed. Also ensure the electrode fixing screws have been screwed in place before replacing the flame tube.
19
19
1919
Jaka HFD Condens
HHHH
HHHH
3333
5555
4444
2222
7777
6666
1111
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
16.7
16.7 Oil pressure adjustment
Oil pressure adjustment
16.716.7
Oil pressure adjustmentOil pressure adjustment
To adjust the oil pump pressure, turn the screw
(1)
(1)
clockwise to increase the pressure, and
(1)(1)
anticlockwise to decrease it.
1 - Pressure adjustment.
DANFOSS ---- MOD. BFP 21 L3
DANFOSS DANFOSS
MOD. BFP 21 L3
MOD. BFP 21 L3MOD. BFP 21 L3
DANFOSS
2 – Vacuum gauge point.
3 - Valve.
4 - Manometer point.
5 - Nozzle outlet.
6 - Return.
7 - Intake.
16.8
16.8 Oil supply piping diagrams
Oil supply piping diagrams
16.816.8
Oil supply piping diagramsOil supply piping diagrams
The diagrams and tables below correspond to installations without reductions and with a perfect hydraulic seal. It is recommended to use copper pipes. A pressure drop of 0.4 bar (30 cmHg) must not be exceeded (reading via a vacuum gauge).
Intake installation
Intake installation
Intake installationIntake installation
Charging installation
Charging installation
Charging installationCharging installation
HHHH
Intake installation
Intake installation
Intake installationIntake installation
HHHH Pipe length
(m)
0.0 25 60
0.5 21 50
1.0 18 44
1.5 15 38
2.0 12 26
2.5 10 26
3.0 8 20
3.5 6 16
int 8 mm. int 10 mm.
Pipe length
Pipe lengthPipe length
Charging installation
Charging installation
Charging installationCharging installation
HHHH Pipe length
(m)
0.5 10 20
1.0 20 40
1.5 40 80
2.0 60 100
int 8 mm. int 10 mm.
Pipe length
Pipe lengthPipe length
20
20
2020
16.9
5 6 8 10 11 12 3
EV2
N
T2 T1 N L1
16.9 Recommended nozzle and pump pressure
Recommended nozzle and pump pressure
16.916.9
Recommended nozzle and pump pressureRecommended nozzle and pump pressure
Jaka HFD Condens
Jaka HFD Condens boilers are supplied with the burner fitted, with their corresponding nozzle
Jaka HFD CondensJaka HFD Condens and with the standard pre-adjustment. The following table shows the nozzles and adjustments for each particular model:
Burner pressure
Burner pressure
MODEL
MODEL Nozzle
MODELMODEL
Nozzle
NozzleNozzle
Burner pressure Burner pressure
(bar)
(bar)
(bar)(bar)
Air adjustment
Air adjustment Line adju
Air adjustmentAir adjustment
Line adjustment
Line adjuLine adju
stment
stmentstment
JAKA 20 HFD CONDENS
JAKA 20 HFD CONDENS
JAKA 20 HFD CONDENSJAKA 20 HFD CONDENS
JAKA 30 HFD CONDENS
JAKA 30 HFD CONDENS
JAKA 30 HFD CONDENSJAKA 30 HFD CONDENS
16.10
16.10 Electrical connection diagram
16.1016.10
Electrical connection diagram
Electrical connection diagramElectrical connection diagram
0.40/ 80º H
0.60/ 60º H
1 2
MB EV1
B4 S3
15 5,5 1
11 3.5 1
4
7
Black
Brown
TR
TP
RP
Blue
Preheater
FR
LB
B4:
B4: Hour meter contact.
B4:B4:
S3:
S3: Cut-out pilot light contact:
S3:S3:
TC:
TC: Control thermostat (in boiler).
TC:TC:
TS:
TS: Safety thermostat (in boiler).
TS:TS:
CH:
CH: Hour meter.
CH:CH:
IG:
IG: Main on/off switch.
IG:IG:
F:
F: Fuse.
F:F:
LB:
LB: Pilot light.
LB:LB:
LB':
LB': External cut-out pilot light.
LB':LB':
TC
TS
LB'
CH
IG
F
Ph
FR:
FR: Photocell.
FR:FR:
TR:
TR: Transformer.
TR:TR:
MB:
MB: Motor pump.
MB:MB:
EV:
EV: Valve.
EV:EV:
RP:
RP:
Preheater element.
RP:RP:
Ph:
Ph: Phase.
Ph: Ph:
N:
N:
Neutral.
N:N:
TP
TP :::: Preheater thermostat.
TPTP
21
21
2121
Jaka HFD Condens
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
16.11
16.11 Quick connector
16.1116.11
Quick connector
Quick connectorQuick connector
To connect and disconnect the red oil intake tube to the nozzle, proceed as follows:
- Press the connector ring in the direction of the arrow, pulling on the red tube at the same time.
R ED PIP E
R ED PIP E
PUSH
PUSH
PUSHP US H
R ING
R ING
R INGR ING
R ED PIP ER ED P IP E
OIL
OIL
OILOIL
QUICK C ONNE CT FITTING
QUICK C ONNE CT FITTING
QUICK C ONNE CT FITTINGQUICK C ONNE CT FITTING
22
22
2222
16.12
16.12 Burner control operating sequence
16.1216.12
Burner control operating sequence
Burner control operating sequenceBurner control operating sequence
The burner's LMO14 control box has a reset button "EK", which is the key element for resetting the burner control and activating/deactivating the diagnostic functions. The multi-colour LED on the reset button is the indicator for visual diagnosis. The "EK" button and the LED are located under the transparent cover of the reset button. During normal functioning, the various operating statuses are indicated in the form of colour codes (see the colour code table below). During ignition, the indication is as shown in the following table:
Reset button
If the button is on, press to reset. If the button stays on, call the Technical Assistance Service.
23
23
2323
Jaka HFD Condens
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
17
17 . TROUBLESHOOTING
TROUBLESHOOTING
1717
TROUBLESHOOTINGTROUBLESHOOTING
This section provides a list of the most common burner and boiler failures.
17.1
17.1 Burner error code
Burner error code
17.117.1
Burner error codeBurner error code
We have already mentioned that the burner is equipped with a cut-out system, indicated by the reset button light. It may cut out accidentally, and in this case the steady red light on this button will come on. You may unblock it by pressing the button for approx. 1 second. When the burner is blocked and the steady red light is on, visual failure diagnosis may be activated, in accordance with the error code table. To enter visual failure diagnosis mode, hold down the reset button for at least three seconds.
Error code table
Error code table
Error code tableError code table
Red flashing LED code
Red flashing LED code "AL" on
Red flashing LED codeRed flashing LED code
Flashes 4 times
Flashes 4 times Flashes 7 times
Flashes 8 times Flashes 10 times
"AL" on
"AL" on "AL" on
term. 10
term. 10
term. 10term. 10
On No flame established when ignition safety time ends.
On External light during burner ignition On Excessive flame loss during functioning (limited number of
On Supervision of fuel pre-heater time On Cabling fault or internal failure, output contacts, other
Possible cause
Possible cause
Possible causePossible cause
- Fuel valves defective or dirty
- Flame detector defective or dirty
- Burner maladjustment, no fuel
- Ignition unit defective
repetitions)
- Fuel valves defective or dirty
- Flame detector defective or dirty
- Burner maladjustment
failures
During the failure diagnosis time, the control outputs are disabled and the burner remains off. To exit failure diagnosis and activate the burner again, reset the burner control. Hold down the reset button for approx. 1 second (<3 s).
17.2
17.2 Boiler failures
Boiler failures
17.217.2
Boiler failuresBoiler failures
FAILURE
FAILURE CAUSE
FAILUREFAILURE
RADIATOR DOES
NOT HEAT UP
EXCESSIVE NOISE
17.3
17.3 Thermostat
Thermostat
17.317.3
ThermostatThermostat
CAUSE SOLUT
CAUSECAUSE
- The pump is not turning Unblock the pump
- Air in hydraulic circuit
- Burner badly adjusted Correctly adjust it
- Flue not correctly sealed Eliminate any leaks
- Flame unstable Examine the burner
- Flue not insulated Suitably insulate it
SOLUTION
ION
SOLUTSOLUT
IONION
Drain the installation and the boiler (the automatic air bleed valve cap must always be loose)
Boiler temperature safety thermostat (TS)
Fumes temperature safety thermostat (TH)
If the boiler goes into safety lockout due to overheating of the boiler (TS) or fumes (TH), reset by pressing the appropriate button on the thermostat. To access the buttons, unscrew the black cap.
24
24
2424
18
22
18 SPARES LIST
SPARES LIST
1818
SPARES LISTSPARES LIST
18.1
18.1 Burner
Burner
18.118.1
BurnerBurner
16
18
19
Pos.
Pos.
Code
Code Description
Pos.Pos.
CodeCode
CTOR000006 Straight connector
1111
CTOE000054 Line adjustment nut
2222
CFER000032 Cable duct
3333
CEXT000720 D4 end cover
4444
CQUE000156 Siemens Photocell
5555
(Jaka FD 30 Condens)
CQUE00050 Red Brahma Photocell
(Jaka FD 20 Condens)
CQUE000149 Photocell support
6666
CQUE000054 Suntec valve coil cable
7777
CQUE000124 Danfoss valve coil cable CQUE000089 Danfoss valve coil
8888
CQUE000062 Suntec oil pump
9999
CQUE000088 Danfoss oil pump CTOR000007 Elbow connector
10
10
1010
CQUE000004 Pump motor coupling
11
11
1111
CQUE000102 Motor
12
12
1212
CTOE000065 Counter thread
13
13
1313
CQUE000147 Oil hose
14
14
1414
CQUE000169 LMO14 Control box
15
15
1515
CQUE000005 Transformer
16
16
1616
20
21
Description
DescriptionDescription
23
25
24
26
17
10
15
14
13
11
28
29
30
27
31
32
33
Pos.
Pos.
Code
Code Description
Pos.Pos.
CodeCode
CQUE000129 LMO14 Control box base
17
17
1717
CQUE000033 Flange seal
18
18
1818
SATQUE0001 Flange
19
19
1919
CQUE000158 Flange support
20
20
2020
SCON0001667 Canon Jaka FD 20 Condens
21
21
2121
CQUE000198 Canon Jaka FD 30 Condens CQUE000018 Manifold
22
22
2222
CQUE000151 D4 air regulating plate
23
23
2323
CTOE000064 Air adjustment screw
24
24
2424
CEXT000719 Air adjustment support
25
25
2525
CQUE000044 Fan
26
26
2626
CEXT000718 Motor support
27
27
2727
CQUE000019 Set of electrodes
28
28
2828
CQUE000155 Turbulator disc
29
29
2929
CQUE000172 Nozzle OD-H 0.40-80º(Jaka FD 20 Cond.)
30
30
3030
CQUE000203 Nozzle OD-H 0.60-60º(Jaka FD 30 Cond.) CQUE000061 Preheater
31
31
3131
CQUE000027 Pre-heater cable
32
32
3232
CTOE000063 D4 burner line
33
33
3333
CFER000033 Cable duct
34
34
3434
12
Description
DescriptionDescription
9
8
7
6
5
4
34
3
2
1
25
25
2525
Jaka HFD Condens
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
18.2
18.2 BOILER
BOILER
18.218.2
BOILERBOILER
8
9 11 1210 1413
7
1
3
2456
26
26
2626
18.3
18.3 FRONT ELECTRICS
FRONT ELECTRICS
18.318.3
FRONT ELECTRICSFRONT ELECTRICS
22
23
23
24
24
21
20
19
Pos.
Pos.
Code
Code Designation
Pos.Pos.
CodeCode
1111 SELEJAF003 Electrical board 2222 TQDFPJ0008 Burner Jaka HFD 20 Condens
TQDFPJ0007 Burner Jaka HFD 30 Condens 3333 SEPO002302 Front panel 4444 CFER000051 Extraflex burner tube 5555 SEPO002325 Left side Jaka HFD 30 Condens
SEPO002307 Left side Jaka HFD 20 Condens 6666 SEPO002308 Left side cover 7777 SEPO002305 Rear cover 8888 SEPO002304 Rear 9999 GCHAEV0010 Condenser Ø100
10
10 CFOV000024 Drain valve
1010 11
11 SEPO002310 Top Jaka HFD 20 Condens
1111
SEPO002326 Top Jaka HFD 30 Condens
12
12 SEPO002316 Right side Jaka HFD 20 Condens
1212
SEPO002324 Right side Jaka HFD 30 Condens
13
13 Rigidity
1313 14
14 SEPO002309 Right side cover
1414 15
15 CELEC000175 Control panel cover
1515 16
16 CELC000040 Amber pilot light
1616 17
17 CELC000137 Manometer
1717 18
18 CELC000178 Panel cover
1818
Designation
DesignationDesignation
18
25
26
27
17
16
15
Pos.
Pos.
Code
Code Designation
Pos.Pos.
CodeCode
19
19 CELC000171 Control panel
1919 20
20 CELC000007 Control thermostat (TC)
2020 21
21 CELC000034 Thermostat 93º (TF3)
2121 22
22 MGALPL0006 Control box fastener
2222 23
23 CELC000042 Weidmuller 12-pole terminal strip
2323 24
24 CELC000022 Safety thermostat 110º (TS)
2424
25
25 CELC000136 Thermometer
2525 26
26 CELC000176 Dial
2626 27
27 CELC000138 Small bipolar switch
2727 28
28 CELC000039 Red pilot light
2828
Designation
DesignationDesignation
Fumes safety thermostat (TH)
28
27
27
2727
Jaka HFD Condens
Jaka HFD Condens
Jaka HFD CondensJaka HFD Condens
NOTES:
NOTES:
NOTES:NOTES:
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
28
28
2828
NOTES:
NOTES:
NOTES:NOTES:
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
29
29
2929
CDOC001418
04/18
UK ADDRESS
UK ADDRESS HEADQUARTERS & FACTORY
UK ADDRESSUK ADDRESS
Apartado 95 Bº San Esteban s/n
20730 AZPEITIA
Tel: (+34) 943 813 899
www.domusateknik.com
www.domusateknik.com
www.domusateknik.comwww.domusateknik.com
HEADQUARTERS & FACTORY
HEADQUARTERS & FACTORYHEADQUARTERS & FACTORY
20737 RÉGIL (Guipúzcoa)
DOMUSA TEKNIK
DOMUSA TEKNIK
DOMUSA TEKNIKDOMUSA TEKNIK
reserves the right to make modifications of any kind to its product
characteristics without prior notice.
*CDOC001418*
Loading...