SP600
AC DRIVES
SP600 Series of AC Drives from 0.5 to 200 Horsepower
DATA SHEET
A full-featured industrial AC drive suitable for wall, machine, flange, and washdown mounted installations
The SP600 provides the benefits of more expensive full-featured drives in a compact, versatile, and cost effective design. Multiple enclosure/packaging options along with a drive mounted graphical keypad and embedded braking circuitry make this drive very versatile. The wide range of network options available for this product will allow you to maximize data acquisition, speed control and application flexibility.
Features/Specifications
• Control Modes
- Volts/Hertz
- Sensorless Vector Control Each method can operate either a single or
multi-motor application from one SP600. SVC is limited to mechanically coupled identical motors.
• Input Voltages/Power Ratings
- 200, 208, 240 (0.5 to 10 HP)
- 380, 400, 415, 480 (0.5 to 200 HP)
- 575 (0.5 to 150 HP)
• Switching Frequency
- Full HP rating at 50°C for (45° for 50 HP; 40° for 200 HP):
• 4 kHz Frames A - D
• 4 kHz Frames 2 -5
• 4 kHz Frame 6 (2 KHz for 200 HP)
- Derating may apply for higher switching frequencies
• Zero-stacking (side by side) panel mounting
possible for all frames.
1
575 VAC models are UL and cUL only
1
• Terminal Block Control
- 6 configurable digital inputs
- Up to 8 pre-set speeds
- Start/Stop, Forward/Reverse,Auto/Manual, Jog, Preset Speed, Function Loss, ProcessPI Control, etc.
- 2 Analog inputs
- 1 Analog output
- 2 Relay outputs, form C contacts.
• Drive Serial Interface
- PC configuration and monitoring of a single drive or multiple drives when using V*S Utilities Software.
• Overload Protecting
- Intelligent Thermal Management (ITM™) system can reduce carrier frequency or trip the drive in overtemp conditions.
- UL and NEC approved electronic motor overload protection.
• Enclosures/Mounting
- Wall or machine mount NEMA 1 (IP20)
- Flange mount NEMA 1 (IP20)
- See RAPS-958-2 for NEMA 4x/12
• Internal Braking transistor as standard (optional
Frames 4, 5, and 6) requires optional drive mounted or externally mounted braking resistor
- Drive mounted resistor available for Frames A, B, C, D, and 2
• Ramp Control
- 2 accel/decel rates
- Frequency avoidance bands (3) to lock out mechanical resonance points.
- “S” curve acceleration and deceleration for smooth speed transitions
• Time Stamped Fault Log
- User Interlock Open
- High DC Bus Voltage
- Low DC Bus Voltage
- Over-Current
- Over-Frequency
- Over-Temperature
- Electronic Motor Overload
- Ground Fault
- Others
• Option Kits
- Braking resistors
- Remote NEMA 4 operator interface
- PC based V*S Utilities
- EMC line filters
- Network communications modules
- ControlNet
- DeviceNet
- Profibus
- Others
• Stopping Modes
- DB Braking
- Ramp Stop
- Coast Stop
- DC Injection Braking
Instruction Manuals
• D2-3485 (6SP Series - Frames A, B, C, D)
• D2-3501 (6SB Series - Frames 2, 3, 4, 5, 6)
Service Conditions
• Elevation to 3300 ft. (1000 meters); Derate 3% for every
1000 ft. above 3300 ft.
• Operating temperature ranges:
- NEMA enclosures:
- 0°C to 40°C (external ambient)
- IP20 enclosures:
- 0°C to 50°C (50 HP - 45°C; 200 HP - 40°C) (panel ambient)
• Atmosphere non-condensing relative humidity: 5% to 95%
• AC line voltage variation: rated input voltage ±10%
• AC line frequency variation (50/60 Hz): 48 - 62 Hz
• Storage temperature:
- - 40°C to 65°C
(-40°F to 149°F)
Application Data
• Pulse width modulation (PWM) sensorless vector control
Quiet Motor Operation Up to 200 Feet
• The SP600 controller uses IGBT transistors switched at frequencies up to 10kHz to reduce PWM induced motor audible noise.
• Unique transistor control circuits also allow drive to motor distances of up to 300 feet when applied with Reliance motors before output filtering considerations must be applied.
• Operator Interface Modules
- Multi-line, 6-language graphical LCD OIM for local or remote operation. Allows drive control, configuration, monitoring and diagnostics. Function keys are configurable for desired functions.
• Drive Protection
- Line-to-line and line-toground and output short circuit protection.
• Maximum load:
- 110% continuous for one minute (Normal Duty Rating)
- 150% continous for one minute (Heavy Duty Rating)
• Frequency stability long term: 0.01%
of base speed with digital keypad
0.5% of base speed with analog speed reference.
• Linearity (speed reference to output
frequency): ± 1.0%
• Tested to ensure that the waveform at the motor conduit box will not exceed the limits specified in NEMA MG1
31.40.4.2. at lead lengths of 200 ft.