DOMUSA TEKNIK Evolution Solar 30 HDX, Evolution Solar 30 HDX with SRX2/EV Installation And Operating Instructions Manual

INSTALLATION AND OPERATING INSTRUCTIONS
EVOLUTION SOLAR HDX
ER-0170/1996
CGM-04/392
Thank you for choosing a DOMUSA TEKNIK heating boiler. From the range of DOMUSA TEKNIK products you have chosen the Evolution Solar HDX model. With a suitable hydraulic installation, this oil-fired boiler will provide the ideal level of comfort for your home. You will also be able to enjoy a balanced, economical supply of domestic hot water.
This manual forms an essential part of the product and it must be given to the user. Read the warnings and recommendations in the manual carefully, as they contain important information on the safety, use and maintenance of the installation.
These boilers are to be installed by skilled personnel only, in accordance with the legislation in force and following the manufacturer’s instructions.
The start-up of these boilers and any maintenance operations must only be carried out by DOMUSA TEKNIK’s Authorised Technical Assistance Services.
Incorrect installation of these boilers could result in damage to people, animals or property, and the manufacturer will hold no liability in such cases.
DOMUSA TEKNIK informs all parties concerned that, in compliance with section 1 of the first additional provision of Law 11/1997, the responsibility for delivering packaging waste or used packaging for its proper environmental management will be that of the final owner of the product (Article 18.1 Royal Decree 782/1998). At the end of its useful life, the product must be taken to a selected collection point for electrical and electronic equipment or must be returned to the distributor at the time of purchasing a new equivalent appliance. For more detailed information on the collection schemes available, contact either the collection facilities of the local authority or the distributor where the purchase was made.
1
INDEX Page
1 COMPONENTS DIAGRAM..................................................................................................................................................................................................................3
2 CONTROL ELEMENTS..........................................................................................................................................................................................................................4
3 INSTALLATION INSTRUCTIONS.......................................................................................................................................................................................................5
3.1 LOCATION AND ASSEMBLY OF THE BOILER/HOT WATER TANK UNIT.......................................................................................................................................................5
3.2 HYDRAULIC INSTALLATION OF THE HEATING AND D.H.W. CIRCUIT......................................................................................................................................................6
3.3 FUEL INSTALLATION ................................................................................................................................................................................................................................6
3.4 ELECTRICAL CONNECTION ......................................................................................................................................................................................................................7
3.5 INSTALLING HEATING CIRCUIT 2 (OPTIONAL).........................................................................................................................................................................................7
3.6 INSTALLING THE SOLAR CIRCUIT..............................................................................................................................................................................................................8
3.7 LOCATION OF THE SOLAR COLLECTOR....................................................................................................................................................................................................9
3.8 REMOVAL OF COMBUSTION PRODUCTS...............................................................................................................................................................................................10
4 REMOVAL OF COMBUSTION PRODUCTS.................................................................................................................................................................................11
4.1 Ø80 DUAL DUCT SYSTEM FOR COMBUSTION PRODUCT REMOVAL AND AIR INTAKE (TYPE C53).........................................................................................................11
4.2 CHANGING FROM DUAL DUCT FUME REMOVAL TO COAXIAL FUME REMOVAL....................................................................................................................................12
4.3 Ø80-125 CONCENTRIC HORIZONTAL DUCT FOR COMBUSTION PRODUCT REMOVAL AND AIR INTAKE (TYPE C13)............................................................................13
4.4 Ø80-125 CONCENTRIC VERTICAL DUCT FOR COMBUSTION PRODUCT EVACUATION AND AIR INTAKE (TYPE C33).............................................................................14
5 STARTING-UP THE BOILER.............................................................................................................................................................................................................15
5.1 PRIOR WARNINGS.................................................................................................................................................................................................................................15
5.2 FILLING THE DOMESTIC HOT WATER TANK...........................................................................................................................................................................................15
5.3 FILLING THE HEATING CIRCUIT..............................................................................................................................................................................................................15
5.4 START-UP .............................................................................................................................................................................................................................................15
5.5 INSTALLATION DELIVERY.......................................................................................................................................................................................................................15
5.6 FILLING THE SOLAR CIRCUIT .................................................................................................................................................................................................................16
5.7 SOLAR PUMP FUNCTIONING IN MANUAL MODE...................................................................................................................................................................................17
5.8 STARTING UP THE SOLAR PUMP WITH TIMER........................................................................................................................................................................................17
5.9 CHECKING THE SOLAR CIRCUIT SEAL....................................................................................................................................................................................................17
5.10 ADJUSTING THE SOLAR CIRCUIT FLOW ..............................................................................................................................................................................................18
6 DIGITAL DISPLAY:..............................................................................................................................................................................................................................19
7 TEMPERATURE SELECTION............................................................................................................................................................................................................21
7.1 SELECTING THE BOILER SET POINT TEMPERATURE................................................................................................................................................................................21
7.2 SELECTING THE THE DHW SETPOINT TEMPERATURE OF THE BACK-UP HOT WATER TANK..................................................................................................................21
7.3 SELECTING THE DHW SETPOINT TEMPERATURE IN THE SOLAR HOT WATER TANK .............................................................................................................................22
7.4 SELECTING THE UNDERFLOOR HEATING FLOW SETPOINT TEMPERATURE (WITH SRX2/EV KIT OPTION)............................................................................................22
8 OPERATION.........................................................................................................................................................................................................................................23
8.1 SOLAR CIRCUIT FUNCTIONING..............................................................................................................................................................................................................23
8.2 HEATING FUNCTION.............................................................................................................................................................................................................................24
8.3 DOMESTIC HOT WATER PRODUCTION FUNCTION OF TANK................................................................................................................................................................24
8.4 HEATING CIRCUIT 2 FUNCTIONING (OPTIONAL)..................................................................................................................................................................................25
8.5 FUNCTIONING WITH AN SRX2/EV UNDERFLOOR HEATING KIT (OPTIONAL)...................................................................................................................................25
9 ADDITIONAL FUNCTIONS..............................................................................................................................................................................................................26
9.1 PUMP ANTI-BLOCK FUNCTION..............................................................................................................................................................................................................26
9.2 ANTI-FROST FUNCTION........................................................................................................................................................................................................................26
9.3 TELEPHONE RELAY CONNECTION.........................................................................................................................................................................................................26
9.4 ANTI-LEGIONELLA FUNCTION (OPTIONAL)...........................................................................................................................................................................................26
9.5 BOILER PRESSURE SENSOR FUNCTION..................................................................................................................................................................................................26
9.6 ROOM THERMOSTAT CONNECTION......................................................................................................................................................................................................26
9.7 DISCONNECTING THE OIL-FIRED BOILERS BACK-UP ENERGY SUPPLY..................................................................................................................................................27
9.8 DISCONNECTING THE SOLAR CIRCUIT...................................................................................................................................................................................................27
9.9 KEYPAD BLOCK FUNCTION ...................................................................................................................................................................................................................27
10 E20 REMOTE CONTROL (OPTIONAL).......................................................................................................................................................................................27
10.1 FUNCTIONING WITHOUT AN OUTDOOR SENSOR ...............................................................................................................................................................................28
10.2 FUNCTIONING WITH AN EXTERNAL SENSOR (OPTIONAL)..................................................................................................................................................................28
10.3 DHW MODE FUNCTIONING...............................................................................................................................................................................................................29
10.4 TELEPHONE RELAY FUNCTION............................................................................................................................................................................................................29
11 SHUTTING DOWN THE BOILER..................................................................................................................................................................................................29
12 DRAINING THE BOILER..................................................................................................................................................................................................................29
13 DRAINING THE SOLAR CIRCUIT.................................................................................................................................................................................................29
14 SAFETY CUT-OUTS.........................................................................................................................................................................................................................30
14.1 TEMPERATURE SAFETY CUT-OUT.......................................................................................................................................................................................................30
14.2 BURNER CUT-OUT..............................................................................................................................................................................................................................30
14.3 LOW PRESSURE CUT-OUT...................................................................................................................................................................................................................30
15 BOILER MAINTENANCE.................................................................................................................................................................................................................31
16 CIRCULATION PUMP FLOW CURVES.......................................................................................................................................................................................33
16.1 CHARACTERISTIC HEATING PUMP......................................................................................................................................................................................................33
16.2 REGULATION PUMP HEATING.............................................................................................................................................................................................................33
16.3 PRESSURE DROP.................................................................................................................................................................................................................................33
17 DIAGRAMS AND MEASUREMENTS...........................................................................................................................................................................................34
17.1 EVOLUTION SOLAR 30 HDX.............................................................................................................................................................................................................34
17.2 EVOLUTION SOLAR 30 HDX WITH SRX2 / EV UNDERFLOOR HEATING KIT....................................................................................................................................35
18 TECHNICAL CHARACTERISTICS.................................................................................................................................................................................................36
19 CONNECTION DIAGRAM..............................................................................................................................................................................................................37
19.1 EVOLUTION SOLAR 30 HDX.............................................................................................................................................................................................................37
Evolution Solar HDX
2
19.2 EVOLUTION SOLAR 30 HDX WITH SRX2 / EV UNDERFLOOR HEATING KIT....................................................................................................................................38
20 ELECTRICAL DIAGRAM..................................................................................................................................................................................................................39
20.1 EVOLUTION SOLAR HDX..................................................................................................................................................................................................................39
20.2 EVOLUTION SOLAR HDX KIT FLOOR HEATING WITH SRX2 / EV.....................................................................................................................................................40
21 ALARM CODES.................................................................................................................................................................................................................................41
22 BURNER..............................................................................................................................................................................................................................................42
22.1 ASSEMBLY..........................................................................................................................................................................................................................................42
22.2 BURNER START-UP.............................................................................................................................................................................................................................42
22.3 ADJUSTING THE COMBUSTION CONDITIONS .....................................................................................................................................................................................42
22.4 OIL PRESSURE ADJUSTMENT..............................................................................................................................................................................................................44
22.5 OIL SUPPLY PIPING DIAGRAMS...........................................................................................................................................................................................................44
22.6 TECHNICAL SPECIFICATIONS..............................................................................................................................................................................................................45
22.7 OPERATING CURVES...........................................................................................................................................................................................................................45
22.8 NOZZLES............................................................................................................................................................................................................................................45
22.9 ELECTRICAL CONNECTION DIAGRAM.................................................................................................................................................................................................46
22.10 QUICK CONNECTOR.........................................................................................................................................................................................................................46
22.11 BURNER CONTROL OPERATING SEQUENCE......................................................................................................................................................................................47
23 SPARES LIST......................................................................................................................................................................................................................................48
24 FAILURES...........................................................................................................................................................................................................................................52
25 GUARANTEE CONDITIONS..........................................................................................................................................................................................................54
3
1 COMPONENTS DIAGRAM
1
2
3
4
5
6
7
8
9 10
11
12
13
14 15
16
18 19
20 21
17
1. Heating circuit drain valve..
2. Solar circuit drain valve.
3. Solar circuit pumps.
4. Flow regulator.
5. 250 litre solar storage tank
6. Solar circuit level gauge.
7. Solar circuit safety valve.
8. Solar circuit fill valve.
9. DHW safety unit
10. Solar capture pump
11. Automatic air vent.
12. DHW expansion vessel.
13. Pressure switch.
14. 130 litre DHW storage tank.
15. Heating circuit expansion vessel.
16. Automatic air vent.
17. Heating circuit safety valve..
18. Heating pump.
19. DHW pump.
20. Fill valve.
21. Sealed burner.
Evolution Solar HDX
4
2 CONTROL ELEMENTS
23 25 2624 27
22
29 28
22. Digital display:
This is the boiler functioning display, on which all the operating information, settings and values appear. In standard operating mode (default display), the actual boiler temperature is shown. If any malfunctioning should occur, the corresponding alarm code will appear on the digital display.
23. Boiler temperature touch button:
This is used to select the boiler setpoint temperature. If oFF is selected, the heating function is disabled. To select the desired temperature, simply place your finger on the "+" or "-" symbols on the touch button to increase or decrease the desired boiler temperature.
24. MODE touch button:
When this button is touched the different boiler temperatures appear on the digital display.
26. ON touch button:
If you place your finger on this button for 1 second the boiler will switch on or off.
26. RESET touch button:
If the boiler is in lock-out mode as the alarm has been triggered, touch the RESET button to reset the lock-out and restore functioning. If you are modifying any of the settings or browsing the user menu, you may touch the RESET button to exit the menu WITHOUT SAVING and return to the previous menu level.
27. DHW temperature touch button:
This is used to select the setpoint temperature for domestic hot water. If oFF is selected, the heating function is disabled. To select the desired temperature, simply place your finger on the "+" or "-" symbols on the touch button to increase or decrease the desired DHW temperature.
28. Boiler safety thermostat:
This is a cut-out mechanism to ensure the boiler temperature does not exceed 110ºC.
29. Fume safety thermostat:
This safety thermostat operates when the temperature of the combustion products exceeds 110ºC, in order to protect the polypropylene duct.
5
3 INSTALLATION INSTRUCTIONS
The boiler must be installed by personnel authorised by the Department of Industry in accordance with the applicable regulations and standards in force. However, the following recommendations must be complied with when installing the boiler:
3.1 Location and assembly of the boiler/hot water tank unit
The boiler must be installed in a sufficiently ventilated site. The boiler has an integrated solar capture system and must therefore be located at a lower level than the solar collector installation.
The two modules are to be placed back-to-back and aligned at the front. The assembly may be made either towards the right or towards the left. Each module is supplied with levelling screws on its base, accessible from the front, as shown in the picture below.
When you have correctly positioned the modules, interconnect them hydraulically using the two flexible connection tubes supplied inside the boiler module. Open the door to access them. Connect socket “A” on the rear of the accumulator module to the corresponding socket “A” of the boiler module, and socket “B” to the corresponding socket “B”, as shown in the picture below.
Finally, connect the two modules electrically using the connectors on the rear of each module, as shown in the picture below.
The boiler must be accessible from the side for maintenance purposes. The solar accumulator module may be placed on either side of the back-up boiler module for this purpose.
ABA
B
Electrical connection
Levelling bolts
Evolution Solar HDX
6
3.2 Hydraulic installation of the heating and D.H.W. circuit.
The hydraulic installation must be made by qualified personnel. The applicable installation legislation is to be complied with, and the following recommendations should also be taken into account:
- The inside of the installation piping should be thoroughly cleaned before switching on the boiler.
- Ensure the two modules have been hydraulically interconnected before connecting the boiler. (See section “3.1”)
- We recommend inserting cut-off valves between the installation piping and the boiler to simplify maintenance tasks.
- If the boiler is installed at a lower height than the heating installation, it is recommendable to create a siphon at the boiler outlet, to prevent the installation from heating up due to natural convection when heating is not required.
- For correct boiler functioning, there must be a pressure of at least 0.5 bar in the domestic hot water circuit.
- When the DHW supply pressure is over 5 bars, a pressure reducer must be fitted.
- It is recommended to install a thermostatic mixing valve at the DHW outlet to protect against burns and to guarantee a constant, stable supply of hot water.
- Before starting up the unit, it is essential to install the condensation siphon supplied with the boiler documentation on the condensation drain tube on the back of the boiler.
- The condensation pipe should lead to a drain outlet, as the Evolution boiler is a condensation boiler and a large amount of water may be generated. This connection should be made in accordance with the regulations for draining off condensation water to the drain network.
- Fill the siphon with water before starting up the unit, to prevent fumes coming out of it.
3.3 Fuel installation
The Evolution Solar HDX boiler is supplied with a Domestic sealed oil burner (see model in “
Technical Characteristics
”). To correctly make the fuel installation, proceed in accordance with the
burner instructions enclosed with this manual (see “
Burner
” section).
The oil line installation and start-up of the burner must be carried out by qualified, authorised personnel.
7
3.4 Electrical Connection
The boiler is equipped for connection at 230 V~, 50 Hz to terminals 1 and 2 of terminal strip J1 (see “
Electrical Connection Diagram
”). Remember to earth the appliance.
The boiler has two terminal strips, TA1 (J5) and TA2 (J6) for connecting room thermostats or room chronothermostats (see “
Electrical Connection Diagram
”) for remote control of heating circuits 1 and 2 respectively. To correctly connect the room thermostats, firstly remove the bridge joining the terminals of terminal strip TA1. For connection to TA2, simply connect the thermostat to the terminal strip.
IMPORTANT: Before carrying out any work on the boiler’s electrical installation, always ensure it is disconnected from the mains.
IMPORTANT: To access the electrical connection terminal strip, remove the protection box under the main board, as shown in the picture below.
Remove the protective box to access the terminal strip
3.5 Installing heating circuit 2 (Optional)
All the models in the Evolution Solar HDX range of boilers are supplied equipped with a circulation pump connected to a heating circuit, circuit 1 (BC
1
). In addition to this circuit, all the models are
designed to control a second heating circulation pump, in a second heating circuit, circuit 2 (BC
2
).
The hydraulic installation of heating circuit 2 should be made using the optional flow circuit (IC') on the rear of the boiler (see "Diagrams and Measurements").
A circulation pump and a shut-off valve or electrovalve will need to be included in heating circuit Nº
2. This pump must be electrically connected between terminals N and 8 on the supply connector block J2 (see “Electrical Connection Diagram").
Evolution Solar HDX
8
3.6 Installing the solar circuit
The solar circuit integrated in the boiler must be installed by qualified personnel. The solar circuit basically consists of a dual-chamber domestic hot water storage tank for exchanging heat with the domestic hot water, two solar circulation pumps, a flow regulator and one or two solar collectors for exchanging heat with the sun.
To make optimum use of the solar energy, take special care when locating and positioning the solar collector. Read the “Location of the Solar Collector” section carefully to obtain full performance from the circuit. To correctly assemble the solar collector and its corresponding supports, carefully follow the assembly instructions included with the same.
The hydraulic connection between the solar collector and the boiler is made using the solar inlet socket "ES" and the solar return socket "RS". See "Diagrams and Measurements". When making the solar circuit and the hydraulic connection between the solar collector and the boiler, the following limitations must be taken into account:
Min. height
(G)
Max. height
(H)
Max. horizontal L. (flow
and return) (L)
Max. total length
Min. slope ( α )
Piping Ø
0.5 m. 10.9 m. 20 m. 40 m. 4% Ø 12 mm.
When the solar circuit hydraulic connections have been made, assemble the collector sensor bulb (Scol) on the bulb-holder provided on the collector, and make the electrical connection on the connector block of sensors J3, terminals 17 and 18 (see “Connection Diagram”). The collector sensor "Scol" is supplied with the solar collectors, in the accessory box.
For the solar circuit to function properly, it is essential to start it up correctly, carefully following the instructions given in the points on this subject in the “Start-up” section of this manual. These sections provide a detailed description of how to correctly fill the circuit, check the seal and adjust the flow.
The heat transmission in the Evolution Solar HDX boiler solar circuit is made by means of a heat­carrying fluid consisting of a mix of water (70%) and DOMUSA TEKNIK inhibitor liquid (minimum 30%). The DOMUSA TEKNIK inhibitor liquid’s resistance and heat transmission properties make it suitable for use in solar heating installations. Its main function is to protect the different components from corrosion, as the installation contains various metals. The Evolution Solar HDX boiler is supplied pre-loaded with 7.5 litres of inhibitor liquid in the solar circuit of the hot water tank, which means the optimum proportion of inhibitor liquid is obtained on filling the circuit (see “Filling the Solar Circuit").
IMPORTANT: The inhibitor liquid must always be mixed with water before use, as otherwise it
could damage the installation.
IMPORTANT: DOMUSA TEKNIK will only be liable for the correct functioning of the system if it
has been filled with DOMUSA TEKNIK inhibitor liquid.
IMPORTANT: Evolution Solar 30 HDX boilers are specifically designed to function with Ø12 mm
diameter tubes for the flow and return connection between the solar collector and the hot water tank. If you wish to use any other diameter, consult the DOMUSA TEKNIK customer service department.
9
3.7 Location of the solar collector
The choice of location for the solar collector is very important, as an unsuitable location could mean a reduction in the efficiency of the solar circuit due to incorrect orientation, shadows being cast on the solar collector, etc.
To correctly locate the solar collector, the calculation methods and reference tables figuring in the “Technical Building Code” (CTE, Section HE 4) should be carefully followed. DOMUSA TEKNIK
provides a calculation computer program for installers, which can be ordered through the website www.DOMUSA TEKNIK.es. However, it is recommended to bear the following indications
in mind when choosing the ideal location:
- Before deciding on the location, the accessibility of the site must be taken into account, both as regards the installation itself and for maintenance work on the solar collectors.
- The solar collector must face south.
- The solar collector should normally be installed with a slope 5º greater than the latitude of the location. Any difference from this angle will reduce its efficiency.
- For installations with integrated supports for slate, the tilt must be at least 27º, and for those with integrated supports for tiles, it must be at least 16º. The solar collector must be levelled on installation, so that the upper part is horizontal.
- According to the Technical Building Code, losses due to orientation/tilt and shade must not exceed the following values:
MAXIMUM LOSSES Case Orientation and tilt Shade Total General 10% 10% 15% Overlap 20% 15% 30% Architectural integration 40% 20% 50%
When installing the solar collector, ensure that no objects cast shadow on it, particularly in winter, when the sun is lower in the sky. The minimum distance from an obstacle the solar collector can be installed at depends on the height of the obstacle and the latitude of the site of installation, as shown in the table below:
Latitude 35º Latitude 40º Latitude 45º
Calculation of X Y x 1.75 Y x 2 Y x 2.25
A
scent (RS) Solar circuit return
Descent (ES) Solar circuit inlet
α
Slope
H
G
L
Y
X
Fig A
Evolution Solar HDX
10
3.8 Removal of combustion products
The combustion product exhaustion ducts must be installed by qualified personnel and must comply with current legislation and standards.
The Evolution Solar HDX boiler is a sealed oil-fired boiler, and the combustion products are therefore removed through an outlet pipe, with a separate air intake from outside. We recommend that the position of the outside exhaustion duct is as shown in the figures and in the table below:
Exhaustion duct position
Minimum distance
(mm)
A under a cornice
300
B between two horizontal ducts
1000
C from an adjacent window
400
D between two vertical ducts
1500
E from an adjacent ventilation grille
600
F under a balcony (*)
300
G under a window
600
H under a ventilation grille
600
I from a recess in the building
300
J from a corner of the building
300
K from the ground
2500
L from a vertical or horizontal duct or outlet (**)
300
M from a frontal surface at a distance of 3 metres from the fume outlet
2000
N as above, but with an opening
3000
(*) Providing the width of the balcony is not over 2000 mm. (**) If the pipe is made of materials sensitive to the action of the flue gases, this distance should be over 500 mm.
Note: Spanish law also stipulates that the end of the exhaustion duct must be at a distance of at least 400 mm from any air intake
opening, and from the wall.
IMPORTANT: All accessories used for combustion product removal and air intake are to be
those supplied by DOMUSA TEKNIK.
11
4 REMOVAL OF COMBUSTION PRODUCTS
4.1 ø80 dual duct system for combustion product removal and air intake (type C53)
For this type of boiler, combustion product removal and air intake take place through separate Ø80 mm dual ducts, using the Ø80 dual duct outlet kit, code CGAS000265. Evolution Solar HDX boilers are equipped with this type of fume removal by default.
The maximum length of piping that can be installed is 12 metres, which is the maximum sum of the metres of the air intake duct and the metres of the combustion product removal duct. Each 90º elbow, or each two 45º elbows, will reduce the available length by 1 m. One horizontal metre is the equivalent of 2 metres.
It is recommended to fit the exhaustion duct in a slightly upwardly-inclined direction, at around 2º ­3º, thus preventing any water and condensation from dripping out.
Dual ex hausti on duct k it 80/100
Co de C GAS000265
Tubo 1m 80i nox Cod. CGAS00 0145 Tubo 1m 100 inox
Cod. CGAS 0 00268
Tubo 1m 100 pp
Cod. CGAS 00 0355
90º elb ow 80 inox Cod . C GAS000147
90º el bo w 100 inox Cod. CGA S000267
90º el bow 100 PP Cod. CGAS000358
45º elbo w 80 inox Cod. CG AS000148
45º elbow  100 i nox Cod . C GAS000266
45º el bow 100 PP Cod. CGA S000357
NOTE: For this co nf igu r ation pipes and e lbo ws ?80 are for air intake.
Examples of installation:
Evolution Solar HDX
12
4.2 Changing from dual duct fume removal to coaxial fume removal
The Evolution Solar HDX boiler has a Ø80 dual duct system for combustion product removal and air intake. If you prefer the combustion products to removed by means of a Ø80/125 coaxial tube, you may use the Ø80/125 coaxial tube adaptor kit (supplied to order), code CGAS000213 + code CGAS000222.
Adaptor for coaxial tube 80/125
Code CGAS000213 + CGAS000222
The changeover may be made with two different assembly configurations:
1. Rear outlet: simply remove the combustion air intake from the boiler, unscrewing the three screws holding it in place, mount the adaptor on the fume outlet towards the rear, and use the flexible air inlet tube to connect it to the adaptor T.
2. Side or top outlet: the procedure is the same, but for side mounting of the adaptor kit a 90º Ø80 elbow (code CGAS000147) needs to be fitted before the adaptor at the fume outlet.
The two configurations are shown in the figures below:
Combustion air intake
Rear outlet
Side outlet
Cod o 90º Ø100
Cód. CGAS000267
13
4.3 ø80-125 concentric horizontal duct for combustion product removal and air intake (type C13)
Combustion product evacuation and air intake can be made using concentric Ø80 mm ducts for combustion product evacuation and Ø125 mm ducts for air intake, using the 1m Ø80-125 horizontal outlet kit, code CGAS000189.
The maximum horizontal length from the boiler, including the kit terminal, is 6 metres for this model. Each 90° elbow, or two 45° elbows, will reduce the available length by 1 metre. One horizontal metre is the equivalent of 2 metres.
It is recommended to fit the pipe in a slightly upwardly-inclined direction, at around 2º - 3º, to prevent any water or condensation from dripping out.
1m horizontal duct kit 80/125
Code CGAS000189
90º coaxial elbow 80/125
Code CGAS000182
45º coaxial elbow 80/125
Code CGAS000183
1m coaxial tube 80/125
Code CGAS000184
Examples of installation:
L 6 mts. (EV SOLAR 30 DX)
Evolution Solar HDX
14
4.4 ø80-125 concentric vertical duct for combustion product evacuation and air intake (type C33)
Combustion product evacuation and air intake can be made using concentric Ø80 mm ducts for combustion product evacuation and Ø125 mm ducts for air intake, using the Ø80-125 vertical duct kit, code CGAS000231.
The maximum vertical length from the boiler, including the kit terminal, is 7 metres. Each 90° elbow, or two 45° elbows, will reduce the available length by 1 metre. One horizontal metre is the equivalent of 2 metres.
Vertical outlet kit 80/125
Code CGAS000231
Black tile 80 / 125
Code
CGA
S0000
74
45º elbow 80/125
Code CGAS000183
90 º elb ow 80/125
Code CGAS000182
1m coaxial duct 80/125
Code CGAS000184
Black tile 80/125
Code CGAS000075
Examples of installation:
L 7 mts.
15
5 STARTING-UP THE BOILER
5.1 Prior warnings
Repair and maintenance of the boiler must be carried out by a qualified professional, authorised by DOMUSA TEKNIK. For optimum functioning and conservation of the boiler, it should be serviced annually.
Carefully read this instructions manual and keep it in a safe, easily-accessible place. Before any servicing, disconnect the boiler from the mains and cut off the oil supply. Any
manipulation of the sealed parts of the boiler is prohibited. DOMUSA TEKNIK will not be liable for any damages caused by failure to follow these instructions.
5.2 Filling the domestic hot water tank
The hot water tanks must be filled before filling the heating circuit. Open the flow of domestic hot water to the hot water tank, and turn on a hot water tap in the installation. When the tap begins to run freely, turn it off, as this means the hot water tank is full.
5.3 Filling the heating circuit
To fill the heating circuit installation, open the fill valve
(20)
until a pressure of 1 - 1.5 bars appears
on the “
boiler pressure
” setting on the display. The circuit should be filled slowly and with the
automatic air bleed valve caps
(16)
and
(11)
loose, to let the air out of the installation. The air should also be bled from the rest of the installation using the air bleed valves provided. When the installation has been filled, close the fill valve.
Evolution Solar HDX boilers have a pressure sensor
(13)
for controlling the pressure of the installation. If the installation pressure drops below a minimum of 0.5 bar, the boiler will not switch on and a low pressure alarm will appear on the display ("AP").
NOTE: Switching on the boiler with no water inside could result in serious damage.
5.4 Start-up In order for the guarantee to be valid, the boiler must be started up by an official DOMUSA
TEKNIK Technical Assistance Service. Before beginning start-up, the following must be complied
with:
- The boiler must be electrically connected to the mains.
- The installation must be filled with water (the manometer must indicate 1 - 1.5 bar).
- Fuel must be reaching the burner at a pressure of no more than 0.5 bar.
- The solar circuit must be filled up to the level socket.
5.5 Installation delivery
After the initial start-up, the Technical Assistance Service will explain to the user how the boiler functions, making any observations they consider relevant.
The installer is responsible for clearly explaining to the user the functioning of any control or regulation device forming part of the installation but not supplied with the boiler.
Evolution Solar HDX
16
5.6 Filling the solar circuit
The Evolution Solar HDX boiler is supplied with the inhibitor liquid required for its correct functioning. The rest of the solar circuit needs to be filled with tap water to obtain a perfect mix of heat-carrying fluid and for optimum circuit functioning. The circuit is filled by connecting a hose to the filling inlet on the solar hot water tank.
To correctly fill the solar circuit, proceed as follows:
- Connect the filling inlet to the water mains with a hose.
- Connect a hose to the level socket and lead it to a container.
- Open the level socket valve.
- Turn on the water supply.
- When liquid begins to come out of the level socket, cut off the water supply to the filling inlet.
- Close the level socket valve when liquid stops coming out of it.
If the solar circuit should need to be drained and filled while carrying out maintenance, ensure it is filled with the correct mix of water and inhibitor liquid, with at least 30% inhibitor liquid (minimum 15 litres).
IMPORTANT: DOMUSA TEKNIK will only be liable for the correct functioning of the system if it
has been filled with DOMUSA TEKNIK inhibitor liquid.
17
5.7 Solar pump functioning in manual mode
For start-up and maintenance of the solar circuit, the solar circulation pumps need to be switched on manually. The Evolution Solar HDX boiler allows the solar pumps to be activated using the "HN"
setting on the digital display. To do this, use the MODE touch button to browse to this setting and the On touch button
(25)
to access it. When you have accessed the setting, use the touch button on
the right of the display
(27)
to change the value, enabling the solar pumps with the following
values selected:
"0" – Automatic functioning mode (default value). "1" – Solar pump is switched off. "2" – The solar pump is activated. "3" – Solar pump speed activated defined " U5" parameter.
When you have selected the desired manual functioning mode, place your finger on the On touch button again to record the value and exit the "HN" setting. Operating modes 0, 1 and 2 will remain activated indefinitely, until another operating mode is selected (even if the boiler is switched off and switched on again). However, for safety reasons, manual modes 3 and 4 will only remain active while they are selected, and the "HN" setting cannot be exited until another mode is selected (if the boiler is switched off at this point, it will return to automatic operating mode when it is switched on again).
IMPORTANT: The solar circuit must only be serviced and installed by sufficiently qualified
personnel, in accordance with current national and local installation and safety legislation and standards.
5.8 Starting up the solar pump with timer
For correct system start-up, the solar circuit is equipped with 2 circulation pumps, one of which has a timer (BST). When the system has started up, after ensuring that the heat-carrying liquid is flowing through the whole circuit and when the flow is stabilised (15 minutes by default), the electronic control switches off the pump with a timer, as one pump is sufficient to maintain the flow, thus optimising the electricity consumption of the solar circuit.
To change the switch-off time for the pump with a timer, use the MODE touch button to browse to the "
Switch-off time for solar pump with timer
" display option. When this option is displayed, touch
the "+/-" symbols on the touch button on the right of the display
(27)
to select the desired time. The
switch-off time can be adjusted between OFF and 5 and 30 minutes. To disable the switch-off function for the pump with a timer, select "
OFF
" for the pump to remain continuously switched on
while there is solar energy.
IMPORTANT: The solar circuit must only be serviced and installed by sufficiently qualified
personnel, in accordance with current national and local installation and safety legislation and standards.
5.9 Checking the solar circuit seal
For the solar circuit to function correctly, it is very important to ensure it is correctly sealed. To do this, switch on the two solar pumps in manual mode by selecting “2” on the “
HN
” setting on the
digital display (see “
Solar pump functioning in manual mode
”).
After 15 minutes have elapsed and with the pumps still switched on, check there are no leaks anywhere in the solar circuit. Make sure no siphons have been created in the installation, as this would prevent correct drainback of the solar circuit.
Evolution Solar HDX
18
IMPORTANT: Insufficient sealing of the solar circuit and a siphon effect caused by incorrect
layout of the piping can cause serious operating problems.
5.10 Adjusting the solar circuit flow
For the solar circuit to function correctly it is essential to regulate its flow. The Evolution Solar HDX boiler has a manual adjustment device with a window for viewing the flow, which is supplied totally open at maximum flow and should be adjusted to 2 l/min. To do this, when the solar circuit has been filled, carefully proceed as follows:
1 - Select the "HN" setting on the display using the MODE
touch button. When you have selected it, access it using the On touch button.
2 - Select 2 on the touch button on the right of the display
(27)
. The two pumps will start up.
3 - Let the pumps run for at least 15 minutes, to ensure the
flow has stabilised.
4 - Repeat step 1 to switch off the solar pump with a timer,
selecting 3 on the "HN" setting.
5 - Remove the red wheel from the interlock switch and fit
it to the end of the flow regulator indicator. Turn the wheel to adjust the flow to 2 l/min, as shown on the display. When you have adjusted the flow, turn the red wheel back in its initial position again.
6 - Lastly, return to automatic solar pump functioning
mode, selecting the value 0 on the "HN" setting.
IMPORTANT: The solar circuit flow must be adjusted to 2 l/min. For installations that do not
reach a flow of 2 l/min, it is recommended to leave the flow regulator totally open.
19
6 DIGITAL DISPLAY:
The Evolution boiler is electronic and includes a digital display
(22)
showing the actual temperatures, the setpoint temperatures and the pressure of the installation. In standby mode, the actual boiler temperature in ºC is shown on the display. The rest of the available display options can be browsed by touching the MODE button below the display, as follows:
MODE tou ch bu tto n
Digital display
Repeatedly place your finger on the MODE touch button to select the different display options. When the desired option has been selected, it will return to standby after 20 seconds have elapsed.
The following table shows the different display options:
Standby. The actual boiler temperature is shown.
Actual boiler temperature.
Actual temperature of the hot water stored in the back-up hot water tank.
Actual flow temperature of the underfloor heating installation (option SRX2/EV only)
Boiler setpoint temperature selected using the corresponding touch button
(23)
.
Underfloor heating installation flow setpoint temperature selected using the corresponding touch button
(23)
.
(option SRX2/EV only)
Evolution Solar HDX
20
DHW setpoint temperature for the back-up hot water tank selected using the corresponding touch button
(27)
.
Actual boiler pressure, measured by the Pressure Sensor
(13)
.
Actual Solar Collector temperature.
Actual temperature of the domestic hot water stored in the solar accumulator.
Maximum desired setpoint temperature for the hot water stored in the solar accumulator.
Manual solar pump operation setting. This setting should only be changed by qualified personnel during start-up of the boiler’s solar circuit.
Switch-off time for the solar pump with a timer. This setting must only be modified by qualified personnel. If there is an error in this setting, it could cause malfunctioning of the boiler’s solar circuit.
The solar pump speed BS.
Indication of the heating demand status of each circuit connected to the boiler.
The desired display contrast can be adjusted using the touch button on the right of the display
(27)
.
21
7 TEMPERATURE SELECTION
7.1 Selecting the boiler set point temperature
The desired boiler operating temperature is selected using the touch button, as shown in the figure. To select the desired temperature, touch the "+" or "-" symbols to increase or decrease the temperature. When the temperature has been selected, the display will return to standby mode after a few seconds.
The boiler setpoint temperature can also be selected by using the MODE touch button to browse to the “
boiler setpoint temperature
" display option. When the display shows this option, touch the "+
/-" symbols to select the desired temperature. If you wish to totally disable the boiler heating function (
Summer
mode), select the setpoint value
"OFF" by touching the "-" symbol until this value appears on the display. The permitted boiler setpoint temperature range is OFF and 30 - 85 ºC. Evolution model boilers are
condensing boilers. In order to obtain maximum boiler performance and energy savings, it is therefore recommended to select a setpoint temperature of 55-70 ºC, providing this is permitted by the heating system installed and the insulation conditions of your home.
7.2 Selecting the the DHW setpoint temperature of the back-up hot water tank
The desired DHW temperature is selected using the touch button, as shown in the figure. To select the desired temperature, touch the "+" or "-" symbols to increase or decrease the temperature. When the temperature has been selected, the display will return to standby mode after a few seconds. The DHW setpoint temperature range permitted is OFF and 15 - 65 ºC.
The DHW setpoint temperature can also be selected by using the MODE touch button to browse to the “
DHW setpoint temperature
" display option. When this option appears on the display, touch
the "+ /-" symbols to select the desired temperature. If you wish to totally disable the boiler’s DHW production function, select the setpoint value "OFF"
by touching the "-" symbol until this value appears on the display. In this case the boiler will only produce DHW through its solar heating system.
Evolution Solar HDX
22
7.3 Selecting the DHW setpoint temperature in the solar hot water tank
The temperature of the DHW in the solar hot water tank is selected by using the MODE touch button to browse to the "
Solar hot water tank DHW setpoint temperature
" viewing option. When this option appears on the display, select the desired temperature by touching the "+" and "-" symbols to increase or decrease the temperature. The DHW setpoint temperature range that may be selected for the solar hot water tank is 10 - 80ºC.
7.4 Selecting the underfloor heating flow setpoint temperature (with SRX2/EV kit option)
If the boiler is supplied with an optional SRX2/EV underfloor heating kit integrated, the desired flow temperature of the installation can be selected using the touch button as shown in the figure above. To select the desired temperature, touch the "+" or "-" symbols to increase or decrease the temperature. When the temperature has been selected, the display will return to standby mode after a few seconds.
The installation flow setpoint temperature can also be selected by using the MODE touch button to browse to the “
underfloor heating installation flow setpoint
" display option. When this option
appears on the display, touch the "+ /-" symbols to select the desired temperature. If you wish to disable the underfloor heating circuit function, select the setpoint value "
OFF" by
touching the "-" symbol until this value appears on the display. The flow setpoint temperature range permitted is OFF and 0 - 45ºC. To obtain optimum
performance from the underfloor heating system installed, we recommend selecting a setpoint temperature of 25 - 35 ºC, providing this is permitted by the heating system installed and the insulation in your home.
23
8 OPERATION
The Evolution Solar HDX boiler is designed to heat a heating installation and provide domestic hot water by solar collection. Optionally, a second heating circuit, heating circuit 2, may be connected to the installation to improve its performance.
The boiler also includes a DHW collecting and storage system whereby installation of the solar collectors supplied with the boiler optimises the use of the solar energy in the collection area, for economical, environment-friendly domestic hot water production. The solar functioning principle consists of heating the solar circuit liquid in the solar collectors and then exchanging the heat absorbed with the domestic hot water in the hot water tank. As an auxiliary source of energy to back the main source, the oil-fired boiler adds the necessary heat to obtain a suitable domestic hot water temperature, if the energy collected from the sun is not sufficient.
8.1 Solar circuit functioning
The Evolution Solar HDX boiler is equipped with a circuit, separate from the heating circuit, for the producing DHW using solar energy. This is called the “Solar Circuit”. This circuit basically consists of a dual-chamber DHW tank, for exchanging heat with the domestic hot water, two solar circulation pumps, a flow regulator and one or two solar collectors, for exchanging heat with the sun.
The functioning of the solar circuit is based on the drainback principle, whereby the heat-carrying liquid in the solar circuit does not completely fill the installation, maintaining the solar collector empty while there is no demand for solar energy and thus preventing freezing or overheating problems. When there is a demand for solar energy, the solar pumps start up so that all the air in the solar collector is conveyed towards the dual chamber of the solar hot water tank. The heat­carrying fluid circulates through the solar collector, collecting the energy provided by the sun and exchanging it with the domestic hot water stored in the solar hot water tank. When there is no demand for solar energy, the solar pumps stop and the heat-carrying fluid returns to the dual chamber of the hot water tank by the force of gravity, and the solar collector drains again (drainback).
Solar sensor "Scol"
Upper solar pump Lower solar pum
p
Hot water tank sensor "Si"
Air
Air
Heat-carrying fluid
Solar sensor "Scol"
Upper solar pump Lower solar pum
p
Hot water tank sensor "Si"
Air
Heat-carrying fluid
Solar circuit not activated Solar circuit activated
The boiler’s electronic control system manages the automatic functioning of the solar circuit, switching on the solar circulation pumps when the temperature difference detected is over 6 ºC.
Evolution Solar HDX
24
Also, the “
Maximum solar water tank DHW setpoint temperature
” display option can be used to limit the maximum desired DHW temperature in the solar hot water tank. When this temperature is reached, or when the temperature difference between the solar sensor “Scol” and the hot water tank sensor “Si” is less than 4ºC, the boiler’s electronic control system switches off the solar pumps.
For correct system start-up, the solar circuit is equipped with 2 circulation pumps, one of which has a timer (BST). When the system has started up, after ensuring that the heat-carrying fluid is flowing through the entire circuit and the flow is stabilised (15 minutes by default, see “
Starting up the solar
pump with timer
”), the electronic control disconnects the pump with a timer as one pump is
sufficient to maintain the flow, which optimises the solar circuit’s electrical energy consumption.
8.2 Heating Function
In this mode, select the desired boiler setpoint temperature (see "
Selecting the boiler setpoint
temperature
") and the temperature of room thermostat 1 (TA1) or remote control E20 (if the boiler is equipped with these). The burner and the heating pump of circuit 1 (BC1) will begin to function until the installation reaches the selected boiler setpoint temperature (or the temperature on room thermostat, if the unit has one). When the temperature of the installation drops below the selected boiler temperature, the burner will start up again, running the heating cycle.
If the DHW temperature in the boiler’s integrated back-up hot water tank is lower than the DHW setpoint temperature selected, the heating function will cut out and priority will be given to domestic hot water production, starting up the hot water tank feed pump.
The boiler heating function can be totally disabled (
Summer
mode) by selecting "OFF" as the boiler setpoint value. In this operating mode, only the DHW production function will remain enabled, providing there is a DHW tank connected to the boiler.
NOTE: When the heating function is disabled, circuit 2 will also be disabled if it is connected.
8.3 Domestic Hot Water production function of tank
In this mode to activate this mode, select the desired DHW setpoint temperature (see "
Selecting the
DHW setpoint temperature
"). The burner will igniteand and the DHW pump. When the tank reaches
the setpoint temperature selected it was ready to heat the heating circuit if it was on. If you wish to totally disable the boiler’s DHW production function, select the setpoint value "
OFF".
In this case DHW will only be produced by the boiler’s solar heating system.
25
8.4 Heating circuit 2 functioning (Optional)
All the models in the Evolution Solar HDX range of boilers have the option of controlling a second heating circuit. This requires the installation of a second circulation pump on the boiler. To correctly install this pump, carefully follow the instructions given in the “Installing heating circuit 2” section of this manual.
Heating circuit 2 will work with the selected boiler setpoint temperature (see “
Selecting the boiler
setpoint temperature
” ) and the temperature of room thermostat 2 (TA2) (if the boiler has one). The burner and the heating pump of circuit 2 (BC2) will begin to function until the installation reaches the selected boiler setpoint temperature (or the temperature on room thermostat 2 (if the unit has one). When the temperature of the installation drops below the selected boiler temperature, the burner will start up again, running the heating cycle.
NOTE: When the heating function is disabled, if OFF is selected circuit 2 will also be disabled.
8.5 Functioning with an SRX2/EV Underfloor Heating Kit (Optional)
The Evolution Solar HDX boiler may optionally be supplied fitted with an SRX2/EV underfloor heating kit (fitted to heating circuit 1). This kit basically consists of a motorised 3-way mixing valve and an underfloor heating installation flow temperature sensor.
The underfloor heating installation is worked by the electronic boiler control. The installation flow sensor is used to adjust the temperature, selecting the installation flow setpoint temperature using the boiler setpoint adjustment touch button on the control panel, between OFF, 0 and 45 ºC (see “
Selecting the Underfloor Heating flow setpoint temperature
”). In this operating mode, the electronic control sets the boiler setpoint temperature to 75ºC by default, and the installation flow temperature can be adjusted to the selected setpoint temperature using the mixing valve.
The boiler setpoint temperature can be changed using the MODE touch button to browse to the “
boiler setpoint temperature
" display option. When the display shows this option, touch the "+ /-"
symbols to select the desired temperature. If you wish, the SRX2/EV Underfloor Heating circuit function can be totally disabled, by selecting
"OFF" as the installation flow setpoint temperature.
NOTE: When the Underfloor Heating circuit function is disabled by selecting OFF as the
setpoint temperature, only circuit 1 will be disabled. Circuit 2 will continue to function.
Evolution Solar HDX
26
9 ADDITIONAL FUNCTIONS
The Evolution Solar HDX boiler is equipped with an electronic control for efficiently regulating the automatic functioning of the boiler. It also has the following additional control features:
9.1 Pump anti-block function
This function prevents the boiler circulation pumps from seizing up if they have been out of use for a long period. This system remains enabled while the boiler is plugged into the mains.
9.2 Anti-frost function
This function protects the boiler from freezing up during cold weather. If the boiler temperature drops to below 6 ºC, the heating circulation pump will start up. If the boiler temperature continues to drop and reaches 4 ºC, the burner will start up, heating the installation. When this function has been activated, it will continue working until the boiler reaches 8 ºC. This system remains on standby while the boiler is plugged into the mains.
9.3 Telephone relay connection
The Evolution boiler is designed to enable a phone relay to be connected for switching the boiler on and off. This feature allows the boiler to be switched on and off remotely, from any location, by means of a phone call. The relay is connected to the boiler via terminal strip J7 (see “Electrical Connection Diagram”). When the telephone relay contact closes the boiler switches on. When the contact opens, the boiler switches off and remains in anti-frost protection and pump anti-block mode.
9.4 Anti-legionella function (optional)
This optional function prevents the bacteria causing legionnaire’s disease from proliferating in the hot water accumulated in the hot water tank. Every 7 days, the temperature of the water in the hot water tank is raised to 70 ºC to kill any such bacteria. This function will only be enabled if the boiler is left switched on.
The boiler is supplied with this function disabled. To enable it, carefully read the "Installation Instructions" section. We recommend that the operation for enabling this function is carried out by qualified personnel.
9.5 Boiler pressure sensor function
This function prevents boiler failure caused by a low water level or excess pressure in the boiler. The pressure is detected by a pressure sensor
(13)
, and its value appears on the control panel display
(see “
Digital display
”). If the pressure drops below 0.5 bar, the electronic control blocks boiler functioning and triggers the “AP” alarm on the display. If boiler pressure exceeds 2.5 bar, the "HI" warning will flash on the display to warn of the excess pressure. If this should occur we recommend calling the nearest Technical Assistance Service, and slightly draining the boiler.
9.6 Room thermostat connection
The boiler has two terminal strips, TA1 and TA2, for connecting room thermostats or room chronothermostats (J5 and J6, see "
Electrical Connection Diagram
”). This allows the heating mode for each circuit installed to be switched off according to the room temperature. To suitably connect them, first remove the bridge joining the terminals of terminal strip TA
1
, and to connect TA2, simply
connect the thermostat to the terminal strip. Installing a room thermostat will optimise the installation’s performance, adapting the heating to
the requirements of your home and obtaining enhanced comfort. Also, if the thermostat allows the
27
hours of functioning to be programmed (chronothermostat), it can adapt the heating system to the hours of use of the installation.
9.7 Disconnecting the oil-fired boiler’s back-up energy supply
The Evolution Solar HDX boiler’s electronic control allows the oil-fired boiler’s function as an auxiliary power source backing the solar energy to be disconnected, so that the only hot water produced by the boiler will be that obtained from the solar energy of the installation site, with only the solar circuit functioning. To disconnect the oil-fired boiler’s back-up energy supply, select the
"
OFF
" as the DHW setpoint temperature (see "
Selecting the DHW setpoint temperature of the back-
up hot water tank
").
9.8 Disconnecting the solar circuit
The Evolution Solar HDX boiler’s electronic control enables the solar circuit functioning to be disconnected, if this should be required for maintenance or start-up. If the solar circuit functioning is disconnected, the boiler will work as a standard oil-fired storage heating and hot water boiler, and will not use the solar energy from the site where it is installed.
To disconnect the solar circuit, firstly disconnect the "Si" and "Scol" sensors from the sensor terminal strip J3 ("Si": terminals 19-21, and "Scol": terminals 17-18), and fit electrical bridges in their place, shorting the inputs of these sensors (see “Electrical Con
nection Diagram
").
9.9 Keypad block function
This function protects the control panel from being accidentally or erroneously pressed while it is being cleaned, by children or by unauthorised persons. When this function is enabled, the electronic control will not react when any of the symbols or touch buttons on the control panel are pressed.
To lock the keypad, keep your finger on the RESET touch button for 5 seconds. The word "LOC" will flash on the display until the control panel is unlocked again.
To unlock the keypad, place your finger on the RESET touch button again for 5 seconds. The display will then return to its normal status.
10 E20 REMOTE CONTROL (OPTIONAL)
A remote control (E20) can optionally be supplied together with the Evolution Solar HDX boiler. This remote control can be used to fully operate the boiler from any room in the home in which it is installed. The E20 remote control governs the settings of heating circuit 1 and the installation’s domestic hot water production (where the case may be).
This remote control allows the hours of home comfort to be programmed for heating circuit 1, adjusting the installation to the particular requirements of the home by measuring the room temperature and consequently adapting the installation temperature. The remote control can also be used to adjust the DHW and heating setpoint temperatures at any time, and for viewing the different boiler operation settings. It also warns of any functioning anomalies affecting the boiler.
The E20 remote control may optionally be connected to an external sensor, for measuring the outside temperature. When this option is installed, the remote control can adjust the home comfort level (circuit 1) according to the weather conditions at each particular time, optimising fuel consumption and heating comfort in the home.
Evolution Solar HDX
28
The E20 remote control takes over the control of the boiler when it is connected to it. The different selectable boiler temperatures must be modified using the remote control. It is easy to install, only requiring 2 wires for communication between the boiler and the E20 control. It is connected to the boiler by connecting the two wires on terminal strip J4 (see “Electrical Connection Diagram”). For correct installation and functioning, carefully read the instructions enclosed with the remote control.
The following sections contain a general explanation of the E20 remote control’s different operating modes and options.
10.1 Functioning without an outdoor sensor Conventional heating installation (direct circuit)
The maximum temperature for heating circuit 1, the scheduled heating times and the desired room temperatures can be selected on the remote control. The E20 remote control will calculate the boiler temperature required at each particular time, depending on the temperature of the room, and it will activate or disable the heating mode of circuit 1 depending on the heating times and room temperatures programmed.
Heating installation with an SRX2/EV underfloor heating kit (mixed circuit)
If the boiler has an SRX2/EV Underfloor Heating Kit installed on circuit 1, the underfloor heating circuit is adjusted and controlled from the boiler control panel (see "
Functioning with an
underfloor heating kit
").
The E20 remote control can be used to programme the desired heating times and room temperatures.
10.2 Functioning with an external sensor (Optional)
If the E20 remote control is fitted with an outdoor temperature sensor, it can calculate the heating temperature of heating circuit 1 according to the outside weather conditions at each particular time, with optimum adjustment of the heating installation conditions for improved comfort in the home and energy savings.
Conventional heating installation (direct circuit)
The maximum temperature, an operating curve for heating circuit 1 (see instructions enclosed with the E20 remote control) and the desired heating times and room temperatures can all be selected on the remote control. The E20 remote control calculates the required boiler temperature at each particular time, depending on the temperature inside the home and the outside weather conditions, in accordance with the operating curve selected (setting HEATSLOPE 1 on the E20), switching the heating on and off in accordance with the heating times and the room temperatures programmed.
Heating installation with an SRX2/EV underfloor heating kit (mixed circuit)
If the boiler has an SRX2/EV underfloor heating kit installed on circuit 1 and the control of this kit is activated on the E20 remote control using the HEATSLOPE 2 setting (see instructions enclosed with the E20 remote control), the adjustment and control of the underfloor heating circuit flow temperature will be performed by the remote control. The E20 will calculate the required flow temperature at each particular time, depending on the temperature inside the home and the outside weather conditions, in accordance with the operating curve selected (the HEATSLOPE 2 setting on the E20 remote control). For mixed underfloor heating circuits, we recommend selecting operating curves of less than 0.8.
The boiler setpoint temperature will be fixed at 75ºC and can be changed using the boiler control panel. This setpoint temperature can be changed by using the MODE touch button to browse to the “
boiler setpoint temperature
" display option. When the display shows this option,
touch the "+ /-" symbols to select the desired temperature.
29
The E20 remote control can also be used to select the maximum flow temperature for heating circuit 1 and to programme the desired heating times and room temperature. The E20 remote control will switch the heating function of this circuit on and off in accordance with the heating times and room temperatures programmed.
NOTE: For mixed underfloor heating circuits, we recommend selecting a maximum flow
temperature NO HIGHER THAN 45 ºC, to protect the underfloor heating installation from overheating.
10.3 DHW mode functioning
The E20 remote control can be used to select up to two DHW temperatures and the desired DHW production times. The E20 remote control regulates the DHW tank temperature at each particular time, and enables or disables the DHW function according to the times scheduled.
The E20 remote control also has an option for enabling a function to protect against legionella bacteria (see instructions enclosed with the E20 remote control).
10.4 Telephone relay function
The E20 remote control is designed for connection to an external telephone relay. If a telephone relay is connected to the E20 remote control, the heating mode of heating circuit 1 and the DHW mode can be switched on and off from anywhere in the world, simply by making a telephone call (see instructions enclosed with the E20 remote control).
11 SHUTTING DOWN THE BOILER
To switch off the boiler, place your finger on the power touch button
(25)
for 1 second. In Off mode, while the boiler is plugged into the mains and connected to the fuel installation, its heating and DHW functions will be switched off but the anti-frost protection and pump anti-block functions will remain activated.
To shut down the boiler functioning completely, unplug it from the mains and cut off the fuel supply.
12 DRAINING THE BOILER
The water is drained from the boiler by opening the air drain valve
(1)
inside the boiler (on the lower right hand side on opening the door). Connect a flexible tube to this valve and run it to a drain. After draining the boiler, close the valve again and remove the flexible tube.
13 DRAINING THE SOLAR CIRCUIT
If you need to drain the solar circuit, connect a hose to the solar accumulator drain valve
(2)
and run the hose to a suitable container (minimum capacity 19 litres), so that the heat-carrying fluid can be reused if necessary. Open the drain valve and the level valve. After draining the circuit, close the shut­off valves and disconnect the hoses.
Evolution Solar HDX
30
14 SAFETY CUT-OUTS
The boiler’s electronic control system may activate the following safety cut-outs to stop the boiler functioning. When one of these safety cut-outs occurs, the boiler will stop functioning, a cut-out code will flash on the display and the red alarm warning pilot light will flash on the control panel.
If any of the safety cut-outs described below should occur repeatedly, switch off the boiler and call your nearest official technical assistance service.
14.1 Temperature safety cut-out
When this cut-out occurs, the alarm code “EAt” (temperature alarm) will begin to flash on the digital display
(19)
. The burner
will switch off and stop heating the installation.
This occurs when the boiler exceeds a temperature of 110 ºC. To unblock it, wait until the boiler drops to below 100ºC and press the button on the safety thermostat, located inside the boiler on the underside of the electrical box, after first having removed the button cover.
14.2 Burner cut-out
When this cut-out occurs, the alarm code “EAQ” (burner alarm) will begin to flash on the digital display
(19)
. The burner will
switch off and stop heating the installation.
This occurs as a result of an anomaly in the burner
(18)
or in the
fuel installation. To unblock it, press the illuminated button that lights up on the burner.
14.3 Low pressure cut-out
When this cut-out occurs, the alarm code “EAP” (pressure alarm) will begin to flash on the digital display
(19)
. The burner and the boiler circulation pumps will switch off, cutting off the heating and water flow to the installation.
This occurs when the boiler pressure drops to below 0.5 bar, preventing the boiler from functioning when the water is drained from the installation, due to either leakage or maintenance operations. To unlock it, fill the installation again until a pressure of 1
- 1.5 bar appears on the “
boiler pressure
” setting on the display
(19)
.
31
15 BOILER MAINTENANCE
To maintain the boiler in perfect working order, a yearly overhaul should be performed by DOMUSA TEKNIK’s authorised personnel.
Cleaning the boiler
To keep the boiler in perfect working order, we recommend cleaning the boiler chamber, exhaustion ducts and condenser on a yearly basis. A cleaning brush of a suitable size for cleaning the inside of the exhaustion ducts is supplied with the boiler for this purpose. This brush is located at the rear of the boiler, beside the condenser.
The combustion chamber and exhaustion ducts should not be cleaned using chemical products or hard steel brushes. After any cleaning operation has been carried out, it is important to run several ignition cycles to check all the elements are functioning correctly.
For correct cleaning, the following recommendations should be carefully observed:
Cleaning the boiler body
- Open and remove the outer door of the boiler.
- Remove the burner
(21)
by unscrewing the fixing nut on the top of the burner.
- Remove the combustion chamber door and the exhaustion duct cover, unscrewing the six fixing nuts beside them.
- Clean the exhaustion ducts on the cast iron body, using the cleaning brush supplied with the boiler.
- Clean the boiler combustion chamber. We recommend using a soft brush for scraping the combustion chamber surfaces, and a blower to remove scale.
- After cleaning, replace the combustion chamber door, the exhaustion duct cover, the burner and the outer door of the boiler.
Cleaning the condenser
- Remove the rear extension on the sides of the boiler to access the condenser on the rear of the boiler body.
- Open the top cover of the condenser
(1)
to access its exhaustion ducts. To open this cover,
firstly release the two side closures
(7)
, turn the locking plate
(2)
anti-clockwise and pull the
cover upwards to remove it.
- Remove the fume deflectors
(6)
inside the fume outlets.
- Clean the exhaustion ducts using the cleaning brush supplied with the boiler. Scale could fall out of the lower condenser cover and come out of the condensation drain, and it is therefore recommendable to pour water into the top of the condenser, for more effective cleaning. This water will be automatically discharged through the condensation drain.
- To clean the outer part of the condenser cylinder, remove the three screws
(3)
and then remove
the metal ring
(4).
Take out the seal
(5)
and use the brush to clean it. Then put the components
back in place again and replace and tighten the three screws and the metal ring.
- If the lower condenser cover
(9)
needs cleaning, remove the side cover of the boiler to access it. Firstly remove the bracket (8) holding it in place and pull on it to open it. Then pull the lower cover down to open and clean it.
- After cleaning, replace the fume deflectors, the top condenser cover and the top outer cover of the boiler. Then put the cleaning brush back inside the boiler.
Evolution Solar HDX
32
- The condensation siphon should be cleaned once a year. To do this, remove it and wash it in soapy water. Replace the siphon after cleaning.
C
leaning brush
1
2
3 4
5 6
7
8
9
Anti-frost protection
The Evolution Solar HDX boiler has a function for preventing frost damage to the installation. This will function as long as the appliance remains plugged into the mains. Despite this function, and particularly in areas with very cold weather, we recommend taking precautions in order to prevent damage to the boiler. It is advisable to add anti-freeze to the water in the heating circuit. If the boiler is to be out of use for long periods of time, we recommend draining all the water and leaving it empty.
Boiler water characteristics
In areas with water hardness of over 25-30ºF, treated water must be used in the heating installation to avoid any scale deposits on the boiler.
It should be noted that even a few millimetres of scale will greatly reduce the boiler’s heat conductivity, causing a major drop in performance.
Treated water must be used in the heating circuit in the following cases:
- Very large circuits (containing a large amount of water).
- Frequent filling of the installation.
If repeated partial or total draining of the installation is necessary, we recommend filling it with treated water.
Heat-carrying solar fluid
The boiler’s solar circuit uses a heat-carrying fluid, which is a mix of water (70%) and inhibitor liquid (30%). This optimises its functioning and helps it remain in perfect working order.
You should check that the heat-carrying fluid in the solar circuit is in good condition. Check that the proportions of the mix of water and inhibitor liquid are correct (70/30).
The heat-carrying fluid needs to be renewed every 3 years, with a minimum concentration of 30% of inhibitor liquid (minimum 15 litres).
33
16 CIRCULATION PUMP FLOW CURVES
The following graphs may obtain hidromotriz pressure available at the facility off the boiler, considering the pressure loss of the boiler and the performance curves of the pump.
16.1 Characteristic heating pump
16.2 Regulation pump heating
To regulate the speed of the circulation pump BC1 by navigating to the "UB" parameter and touching on the touch button
(28)
to access it touch MODE button. Once inside the setting, using the jog dial on the right side of the display
(24)
the value is changed. After selecting
the desired speed, to touch the touch button to record the value and exit the parameter "UB".
ATTENTION: Any interference in the operation and installation of the heating circuit must be done
by suitably qualified personnel, always respecting current legislation and installation and safety standards, both national and local level.
16.3 Pressure drop Evolution Solar 30 HDX: Evolution Solar 40 HDX:
Evolution Solar HDX
34
17 DIAGRAMS AND MEASUREMENTS
17.1 Evolution Solar 30 HDX
1
6
4
0
1110
L
3
0
0
5
5
5
7
0
5
1
4
1
3
1
5
1
8
150
485
330 75 90 400
1
4
2
6
2
2
5
1
4
2
5
1
5
4
0
7
3
5
4
2
3
9
70
6
3
5
4
9
5
140
120
270
IC: Heating Flow. IC': Optional Heating Flow. RC: Heating return.
EAS: Domestic cold water inlet. IAS: Domestic hot water inlet.
MODEL
IC/IC'
RC
EAS
IAS
ES RS
DIM.
L
SC: Condensation outlet, 1" H.
EV SOLAR 30
HDX
3/4"M 910
ES: Solar outlet.
EV SOLAR 40
HDX
1"M
3/4"M 1/2”M
960
RS: Solar return. TR: Recirculation socket. SH: Fume exhaustion duct, Ø100. EA: Combustion air intake, Ø80. VS: Domestic hot water safety valve.
35
17.2 Evolution Solar 30 HDX with SRX2 / EV underfloor heating kit
1
6
4
0
1110
910
3
1
0
5
5
5
7
0
5
1
4
1
5
1
5
2
0
150
140
485
330 75 90 400 70
1
4
2
5
2
3
5
6
1
5
1
4
2
5
1
5
4
0
7
3
5
4
2
3
9
4
2
5
270
4
6
0
120
IC: Heating Flow. IC': Optional Heating Flow.
RC: Heating return. EAS: Domestic cold water inlet.
IAS: Domestic hot water inlet.
MODEL
IC/IC'
RC
ICM/RCM EAS
IAS
ES RS
DIM
L
SC: Condensation outlet, 1" H. VS: Domestic hot water safety valve.
EV SOLAR 30 HDX
+ SR
3/4"M 3/4"M 3/4"M 1/2"M 910
ICM: Mixed Heating Flow. RCM: Mixed Return Flow.
EV SOLAR 40 HDX
+ SR
1"M 1"M 960
ES: Solar outlet. RS: Solar return. SH: Fume exhaustion duct, Ø100. EA: Combustion air intake Ø80. TR: Recirculation socket.
Evolution Solar HDX
36
18 TECHNICAL CHARACTERISTICS
EVOLUTION SOLAR HDX 30 HDX 40 HDX
condensación
Boiler type -
Calef. y ACS acumulación
Rated heat output P
rated
kW 30 40 Useful heat output P4 kW 28,7 38,7 Useful heat output (30%) P1 kW 8,5 12,4 Seasonal space heating energy efficiency
Ƞ
S
% 91 92
% (PCI) 97,96 97,29
Useful efficiency
Ƞ
4
% (PCS) 92,38 91,74
% (PCI) 103,45 104,15
Useful efficiency (30%)
Ƞ
1
% (PCS) 97,55 98,21
Auxiliary electricity consumption at full load el
max
kW 0,226 Auxiliary electricity consumption at part load el
min
kW 0,078 Auxiliary electricity consumption in standby mode PSB kW 0,001 Standby heat loss P
stby
kW 0,135 0,17 Emissions of nitrogen oxides NOx mg/kWh 118 119 Declared load profile - XXL Water heating energy efficiency
Ƞ
wh
% 68 67
Daily electricity consumption Q
elec
kWh 0,533 0,402
Daily fuel consumption Q
fuel
kWh 36,709 37,890 Hot water tank capacity Lts 130 130 Solar accumulator capacity Lts 250 250
D.H.W. production in 10 min. t=30ºC without solar energy input
Lts
321 321
D.H.W. production in 1 hour t=30ºC without solar energy input
Lts
846 846
DHW recover time from 35 to 58 ºC min 8 Heating temperature range ºC OFF, 30-85 DHW temperature range ºC OFF, 15-65 Solar accumulator temperature adjustment ºC 10-80 Heating security maximum temperature ºC 110 Heating security maximum pressure bar 3 DHW security maximum pressure bar 7 Heating expansion vessel capacity Lts 8 12 Boiler water capacity Lts 19,2 23,2 Water pressure drop mbar 163 272 Flue gases temperature ºC 67 83 Flue gases volume m3 0,114 0,175 Maximum flue gases flow Kg/s 0,0132 0,0186 Flue gases pressure drop mbar 0,20 0,21 Combustion chamber lenght mm 300 400 Combustion chamber type - húmeda + 3 paso de humos Burner type - ON/OFF Electric power - ~220-230 V - 50 Hz - 200 W Weight Kg 421 448
37
19 CONNECTION DIAGRAM
There are a series of removable terminal strips located on the rear of the control panel, for connecting the various options and components of this model. To connect them correctly, carefully follow the indications shown in the diagram below:
19.1 Evolution Solar 30 HDX
F: Phase. N: Neutral. BA: Solar capture pump. BC1: Heating pump, circuit nº 1. BC2: Heating pump, circuit nº 2. BV: Domestic hot water pump. Q: Burner. bc10: Burner terminal nº 10. BS: Solar pump. E20: E20 remote control (optional). TA1: Room thermostat, circuit nº 1. TA2: Room thermostat, circuit nº 2.
PWMc: Heating Cable PWM. PWMs: PWM Solar Cable. SC: Boiler sensor. Sacs: Domestic hot water sensor. Si: Lower solar accumulator sensor. Scol: Solar collector sensor. J1: Supply connector. J2: Component connector. J
3
: Sensor connector.
J
4
: Remote control connector.
J5: Room thermostat connector 1. J6: Room thermostat connector 2. J7: Phone relay connector.
Evolution Solar HDX
38
19.2 Evolution Solar 30 HDX with SRX2 / EV underfloor heating kit
F: Phase.
N: Neutral. BA: Solar capture pump. BC1: Heating pump, circuit nº 1. BC2: Heating pump, circuit nº 2. BV: Domestic hot water pump. M: 3-way valve motor. V3V: Floor heating mixing valve. Q: Burner. bc10: Burner terminal nº 10. BS: Solar pump. E20: E20 remote control (optional). TA1: Room thermostat, circuit nº 1. TA2: Room thermostat, circuit nº 2. SC: Boiler sensor. Sacs: Domestic hot water sensor.
Sr: Underfloor heating sensor. Si: Lower solar accumulator sensor. Scol: Solar collector sensor. J1: Supply connector. J2: Component connector. J3: Sensor connector. J4: Remote control connector. J
5
: Room thermostat connector 1.
J
6
: Room thermostat connector 2.
J7: Phone relay connector.
J8: Leading power connector. J
9
: V3V connector underfloor. PWMc: Heating Cable PWM. PWMs: PWM Solar Cable.
39
20 ELECTRICAL DIAGRAM
20.1 Evolution Solar HDX
Red
Red
2829
30
J7
SP
Supply Card
J8
R
Display Card
J8
S2
ON
1 2 3 4
ON
S1
12
T
H
C
2
1
black
White
Pin
k
T
S
C
2
1
Black
Red
Pink
TS: Safety thermostat.
TH: Fumes thermostat
R: Telephone relay. SP: Pressure sensor.
J7 Telephone relay connector. J8: Communication connector between plates. S1,S2: Boiler model selector.
Evolution Solar HDX
40
20.2 Evolution Solar HDX Kit floor heating with SRX2 / EV
Red
Red
23 24
25
J7
SP
Supply Card
J8
R
Display Card
J8
ELECTRONIC CARD UNDERFLOOR
Blue
Earth
Brown
Blue
Earth
Brown
T
H
C
2
1
Black
White
Pin
k
T
S
C
2
1
Black
Red
Pink
S2
ON
1234
ON
S1
12
TS: Safety thermostat.
TH: Fumes thermostat
R: Telephone relay. SP: Pressure sensor.
J7: Telephone relay connector. J8: Communication connector between plates. S1,S2: Boiler model selector.
41
21 ALARM CODES
The Evolution Solar HDX boiler has an electronic circuit which performs continuous self-testing to detect any operating failures in the boiler. When the electronic control detects an operating error, it indicates this by showing an alarm code on the display. The following list describes the possible alarm codes:
CODE ALARM DESCRIPTION
Pressure
The pressure in the installation has dropped to below 0.5 bar. The boiler will cut out. To unblock it, fill the installation at a pressure of 1 - 1.5 bar. This alarm may be set off due to the water having been drained from the boiler or leakage in the installation. If this alarm occurs repeatedly, you should contact the nearest official technical assistance service.
Temperature
The boiler has exceeded the safety temperature of 110 ºC. The boiler will cut out. To unblock it, press the safety thermostat button when the temperature has dropped. If this alarm occurs repeatedly, you should contact the nearest official technical assistance service.
Burner
The burner has cut out. To unblock it, press the illuminated button on the burner
(21)
. This alarm is set off when there is a functioning anomaly in the burner or the fuel installation. If this alarm occurs repeatedly, you should contact the nearest official technical assistance service.
Boiler sensor
The boiler sensor is damaged or disconnected. Contact your nearest official technical assistance service to have it replaced.
DHW sensor.
The tank DHW sensor is damaged or disconnected. Contact your nearest official technical assistance service to have it replaced.
SRX2/EV flow sensor (only with SRX2/EV kit)
The underfloor heating sensor is damaged or disconnected. Contact your nearest official technical assistance service to have it replaced.
Pressure sensor
The pressure sensor
(13)
is damaged or disconnected. Contact your
nearest official technical assistance service to have it replaced.
Solar collector sensor.
The solar collector sensor is damaged or disconnected. Contact your nearest official technical assistance service to have it replaced.
Lower solar hot water tank sensor.
The lower solar hot water tank sensor is damaged or disconnected. Contact your nearest official technical assistance service to have it replaced.
Overpressure
This indicates that the water pressure in the boiler is over 2.5 bar, warning that the installation is in overpressure status. Boiler functioning will NOT cut out. To restore normal boiler functioning, drain the boiler until it reaches a pressure of 1 – 1.5 bar. If this warning occurs repeatedly, you should contact the nearest official technical assistance service.
NOTE: It will be very useful for the technical assistance service if you can inform them of the alarm
code that has appeared on call-out.
Evolution Solar HDX
42
22 BURNER.
22.1 Assembly
Fix the burner support to the boiler, then fix the burner to the support. This will allow the correct tilt of the flame tube towards the combustion chamber. Fit the intake and return tubes, inserting the oil filter in the intake tube.
22.2 Burner start-up
The "Domestic" burner is equipped with a self-extracting pump to enable fuel intake from a tank installed at a lower level than the burner, providing the pressure difference measured with the vacuum gauge at the pump does not exceed 0.4 bar (30 cmHg).
Ensure there is fuel in the tank, that the oil valves are open and that voltage is reaching the burner. Turn on the master switch. Unscrew the air bleed screw (manometer point). Then, when the valve opens, remove the photocell sensor and move it towards a light source until the oil comes out. Disconnect the burner and screw the bleed screw back in.
22.3 Adjusting the combustion conditions
As each particular installation has a different combustion circuit, it is essential to adjust the combustion conditions of each boiler. In order for the guarantee to be valid, the burner must be adjusted by an official DOMUSA TEKNIK Technical Assistance Service.
Observe the flame. If there is insufficient combustion air, it will be dark in colour and will produce smoke, rapidly obstructing the flue outlet.
On the contrary, if there is an excess of combustion air, the flame will be whitish or bluish-white in colour. This will reduce the performance of the boiler and it will fail to comply with anti-pollution standards, and the excess air may also hinder the ignition process.
The flame should be orange in colour. If the shape of the boiler makes it difficult or impossible to observe the flame, the combustion air
flow can be regulated by observing the smoke coming out of the flue. If the smoke is dark in colour, more air will need to be provided to the burner, or if it is a very whitish colour, the air in the burner will need to be decreased until no smoke at all is observed.
If you have a device for determining the composition of the combustion gases, this will be the best guide for flame adjustment. If not, simply follow the above indications.
To adjust the air and burner line conditions, carefully follow the instructions given below.
43
Primary air adjustment
To adjust the primary combustion air, turn the screw using a 6 mm. Allen key, as shown in the diagram. Turn it clockwise to increase the airflow, and anticlockwise to decrease it.
Combustion line adjustment
To adjust the combustion line, loosen the combustion line blocking screw "BL". Turn the line regulator "RL" clockwise to increase the airflow and anticlockwise to decrease it. After adjustment, tighten the combustion line blocking screw "BL".
BL
RL
+
-
3 mm
0
1
Correct position of electrodes
To ensure correct ignition of the “Domestic” burner, the measurements shown in the diagram must be observed. Also ensure the electrode fixing screws have been screwed in place before replacing the flame tube.
2/3 mm
3 mm
10
0
Evolution Solar HDX
44
22.4 Oil pressure adjustment
To adjust the oil pump pressure, turn the screw
(1)
clockwise to increase the pressure, and
anticlockwise to decrease it.
1 – Pressure adjustment. 2 - Vacuum gauge point. 3 - Valve. 4 - Manometer point. 5 – Nozzle outlet. 6 - Return. 7 – Intake.
22.5 Oil supply piping diagrams
The diagrams and tables below correspond to installations without reductions and with a perfect hydraulic seal. It is recommended to use copper pipes. A pressure drop of 0.4 bar (30 cmHg) must not be exceeded.
Intake installation
H Pipe length
(m)
int 8 mm. int 10 mm.
0.0 25 60
0.5 21 50
1.0 18 44
1.5 15 38
2.0 12 26
2.5 10 26
3.0 8 20
3.5 6 16
Charging installation
H Pipe length
(m)
int 8 mm. int 10 mm.
0.5 10 20
1.0 20 40
1.5 40 80
2.0 60 100
Intake installation
H
Charging installation
H
H
SUNTEC - MOD. AS47C
1
2
3
4
5
6
7
DANFOSS - MOD. BFP 21 L3
3
5
4
2
7
6
1
45
22.6 Technical specifications
MODEL D-3 Minimum consumption Kg/h
1.5
Maximum consumption Kg/h
3
Minimum power kW
17.7
Maximum power kW
35.5
Motor power at 2800 r.p.m. W
90-110
Adjustment type
On/Off
Electric voltage
220 V - 50 Hz
Weight Kg
12.5
Preheater
YES
22.7 Operating curves
5
10
15
1
2345
Kg/h
10200 20400 30600 40800 51000
Kcal/h
11. 86 23.72 47.4435.58 59 .3 Kw
mmH
2
O
OVERPRESSURE / FLOW
D-3
22.8 Nozzles Evolution boilers are supplied with the burner fitted, together with its corresponding nozzle and a
standard pre-adjustment. The following table shows the nozzles and adjustments for each particular model:
MODEL Nozzle
Burner pressure
(bar)
Air adjustment
Line
adjustment
EVOLUTION SOLAR 30
HDX
0,55 60º H 13 2,5 1
EVOLUTION SOLAR 40
HDX
0,60 45º H 18,5 2,5 1
Evolution Solar HDX
46
22.9 Electrical connection diagram
1 2 5 6 8 10 11 123
FR
TR
MB
EV1
LB
RP
Black
Blue
TCTS
Ph
N
4
EV2
Pre-heater
F
7
TP
Brown
TC: Boiler thermostat TS: Safety thermostat. F: Fuse. LB: Cut-off light. FR: Photocell. TR: Transformer.
MB: Motor pump. EV: Valve. RP: Preheater element. Ph: Phase. N: Neutral.
TP: Pre-heater thermostat.
22.10 Quick connector
To connect and disconnect the red oil intake tube to the nozzle, proceed as follows:
- Press the connector ring in the direction of the arrow, pulling on the red tube at the same time.
PRESS
RING
TUBE
OIL
QUICK C ONNECTOR
47
22.11 Burner control operating sequence
The burner’s LMO control box has a reset button which is the key element for resetting the burner control and activating/deactivating the diagnosis functions. The multi-colour LED on the reset button is the indicator for visual diagnosis. The button and the LED are located under the transparent cover of the reset button. During normal functioning, the various operating statuses are indicated in the form of colour codes (see the colour code table below). During ignition, the indication is as shown in the following table:
Colour code table for multi-colour indicator lights (LEDs)
Status Colour code Colour
Wait time «tw», other standby statuses
...................................................................
Off
Fuel pre-heater on
……………………………………
Yellow
Ignition phase, controlled ignition
Flashing yellow
Functioning, flame OK
……………………………………
Green
Functioning, flame not OK
Flashing green
External light during burner ignition
Red/green
Undervoltage
Yellow/red
Failure, alarm
……………………………………
Red
Error code output (see «Error code table»)
Flashing red
Interface diagnosis
Flashing red light
….. Steady light Red Off Yellow Green
Botón de rearme
Reset button
Evolution EV FHDX
48
23 SPARES LIST
Mod. Evolution Solar 30 HDX boiler
12345678911 1012131415
16 17 18 19 20 21 22 23
24 25
26
27
Pos Code Designation
1 CEXT000727 Door 2 CEXT000728 Front panel 3 CFER000059 Automatic closure 4 CVAL000002 Fill/drain valve 5 CVAL000034 Drain valve 7
CFOV000148
Summer pump
6
CFOV000148
Winter pump (Evo 30)
CFOV000149
Winter pump (Evo 40) 8 CFER000051 Extendable tube 9 CFUC000052 Burner support door
10 CFUC000053 Fume inspection window cover 11 CVAL000004 Safety valve 12 CFUR000019 Manifold (Evo 30)
CFUR000018 Manifold (Evo 40)
13 CFOV000032 Expansion vessel (Evo 30)
CFOV000005 Expansion vessel (Evo 40)
14 CELC000252 Pressure transducer
Pos Code Designation
15 CEXT000734 Side extension (Evo 30)
CEXT000738 Side extension (Evo 30) 16 CQUE000042 Male 7-pole plug 17 CEXT001257 Rear 18 CEXT000733 Rear cover 19 CFOV000077 Solar pump
20 CFOV000030
Domestic hot water expansion vessel
21 CEXT000726 Top cover (Evo 30)
CEXT000830 Top cover (Evo 40) 22 CFOV000024 Drain valve 23
GDEPMCX004
130-litre tank 24 CTOE000012 Fixing clip 25 CFER000048 Spring closure 26 CEXT000729 Right side
CEXT000730 Left side
27
SELEEVOS11
Control panel
49
Mod. Evolution Solar 30 HDX hot water tank
12
3
4
56
7
8
9
10
11 12
13
14
Pos Code Designation
1 CEXT001033 Front panel 2 CFOV000152 Winter pump 3 CVAL000037 Drain valve 4 CVAL000034 Drain valve 5 CVAL000017 Safety valve 6 CEXT001031 Left side panel 7 CEXT001043 Rear 8 CFOV000072 Siphon
Pos
Code Designation
9 CFOV000001 Safety unit 10 CEXT001042 Top cover 11 GDEPSLE002 250-litre tank 12 CTOE000012 Fixing clip 13 CFER000048 Spring closure 14 CEXT001032 Right side panel
Evolution EV FHDX
50
Electrical board
1 2 4 5 7 98 10
11
12
10
13
14
16
3
15
6
Pos. Code Designation
1
CELC000294 Control panel embellisher
2
COTR000046 Control panel glass
3
CELC000360 Display card
4
CMAZ000128 Cable harness
5
CELC000364 Electronic supply solar card
6
SEPO001366 Connection cover
7
CELC000036 Weidmuller strip 3 poles
8
CELC000234 Temp. Evolution sensor 0,90 mts
9
CELC000211 Electronic control sensor 1,5 mts.
10
SEPO001303 Panel fastening
11
SEPO001976 Drawer
12
SEPO001304 Drawer cover
13
CELC000255 Pressure sensor cable
14
CELC000022 Safety thermostat 110º 1,5m
15
CELC000298 Electronic cards cable
16
Display support
51
Burner
5
6
7
8
9
15
16
17
18
19
20
24
28
29
31
25
27
26
11
10
13
12
23
22
21
4
2
1
30
32
33 34 35
14
3
Pos. Code Designation Pos. Code Designation
1
CFER000032 Cable duct 19 CQUE000147 Oil hose
2 CFER000033 Cable duct 20 CQUE000055 Oil filter 3 CQUE000027 Pre-heater cable 21 CTOR000007 Elbow connector 4 CTOE000063 D3 burner line 22 CQUE000011 Oil pump Suntec 5 CQUE000155 Turbulator disc D3 CQUE000088 Oil pump Danfoss
CQUE000013 Turbulator disc D4 23 CQUE000056 Valve coil Suntec 6 CQUE000019 Set of electrodes CQUE000089 Valve coil Danfoss 7 CQUE000044 Fan 24 CQUE000054 Valve coil cable Suntec 8 CQUE000095 Air adjustment support CQUE000124 Valve coil cable Danfoss 9 CTOE000064 Air adjustment screw 25 CTOE000065 Counter thread
10 CQUE000151 D3 air regulating plate 26 CQUE000004 Pump motor coupling
CQUE000152 D4 air regulating plate 27 CQUE000102 Motor
11 CGAS000220 Manifold 28 CQUE000094 Motor support 12 CQUE000173 Flange seal 29 CQUE000080 Nozzle OD-H 0.55 – 60º (D3) 13 SATQUE0001 Flange CQUE000081 Nozzle OD-H 0.60 – 45º (D4) 14 CQUE000158 Flange support 30 CQUE000061 Preheater 15 D3 tube Ø84x25 31 CQUE000096 Line cover
D4 tube Ø84x45 32 CQUE000149 Photocell support
16 CQUE000129 Control box base 33 CQUE000156 Photocell 18 CQUE000005 Transformer 34 CTOE000054
Line adjustment nut
17 CQUE000169 Control box 35 CTOR000006
Straight connector
Evolution EV FHDX
52
24 FAILURES
This section provides a list of the most common burner and boiler failures.
Burner error code
We have already mentioned that the burner is equipped with a cut-out system, indicated by the reset button light. It may cut out accidentally, and in this case the steady red light on this button will come on. You may unblock it by pressing the button for approx. 1 second. When the burner is blocked and the steady red light is on, visual failure diagnosis may be activated, in accordance with the error code table. To enter visual failure diagnosis mode, hold down the reset button for at least three seconds.
Error code table
Red flashing LED code “AL” on
term. 10
Possible cause
Flashes 2 times On No flame established when ignition safety time
ends.
- Fuel valves defective or dirty
- Flame detector defective or dirty
- Burner maladjustment, no fuel
- Ignition unit defective Flashes 4 times On External light during burner ignition Flashes 7 times On Excessive flame loss during functioning (limited
number of repetitions)
- Fuel valves defective or dirty
- Flame detector defective or dirty
- Burner maladjustment Flashes 8 times On Supervision of fuel pre-heater time Flashes 10 times On Cabling fault or internal failure, output contacts,
other failures
During the failure diagnosis time, the control outputs are disabled and the burner remains off. To exit failure diagnosis and activate the burner again, reset the burner control. Hold down the reset button for approx. 1 second (<3 s).
Boiler failures
FAILURE CAUSE SOLUTION
- Pump not turning Unblock the pump
RADIATOR DOES NOT
HEAT UP
- Air in hydraulic circuit Drain the installation and the boiler (the automatic air bleed valve cap must always be loose)
- Burner badly adjusted Correctly adjust it
- Flue not correctly sealed Eliminate any leaks
- Flame unstable Examine the burner
EXCESSIVE
NOISE
- Flue not insulated Suitably insulate it
53
Circulating pump alarms
The high efficiency pumps include a Led (light) which displays their status.
PUMP LIGHT DESCRIPTION STATUS CAUSE SOLUTION
It is lit green
The pump is functioning
The pump operates according to its setting
Standard functioning
It flashes green
Standby mode (PWM version)
The pump is in standby mode
1. Low voltage U<160 V or Excess voltage U>253 V
1. Check the power supply
195 V<U<253 V It flashes red/green
The is ready for service but is not functioning
The pump will start up again automatically once the error has been solved
2. Excess temperature of the module: the temperature of the motor is too high
2. Check the
room
temperature and that
of the fluid
Flashes red
The pump is out of order
The pump is stopped (blocked)
The pump does not start up automatically.
Change the pump. Please
contact your nearest
official technical
assistance service to have
it replaced
1. The pump is not connected to the power supply
1. Check the
connection of the
cable
2. The LED is faulty 2. Check if the pump works
Light off
There is no power supply
The electrical system is not receiving power supply
3. The electrical system is
faulty
3. Change the Pump. Change the pump. Please contact your nearest official technical assistance service to have it replaced
Evolution EV FHDX
54
25 GUARANTEE CONDITIONS
DOMUSA TEKNIK’s commercial guarantee(*) covers the standard functioning of the products manufactured by DOMUSA TEKNIK Calefacción S.Coop., in accordance with the following conditions and time periods:
1. This commercial guarantee is valid for the following periods, as from the start-up date:
2 Years for electric and hydraulic elements: pumps, valves, etc. 5 Years for heat exchangers. 5 Years for domestic hot water tanks. 8 Years for the solar collector.
During the 2-year period following the start-up date, DOMUSA TEKNIK will carry out any repairs of original flaws or defects totally free of charge.
After these 2 years have elapsed and until the end of the guarantee period, labour costs and call­out charges will be payable by the user.
2. The annual overhaul is not included in the terms of this guarantee.
3. The start-up and annual overhaul are to be carried out by personnel authorised by DOMUSA TEKNIK.
4. The commercial guarantee will be null and void in the following cases:
- If the annual overhaul by personnel authorised by DOMUSA TEKNIK has not been carried out.
- If the boiler has not been installed in accordance with the applicable laws and regulations for this type of appliance.
- If the boiler has not been started up immediately after its installation, by personnel authorised by DOMUSA TEKNIK.
Failures due to misuse or incorrect installation, use of non-suitable electrical power or fuel, supply with water with physical or chemical properties causing incrustation or corrosion, incorrect handling of the appliance and, in general, for any reason beyond DOMUSA TEKNIK’s control, are excluded from this guarantee.
This guarantee does not affect the consumer’s rights as stipulated by law. Note:
Start-up is included in the price of the boiler. The call-out charge is not included.
55
NOTES:
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
Evolution EV FHDX
56
NOTES:
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
57
NOTES:
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
UK ADDRESS HEADQUARTERS & FACTORY
Unit D4 Stanlaw Abbey Business Centre, Bº San Esteban s/n Ellesmere Port, CH65 9BF
20737 ERREZIL (Gipuzkoa)
Tel: 0151 909 6222 Tel: (+34) 943 813 899
www.domusateknik.com
DOMUSA TEKNIK reserves the right to make modifications of any kind to its product
characteristics without prior notice.
*CDOC001276*
CDOC001276 09/16
Loading...