Doepke Dupline Operating Instructions Manual

Page 1
Doepke
1. Allgemeines....................................2
2. Wichtige Hinweise vorab................2
3. Kodierung.......................................2
4. Installation......................................3
5. Inbetriebnahme ..............................3
6. LED-Anzeige..................................3
7. Garantie..........................................3
8. Technische Daten .......................... 4
17. Anschlussbeispiel / Conn. Ex. ........8
Table of Contents
9. General Information.. ... .. ................ 5
10. Important Notes in Advance........... 5
11. Coding............................................ 5
12. Installation...................................... 6
13. Putting into Service........................ 6
14. LED Indicator ................................. 6
15. Guarantee ...................................... 6
16. Technical Data ....................... ... ..... 7
17. Anschlussbeispiel / Conn. Ex......... 8
Dupline
Infrarot-Empfänger DIR 2
DIR 2 Infrared Receiver
Bedienungsanleitung
Operating Instructions
3931222/2009.06/F
Page 2
Doepke
Bedienungsanleitung
Infrarot-Empfänger DIR 2

1. Allgemeines

Der Infrarot-Empfänger DIR 2 ist eine Komponente des Dupline Installationssystems und ermöglicht das Fernschalten und Ferndimmen von bis zu 8 Kanälen je Einheit. Eine Einheit besteht dabei aus dem Empfänger DIR2 und dem separat erhältlichen Handsen­der DIR 2T.
Deutsch
Der Empfänger wird aus dem Dupline Bussignal mit Spannung versorgt, sodass keine weiteren Anschlüsse erforderlich sind. Er ist sowohl für die Aufputzmontage als auch für den Einbau in Unterputz-Schalterdosen geeignet. Mit der Kombination aus einem Empfänger DIR2 und einem Handsender DIR 2T kön­nen acht Dupline-Kanäle geschaltet werden. Sollen mit eine m Sender mehr a ls acht Ka­näle geschaltet werden, ist die entsprechende Anzahl an Empfängern, eingestellt auf unterschiedliche Schaltgruppen im Bereich A bis H, einzusetzen. Die Bezeichnung der Schaltgruppen (A bis H) steht dabei in keinem Zusammenhang mit den Dupline Kanal­bezeichnungen. Der Handsender DIR 2T muss dann nur noch auf die Schaltgruppe des anzusprechenden Empfängers eingestellt werden. Der jeweilige Schaltbefehl wird über einen der acht Taster ausgelöst.

2. Wichtige Hinweise vorab

• Die Installation darf nur von einer autorisierten Fachkraft vorgenommen werden.
• Die Dupline-Signalversorgung muss aus Quellen erfolgen, die den Anforderungen für Schutzkleinspannung entsprechen, ebenso , wie d ie I nstallat ion die sen A nfo rde­rungen genügen muss (siehe hierzu die VDE0100, Teil 410 sowie die EN 50090-1-
1). Andere Spannungen an den Signaleingängen können, trotz umfangreicher Schutzmaßnahmen im Gerät, zur Zerstörung des Gerätes und Gefährdung von Menschen führen. Weitere Hinweise finden Sie in der Dupline Planungshilfe.

3. Kodierung

Mit dem Handkodiergerät DHK 1 kann über die, unter dem hinteren Gehäusedeckel an­gebrachte, Stiftleiste jedem Schaltbefehl jede belieb ige Adresse zwischen A1 und P8 zu­geordnet werden. Die Aufteilung der Kanäle ist wie folgt:
Kanal Beschreibung Kanal Beschreibung
1..4 Handsender-Schaltbefehl 1..4 5..8 Handsender-Schaltbefehl 5..8
Schaltbefehle, die nicht benötigt werden, sollten unkodiert bleiben. Die Kodierung des DIR 2 kann ohne Versorgungsspannung sowie ohne Dupline-Signal vorgenommen wer­den. Sie bleibt dauerhaft erhalten, kann aber jederzeit überschrieben werden.
1-Inh altsverzeichnis
2
3931222/2009.06/F - Technische Änderungen vorbehalten!
Page 3
Doepke

4. Installation

Der Empfänger muss so platziert werden, dass zwischen Handsender und Empfänger "Sichtkontakt" herrscht bzw. Reflexionsempfang möglich ist. Dabei darf die maximale Reichweite von 15 m nicht überschritten werden. Wände, Scheiben oder starke Fremd­lichteinwirkung behindern den Empfang und sind daher zu vermeiden. Bei der Installation ist das Anschlussschema auf Seite 8 zu beachten. Alle anzuschlie­ßenden Leitungen müssen spannungsfrei sein. Verbindungen zwischen dem Dupline-Signal und Erdpotenzial führen zu Störungen und sind nicht zulässig. Auf die richtig e Polarität des Dupline-Signals i st zu achten. Folgende Tabelle zeigt die Anschlussbelegung des DIR 2:
Klemme Beschreibung Klemme Beschreibung
1 Dupline Signalleiter + (D+) 2 Dupline Signalleiter - (D-)

5. Inbetriebnahme

Der Empfänger ist nach Anschluss des Dupline-Busses und Adresskodierung betriebs­bereit. Bei Verwendung mehrerer Empfänger sind diese jeweils auf unterschiedliche Schaltgruppen von A bis H einzustellen. Dieses geschieht über den DIP-Schalter, der nach Öffnen des Gehäuses zugänglich ist (siehe Kapitel18 ”DIP-Schalter / DIP Swit­ches” auf Seite 8).

6. LED-Anzeige Anzeige Beschreibung

Rote LED
a. Nach dem Einschalten des Busses bleibt die LED bis zum erstmaligen Empfang eines gül-
tigen Sendebefehls aktivi ert.

7. Garantie

Für fachgerecht montierte, unveränderte Geräte gewähren wir ab Kauf durch den End­verbraucher die gesetzliche Gewährleistungsfrist. Die Garantie bezieht sich nicht auf Transportschäden sowie Schäden, die durch Kurzschluss oder Überlastung ent stan den sind. Bei Fertigungs- und Materialfehlern, di e innerhalb der Gewährleist ungsfrist erkannt werden, leistet unser Werk kostenlosen Ersatz.
Aus: Kein oder ein ungültiges Telegramm erhalten An: Gültiges Telegramm erhalten
a
Deutsch
3931222/2009.06/F - Technische Änderungen vor be hal t en!
3
Page 4
Doepke

8. Technische Daten

Dupline
Übertragung
Deutsch
Betriebsspannung
Anschlüsse
Gehäuse
Allg. technische Daten
Bestellnummer, -bezeichnung 09 501 169, IR-Empfänger DIR 2
Stromaufnahme 1,8 mA 3,2 mA
Ein-/Ausgangskanäle Keine / 8 Schaltbefehle
Art Infrarotlicht, 950 nm
Trägerfrequenz 38 kHz
Anzahl Schaltgruppen 8 („A“ bis „H“), einstellbar
Nennbetriebsspannung nicht erforderlich (aus Dupline-Signalleiter)
Art Steckklemmen, Schraubklemmen beigelegt
Klemmbereich 0,4 mm 2,5 mm²
Art polarweißes Gehäuse für AP- und UP-Montage
Maße 80 x 80 x 15 (B x H x T in mm)
Material Polycarbonat
Betriebstemperatur -10°C +45°C
Schutzart / Normen IP 40, IEC 60669, EN 50428, EN 55090 / EN 61000-
Min. Typ. Max.
6-3, EN 55024 / EN 61000-6-1
4
3931222/2009.06/F - Technische Änderungen vorbehalten!
Page 5
Doepke
Operating Instructions
DIR 2 Infrared Receiver

9. General Information

The DIR 2 infrared receiver is a component of the Dupline installation system and per­mits remote switching and dimming of up to 8 channels per unit. Here, one unit consists of a receiver (DIR 2) and a separately available hand transmitter DIR 2T. The receiver is supplied with voltage by the Dupline bus signal so that no further co nnec­tions are required. It is suitable for surface mounting as well as f or fitting into flush-mount­ed sockets. With the combination of one DIR 2 receiver and one DIR 2T hand transmitter up to eight Dupline channels may be switched. If more than eight channels are to be switched with one transmitter, the appropriate number of receive rs has to be used and adju sted t o dif­ferent switching groups in the range A to H which is done once at each DIR2 by means of DIP switches. There is no relation between the designation of the switching groups (A to H) and the Dupline channel addresses. Then the transmitter simply has to be adjusted to the switching group of the receiver to be addressed. The respective switching com­mand is given by means of one of the eight push buttons.

10. Important Notes in Advance

• The installation may only be carried out by an authorised technician
• The Dupline signal supply has to be delivered b y sources, which have to be installed in accordance with the regulations governing protective low-voltage (see VDE 0100, Part 410, or EN 50090-9-1) as well as the installation has to comply with these re­quirements. Even if extensive protective measures have been implemented in the device, other voltages at the signal inputs could result not only in the destruction of the device, but also endanger people. For further infor mation please refe r to the Du­pline Planning Aid.

11. Coding

At the 4-pole flat pack connector behind the rear housing co ver, any address between A1 and P8 can be assigned to each switching command using the DKH1 hand encoder. The allocation of the channels is as follows:
Channel Description Channel Description
Switching commands which are not required should remain uncoded. Encoding the DIR 2 requires neither a power supply nor the Dupline signal. Although the coding is per­manently retained, it may always be overwritten.
Switching command 1..4
1..4
1-Table of Contents
Switching command 5..8
5..8
English
3931222/2009.06/F - The right to make technical changes reserved!
5
Page 6
Doepke

12. Installation

The receiver must be sited so that „visual contact“ between hand transmitter and receiver is ensured or reflection reception is possible. In so doing, the maximum range of 15 m may not be exceeded. Walls, glass panes and light and sun insolation may impair the re­ceive characteristics and thus are to be avoided. Follow the connection diagram on page 8 when installing. All leads to be connected must be dead. Connections between the Dupline signal and earth potential will cause malfuncti ons and are not permissible. In addition, check for the correct polarity of the Dupline signal. The following table illustrates the connection configuration:
Terminal Description Terminal Description
1 Dupline signal conductor + (D+) 2 Dupline signal conductor - (D-)

13. Putting into Service

The receiver is operational after connecting the Dupline bus and coding the addresses. When using several receiver each of them have to be adjusted to work on different switching groups A to H. This is done by means of the DIP switch which is accessible af­ter opening the housing (see Chapter 18 “DIP-Schalter / DIP Switches” on page 8).
English

14. LED Indicator Indicator Description

Red LED
a. After switching on the bus the LED remains activated until the first valid comm and has
been received.

15. Guarantee

All professionally installed, unaltered devices are covered by warranty during the statu­tory guarantee period from the day of purchase by the end user. The guaran tee is not ap­plicable to damage incurred during transport or caused by short-circ uit or overloading. In the event of defects in workmanship or material, which are discovered within the guar­antee period, the company will provide a replacement free of charge.
Off: No or invalid telegram received On: Valid telegram received
a
6
3931222/2009.06/F - The right to make technical changes reserved!
Page 7
Doepke

16. Technical Data

Dupline
Current input 1.8 mA 3.2 mA
Input / output channels
Transmission
Type Infrared light, 950 nm
Carrier frequency 38 kHz
Number of groups 8 („A“ to „H“), adjustable
Operating Voltage
Rated operating voltage Not required (supplied by Dupline signal line)
Terminals
Type Spring-loaded terminals, screw terminals enclosed
Contact area 0.4 mm 2.5 mm²
Housing
Type
Dimensions
Material Polycarbonate
General technical data
Ambient temperature -10°C +45°C
Encl. protection type / standards IP 40, IEC 60669, EN 50428, EN 55090 / EN 61000-
Order number, description 09 501 169, IR receiver DIR 2
Min. Typ. Max.
None / 8 switching commands
Polar-white housing for surface and flush mounting 80 x 80 x 15 (W x H x D in mm)
6-3, EN 55024 / EN 61000-6-1
English
3931222/2009.06/F - The right to make technical changes reserved!
7
Page 8
Doepke
Dupline +
Dupline -
ON
12 4
3
DIP
3931222_2A
UP
ON
12 4
3
DIP
3931222_3A
ON
12 4
3
DIP
ON
12 4
3
DIP
ON
12 4
3
DIP
ON
12 4
3
DIP
ON
12 4
3
DIP
ON
12 4
3
DIP
ON
12 4
3
DIP
A
B
C D
E F G H
ON OFF
Schaltgruppe: Switching Group:
Schaltgruppe: Switching Group:

17. Anschlussbeispiel / Conn. Ex.

18. DIP-Schalter / DIP Switches

Zeichnungen / Drawings
Sollten Sie Fragen zu diesem Produkt oder zum Dupline-System haben, wen­den Sie sich bitte an:
Doepke
Schaltgeräte GmbH & Co. KG Stellmacherstraße 11 D-26506 Norden, Germany Tel.: +49 (0) 4931/1806-0 Fax: +49 (0) 4931/1806-101
8
3931222/2009.06/F - The right to make technical changes reserved!
In case of queries concerning this product or the Dupline system please contact:
Internet:
E-mail:
info@doepke.de
http://www.doepke.de