DOMUSA TEKNIK EVOLUTION EV HFM, EVOLUTION EV HFC, evolution ev 25 hac, evolution ev 35 hac Installation And Operating Instructions Manual

INSTALLATION AND OPERATING INSTRUCTIONS
EVOLUTION EV HFM
ER-0170/1996
CGM-04/392
Thank you for choosing a DOMUSA TEKNIK heating boiler. From the range of DOMUSA TEKNIK products you have chosen the Evolution EV HFM model. This boiler is capable of providing you with the temperature comfort suitable for your home, as well as balanced and economical Domestic Hot Water (DHW). This always together with a proper and gas-oil fed hydraulic installation.
This manual forms an essential part of the product and it must be given to the user. Read the warnings and recommendations in the manual carefully, as they contain important information on the safety, use and maintenance of the installation.
These boilers are to be installed by skilled personnel only, in accordance with the legislation in force and following the manufacturer’s instructions.
The start-up of these boilers and any maintenance operations must only be carried out by DOMUSA TEKNIK’s Authorised Technical Assistance Services.
Incorrect installation of these boilers could result in damage to people, animals or property, and the manufacturer will hold no liability in such cases.
DOMUSA TEKNIK informs all parties concerned that, in compliance with section 1 of the first additional provision of Law 11/1997, the responsibility for delivering packaging waste or used packaging for its proper environmental management will be that of the final owner of the product (Article 18.1 Royal Decree 782/1998). At the end of its useful life, the product must be taken to a selected collection point for electrical and electronic equipment or must be returned to the distributor at the time of purchasing a new equivalent appliance. For more detailed information on the collection schemes available, contact either the collection facilities of the local authority or the distributor where the purchase was made.
1
INDEX Page
1 DESCRIPTION OF COMPONENTS.....................................................................................................................................................................................................................2
2 CONTROL ELEMENTS............................................................................................................................................................................................................................................3
3 INSTALLATION INSTRUCTIONS.........................................................................................................................................................................................................................4
3.1
LOCATION.................................................................................................................................................................................................................................................................4
3.2
HYDRAULIC INSTALLATION.....................................................................................................................................................................................................................................4
3.3
ELECTRICAL CONNECTION......................................................................................................................................................................................................................................4
3.4
FUEL INSTALLATION.................................................................................................................................................................................................................................................4
3.5
COMBUSTION PRODUCTS EXHAUSTION................................................................................................................................................................................................................5
3.6
INSTALLING THE SRFM2/EV UNDERFLOOR HEATING KIT (OPTIONAL)...........................................................................................................................................................7
3.7
INSTALLING HEATING CIRCUIT 2 (OPTIONAL).......................................................................................................................................................................................................7
4 COMBUSTION PRODUCTS EXHAUSTION......................................................................................................................................................................................................8
4.1
COMBUSTION PRODUCTS EXHAUSTION AND AIR INTAKE DUAL-DUCT DEVICE Ø80/ Ø100 (TYPR C
53
)........................................................................................................8
4.2
DOUBLE CONDUIT TO COAXIAL EXHAUSTION TRANSFORMATION (ONLY FOR EV 30 HFM).........................................................................................................................9
4.3
COMBUSTION PRODUCTS EXHAUSTION AND AIR INTAKE HORIZONTALLY-ARRANGED COAXIAL DEVICE Ø80-125 (TYPE C
13
) (ONLY FOR EV 30 HFM)...................10
4.4
COMBUSTION PRODUCTS EXHAUSTION AND AIR INTAKE VERTICALLY-ARRANGED COAXIAL DEVICE Ø80-125 (TYPE C
33
) (ONLY FOR EV 30 HFM).........................11
5 FILLING THE INSTALLATION............................................................................................................................................................................................................................12
6 DRAINING THE BOILER......................................................................................................................................................................................................................................12
7 SHUTTING DOWN THE BOILER.......................................................................................................................................................................................................................12
8 FIRST START-UP...................................................................................................................................................................................................................................................12
9 INSTALLATION DELIVERY.................................................................................................................................................................................................................................12
10 DIGITAL DISPLAY..............................................................................................................................................................................................................................................13
11 TEMPERATURE SELECTION...........................................................................................................................................................................................................................15
11.1
SELECTING THE BOILER SET POINT TEMPERATURE ..........................................................................................................................................................................................15
11.2
SELECTING THE DHW SETPOINT TEMPERATURE.............................................................................................................................................................................................15
11.3
SELECTING THE UNDERFLOOR HEATING FLOW SETPOINT TEMPERATURE (WITH SRFM2/EV KIT OPTION).............................................................................................16
12 OPERATION.........................................................................................................................................................................................................................................................17
12.1
HEATING FUNCTION ..........................................................................................................................................................................................................................................17
12.2
DOMESTIC HOT WATER PRODUCTION FUNCTION..........................................................................................................................................................................................17
12.3
FUNCTIONING WITH AN SRFM2/EV UNDERFLOOR HEATING KIT (OPTIONAL).........................................................................................................................................18
12.4
HEATING CIRCUIT 2 FUNCTIONING (OPTIONAL)..............................................................................................................................................................................................18
13 ADDITIONAL FUNCTIONS..............................................................................................................................................................................................................................19
13.1
PUMP ANTI-BLOCK FUNCTION ..........................................................................................................................................................................................................................19
13.2
ANTI-FROST FUNCTION......................................................................................................................................................................................................................................19
13.3
BOILER PRESSURE SENSOR FUNCTION..............................................................................................................................................................................................................19
13.4
TELEPHONE RELAY CONNECTION .....................................................................................................................................................................................................................19
13.5
ROOM THERMOSTAT CONNECTION..................................................................................................................................................................................................................19
13.6
KEYPAD BLOCK FUNCTION ................................................................................................................................................................................................................................20
14 E20 REMOTE CONTROL (OPTIONAL).........................................................................................................................................................................................................21
14.1
FUNCTIONING WITHOUT AN OUTDOOR SENSOR.............................................................................................................................................................................................21
14.2
FUNCTIONING WITH AN EXTERNAL SENSOR (OPTIONAL)..............................................................................................................................................................................22
14.3
DHW MODE FUNCTIONING..............................................................................................................................................................................................................................22
14.4
TELEPHONE RELAY FUNCTION...........................................................................................................................................................................................................................22
15 SAFETY CUT-OUTS...........................................................................................................................................................................................................................................23
15.1
TEMPERATURE SAFETY CUT-OUT......................................................................................................................................................................................................................23
15.2
BURNER CUT-OUT...............................................................................................................................................................................................................................................23
15.3
LOW PRESSURE CUT-OUT ..................................................................................................................................................................................................................................23
16 BOILER MAINTENANCE...................................................................................................................................................................................................................................24
16.1
CLEANING THE BOILER.......................................................................................................................................................................................................................................24
16.2
ANTI-FROST PROTECTION..................................................................................................................................................................................................................................25
16.3
BOILER WATER CHARACTERISTICS ....................................................................................................................................................................................................................25
17 CIRCULATING PUMPS FLOW CURVES.......................................................................................................................................................................................................26
17.1
CHARACTERISTIC CURVES OF THE PUMP..........................................................................................................................................................................................................26
17.2
REGULATION OF THE CIRCULATION PUMP.......................................................................................................................................................................................................26
17.3
PRESSURE DROP .................................................................................................................................................................................................................................................26
18 DIMENSIONS......................................................................................................................................................................................................................................................27
19 TECHNICAL DATA.............................................................................................................................................................................................................................................28
20 ALARM CODES...................................................................................................................................................................................................................................................29
21 ELECTRICAL CONNECTION DIAGRAM......................................................................................................................................................................................................30
22 ELECTRICAL DIAGRAM...................................................................................................................................................................................................................................31
23 BURNER................................................................................................................................................................................................................................................................32
23.1
ASSEMBLY...........................................................................................................................................................................................................................................................32
23.2
BURNER START-UP..............................................................................................................................................................................................................................................32
23.3
ADJUSTING THE COMBUSTION CONDITIONS...................................................................................................................................................................................................32
23.4
OIL PRESSURE ADJUSTMENT .............................................................................................................................................................................................................................34
23.5
OIL SUPPLY PIPING DIAGRAMS..........................................................................................................................................................................................................................34
23.6
TECHNICAL SPECIFICATIONS .............................................................................................................................................................................................................................35
23.7
OPERATING CURVES...........................................................................................................................................................................................................................................35
23.8
NOZZLES.............................................................................................................................................................................................................................................................35
23.9
ELECTRICAL CONNECTION DIAGRAM................................................................................................................................................................................................................36
23.10
QUICK CONNECTOR.........................................................................................................................................................................................................................................36
23.11
BURNER CONTROL OPERATING SEQUENCE ...................................................................................................................................................................................................37
24 FAILURES..............................................................................................................................................................................................................................................................38
25 SPARE PARTS LIST............................................................................................................................................................................................................................................40
26 WARRANTY CONDITIONS..............................................................................................................................................................................................................................43
Evolution EV HFM
2
1 DESCRIPTION OF COMPONENTS
123
4
5
6
7
8
9
10
11 12 13 10
15
14
16
17
1. Blowoff valve.
2. Filling valve.
3. DHW temperature sensor
4. Balance flue burner.
5. DHW exchanger.
6. Heating pump.
7. DHW pump.
8. Boiler temperature sensors.
9. Safety valve.
10. Automatic air vent.
11. Pressure sensor.
12. Expansion vessel.
13. Condensator INOX.
14. Flue gases outlet.
15. Cast iron corp.
16. DHW flow switch.
17. DHW flow limiter.
3
2 CONTROL ELEMENTS
19 21 2220 23
18
25 24
18. Digital display:
This is the boiler functioning display, on which all the operating information, settings and values appear. In standard operating mode (default display), the actual boiler temperature is shown. If any malfunctioning should occur, the corresponding alarm code will appear on the digital display.
19. Boiler temperature touch button:
This is used to select the boiler setpoint temperature. If oFF is selected, the heating function is disabled. To select the desired temperature, simply place your finger on the "+" or "-" symbols on the touch button to increase or decrease the desired boiler temperature.
20. MODE touch button:
When this button is touched the different boiler temperatures appear on the digital display.
21. ON touch button:
If you place your finger on this button for 1 second the boiler will switch on or off.
22. RESET touch button:
If the boiler is in lock-out mode as the alarm has been triggered, touch the RESET button to reset the lock-out and restore functioning.
If you are modifying any of the settings or browsing the user menu, you may touch the RESET button to exit the menu WITHOUT SAVING and return to the previous menu level.
23. DHW temperature touch button:
This is used to select the setpoint temperature for domestic hot water. If oFF is selected, the DHW function will be disabled. To select the desired temperature, simply place your finger on the "+" or "-" symbols on the touch button to increase or decrease the desired DHW temperature.
24. Boiler safety thermostat:
This is a cut-out mechanism to ensure the boiler temperature does not exceed 110ºC.
25. Fume safety thermostat:
This safety thermostat operates when the temperature of the combustion products exceeds 110ºC, in order to protect the polypropylene duct.
Evolution EV HFM
4
3 INSTALLATION INSTRUCTIONS
The boiler must be installed by personnel authorised by the Department of Industry in accordance with the applicable regulations and standards in force. However, the following recommendations must be complied with when installing the boiler:
3.1 Location
The boiler must be installed in a sufficiently ventilated site. It is essential to leave a space at the top of the boiler so that it is accessible for maintenance operations. It must therefore not be
installed under a fixed worktop or any other obstacle preventing access.
3.2 Hydraulic installation
The hydraulic installation must be made by qualified personnel. The applicable installation legislation is to be complied with, and the following recommendations should also be taken into account.
- The inside of the installation piping should be thoroughly cleaned before switching on the boiler.
- We recommend inserting cut-off valves between the installation piping and the boiler to simplify maintenance tasks.
- If a shut-off valve is fitted at the DHW inlet, it must have a safety valve incorporated, calibrated to 9 bar.
- For correct boiler functioning, there must be a pressure of at least 0.5 bar in the domestic hot water circuit.
- Before starting up the unit, it is essential to install the condensation siphon supplied with the boiler documentation on the condensation drain tube on the back of the boiler.
- The condensation pipe should lead to a drain outlet, as the
Evolution boiler is a condensation boiler and a large amount of water may be generated. This connection should be made in
accordance with the regulations for draining off condensation water to the drain network.
- Fill the siphon with water before starting up the unit, to prevent fumes coming out of it.
3.3 Electrical Connection
The boiler is equipped for connection at 230 V~, 50 Hz to terminals 1 and 2 of terminal strip J1 (see
Electrical Connection Diagram
). Remember to earth the appliance.
The boiler has two terminal strips, TA1 (J5) and TA2 (J7) for connecting room thermostats or room chronothermostats (see “
Electrical Connection Diagram
”) for remote control of heating circuits 1 and 2 respectively. To correctly connect the room thermostats, firstly remove the bridge joining the terminals of terminal strip TA1. For connection to TA2, simply connect the thermostat to the terminal strip.
3.4 Fuel installation
The Evolution boiler is supplied with a Domestic sealed oil burner
(4)
(see model in “Technical
Characteristics”). For the fuel installation, proceed in accordance with the burner instructions
5
enclosed with this manual (see “Burner” section). The oil line installation and start-up of the burner must be carried out by qualified, authorised personnel.
3.5 Combustion products exhaustion
The installation of exhaustion of the products of combustion has to be carried out by qualified personnel staff and it will fulfill the requirements demanded in the legislation and effective regulatory schemes.
The Evolution boilers are balanced flue oil boilers, so that the combustion products exhaustion is carried out by means of an outlet duct and an air intake from outside. It is recommended that the position at the exhaustion duct exterior portion should be in accordance with the data of the following figures and table:
Position of the exhaustion duct
Minimum distance
mm
A under a cornice
300
B between two horizontally-arranged ducts
1000
C from a next window
400
D between two vertically-arranged ducts
1500
E from a next venting grid
600
F under a balcony (*)
300
G under a window
600
H under a venting grid
600
I from a break back of a building
300
J from an angle of a building
300
K from the floor level
2500
L from a vertically/horizontally-arranged outlet or pipe (**)
300
M from a front surface at a distance of 3 metres from the exhaust gas outlet
2000
N like the previous one, but with opening
3000
(*) In so far the balcony width does not exceed 2000 mm. (**) If the pipe constructive materials were sensitive to the action from the flue gases, this distance should be longer
than 500 mm.
ATTENTION: All the fittings used in the combustion products exhaustion and air intake are to be those supplied
by DOMUSA TEKNIK firm.
Evolution EV HFM
6
7
3.6 Installing the SRFM2/EV Underfloor Heating Kit (Optional) The procedure for suitably connecting the SRFM2/EV Underfloor Heating Kit to the Evolution EV
HFM boiler is as follows:
- Unplug the boiler from the mains.
- Connect a flow temperature sensor (supplied with the kit) to sensor terminal strip J3 (terminals 15 and 16), first removing the resistance (Rr) supplied by default (see “Electrical Connection Diagram").
- Fit the temperature sensor bulb according to the instructions enclosed with the kit.
- Connect the heating pump to supply terminal strip J2 on the circuit 1 pump connection (pump BC
1
; terminals N and 7) (see “Electrical Connection Diagram").
- Connect the pump´s PWM
C
cable to sensor terminal strip J3 (terminals 13 and 14) (see
“Electrical Connection Diagram").
- Connect the 3-way mixer valve motor to supply terminal strip J2 (terminals N, 8 (+) and 9 (-)) (see “Electrical Connection Diagram").
For correct hydraulic installation, carefully follow the assembly and connection instructions enclosed with the SRFM2/EV kit.
3.7 Installing heating circuit 2 (Optional)
All the models in the Evolution range of boilers are supplied with a circulation pump connected to heating circuit 1 (BC1). In addition to this circuit, all the models are designed to control a second heating circulation pump in a second heating circuit (circuit 2, BC2).
The hydraulic installation of heating circuit 2 should be made using the optional flow circuit (IC') on the rear of the boiler (see "Diagrams and Measurements"). If there is an SRFM2/EV underfloor heating kit connected to the optional flow IC', heating circuit 2 should be connected at the additional sockets provided in the kit (on the boiler T-connectors).
The circulation pump installed in heating circuit 2 must be electrically connected between terminals N and 6 on the supply connector block J2 (see "Connection Diagram").
Evolution EV HFM
8
4 COMBUSTION PRODUCTS EXHAUSTION
4.1 Combustion products exhaustion and air intake dual-duct device ø80/ ø100 (typr C53)
In this type, the combustion products exhaustion and air intake are carried out with separated pipes of ø80/100mm., by means of the dual-duct outlet Kits of ø80/100 code CGAS000265. It is the default type of exhaustion for boilers Evolution.
The maximum length of pipe that can be installed is 12 metres (EV 40 HFM) and 15 metres (EV 30 HFM), which is the result from adding the pipe metres for the air intake and those of the combustion products exhaustion. Each elbow of 90°, or two of 45°, reduces the available length by 1 metre and 1 metre in horizontal, reduces the available length by 2 metres.
It is recommended that the flue gases outlet pipe be fitted slightly upwardly-inclined 2º to 3º thus preventing water and condensate projections from being ejected outside.
Dual-duct outl et Ki t 80/100 inox
Co d. CG AS000265
1m. du ct 80 inox. Cod. CGAS000145
1m. duct 100 ino x. Co d. CGAS000268
1m. duct 100 PP Cod . CGA S000355
90º elbo w 80 inox Cod . CGA S000147
90º elbow 100 ino x Cod . CGAS000267
90º elbow 100 PP Cod. CGAS000358
45º elbow 80 inox. Cod . C GAS000148
45º el bow 100 in ox. Co d. CGA S000266
45º elbow 100 PP Cod. CGAS000357
Examples of installation:
L 12 mts. (EV 30 FM) L 12 mts. (EV 40 FM)
9
4.2 Double conduit to coaxial exhaustion transformation (Only for EV 30 HFM)
The boiler Evolution is given prepared for the exhaustion of the products of combustion and air intake by means of the system of double conduit of Ø80. When you want to carry out the exhaustion of combustion gases by means of coaxial tube of Ø80/125, you will use for it a Kit adaptor for coaxial tube Ø80/125 (given under order) Code CGAS000213 +Cód. CGAS000222.
Kit adaptor for coaxial tube 80/125
Cod . CGAS000213+ Cod. CGAS000222
The transformation will be able to realize with two different mounting setups:
1. Back exit: it will be enough with disassembling the combustion air intake of the boiler, unscrewing the three screw, mount the adaptor in the exit of flue gases of the boiler backwards and using the flexible tube of entry of air, connect it to the adaptor.
2. Lateral or upwards exit: it will be realized in the same way, but to mount the adaptor kit laterally it is necessary to mount an elbow of 90º Ø80 (code CGAS000147), before the adaptor in the exit of flue gases.
In the following pictures they can observe both setups:
Combu sti o n air i ntake
Bac k e xi t
Lateral exit
90º elbow Ø80
Evolution EV HFM
10
4.3 Combustion products exhaustion and air intake horizontally-arranged coaxial device ø80-125 (type C13) (Only for EV 30 HFM)
The combustion products exhaustion and air intake can be carried out through concentric pipes of Ø80 mm. for the combustion products exhaustion and Ø125 mm. for the air intake by means of the horizontally-arranged outlet Kit 1m Ø80-125 code CGAS000189.
The maximum horizontal length counted from the boiler, including the kit end, is 6 metres. Each elbow of 90°, or two of 45°, reduces the available length by 1 metre.
It is recommended that the flue gases outlet pipe be fitted slightly upwardly-inclined 2º to 3º thus preventing water and condensate projections from being ejected outside.
Horizontally-arranged out l et 1m 80/125
Cod. CGAS000189
90º coaxial elbow 80/125
Cod. CGAS000182
45º coaxial elbow 80/125
Cod. CGAS000183
1m coaxial duct 80/125
Cod. CGAS000184
Examples of installation:
L 6 mts. (EV 30 FM)
11
4.4 Combustion products exhaustion and air intake vertically-arranged coaxial device ø80-125 (type C33) (Only for EV 30 HFM)
The combustion products exhaustion and air intake can be carried out through concentric pipes of Ø80 mm. for the combustion products exhaustion and Ø125 mm. for the air intake, by means of the vertically-arranged outlet Kit Ø80-125 code CGAS000231.
The maximum vertical length counted from the boiler, including the kit end, is 7 metres. Each elbow of 90°, or two of 45°, reduces the available length by 1 metre.
Vertically outlet 80/125
Cód. CGAS000231
Black tile 80/125 Cód. CGAS 000 07 4
45º elbow 80/125
Cód. CGAS000183
90º elbow 80/125
Cód. CGAS000182
1m coaxial duct 80/125
Cód. CGAS 000 18 4
Black tile 80/125 Cód. CGAS 000075
Examples of installation:
L 7 mts. (EV 30 FM)
Evolution EV HFM
12
5 FILLING THE INSTALLATION
To fill the installation, open the fill valve
(2)
until a pressure of 1 - 1.5 bars appears on the
“boiler
pressure”
setting on the display. The circuit should be filled slowly and with the automatic air bleed
valve cap
(10)
loose, to let the air out of the installation. The air should also be bled from the rest of the installation using the air bleed valves provided. When the installation has been filled, close the fill valve.
Evolution boilers have a pressure sensor
(11)
for controlling the pressure of the installation. If the installation pressure drops below a minimum of 0.5 bar, the boiler will not switch on and a low pressure alarm will appear on the display ("AP").
NOTE: Switching on the boiler with no water inside could result in serious damage.
6 DRAINING THE BOILER
The water is drained from the boiler by opening the air drain valve
(1)
inside the boiler (on the lower right hand side on opening the door). Connect a flexible tube to this valve and run it to a drain. After draining the boiler, close the valve again and remove the flexible tube.
7 SHUTTING DOWN THE BOILER
To switch off the boiler, place your finger on the power touch button
(21)
for 1 second. In Off mode, while the boiler is plugged into the mains and connected to the fuel installation, its heating and hot water functions will be switched off but the anti-frost protection and pump anti-block functions will remain activated.
To shut down the boiler functioning completely, unplug it from the mains and cut off the fuel supply.
8 FIRST START-UP
For the guarantee to be valid, the boiler must be started up for the first time by an official DOMUSA TEKNIK Technical Assistance Service. Before beginning start-up, the following must be complied with:
- The boiler must be electrically connected to the mains.
- The installation must be filled with water (1 - 1.5 bar must be indicated on the digital display).
- Fuel must be reaching the burner at a pressure of no more than 0.5 bar.
9 INSTALLATION DELIVERY
After the initial start-up, the Technical Assistance Service will explain to the user how the boiler functions, making any observations they consider relevant.
The installer is responsible for clearly explaining to the user the functioning of any control or regulation device forming part of the installation but not supplied with the boiler.
13
10 DIGITAL DISPLAY
The Evolution boiler is electronic and includes a digital display
(18)
showing the actual temperatures, the setpoint temperatures and the pressure of the installation. In standby mode, the actual boiler temperature in ºC is shown on the display. The rest of the available display options can be browsed by touching the MODE button below the display, as follows:
MODE tou ch bu tto n
Digital display
Repeatedly place your finger on the MODE touch button to select the different display options. When the desired option has been selected, it will return to standby after 20 seconds have elapsed.
The following table shows the different display options:
Standby. The actual boiler temperature is shown.
Actual boiler temperature.
Actual Domestic Hot Water temperature.
Actual flow temperature of the underfloor heating installation. (option SRFM2/EV only)
Boiler setpoint temperature selected using the corresponding touch button
(19)
.
Evolution EV HFM
14
Underfloor heating installation flow setpoint temperature selected using the corresponding touch button
(19)
.
(option SRFM2/EV only)
DHW setpoint temperature selected using the corresponding touch button
(23)
.
Actual boiler pressure, measured by the Pressure Sensor
(11)
.
Indication of the heating demand status of each circuit connected to the boiler.
Setpoint of the heating pump speed BC1.
The desired display contrast can be adjusted using the touch button on the right of the display
(23)
.
15
11 TEMPERATURE SELECTION
11.1 Selecting the boiler set point temperature
The desired boiler operating temperature is selected using the touch button, as shown in the figure. To select the desired temperature, touch the "+" or "-" symbols to increase or decrease the temperature respectively. When the temperature has been selected, the display will return to standby mode after a few seconds.
The boiler setpoint temperature can also be selected by using the MODE touch button to browse to the “
boiler setpoint temperature"
display option. When the display shows this option, touch the "+
/-" symbols to select the desired temperature. If you wish to totally disable the boiler heating function (
Summer
mode), select the setpoint value
"OFF" by touching the "-" symbol until this value appears on the display. The permitted boiler setpoint temperature range is OFF and 30 - 85 ºC. Evolution model boilers are
condensing boilers. In order to obtain maximum boiler performance and energy savings, it is therefore recommended to select a setpoint temperature of 55-70 ºC, providing this is permitted by the heating system installed and the insulation conditions of your home.
11.2 Selecting the DHW setpoint temperature
The desired DHW temperature is selected using the touch button, as shown in the figure. To select the desired temperature, touch the "+" or "-" symbols to increase or decrease the temperature respectively. When the temperature has been selected, the display will return to standby mode after a few seconds. The DHW setpoint temperature range permitted is OFF and 30 - 65 ºC.
The DHW setpoint temperature can also be selected by using the MODE touch button to browse to the “
DHW setpoint temperature
" display option. When this option appears on the display, touch
the "+ /-" symbols to select the desired temperature. If you wish to totally disable the boiler’s DHW production function, select the setpoint value "OFF"
by touching the "-" symbol until this value appears on the display.
Evolution EV HFM
16
11.3 Selecting the Underfloor Heating flow setpoint temperature (with SRFM2/EV kit option)
When the boiler is installed with the optional SRFM2/EV underfloor heating kit, the desired flow temperature of the installation can be selected using the touch button as shown in the figure above. To select the desired temperature, touch the "+" or "-" symbols to increase or decrease the temperature respectively. When the temperature has been selected, the display will return to standby mode after a few seconds.
The installation flow setpoint temperature can also be selected by using the MODE touch button to browse to the “
underfloor heating installation flow setpoint
" display option. When this option
appears on the display, touch the "+ /-" symbols to select the desired temperature. If you wish to disable the underfloor heating circuit function, select the setpoint value "OFF" by
touching the "-" symbol until this value appears on the display. The flow setpoint temperature range permitted is OFF and 0 - 45ºC. To obtain optimum
performance from the underfloor heating system installed, we recommend selecting a setpoint temperature of 25 - 35 ºC, providing this is permitted by the heating system installed and the insulation in your home.
17
12 OPERATION
The Evolution EV HFM boiler is designed to heat a heating installation and provide instantaneous domestic hot water. Optionally, an Underfloor Heating Kit (SRFM2/EV) and/or a second heating circuit, heating circuit 2, may be connected to the installation to improve its performance.
12.1 Heating Function
In this mode, the boiler can heat up the heating installation. To do this, select the desired boiler setpoint temperature (see
"Selecting the boiler setpoint temperature"
) and the temperature of room thermostat 1 (TA1) or remote control E20 (if the boiler is equipped with these). The burner will switch on. When the boiler reaches 60ºC it is ready to heat up the heating installation and will start up the heating pump for this purpose. The burner will shut down when the boiler reaches the adjusted setpoint temperature. The heating pump and the burner will stop when the room temperature reaches or exceeds the temperature set on the installation’s room thermostat (if it has one). If a hot tap is turned on, the instantaneous DHW production function will start up and provide constant domestic hot water at the selected DHW setpoint temperature.
The boiler heating function can be totally disabled (
Summer
mode) by selecting "OFF" as the boiler setpoint value. In this operating mode, only the instantaneous DHW production function will remain enabled. NOTE: When the heating function is disabled, circuit 2 will also
be disabled if it is connected.
12.2 Domestic Hot Water production function
In this mode, the boiler provides instantaneous DHW. To activate this mode, select the desired DHW setpoint temperature (see
"Selecting the DHW setpoint temperature"
). The burner will ignite until the boiler reaches 60 ºC. If a hot tap is turned on, the instantaneous DHW production system will start up and provide constant hot water at the selected setpoint temperature.
The Evolution EV HFM boiler is equipped with system for modulating instantaneous DHW production and progressive adjustment of the Domestic Hot Water consumption temperature:
- The modulation allows the boiler power to constantly adapt to the hot water consumption requirements at all times, without altering the efficiency of the boiler. Consumption savings are thus obtained together with improved boiler functioning and lower emissions.
- Progressive electronic adjustment of the DHW temperature, a system designed by DOMUSA
TEKNIK, enables the DHW consumption temperature to be stabilised at the temperature selected using the button on the control panel, and a constant hot water temperature with no variations is obtained regardless of the water flow required and the cold water inlet temperature at any given time. This enables optimum hot water comfort and adaptation to
each user’s particular needs.
If you wish, you may totally disable the Domestic Hot Water production function by selecting "OFF" as the DHW setpoint temperature.
Evolution EV HFM
18
12.3 Functioning with an SRFM2/EV Underfloor Heating Kit (Optional)
The Evolution EV HFM boiler may be used with an SRFM2/EV Underfloor Heating Kit (fitted to heating circuit 1). This kit basically consists of a motorised 3-way mixing valve, a circulating pump and an underfloor heating installation flow temperature sensor. For correct hydraulic installation, carefully follow the assembly and connection instructions enclosed with the kit.
The underfloor heating installation is worked by the electronic boiler control. The installation flow sensor is used to adjust the temperature, selecting the installation flow setpoint temperature using the boiler setpoint adjustment touch button on the control panel, between OFF, 0 and 45 ºC (see
“Selecting the Underfloor Heating flow setpoint temperature
”). In this operating mode, the electronic control sets the boiler setpoint temperature to 75ºC by default, and the installation flow temperature can be adjusted to the selected setpoint temperature using the mixing valve.
The boiler setpoint temperature can be changed using the MODE touch button to browse to the “
boiler temperature setpoint
" display option. When the display shows this option, touch the "+ /-"
symbols to select the desired temperature. If you wish, the SRFM2/EV Underfloor Heating circuit function can be totally disabled, by selecting
"OFF" as the installation flow setpoint temperature.
NOTE: When the Underfloor Heating circuit function is disabled by selecting OFF as the
setpoint temperature, only circuit 1 will be disabled. Circuit 2 will continue to function.
12.4 Heating circuit 2 functioning (optional)
All the models in the Evolution EV HFM range of boilers have the option of controlling a second heating circuit. This requires the installation of a second circulation pump on the boiler. To correctly install this pump, carefully follow the instructions given in the “
Installing heating circuit 2
” section
of this manual. Heating circuit 2 will work with the selected boiler setpoint temperature (see “
Selecting the boiler
setpoint temperature”
) and the temperature of room thermostat 2 (TA2) (if the boiler has one). The
burner and the heating pump of circuit 2 (BC
2
) will begin to function until the installation reaches the selected boiler setpoint temperature (or the temperature on room thermostat 2, if the unit has one). When the temperature of the installation drops below the selected boiler temperature, the burner will start up again, running the heating cycle.
NOTE: When the heating function is disabled, if OFF is selected circuit 2 will also be disabled.
19
13 ADDITIONAL FUNCTIONS
The Evolution EV HFM boiler is equipped with an electronic control for efficiently regulating automatic boiler functioning. It also has the following additional control features:
13.1 Pump anti-block function
This function prevents the boiler circulation pumps from seizing up if they have been out of use for a long period. This system remains enabled while the boiler is plugged into the mains.
13.2 Anti-frost function
This function protects the boiler from freezing up during cold weather. If the boiler temperature drops to below 6 ºC, the heating circulation pump will start up. If the boiler temperature continues to drop and reaches 4 ºC, the burner will start up, heating the installation. When this function has been activated, it will continue working until the boiler reaches 8 ºC. This system remains on standby while the boiler is plugged into the mains.
13.3 Boiler pressure sensor function
This function prevents boiler failure caused by a low water level or excess pressure in the boiler. The pressure is detected by a pressure sensor
(11)
, and its value appears on the control panel display (see
“Digital display”).
If the pressure drops below 0.5 bar, the electronic control blocks boiler functioning and triggers the “AP” alarm on the display. If boiler pressure exceeds 2.5 bar, the "HI" warning will flash on the display to warn of the excess pressure. If this should occur we recommend calling the nearest Technical Assistance Service, and slightly draining the boiler.
13.4 Telephone relay connection
The Evolution boiler is designed to enable a phone relay to be connected for switching the boiler on and off. This feature allows the boiler to be switched on and off remotely, from any location, by means of a phone call. The relay is connected to the boiler via terminal strip J6 (see “
Electrical
Connection Diagram
”). When the telephone relay contact closes the boiler switches on. When the contact opens, the boiler switches off and remains in anti-frost protection and pump anti-block mode.
13.5 Room thermostat connection
The boiler has two terminal strips, TA1 and TA2, for connecting room thermostats or room chronothermostats (J5 and J7, see "
Electrical Connection Diagram
”). This allows the heating mode for each circuit installed to be switched off according to the room temperature. To suitably connect them, first remove the bridge joining the terminals of terminal strip TA1, and to connect TA2, simply connect the thermostat to the terminal strip.
Installing a room thermostat will optimise the installation’s performance, adapting the heating to the requirements of your home and obtaining enhanced comfort. Also, if the thermostat allows the hours of functioning to be programmed (chronothermostat), it can adapt the heating system to the hours of use of the installation.
Evolution EV HFM
20
13.6 Keypad block function
This function protects the control panel from being accidentally or erroneously pressed while it is being cleaned, by children or by unauthorised persons. When this function is enabled, the electronic control will not react when any of the symbols or touch buttons on the control panel are pressed.
To lock the keypad, keep your finger on the RESET touch button for 5 seconds. The word "LOC" will flash on the display until the control panel is unlocked again.
To unlock the keypad, place your finger on the RESET touch button again for 5 seconds. The display will then return to its normal status.
21
14 E20 REMOTE CONTROL (OPTIONAL)
A remote control (E20) may optionally be supplied together with the Evolution EV HFM boiler. This remote control can be used to fully operate the boiler from any room in the home it is installed in. The E20 remote control governs the settings of heating circuit 1 and the installation’s domestic hot water production (where the case may be).
This remote control allows the hours of home comfort to be programmed for heating circuit 1, adjusting the installation to the particular requirements of the home by measuring the room temperature and consequently adapting the installation temperature. The remote control can also be used to adjust the DHW and heating setpoint temperatures at any time, and for viewing the different boiler operation settings. It also warns of any functioning anomalies affecting the boiler.
The E20 remote control may optionally be connected to an external sensor, for measuring the outside temperature. When this option is installed, the remote control can adjust the home comfort level (circuit 1) according to the weather conditions at each particular time, optimising fuel consumption and heating comfort in the home.
The E20 remote control takes over the control of the boiler when it is connected to it. The different selectable boiler temperatures must be modified using the remote control. It is easy to install, only requiring 2 wires for communication between the boiler and the E20 control. It is connected to the boiler by connecting the two wires on terminal strip J4 (see “
Electrical Connection Diagram
”). For
correct installation and functioning, carefully read the instructions enclosed with the remote control. The following sections contain a general explanation of the E20 remote control’s different operating
modes and options.
14.1 Functioning without an outdoor sensor Conventional heating installation (direct circuit)
The maximum temperature for heating circuit 1, the scheduled heating times and the desired room temperatures can be selected on the remote control. The E20 remote control will calculate the boiler temperature required at each particular time, depending on the temperature of the room, and it will activate or disable the heating mode of circuit 1 depending on the heating times and room temperatures programmed.
Installing heating with an SRFM2/EV underfloor heating kit (mixed circuit)
If the boiler has an SRFM2/EV Underfloor Heating Kit installed on circuit 1, the underfloor heating circuit is adjusted and controlled from the boiler control panel (see
"Functioning with an
underfloor heating kit"
).
The E20 remote control can be used to programme the desired heating times and room temperatures.
Evolution EV HFM
22
14.2 Functioning with an external sensor (Optional)
If the E20 remote control is fitted with an outdoor temperature sensor, it can calculate the heating temperature of heating circuit 1 according to the outside weather conditions at each particular time, with optimum adjustment of the heating installation conditions for improved comfort in the home and energy savings.
Conventional heating installation (direct circuit)
The maximum temperature, an operating curve for heating circuit 1 (see instructions enclosed with the E20 remote control) and the desired heating times and room temperatures can all be selected on the remote control. The E20 remote control calculates the required boiler temperature at each particular time, depending on the temperature inside the home and the outside weather conditions, in accordance with the operating curve selected (setting HEATSLOPE 1 on the E20), switching the heating on and off in accordance with the heating times and the room temperatures programmed.
Heating installation with an SRFM2/EV underfloor heating kit (mixed circuit)
If the boiler has an SRFM2/EV underfloor heating kit installed on circuit 1 and the control of this kit is activated on the E20 remote control using the HEATSLOPE 2 setting (see instructions enclosed with the E20 remote control), the adjustment and control of the underfloor heating circuit flow temperature will be performed by the remote control. The E20 will calculate the required flow temperature at each particular time, depending on the temperature inside the home and the outside weather conditions, in accordance with the operating curve selected (the HEATSLOPE 2 setting on the E20 remote control). For mixed underfloor heating circuits, we recommend selecting operating curves of less than 0.8.
The boiler setpoint temperature will be fixed at 75ºC and can be changed using the boiler control panel. This setpoint temperature can be changed by using the MODE touch button to browse to the “
boiler temperature setpoint
" display option. When the display shows this option,
touch the "+ /-" symbols to select the desired temperature. The E20 remote control can also be used to select the maximum flow temperature for heating
circuit 1 and to programme the desired heating times and room temperature. The E20 remote control will switch the heating function of this circuit on and off in accordance with the heating times and room temperatures programmed.
NOTE: For mixed underfloor heating circuits, we recommend selecting a maximum flow
temperature NO HIGHER THAN 45 ºC, to protect the underfloor heating installation from overheating.
14.3 DHW mode functioning
The remote control can be used to select the DHW setpoint temperature and the desired DHW production times. The E20 remote control regulates the instantaneous hot water temperature at each particular time and enables or disables DHW mode in accordance with the times programmed.
14.4 Telephone relay function
The E20 remote control is designed for connection to an external telephone relay. If a telephone relay is connected to the E20 remote control, the heating mode of heating circuit 1 and the DHW mode can be switched on and off from anywhere in the world, simply by making a telephone call (see instructions enclosed with the E20 remote control).
23
15 SAFETY CUT-OUTS
The boiler’s electronic control system may activate the following safety cut-outs to stop the boiler functioning. When one of these safety cut-outs occurs, the boiler will stop functioning, a cut-out code will flash on the display and the red alarm warning pilot light will flash on the control panel.
If any of the safety cut-outs described below should occur repeatedly, switch off the boiler and call your nearest official technical assistance service.
15.1 Temperature safety cut-out
When this cut-out occurs, the alarm code "EAt" (temperature alarm) will begin to flash on the digital display
(18)
. The burner
will switch off and stop heating the installation.
This occurs when the boiler exceeds a temperature of 110 ºC. To unblock it, wait until the boiler drops to below 100 ºC and press the button on the safety thermostat, located inside the boiler on the underside of the electrical box, after first having removed the button cover.
15.2 Burner cut-out
When this cut-out occurs, the alarm code "EAQ" (burner alarm) will begin to flash on the digital display
(18)
. The burner will
switch off and stop heating the installation.
This occurs as a result of an anomaly in the burner
(4)
or in the
fuel installation. To unblock it, press the illuminated button that lights up on the burner.
15.3 Low pressure cut-out
When this cut-out occurs, the alarm code "EAP" (pressure alarm) will begin to flash on the digital display
(18)
. The burner and the boiler circulation pumps will switch off, cutting off the heating and water flow to the installation.
This occurs when the boiler pressure drops to below 0.5 bar, preventing the boiler from functioning when the water is drained from the installation, due to either leakage or maintenance operations. To unlock it, fill the installation again until a pressure of 1
- 1.5 bar appears on the “
boiler pressure
” setting on the display
(18)
.
Evolution EV HFM
24
16 BOILER MAINTENANCE
To maintain the boiler in perfect working order, a yearly overhaul should be performed by DOMUSA TEKNIK’s authorised personnel.
16.1 Cleaning the boiler
To keep the boiler in perfect working order, we recommend cleaning the boiler chamber, exhaustion ducts and condenser on a yearly basis. A cleaning brush of a suitable size for cleaning the inside of the exhaustion ducts is supplied with the boiler for this purpose. This brush is located at the rear of the boiler, beside the condenser.
The combustion chamber and exhaustion ducts should not be cleaned using chemical products or hard steel brushes. After any cleaning operation has been carried out, it is important to run
several ignition cycles to check all the elements are functioning correctly. For correct cleaning, the following recommendations should be carefully observed:
Cleaning the boiler body
- Open and remove the outer door of the boiler.
- Remove the burner
(4)
by unscrewing the fixing nut on the top of the burner.
- Remove the combustion chamber door and the exhaustion duct cover, unscrewing the six fixing nuts beside them.
- Clean the exhaustion ducts on the cast iron body, using the cleaning brush supplied with the boiler.
- Clean the boiler combustion chamber. We recommend using a soft brush for scraping the combustion chamber surfaces, and a blower to remove scale.
- After cleaning, replace the combustion chamber door, the exhaustion duct cover, the burner and the outer door of the boiler.
Cleaning the condenser
- Open and remove the top cover of the boiler to access the condenser on the rear of the boiler body.
- Open the top cover of the condenser (1) to access its exhaustion ducts. To open this cover, firstly release the two side closures (7), turn the locking plate (2) anti-clockwise and pull the cover upwards to remove it.
- Remove the fume deflectors (6) inside the fume outlets.
- Clean the exhaustion ducts using the cleaning brush supplied with the boiler. Scale could fall out of the lower condenser cover and come out of the condensation drain, and it is therefore recommendable to pour water into the top of the condenser, for more effective cleaning. This water will be automatically discharged through the condensation drain.
- To clean the outer part of the condenser cylinder, remove the three screws (3) and then remove the metal ring (4). Take out the seal (5) and use the brush to clean it. Then put the components back in place again and replace and tighten the three screws and the metal ring.
- If the lower condenser cover (9) needs cleaning, remove the side cover of the boiler to access it. Firstly remove the bracket (8) holding it in place and pull on it to open it. Then pull the lower cover down to open and clean it.
- After cleaning, replace the fume deflectors, the top condenser cover and the top outer cover of the boiler. Then put the cleaning brush back inside the boiler.
25
- The condensation siphon should be cleaned once a year. To do this, remove it and wash it in soapy water. Replace the siphon after cleaning.
Cleaning brush
1
2
3 4
5 6
7
8
9
16.2 Anti-frost protection
The Evolution boiler has a function for preventing frost damage to the installation. This will function as long as the appliance remains plugged into the mains. Despite this function, and particularly in areas with very cold weather, we recommend taking precautions in order to prevent damage to the boiler. It is advisable to add anti-freeze to the water in the heating circuit. If the boiler is to be out of use for long periods of time, we recommend draining all the water and leaving it empty.
16.3 Boiler water characteristics
In areas with water hardness of over 25-30ºF, treated water must be used in the heating installation to avoid any scale deposits on the boiler. It should be noted that even a few millimetres of scale will greatly reduce the boiler’s heat conductivity, causing a major drop in performance.
Treated water must be used in the heating circuit in the following cases:
- Very large circuits (containing a large amount of water).
- Frequent filling of the installation.
If repeated partial or total draining of the installation is necessary, we recommend filling it with treated water.
Evolution EV HFM
26
17 CIRCULATING PUMPS FLOW CURVES
The hydrodriving pressure available in the installation at the boiler output can be deduced from the following graphs, having taken the boiler pressure drop into account.
17.1 Characteristic curves of the pump
17.2 Regulation of the circulation pump
To regulate the speed of the circulation pump BC1 you should navigate to the "UB" parameter by touching MODE button and
touch ON button (21) to access it. Once inside the setting, using the jog dial on the right side of the display (23) the value changes. After selecting the desired speed, touch the ON touch
button to record the value and exit the parameter "UB". WARNING: Any interference in the operation and installation of the heating circuit must be done
by authorised personnel, always respecting current legislation and installation safety standards, both national and local level.
17.3 Pressure drop Evolution 30 HFC: Evolution 40 HFC:
27
18 DIMENSIONS
IC: Heating outlet. RC: Heating return. EAS: DHW inlet.
IAS: DHW outlet.
MODEL
IC
RC
EAS
IAS
DIM.
L
VS: Safety valve. EV 30 HFM
3/4"M 855
SC: Condensate drainage, 1" H. EV 40 HFM
1"M
1/2"M
955
EA: Combustion air inlet, Ø80. SH: Flue gases outlet.
Evolution EV HFM
28
19 TECHNICAL DATA
EVOLUTION HFM EV 30 HFM EV40 HFM
Condensation
Boiler type -
combi
Rated heat output
P
rated
kW 30 40
Useful heat output
P4 kW 28,7 38,7
Useful heat output (30%)
P1 kW 8,5 12,4
Seasonal space heating energy efficiency
Ƞ
S
% 91 92
% (PCI) 97,96 97,29
Useful efficiency
Ƞ
4
% (PCS) 92,38 91,74
% (PCI) 103,45 104,15
Useful efficiency (30%)
Ƞ
1
% (PCS) 97,55 98,21
Auxiliary electricity consumption at full load
el
max
kW 0,226
Auxiliary electricity consumption at part load
el
min
kW 0,078
Auxiliary electricity consumption in standby mode
PSB kW 0,001
Standby heat loss
P
stby
kW 0,135 0,17
Emissions of nitrogen oxides
NOx mg/kWh 118 119
Declared load profile
- XL XL
Water heating energy efficiency
Ƞ
wh
% 80 80
Daily electricity consumption
Q
elec
kWh 0,337 0,296
Daily fuel consumption
Q
fuel
kWh 24,110 24,630
DHW Production ∆t = 30ºC
l/min. 12,8 17,8
Heating temperature adjustment
ºC OFF, 30-85
DHW temperature adjustment
ºC OFF, 15-65
Maximum safety temperature
ºC 110
Maximum pressure for heating mode
bar 3
Heating expansion vessel capacity
Lts 8 12
Heating water volume
Lts 19,2 23,2
Water pressure drop
mbar 163 272
Fume temperature
ºC 67 83
Volume on fume side
m3 0,114 0,175
Maximum fume flow
Kg/s 0,0132 0,0186
Fume pressure drop
mbar 0,20 0,21
Combustion chamber length
mm 300 400
Combustion chamber type -
wet, three smoke steps
Burner adjustment type
- ON/OFF
Electrical supply
- ~220-230 V - 50 Hz - 200 W
Gross weight
Kg 160 190
29
20 ALARM CODES
The boiler Evolution EV HFM is equipped by an electronic circuit able to sense, by means of a continuing autotest, the operation lockouts and alarms of the boiler. When the electronic control senses an operation error, indicates it showing an alarm code in the screen of the display. In the following list the possible alarm codes are described:
CODE ALARM DESCRIPTION
Pressure
The pressure in the installation has dropped to below 0.5 bar. The boiler will cut out. To unblock it, fill the installation at a pressure of 1 - 1.5 bar. This alarm may be set off due to the water having been drained from the boiler or leakage in the installation. If this alarm occurs repeatedly, you should contact the nearest official technical assistance service.
Temperature
The boiler has exceeded the safety temperature of 110 ºC. The boiler will cut out. To unblock it, press the safety thermostat button when the temperature has dropped. If this alarm occurs repeatedly, you should contact the nearest official technical assistance service.
Burner
The burner has cut out. To unblock it, press the illuminated button on the burner
(4)
. This alarm is set off when there is a functioning anomaly in the burner or the fuel installation. If this alarm occurs repeatedly, you should contact the nearest official technical assistance service.
Boiler sensor
The boiler sensor
(8)
is damaged or disconnected. Contact your nearest official technical assistance service to have it replaced.
DHW sensor.
The DHW sensor is damaged or disconnected. Contact your nearest official technical assistance service to have it replaced.
SRFM2/EV flow sensor (only with SRFM2/EV kit)
The underfloor heating sensor is damaged or disconnected. Contact your nearest official technical assistance service to have it replaced.
Pressure sensor
The pressure sensor
(11)
is damaged or disconnected. Contact your nearest official technical assistance service to have it replaced.
Overpressure
This indicates that the water pressure in the boiler is over 2.5 bar, warning that the installation is in overpressure status. Boiler functioning will NOT cut out. To restore normal boiler functioning, drain the boiler until it reaches a pressure of 1 – 1.5 bar. If this warning occurs repeatedly, you should contact the nearest official technical assistance service.
NOTE: It will be very useful for the technical assistance service if you can inform them of the alarm
code that has appeared on call-out.
Evolution EV HFM
30
21 ELECTRICAL CONNECTION DIAGRAM
There are a series of removable copnnectors located on the rear of the control panel, for connecting the various options and components for this model. For correct connection, carefully follow the indications shown below:
1 86543NNN 7
J1J2
J4
N F
Q
J5
T
A
1
E20
BV
2
220 V
J7
T
A
2
c7
Black
Blue
Blue
Blue
Brown
BC
2
BC
1
M
J6
1918171615
J3
Sc
Blue
SaRr
Blue
PWM
c
Blue
141312
PWM
a
9
(+)
(-)
Ph: Phase. N: Neutral. bc7: Burner terminal n. 7. Q: Burner. BV: DHW charge pump. BC
1
: Heating circuit N. 1 circulating pump.
BC2: Heating circuit N. 2 circulating pump. M: Underfloor 3 way valve motor. E20: Remote control E20 (optional). TA
1
: Heating circuit N. 1 room thermostat.
TA
2
: Heating circuit N. 1 room thermostat.
PWM
a
: DHW PWM cable.
PWMc: Heating PWM cable.
Rr: Underfloor heating option resistance. Sa: DHW temperature sensor. Sc: Boiler temperature sensor. J1: Power supply connector. J2: Components connector. J3: Sensor connector. J4: Remote control connector. J5: Room thermostat N. 1 connector. J6: Telephone relay connector. J7: Room thermostat N. 2 connector.
31
22 ELECTRICAL DIAGRAM
Red
Red
12
3
J6
SP
Power supply card
J8
R
Display Card
J8
S2
ON
1234
ON
S1
12
Brown
Blue
FL
T
H
C
2
1
Blac
k
White
Pin
k
T
S
C
2
1
Black
Red
Pink
TS: Security thermostat. TH: Fumes thermostat. SP: Pressure sensor. R: Phone relay. FL: DHW flow switch.
J6: Phone relay connector. J8: PCB's connector. S1: Boiler model selection switches. S2: Floor heating selection switches.
Evolution EV HFM
32
23 BURNER
23.1 Assembly
Fix the burner support to the boiler, then fix the burner to the support. This will allow the correct tilt of the flame tube towards the combustion chamber. Fit the intake and return tubes, inserting the oil filter in the intake tube.
23.2 Burner start-up
The "Domestic" burner is equipped with a self-extracting pump, enabling fuel intake from a tank installed at a lower level than the burner, provided the pressure difference measured with the vacuum gauge at the pump does not exceed 0.4 bar (30 cmHg).
Ensure there is fuel in the tank, that the oil valves are open and that there is an electric connection to the burner. Turn on the master switch. Unscrew the air bleed screw (manometer point). Then, when the valve opens, remove the photocell sensor and move it towards a light source until fuel comes out. Disconnect the burner and screw the bleed screw back in.
23.3 Adjusting the combustion conditions
As each particular installation has a different combustion circuit, it is essential to adjust the combustion conditions of each boiler. For the guarantee to be valid, the burner must be adjusted by an official DOMUSA TEKNIK Technical Assistance Service.
Observe the flame. If there is insufficient combustion air, it will be dark in colour and will produce smoke, obstructing the flue outlet.
On the contrary, if there is an excess of combustion air, the flame will be pale or bluish in colour. This will reduce the performance of the boiler and it will fail to comply with anti-pollution standards, and the excess air may also hinder the ignition process.
The flame should be orange in colour. If the shape of the boiler makes it difficult or impossible to observe the flame, the combustion air
flow can be regulated by observing the smoke coming out of the flue. If the smoke is dark in colour, more air will need to be provided to the burner, and if it is very white, the air in the burner will need to be decreased until no smoke at all is observed.
If you have a device for determining the composition of the combustion gases, this will be the best guide for flame adjustment. If not, simply follow the above indications.
To adjust the air and burner line conditions, carefully follow the instructions given below.
33
Primary air adjustment
To adjust the primary combustion air, turn the screw using a 6 mm. Allen key, as shown in the diagram. Turn it clockwise to increase the airflow, and anticlockwise to decrease it.
Combustion line adjustment
To adjust the combustion line, loosen the combustion line blocking screw "BL". Turn the line regulator "RL" clockwise to increase the airflow and anticlockwise to decrease it. After adjustment, tighten the combustion line blocking screw "BL".
BL
RL
+
-
3 mm
0
1
Correct position of electrodes
To ensure correct ignition of the “Domestic” burner, the measurements shown in the diagram must be observed. Also ensure the electrode fixing screws have been screwed in place before replacing the flame tube.
2/3 mm
3 mm
10
0
Evolution EV HFM
34
23.4 Oil pressure adjustment
To adjust the oil pump pressure, turn the screw
(1)
clockwise to increase the pressure, and
anticlockwise to decrease it.
1 - Pressure adjustment. 2 – Vacuum gauge point. 3 - Valve. 4 - Manometer point. 5 - Nozzle outlet. 6 - Return. 7 - Intake.
23.5 Oil supply piping diagrams
The diagrams and tables below correspond to installations without reductions and with a perfect hydraulic seal. It is recommended to use copper pipes. A pressure drop of 0.4 bar (30 cmHg) must not be exceeded.
Intake installation
H Pipe length
(m)
int. 8 mm. int. 10 mm.
0.0 25 60
0.5 21 50
1.0 18 44
1.5 15 38
2.0 12 26
2.5 10 26
3.0 8 20
3.5 6 16
Charging installation
H Pipe length
(m)
int. 8 mm. int. 10 mm.
0.5 10 20 1,0 20 40
1.5 40 80
2.0 60 100
Intake installation
H
Charging installation
H
H
SUNTEC - MOD. AS47C
1
2
3
4
5
6
7
DANFOSS - MOD. BFP 21 L3
3
5
4
2
7
6
1
35
23.6 Technical specifications
MODEL D-3 D-4 Minimum consumption Kg/h
1,5 2,3
Maximum consumption Kg/h
3 4,65
Minimum power kW
17,7 27,2
Maximum power kW
35,5 55,2
Motor power at 2800 r.p.m. W
200
Adjustment type
On/Off
Electric current
220 V - 50 Hz
Weight Kg
12,5
Preheater
YES
23.7 Operating curves
5
10
15
1
2 3 4 5
Kg/h
10200
20400 30600 40800 51000
Kcal/h
11.8 23.72 47.44 35.58 59.3 Kw
mmH
2
O
OVERPRESSURE / FLOW
D-3
D-4
23.8 Nozzles Evolution boilers are supplied with the burner fitted, together with its corresponding nozzle and a
standard pre-adjustment. The following table shows the nozzles and adjustments for each particular model:
MODEL Nozzle
Burner pressure
(bar)
Air adjustment Line adjustment
EVOLUTION EV 30 HFM
0,55 60º H 13 2,5 1
EVOLUTION EV 40 HFM
0,60 45º H 18,5 2,5 1
Evolution EV HFM
36
23.9 Electrical connection diagram
1 2 5 6 8
10 11 12
3
FR
TR
MB
EV1
LB
RP
Black
Blue
TCTS
Ph
N
4
EV2
Preheater
F
7
TC: Boiler Thermostat. TS: Safety Thermostat. F: Fuse. LB: Cut-off Light. FR: Photocell. TR: Transformer.
MB: Oil Pump Motor. EV: Valve. RP: Preheater Element. Ph: Phase. N: Neutral.
23.10 Quick connector
To connect and disconnect the red oil intake tube to the nozzle, proceed as follows:
- Press the connector ring in the direction of the arrow, pulling on the red tube at the same time.
PRES S
RING
TUBE
OIL
QUICK CONNECTOR
37
23.11 Burner control operating sequence
The burner’s LMO control box has a reset button which is the key element for resetting the burner control and activating/deactivating the diagnosis functions. The multi-colour LED on the reset button is the indicator for visual diagnosis. The button and the LED are located under the transparent cover of the reset button. During normal functioning, the various operating statuses are indicated in the form of colour codes (see the colour code table below). During ignition, the indication is as shown in the following table:
Colour code table for multi-colour indicator lights (LEDs)
Status Colour code Colour
Wait time «tw», other standby statuses
...................................................................
Off
Fuel pre-heater on
……………………………………
Yellow
Ignition phase, controlled ignition
Flashing yellow
Functioning, flame OK
……………………………………
Green
Functioning, flame not OK
Flashing green
External light during burner ignition
Red/green
Undervoltage
Yellow/red
Failure, alarm
……………………………………
Red
Error code output (see «Error code table»)
Flashing red
Interface diagnosis
Flashing red light
….. Steady light Red Off Yellow Green
Botón de rearme
Evolution EV HFM
38
24 FAILURES
This section provides a list of the most common burner and boiler failures.
Burner error code
We have already mentioned that the burner is equipped with a cut-out system, indicated by the reset button light. It may cut out accidentally, and in this case the steady red light on this button will come on. You may unblock it by pressing the button for approx. 1 second. When the burner is blocked and the steady red light is on, visual failure diagnosis may be activated, in accordance with the error code table. To enter visual failure diagnosis mode, hold down the reset button for at least three seconds.
Error code table
Red flashing LED code “AL” on
term. 10
Possible cause
Flashes 2 times On No flame established when ignition safety time
ends.
- Fuel valves defective or dirty
- Flame detector defective or dirty
- Burner maladjustment, no fuel
- Ignition unit defective Flashes 4 times On External light during burner ignition Flashes 7 times On Excessive flame loss during functioning (limited
number of repetitions)
- Fuel valves defective or dirty
- Flame detector defective or dirty
- Burner maladjustment Flashes 8 times On Supervision of fuel pre-heater time Flashes 10 times On Cabling fault or internal failure, output contacts,
other failures
During the failure diagnosis time, the control outputs are disabled and the burner remains off. To exit failure diagnosis and activate the burner again, reset the burner control. Hold down the reset button for approx. 1 second (<3 s).
Boiler failures:
FAILURE CAUSE SOLUTION
- The pump is not turning Unblock the pump
RADIATOR DOES NOT
HEAT UP
- Air in hydraulic circuit Drain the installation and the boiler (the automatic air drain valve cap must always be loose)
- Burner badly adjusted Adjust it correctly
- Flue not correctly sealed Eliminate any leaks
- Flame unstable Examine the burner
EXCESSIVE
NOISE
- Flue not insulated Suitably insulate it
39
Circulating pump alarms
The high efficiency pumps include a Led (light) which displays their status.
PUMP LIGHT DESCRIPTION STATUS CAUSE SOLUTION
It is lit green
The pump is functioning
The pump operates according to its setting
Standard functioning
It flashes green
Standby mode (PWM version)
The pump is in standby mode
1. Low voltage U<160 V or Excess voltage U>253 V
1. Check the power supply
195 V<U<253 V It flashes red/green
The is ready for service but is not functioning
The pump will start up again automatically once the error has been solved
2. Excess temperature of the module: the temperature of the motor is too high
2. Check the
room
temperature and that
of the fluid
Flashes red
The pump is out of order
The pump is stopped (blocked)
The pump does not start up automatically.
Change the pump. Please
contact your nearest
official technical
assistance service to have
it replaced
1. The pump is not connected to the power supply
1. Check the
connection of the
cable
2. The LED is faulty 2. Check if the pump works
Light off
There is no power supply
The electrical system is not receiving power supply
3. The electrical system is
faulty
3. Change the Pump. Change the pump. Please contact your nearest official technical assistance service to have it replaced
Evolution EV HFM
40
25 SPARE PARTS LIST
Burner
5
6
7
8
9
15
16
17
18
19
20
24
28
29
31
25
27
26
11
10
13
12
23
22
21
4
2
1
30
32
33 34 35
14
3
Pos. Code Name Pos. Code Name
1
CFER000032 Cable gland 19 CQUE000147 Oil hose
2 CFER000033 Cable gland 20 CQUE000055 Oil filter 3 CQUE000027 Preheater cable 21 CTOR000007 Elbow connector 4 CTOE000063 Burner line D3 22 CQUE000011 Oil pump Suntec 5 CQUE000155 Turbulator disc D3 CQUE000088 Oil pump Danfoss 5 CQUE000013 Turbulator disc D4 23 CQUE000056 Valve coil Suntec 6 CQUE000019 Set of electrodes CQUE000089 Valve coil Danfoss 7 CQUE000044 Fan 24 CQUE000054 Valve coil cable Suntec 8 CQUE000095 Air adjustment support CQUE000124 Valve coil cable Danfoss 9 CTOE000064 Air adjustment screw 25 CTOE000065 Counter thread
10 CQUE000151 Air adjustment plate D3 26 CQUE000004 Motor pump coupling
CQUE000152 Air adjustment plate D4 27 CQUE000102 Motor 11 CGAS000220 Manifold 28 CQUE000094 Motor support 12 CQUE000173 Flange seal 29 CQUE000080 Nozzle D3 13 SATQUE0001 Flange CQUE000081 Nozzle D4 14 CQUE000158 Support seal 30 CQUE000061 Preheater 15 Short flame tube D3 ø84x25 31 CQUE000096 Line cover
Long flame tube D4 ø84x45 32 CQUE000149 Photocell support 16 CQUE000129 Control box plugs 33 CQUE000156 Photocell 17 CQUE000169 Control box 34 CTOE000054 Line adjustment 18 CQUE000005 Transformer 35 CTOR000006 Straight connector
41
Boiler
1234246789711
12
13
14
15
16
17
18 19
21
20
22
23
Evolution EV HFM
42
24 25 26 27 28 29 30 31
32
33
31
34
39
36
37
38
35
Pos.
Code
Name
1 CEXT000717 Door 2 CFER000059 Automatic door-close 3 CVAL000034 Drainage valve 4 CVAL000002 3/8 full/empty valve 5 CFOV000148 Heating pump 30 HFM
CFOV000149 Heating pump 40 HFM 6 CFER000051 Extraflex 80 extendable tube 7 CFUC000052 Cast iron burner support door 8 CFUC000053 Cast iron vent cover
9 CVAL000004
½ 3kg. Safety valve with man. pt.
10 CFUR000020 Manifold 30 HFM
CFUR000017 Manifold 40 HFM
11 CEXT000702 Left side 30 HFM
CEXT000703 Roght side 30 HFM
11 CEXT000725 Left side 40 HFM
CEXT000736 Right side 40 HFM
12 CEXT000975 Cover side 13 CEXT001247 Rear panel 30 HFM
CEXT001248 Rear panel 40 HFM
14 CEXT000716 Roof 30 HFM
CEXT000737 Roof 40 HFM
15 CTOE000012 Fixing clip 16 CFOV000025 Expansion vessel 30 HFM
CFOV000043 Expansion vessel 40 HFM
Pos.
Code Name
17 CFER000048 Spring closure 18 CFOV000024 3/8 PURGOMAT drain valve 19 CELC0000252 Presure transducer 20 CFOV000061 Flowswitch 21 CFOV000148 Pump 22 CFOV000033 Heatexchanger 30 HFM
CFOV000067 Heatexchanger 40 HFM 23 SELEEVO021 Electrical main board HFM 24 CELC000294 Control panel embellisher 25 COTR000046 Main board glass 26 CELC000360 Display card 27 CMAZ000128 Cable harness 28 CELC000240 Flowswitch connector 29 CELC000036 Weidmuller strip 3 poles 30 SEPO001947 Drawer 31 SEPO001325 Panel fastening
32 CELC000234
Temperature Evolution sensor
0,90 mts. 33 SEPO001326 Drawer cover 34 CELC000255 Pressure sensor cable 35 CELC000022 Safety thermostat 110º 1,5m 36 CELC000358 Power supply card 37 CELC000298 Electronic cards cable 38 SCHA008320 Display suport 39 CELC000022 Fumes thermostat
43
26 WARRANTY CONDITIONS
DOMUSA TEKNIK’s commercial guarantee(*) covers the standard functioning of the products manufactured by DOMUSA TEKNIK Calefacción S.Coop., in accordance with the following conditions and time periods:
1. This commercial guarantee is valid for the following periods, as from the start-up date:
2 Years for electric and hydraulic elements: pumps, valves, etc. 5 Years for heat exchangers. 5 Years for domestic hot water tanks.
During the 2-year period following the start-up date, DOMUSA TEKNIK will carry out any repairs of original flaws or defects totally free of charge.
After these 2 years have elapsed and until the end of the guarantee period, labour costs and call­out charges will be payable by the user.
2. The annual overhaul is not included in the terms of this guarantee.
3. The start-up and annual overhaul are to be carried out by personnel authorised by DOMUSA TEKNIK.
4. The commercial guarantee will be null and void in the following cases:
- If the annual overhaul by personnel authorised by DOMUSA TEKNIK has not been carried out.
- If the boiler has not been installed in accordance with the applicable laws and regulations for this type of appliance.
- If the boiler has not been started up immediately after its installation, by personnel authorised by DOMUSA TEKNIK.
Failures due to misuse or incorrect installation, use of non-suitable electrical power or fuel, supply with water with physical or chemical properties causing incrustation or corrosion, incorrect handling of the appliance and, in general, for any reason beyond DOMUSA TEKNIK’s control, are excluded from this guarantee.
This guarantee does not affect the consumer’s rights as stipulated by law. Note: Start-up is included in the price of the boiler. The call-out charge is not included.
Evolution EV HFM
44
NOTES:
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
45
NOTES:
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
..............................................................................................................................................................................................................
UK ADDRESS HEADQUARTERS & FACTORY
Unit D4 Stanlaw Abbey Business Centre, Bº San Esteban s/n Ellesmere Port, CH65 9BF
20737 RÉGIL (Guipúzcoa)
Tel: 0151 909 6222 Tel: (+34) 943 813 899
www.domusateknik.com
DOMUSA TEKNIK reserves the right to make modifications of any kind to its product
characteristics without prior notice.
*CDOC001110*
CDOC001110 05/16
Loading...