Dometic 3109228.001 Troubleshooting Manual

Page 1
TROUBLESHOOTING
Manual Compliments of
Northwest RV Supply
Printed From
http://www.nwrvsupply.com
for the
5 BUTTON 3109228.001
COMFORT CONTROL
CENTER SYSTEM
AIR CONDITIONER BULLETIN A29/2A JANUARY 2002
INTRODUCTION
The Comfort Control Center control system can be used to operate the following Duo-Therm Units:
Roof Top Air Conditioners Roof Top Heat Pumps Basement Air Conditioners Basement Heat Pumps Dual Basement Air Conditioners Dual Basement Heat Pumps Other Manufacturer’s Furnaces
A majority of air conditioner and heat pump problems are electrical and can be found very easily.
To find a problem in the electrical system, you need to be able to diagnose the following:
1. Power Source 10. PTCR Device
2. Cable Assembly 11. Heat Strip
3. Compressor 12. Cold Control
4. Capacitors 13. Ambient Sensor
5. Motors 14. Configuration
6. Remote Sensor 15. Comfort Control Center
7. Wiring 16. System Reset
8. AC Power Module 17. DC Voltage
9. Reversing Valve
TOOLS REQUIRED
The air conditioner can be checked with a voltmeter, ohm­meter, clamp-on ammeters and two good thermometers. Some clamp-on ammeters can read voltage and ohms.
FIG. 1
Form No. 3307835.003 1/02 (French 3307836.001) ©2002 Dometic Corporation LaGrange, IN 46761
A. QUICK-CHECK TROUBLE-
SHOOTING FOR COMFORT CONTROL CENTER (CCC) CONTROLS
For detailed troubleshooting, refer to sec­tion noted.
1. Air Conditioner/Heat Pump turned on – No display
a. Reset - Sec. B15 b. DC Voltage - Sec. B17 c. Cable Assembly - Sec. B2 d. AC Control Module - Sec. B8 e. Comfort Control Center (CCC) - Sec. B15
2. Air Conditioner/Heat Pump turned on – Has display, improper operation
a. Power Source - Sec. B1 b. Reset - Sec. B16 c. Configuration - Sec. B14 d. Wiring - Sec. B7 e. AC Control Module - Sec. B8 f. Comfort Control Center (CCC) - Sec. B15
3. Air Conditioner/Heat Pump turned on – Fan runs, No compressor operation
a. Start Relay/PTCR - Sec. B10 b. Start Capacitor - Sec. B5 c. Fan/Run Capacitor - Sec. B4 d. Cold Control - AC Only, Sec. B12 e. Outdoor Ambient Sensor (HP) - Sec. B13 f. Compressor - Sec. B3 g. Wiring - Sec. B7 h. Comfort Control Center - Sec. B15 i. AC Control Module - Sec. B8
4. Air Conditioner/Heat Pump turned on – Com­pressor runs, No fan operation
a. Fan/Run Capacitor - Sec. B4 b. Motor - Sec. B5 c. Wiring - Sec. B7 d. Comfort Control Center (CCC) - Sec. B15 e. AC Control Module - Sec. B8
5. Heat Pump turned on – Compressor runs and fan runs, No heat output
a. Reversing Valve - Sec. B9 b. Wiring - Sec. B7 c. AC Control Module - Sec. B8
1
Page 2
B. DETAILED TROUBLESHOOTING
Manual Compliments of
Northwest RV Supply
Printed From
http://www.nwrvsupply.com
FOR COMFORT CONTROL CENTER (CCC) CONTROLS
We will now start electrically troubleshooting Comfort Con­trol Center (CCC) controlled units. The best place to begin is at the power source.
1. POWER SOURCE
If the compressor or fan fails to operate, it is probably not receiving power. Be sure the power cord is plugged in and no fuses or breakers are tripped.
Note: Many customers use extremely long power cords that are undersized. If possible, ask the owner to hook up the RV just like it was when the problem occurred.
FIG. 2
Make note of the wire size and length of wire. Compare it to the chart for wire sizing.
For normal operation of the unit, AC voltage must stay between 103.5 VAC and 126.5 VAC. Operation of the unit outside of this voltage range can result in component damage.
To determine if power is reaching the air conditioner, the inside plastic air diffuser box must be removed. The junction box will now be exposed. Remove the cover from the junc­tion box to gain access to the connection between the RV and the unit wires (FIG. 3). Check with a voltmeter for volt­age at the connections of the unit to RV wires. USE CAU- TION as 115 volts may be present.
If no voltage is present, the problem is in the coach wiring or breaker/fuse box.
2. CABLE ASSEMBLY
A flat control cable must be routed from the unit to the Com­fort Control Center. It must be 26 gauge, stranded copper wire, four (4) conductor (yellow, green, red, and black). The cable must be terminated with a four (4) position telephone RJ-11 Connector.
Note: Do not use a pre-made telephone extension cable. The order of the connectors is reversed and will cause a failure of the system.
CURRENT WIRE SIZE
IN
AMPS 16 14 12 10 8 6
LENGTH IN FEET
5 47 76 121 192 216 486
10 38 60 96 153 243
15 25 40 64 102 162
20 30 48 76 121
FIG. 3
FIG. 4
2
Page 3
The cable should be made in the following manner:
Manual Compliments of
Northwest RV Supply
Printed From
http://www.nwrvsupply.com
Cut the control cable to the desired length. When cutting make sure ends are cut straight, not diagonally. Next, use an RJ-11 connector crimping tool.
Use the stripper section of the tool to remove the outer insu­lation of the cable. Be careful not to remove or break the colored insulation of the inner conductors. Repeat on oppo­site end.
Insert the prepared cable into the RJ-11 plug. When insert­ing cable you MUST be sure that the black wire is on your left as you look at the top of the plug. See FIG. 5. Insert the RJ-11 plug into the tool and squeeze to the stop. Repeat the procedure for other end.
FIG. 5
The finished cable can be tested with a 3107127.007 com­fort control cable tester. See Section B16 for more informa­tion on the testing of the cable.
3. COMPRESSOR
The compressor motor can be electrically checked. Be sure to disconnect all power and turn all switches to the “OFF” position, before starting to do the tests.
Remove the terminal cover from the compres­sor and disconnect the three leads connected to the terminals. Make note of the positions so the wires can be replaced correctly.
Use an ohmmeter to check for continuity through the over­load device. If no continuity is found and the compressor is hot, allow 15 to 20 minutes for the compressor to cool. If a repeat of the test shows the overload to be open, it is defec­tive and requires replacement.
Continuity should exist between all three terminals of the compressor. If there is no continuity the compressor wind­ings are open and the compressor is defective.
Scrape the compressor casing to bare metal and check continuity from each terminal to the casing. If continuity is found to the casing on any of the terminals, the compressor is shorted and it is defective.
4. CAPACITORS
Duo-Therm Air Conditioners and Heat Pumps use three dif­ferent capacitors: 1) compressor run capacitor 2) compres­sor start capacitor and 3) fan/blower capacitor. On some
units the compressor run and fan/blower capacitor are in the same case.
The compressor run and fan/blower capacitor are housed in a steel or aluminum case. The start capacitor is in a bake­alite or plastic shell. Some have a 15,000 ohm bleeder resistor across the terminals.
The power must be turned “OFF” and capacitors must be discharged before making the test. Use an AC voltmeter (set to the highest scale) or a 15,000 ohm 2 watt resistor to bleed away any charge left in the capacitor.
Remove the wires from the terminals and inspect the cas­ing. If it is bulged, cracked or split, the capacitor is defec­tive.
Use an analog voltmeter (dial or hand reading indicator) to test the capacitor after it has been discharged. Set the ohmmeter to mid-range and check for resistance to the case. Any resistance to the case from the terminals indicates it is defective and it needs to be replaced.
Set the ohmmeter to the highest scale and read across the terminals on the capacitor. The ohmmeter should swing towards zero and slowly move back towards infinity. Re­verse the leads and repeat the test. If the ohmmeter stays on infinity, it is open and needs to be replaced. If very little meter movement is noticed, switch the meter to a lower scale and repeat test.
The capacitors with the 15,000 ohm resistor should be checked on the 1,000 ohm scale. The ohmmeter should swing below 15,000 ohms and return. Reverse leads and repeat test. If the capacitor does not act as described it is defective and needs to be replaced.
5. MOTORS
To determine if a motor is good, test the windings with an ohmmeter. Disconnect the power supply, and turn all the switches to the “OFF” position. Disconnect the motor leads (on some models disconnect the 6 pin plug from the electri­cal box). The motor should show continuity between all leads and the white wire. Infinity or no continuity indicates the winding is open and the motor is defective.
Check for continuity between the motor frame and each lead. If a continuity reading is present to any lead, the motor is shorted and defective.
The motor can be tested with an ammeter to determine if the operation is within the rating (±10%) listed on the model plate. Many times the motor windings will check good, but bad bearings or capacitor may be found in an ampere test.
6. REMOTE SENSOR
The remote sensor is the temperature sensor that allows the unit for a zone to cycle “ON” and “OFF” by temperature. A remote sensor is used for each unit or zone. A remote sensor is usually optional for zone 1; but, in some applica­tions the Comfort Control Center is located for convenience of access and the remote sensor placed for temperature control.
3
Page 4
The proper location of the remote sensor is very important
Manual Compliments of
Northwest RV Supply
Printed From
http://www.nwrvsupply.com
to maintain a comfortable temperature in the RV. The fol­lowing rules should be observed when selecting a location:
a. Locate the remote sensor 54" above the floor. b. Install the remote sensor on a partition, never on an
outside wall.
c. Avoid locations that are close to doors that lead out-
side, windows or outside adjoining walls. d. Keep them away from discharge from supply registers. e. Place them in areas that have good air movement.
Avoid corners and under cupboards.
Unplug the remote sensor and test its cable with an ohm­meter. See figure 10. The ohm reading should be as follows:
TEMPERATURE OHM READING
55oF 11667 60oF 10212 65oF 8959 70oF 7876 75oF 6939 80oF 6126 85oF 5418 90oF 4802 95oF 4264
100oF 3793
Note: Any ohm reading has a tolerance of plus or minus 10%.
If the circuit is competed to a particular component and that component will not operate, the problem is in the roof top unit.
b. Roof Top Heat Pump
The operation of the AC control box can be checked at the 6-pin plug connection. See FIG. 6. When the Comfort Control Center is set to operate the heat pump the fan will operate in the low speed only in the Auto fan mode.Disconnect the unit and use a 115 volt light bulb to checkfrom terminal 5 (the white or com­mon wire) to: Terminal 1 (blue) is the compressor Terminal 2 (black) is high speed fan Terminal 3 (yellow) reversing valve - this wire is ener-
gized in cooling mode only Terminal 4 (red) is low speed fan Terminal 6 (green/yellow) chassis ground
If the circuit is completed the light bulb will illumi nate.
Note: Do not use a voltmeter to do the above tests as it will give erroneous readings.
If the circuit is completed to a particular component and that component will not operate, the problem is in the roof top unit. NEVER MIX 4 button circuit
boards and Comfort Control Centers with the 5 button circuit boards and Comfort Control Cen­ter.
7. WIRING
Mis-wiring or loose wires can cause electrical short or com­ponent failure. Use the wiring diagram to verify and correct wiring. Loose terminals should be tightened or replaced.
8. AC POWER MODULE
The AC power module board consists of a relay, dip switches, plug receptacles and other electrical components. If an one of these are defective the complete AC Control Box (some models only AC power module) must be replaced. The 3 amp fuse is the only replaceable part on the module board.
The board receives messages from the Comfort Control Center, and completes AC circuits to operate the unit. Be­fore diagnosing the AC power module, make sure the con­figuration, DC and AC voltages and operation is correct.
a. Roof Top Air Conditioners
The operation of the AC control box can be checked at the 6-pin plug connection. Disconnect the unit and use a 115 volt light bulb to check from terminal 5 (the white or common wire) to: Terminal 1 (blue) is the compressor Terminal 2 (black) is high speed fan Terminal 3 (yellow) is medium speed fan Terminal 4 (red) is low speed fan Terminal 6 (green/yellow) chassis ground
If the circuit is completed the light bulb will illuminate.
FIG. 6
c. Single Basement Air Conditioners and Heat
Pumps
The single air conditioner/heat pump require check out and replacement of the AC power module board only. The diagnosis of the board would be similar to the complete control box except the tests are done directly on the board. See FIG. 7.
FIG. 7
WHITE COMMON
Note: Do not use a voltmeter to do the above tests as it will
give erroneous readings.
4
Page 5
Use an AC light bulb to test if the relays on the board
Manual Compliments of
Northwest RV Supply
Printed From
http://www.nwrvsupply.com
are completing a circuit. Check from the common
(white wire) to:
“NO” is a black or blue wire on the compressor relay Terminal T1 is a black wire for high fan speed Terminal T2 is the reversing valve on heat pumps. If the violet wire is connected to T4 (Violet), it will oper­ate in reverse of the mode selected. Terminal T3 is a red wire for low fan speed Note: Do not use a voltmeter to do these checks as it will give erroneous readings.When the Comfort Con trol Center is set to operate the heat pump the fan will operate in the low speed only the Auto fan mode.
If the circuit is completed and that component is not operating, the problem is in the wiring to the compo­nent.
d. Dual Basement Air Conditioners and Heat Pumps
The operation of the dual air conditioner and heat pump can be checked in the same manner as the single basement air conditioner and heat pump. The stage dip switch (switch 7) is turned to the “ON” position to control the operation of the second compressor. See FIG. 8.
cold line in the cooling mode, the direction of flow is not correct.
Check the solenoid coil for ohms continuity. An open cir­cuit (no continuity) shows the solenoid is defective and must be replaced.
10. PTCR DEVICE
The positive temperature coefficient resistor/PTCR has re­placed the compressor start relay and in some cases the start capacitor. It should be checked in two different ways:
1. Check continuity. Turn “OFF” the AC power at the main breaker and Comfort Control Center system switch. Dis­connect the PTCR from the circuit. Using an ohmme­ter,check for continuity through the PTCR. If there is no continuity the PTCR is open and needs to be replaced.
This is an energized circuit. Shock can oc­cur if not tested properly. Testing is to be done by a qualified service technician.
FIG. 9
FIG. 8
2. The second check is an amp reading. Clamp an amme­ter around the wire from the start capacitor. See FIG. 9.
Use a 115 volt AC light bulb to check from common (white wire) to the other terminals to determine if the circuits are being completed. If the circuit is com­plete the light will illuminate.
Note: When the Comfort Control Center is set to op­erate the heat pump the fan will operate in the low speed only the Auto fan mode.
9. REVERSING VALVE
The reversing valve is the heart of a heat pump. It changes the direction of the refrigerant flow through the coils, and changes the system from cooling to heating.
Turn on the AC power and set the Comfort Control Cen­ter to the cooling mode. When the compressor starts, the ammeter should show a reading for approximately one second. If there is no amperage reading or a pro longed reading, the PTCR is faulty and must be replaced.
11. HEAT STRIP
Check the heat strip for continuity across the outside termi­nals at the heat strip plug. If the circuit is open (no continu­ity) the fuse link limit or heater element may be defective. When the Comfort Control Center is set to operate the heat strip the fan will operate in the low speed only the Auto fan mode.
The reversing valve’s solenoid can be energized in either the heat or cool mode of operation. Duo-Therm roof top heat pumps have the solenoid energized in the cool mode.
One method of checking the reversing valve is to feel the refrigerant line at the top of the inside coil. In the COOL mode, this line will be cool to the touch. In the heat mode the line will be warm or hot to the touch. If you do not feel a
5
Page 6
12. COLD CONTROL
Manual Compliments of
Northwest RV Supply
Printed From
http://www.nwrvsupply.com
(Low Temperature Protection Device)
The cold (freeze) control is used on both air conditioners and heat pumps. When the temperature of the coil reaches the freezing point the compressor will stop operation and the fan will automatically go to high speed.
The cold control is a thermistor and senses the coil tem­perature. Check continuity through the sensor and compare it to the chart below. Any variation requires the sensor to be replaced. See Figures 10, 10A & 10B
TEMPERATURE OHM READING
25oF 27271 30oF 23528 35oF 20348 40oF 17642 45oF 15334 50oF 13360
55oF 11667 Note: Any ohms reading has a tolerance of plus or minus 10% to be a good component. A very precise and accu-
rate ohmmeter must be used before replacing the cold control. Never use a cold control designed to operate with a different control system.
13. AMBIENT SENSOR
The ambient sensor is the outside air temperature sensor and used on heat pumps only. This device allows the heat pump to operate down to 30oF.
To check the ambient sensor, first measure the outside temperature near the sensor. Unplug the sensor (red plug) from the AC power module board. Using an ohmmeter, check the ohms through the ambient sensor on the wire side of the plug. See figure 10.
The temperature reading taken near the ambient sensor should correspond to the readings on the chart below:
TEMPERATURE OHM READING
55oF 11667 60oF 10212 65oF 8959 70oF 7876 75oF 6939 80oF 6126 85oF 5418 90oF 4802 95oF 4264
100oF 3793
FIG. 10
FIG. 10A
579, 591 & 595 SERIES UNITS
FIG. 10B
600, 620 & 630 SERIES UNITS
OUTDOOR
AMBIENT
SENSOR
GROMMET
Remove Hang Tag
Do
kdkd
mfmf
REMOTE SENSOR
Red
Bend fins over sensor to hold in place
Freeze control sensor
Insert Freeze Control Sensor at a slight angle between bottom coil approximately 1
Freeze Control with wires.
White
Freeze Control with wires to the right side
FREEZE CONTROL Blue
Remove Hang Tag
Insert Freeze Control Sensor at a slight angle between bottom coil approximately 1
Bend fins over sensor to hold in place
Freeze control sensor
10% to be a good component. A very precise and accu­rate ohmmeter must be used before replacing the ambient sensor.
Liquid Crystal Display
MODE OFF
ZONE 1
Comfort Control
Note: Any ohms reading has a tolerance of plus or minus
FIG. 11
MODE
FAN
UP
DOWN
ZONE
OFF ON
TEMP
Mode Selector Button
Fan Speed Selector Button
Temperature Selector Button
On/Off Switch
6
Zone and Stage Switch
Page 7
14.CONFIGURATION
Manual Compliments of
Northwest RV Supply
Printed From
http://www.nwrvsupply.com
The Comfort Control Center configuration relates to setting the dip switches and particular components (remote sen­sor, cold control, furnace, ambient sensor and load man­agement system) that can be connected to the AC power module board. The Comfort Control Systems can operate up to 4 units for one Comfort Control Center (thermostat) provided the configuration is correct. Note: If the configuration of the dip switches and other com­ponents are not correct, the unit could operate erratically or not at all.
Improper configuration could cause damage to components of the system.
Configuration is done on the AC power module board, usu­ally at the time of installation of the unit. Locate the control box or electric box that contains the AC power module board.
If a furnace is operated by the Comfort Control Center, the thermostat wires are attached to the two (2) blue wires from the control box. The furnace dip switch for that zone (con­trol box or power module) is turned on.
If the unit is a heat pump, the ambient sensor for the out­door temperature is plugged into the red P3 connection. If more than one unit is used, the zone dip switch must be turned on.
The two yellow leads on the control box are for use with the load management system. If the wires are connected or shorted to each other through the metal of the mounting or electrical box, the compressor will not operate.
The stage dip switch is used in dual basement heat pumps or air conditioners. It prevents both compressors from starting at the same time. The second stage is controlled by a temperature differential that is set in the Comfort Control
Center. The differen­tial can be set from 0
- 10o.
o
The configuration for zone 1 is all dip switches “OFF”. All units require the cold control to be plugged into the blue P5 connector on the board and the sensor is in­serted in the evaporator coil. If a remote sensor is used it will be plugged into the white P4 con­nector. See FIG. 10 &12.
The Comfort Control Center requires DC volt­age to be supplied to the red (positive +) and black (negative -) leads of the control box or power module.
The control box or power module is connected to the Comfort Control Center (wall thermostat) by a telephone type cable. See section B2. If more than one unit is to be operated off the Comfort Control Center, a second telephone type cable is needed. Both telephone cables are plugged into the control box or power module for the first unit. The second cable is routed to the control box or power module for the second unit. The dip switch for zone 2 needs to be turned on. See FIG. 8. Each additional zone (up to four total zones) requires only the dip switch for its zone number to be turned on.
If an electric heat strip is to be operated by the Comfort Control Center, it is plugged into the control box and the heat strip dip switch is turned to “ON”. If a second unit is equipped with a heat strip, the dip switch for the heat strip is turned on along with zone 2 dip switch.
FIG. 12
on an outside wall.
c. Avoid locations that are close to doors that lead out­side, windows or outside adjoining walls. d. Keep away from discharge from supply registers. e. Place in areas that have good air movement. Avoid
corners and under cupboards.
If the remote sensor is used for all zones, the Comfort Con­trol Center can be located anywhere that is convenient.
To check the Comfort Control Center, make sure the ON/ OFF switch is in the ON position. Check for DC voltage (10-16 VDC) to the CCC and that the polarity is correct. If the previously mentioned items are correct then do a reset on the CCC. NOTE: When the Comfort Control Center is set to operate the heat strip or heat pump, the fan will operate in the low speed only the Auto fan mode. NEVER MIX 4 button cir-
cuit boards and Comfort Control Centers with the 5 button circuit boards and Comfort Control Center.
7
b.Install the remote sensor on a partition, never
15. COMFORT CONTROL CENTER
The Comfort Control Center is the compo­nent that makes all the decisions for op­eration depending on the system and the accessories con­nected to it.
The location of the Comfort Control Cen-
ter is very important if it
is being used without a re-
mote sensor. Use the following
guidelines for the location:
a.Locate the remote sensor 54" above
the floor.
Page 8
16. SYSTEM RESET
Manual Compliments of
Northwest RV Supply
Printed From
http://www.nwrvsupply.com
a. Turn the ON/OFF switch to “OFF” position. b. Simultaneously depress and hold the MODE and ZONE
push-buttons while turning the ON/OFF switch to “ON”. FF should appear in the LCD display until the MODE and ZONE push-buttons are released.
c. When a dip switch is turned on or off after initial configu
ration, a system reset will need to be done before the Comfort Control Center lection. See figure 11.
17. DC VOLTAGE
A DC volt supply is required for operation of the Comfort Control Center. The operating range is 10 to 16 volts DC. If DC voltages are outside of the operating range, erratic op­eration may result.
Use a DC voltmeter to check for the incoming DC voltage between the red positive (+) and the black negative (-) at the connections of the electronic control box. If no DC voltage is found check the supply breaker or fuses.
Check the output voltage by using the telephone wall jack. One end of the cable is plugged into the A/C power module RJ-11 jack. The Comfort Control Center end is plugged into the telephone wall jack. Use a DC voltmeter to test for DC power between the red and black terminals. See FIG. 13 and 14. If there is no voltage present, check the control cable. See Section B2.
TM
will recognize the updated se-
FIG. 13
FIG. 14
8
Page 9
Manual Compliments of
Northwest RV Supply
Printed From
http://www.nwrvsupply.com
This Manual is Compliments of
Northwest RV Supply
86325 College View Road
Eugene, OR 97405
Local: 541-746-9092
Toll-Free: 866-678-7467
Fax: 541-736-5573
http://www.nwrvsupply.com
mail@nwrvsupply.com
Northwest RV Supply carries a large spectrum of surplus, used, and new
RV parts and components. Please feel free to visit our website for
additional information.
Loading...