Dometic 3109228.001 Troubleshooting Manual

TROUBLESHOOTING
Manual Compliments of
Northwest RV Supply
Printed From
http://www.nwrvsupply.com
for the
5 BUTTON 3109228.001
COMFORT CONTROL
CENTER SYSTEM
AIR CONDITIONER BULLETIN A29/2A JANUARY 2002
INTRODUCTION
The Comfort Control Center control system can be used to operate the following Duo-Therm Units:
Roof Top Air Conditioners Roof Top Heat Pumps Basement Air Conditioners Basement Heat Pumps Dual Basement Air Conditioners Dual Basement Heat Pumps Other Manufacturer’s Furnaces
A majority of air conditioner and heat pump problems are electrical and can be found very easily.
To find a problem in the electrical system, you need to be able to diagnose the following:
1. Power Source 10. PTCR Device
2. Cable Assembly 11. Heat Strip
3. Compressor 12. Cold Control
4. Capacitors 13. Ambient Sensor
5. Motors 14. Configuration
6. Remote Sensor 15. Comfort Control Center
7. Wiring 16. System Reset
8. AC Power Module 17. DC Voltage
9. Reversing Valve
TOOLS REQUIRED
The air conditioner can be checked with a voltmeter, ohm­meter, clamp-on ammeters and two good thermometers. Some clamp-on ammeters can read voltage and ohms.
FIG. 1
Form No. 3307835.003 1/02 (French 3307836.001) ©2002 Dometic Corporation LaGrange, IN 46761
A. QUICK-CHECK TROUBLE-
SHOOTING FOR COMFORT CONTROL CENTER (CCC) CONTROLS
For detailed troubleshooting, refer to sec­tion noted.
1. Air Conditioner/Heat Pump turned on – No display
a. Reset - Sec. B15 b. DC Voltage - Sec. B17 c. Cable Assembly - Sec. B2 d. AC Control Module - Sec. B8 e. Comfort Control Center (CCC) - Sec. B15
2. Air Conditioner/Heat Pump turned on – Has display, improper operation
a. Power Source - Sec. B1 b. Reset - Sec. B16 c. Configuration - Sec. B14 d. Wiring - Sec. B7 e. AC Control Module - Sec. B8 f. Comfort Control Center (CCC) - Sec. B15
3. Air Conditioner/Heat Pump turned on – Fan runs, No compressor operation
a. Start Relay/PTCR - Sec. B10 b. Start Capacitor - Sec. B5 c. Fan/Run Capacitor - Sec. B4 d. Cold Control - AC Only, Sec. B12 e. Outdoor Ambient Sensor (HP) - Sec. B13 f. Compressor - Sec. B3 g. Wiring - Sec. B7 h. Comfort Control Center - Sec. B15 i. AC Control Module - Sec. B8
4. Air Conditioner/Heat Pump turned on – Com­pressor runs, No fan operation
a. Fan/Run Capacitor - Sec. B4 b. Motor - Sec. B5 c. Wiring - Sec. B7 d. Comfort Control Center (CCC) - Sec. B15 e. AC Control Module - Sec. B8
5. Heat Pump turned on – Compressor runs and fan runs, No heat output
a. Reversing Valve - Sec. B9 b. Wiring - Sec. B7 c. AC Control Module - Sec. B8
1
B. DETAILED TROUBLESHOOTING
Manual Compliments of
Northwest RV Supply
Printed From
http://www.nwrvsupply.com
FOR COMFORT CONTROL CENTER (CCC) CONTROLS
We will now start electrically troubleshooting Comfort Con­trol Center (CCC) controlled units. The best place to begin is at the power source.
1. POWER SOURCE
If the compressor or fan fails to operate, it is probably not receiving power. Be sure the power cord is plugged in and no fuses or breakers are tripped.
Note: Many customers use extremely long power cords that are undersized. If possible, ask the owner to hook up the RV just like it was when the problem occurred.
FIG. 2
Make note of the wire size and length of wire. Compare it to the chart for wire sizing.
For normal operation of the unit, AC voltage must stay between 103.5 VAC and 126.5 VAC. Operation of the unit outside of this voltage range can result in component damage.
To determine if power is reaching the air conditioner, the inside plastic air diffuser box must be removed. The junction box will now be exposed. Remove the cover from the junc­tion box to gain access to the connection between the RV and the unit wires (FIG. 3). Check with a voltmeter for volt­age at the connections of the unit to RV wires. USE CAU- TION as 115 volts may be present.
If no voltage is present, the problem is in the coach wiring or breaker/fuse box.
2. CABLE ASSEMBLY
A flat control cable must be routed from the unit to the Com­fort Control Center. It must be 26 gauge, stranded copper wire, four (4) conductor (yellow, green, red, and black). The cable must be terminated with a four (4) position telephone RJ-11 Connector.
Note: Do not use a pre-made telephone extension cable. The order of the connectors is reversed and will cause a failure of the system.
CURRENT WIRE SIZE
IN
AMPS 16 14 12 10 8 6
LENGTH IN FEET
5 47 76 121 192 216 486
10 38 60 96 153 243
15 25 40 64 102 162
20 30 48 76 121
FIG. 3
FIG. 4
2
The cable should be made in the following manner:
Manual Compliments of
Northwest RV Supply
Printed From
http://www.nwrvsupply.com
Cut the control cable to the desired length. When cutting make sure ends are cut straight, not diagonally. Next, use an RJ-11 connector crimping tool.
Use the stripper section of the tool to remove the outer insu­lation of the cable. Be careful not to remove or break the colored insulation of the inner conductors. Repeat on oppo­site end.
Insert the prepared cable into the RJ-11 plug. When insert­ing cable you MUST be sure that the black wire is on your left as you look at the top of the plug. See FIG. 5. Insert the RJ-11 plug into the tool and squeeze to the stop. Repeat the procedure for other end.
FIG. 5
The finished cable can be tested with a 3107127.007 com­fort control cable tester. See Section B16 for more informa­tion on the testing of the cable.
3. COMPRESSOR
The compressor motor can be electrically checked. Be sure to disconnect all power and turn all switches to the “OFF” position, before starting to do the tests.
Remove the terminal cover from the compres­sor and disconnect the three leads connected to the terminals. Make note of the positions so the wires can be replaced correctly.
Use an ohmmeter to check for continuity through the over­load device. If no continuity is found and the compressor is hot, allow 15 to 20 minutes for the compressor to cool. If a repeat of the test shows the overload to be open, it is defec­tive and requires replacement.
Continuity should exist between all three terminals of the compressor. If there is no continuity the compressor wind­ings are open and the compressor is defective.
Scrape the compressor casing to bare metal and check continuity from each terminal to the casing. If continuity is found to the casing on any of the terminals, the compressor is shorted and it is defective.
4. CAPACITORS
Duo-Therm Air Conditioners and Heat Pumps use three dif­ferent capacitors: 1) compressor run capacitor 2) compres­sor start capacitor and 3) fan/blower capacitor. On some
units the compressor run and fan/blower capacitor are in the same case.
The compressor run and fan/blower capacitor are housed in a steel or aluminum case. The start capacitor is in a bake­alite or plastic shell. Some have a 15,000 ohm bleeder resistor across the terminals.
The power must be turned “OFF” and capacitors must be discharged before making the test. Use an AC voltmeter (set to the highest scale) or a 15,000 ohm 2 watt resistor to bleed away any charge left in the capacitor.
Remove the wires from the terminals and inspect the cas­ing. If it is bulged, cracked or split, the capacitor is defec­tive.
Use an analog voltmeter (dial or hand reading indicator) to test the capacitor after it has been discharged. Set the ohmmeter to mid-range and check for resistance to the case. Any resistance to the case from the terminals indicates it is defective and it needs to be replaced.
Set the ohmmeter to the highest scale and read across the terminals on the capacitor. The ohmmeter should swing towards zero and slowly move back towards infinity. Re­verse the leads and repeat the test. If the ohmmeter stays on infinity, it is open and needs to be replaced. If very little meter movement is noticed, switch the meter to a lower scale and repeat test.
The capacitors with the 15,000 ohm resistor should be checked on the 1,000 ohm scale. The ohmmeter should swing below 15,000 ohms and return. Reverse leads and repeat test. If the capacitor does not act as described it is defective and needs to be replaced.
5. MOTORS
To determine if a motor is good, test the windings with an ohmmeter. Disconnect the power supply, and turn all the switches to the “OFF” position. Disconnect the motor leads (on some models disconnect the 6 pin plug from the electri­cal box). The motor should show continuity between all leads and the white wire. Infinity or no continuity indicates the winding is open and the motor is defective.
Check for continuity between the motor frame and each lead. If a continuity reading is present to any lead, the motor is shorted and defective.
The motor can be tested with an ammeter to determine if the operation is within the rating (±10%) listed on the model plate. Many times the motor windings will check good, but bad bearings or capacitor may be found in an ampere test.
6. REMOTE SENSOR
The remote sensor is the temperature sensor that allows the unit for a zone to cycle “ON” and “OFF” by temperature. A remote sensor is used for each unit or zone. A remote sensor is usually optional for zone 1; but, in some applica­tions the Comfort Control Center is located for convenience of access and the remote sensor placed for temperature control.
3
Loading...
+ 6 hidden pages