Aggregate/Cement
Food
✓
Mining
Forest/Paper
✓
Petro/Chem
✓
Unit/Baggage
✓
Handling
HVAC/Industrial Air
✓
Handling
Environmental/Fluid
✓
Power
Automotive
✓
Metals
SP600
AC DRIVES
SP600 Series of AC
Drives from 0.5 to 200
Horsepower
DATA SHEET
A full-featured industrial AC drive
suitable for wall, machine, flange, and
washdown mounted installations
The SP600 provides the benefits of
more expensive full-featured drives in a
compact, versatile, and cost effective
design. Multiple enclosure/packaging
options along with a drive mounted
graphical keypad and embedded
braking circuitry make this drive very
versatile. The wide range of network
options available for this product will allow
you to maximize data acquisition, speed
control and application flexibility.
Features/Specifications
• Control Modes
- Volts/Hertz
- Sensorless Vector Control
Each method can operate either a single or
multi-motor application from one SP600. SVC
is limited to mechanically coupled identical
motors.
• Input Voltages/Power Ratings
- 200, 208, 240 (0.5 to 10 HP)
- 380, 400, 415, 480 (0.5 to 200 HP)
- 575 (0.5 to 150 HP)
• Switching Frequency
- Full HP rating at 50°C for (45° for 50 HP;
40° for 200 HP):
• 4 kHz Frames A - D
• 4 kHz Frames 2 -5
• 4 kHz Frame 6 (2 KHz for 200 HP)
- Derating may apply for higher switching
frequencies
• Zero-stacking (side by side) panel mounting
possible for all frames.
1
575 VAC models are UL and cUL only
1
• Terminal Block Control
- 6 configurable digital inputs
- Up to 8 pre-set speeds
- Start/Stop, Forward/Reverse,Auto/Manual,
Jog, Preset Speed, Function Loss, ProcessPI
Control, etc.
- 2 Analog inputs
- 1 Analog output
- 2 Relay outputs, form C contacts.
• Drive Serial Interface
- PC configuration and monitoring of a single
drive or multiple drives when using V*S Utilities
Software.
• Overload Protecting
- Intelligent Thermal Management (ITM™) system
can reduce carrier frequency or trip the drive in
overtemp conditions.
- UL and NEC approved electronic motor
overload protection.
• Enclosures/Mounting
- Wall or machine mount NEMA 1 (IP20)
- Flange mount NEMA 1 (IP20)
- See RAPS-958-2 for NEMA 4x/12
• Internal Braking transistor as standard (optional
Frames 4, 5, and 6) requires optional drive
mounted or externally mounted braking resistor
- Drive mounted resistor available for Frames A,
B, C, D, and 2
• Ramp Control
- 2 accel/decel rates
- Frequency avoidance bands (3)
to lock out mechanical resonance
points.
- “S” curve acceleration and
deceleration for smooth speed
transitions
• Time Stamped Fault Log
- User Interlock Open
- High DC Bus Voltage
- Low DC Bus Voltage
- Over-Current
- Over-Frequency
- Over-Temperature
- Electronic Motor Overload
- Ground Fault
- Others
• Option Kits
- Braking resistors
- Remote NEMA 4 operator
interface
- PC based V*S Utilities
- EMC line filters
- Network communications modules
- ControlNet
- DeviceNet
- Profibus
- Others
• Stopping Modes
- DB Braking
- Ramp Stop
- Coast Stop
- DC Injection Braking
Instruction Manuals
• D2-3485
(6SP Series - Frames A, B, C, D)
• D2-3501
(6SB Series - Frames 2, 3, 4, 5, 6)
Service Conditions
• Elevation to 3300 ft.
(1000 meters); Derate 3% for every
1000 ft. above 3300 ft.
• Operating temperature ranges:
- NEMA enclosures:
- 0°C to 40°C (external ambient)
- IP20 enclosures:
- 0°C to 50°C
(50 HP - 45°C; 200 HP - 40°C)
(panel ambient)
• Atmosphere non-condensing relative
humidity: 5% to 95%
• AC line voltage variation: rated input
voltage ±10%
• AC line frequency variation (50/60
Hz): 48 - 62 Hz
• Storage temperature:
- - 40°C to 65°C
(-40°F to 149°F)
Application Data
• Pulse width modulation (PWM)
sensorless vector control
Quiet Motor Operation Up
to 200 Feet
• The SP600 controller uses IGBT
transistors switched at frequencies up
to 10kHz to reduce PWM induced
motor audible noise.
• Unique transistor control circuits also
allow drive to motor distances of
up to 300 feet when applied with
Reliance motors before output filtering
considerations must be applied.
• Operator Interface Modules
- Multi-line, 6-language graphical
LCD OIM for local or remote
operation. Allows drive control,
configuration, monitoring and
diagnostics. Function keys are
configurable for desired functions.
• Drive Protection
- Line-to-line and line-toground and
output short circuit protection.
• Maximum load:
- 110% continuous for one minute
(Normal Duty Rating)
- 150% continous for one minute
(Heavy Duty Rating)
• Frequency stability long term: 0.01%
of base speed with digital keypad
0.5% of base speed with analog
speed reference.
• Linearity (speed reference to output
frequency): ± 1.0%
• Tested to ensure that the waveform at
the motor conduit box will not exceed
the limits specified in NEMA MG1
31.40.4.2. at lead lengths of 200 ft.