Installation and operation conventional fire detectors
D9000 series
Nom.№
Type
Characteristics
Sensitivity / Class
1001
D9000 SR
Optical smoke detector
EN 54-7
1002
D9000 T / A1R
Rate of rise heat detector
A1R, EN 54-5
1003
D9000 T / A1S
Fixed temerature heat detector
A1S, EN 54-5
1004
D9000 MSR
Combines optical smoke and heat detector
A1R, EN 54-5 / EN 54-7
Caution : Read this manual before attempting to install the detector.
1. Technical specifications
Supply voltage 9-30 V DC Power consumption in Duty condition ≤ 130 µА Consumption in " Fire " condition 20 mА/ 24V DC limiting resistor output 2 Degree of protection IP 40 Cross section of the connecting wire 0,4÷2,0 mm2 Operating temperature range 10ºС ÷ 50ºС Humidity (93 ± 3)% при 25ºС Dimensions with base f 100mm h ≤ 52mm Weight ≤ 100g
Mounting the detector
Choose the place (according to the plans of the project) for the installation of the detector ; Mount the base with appropriate fixings ; Connect the electrical cables according to the attached diagram ( Figure 1) ;);
Fig.1
Place the detector base and rotate clockwise till matching markers; If you want to lock detector ::
Pre remove the key from the base ( Figure 2). Break the plastic at the specified location on the bottom of the sensor ( Figure 3 ).
Page 2
Instructions for installation and commissioning conventional of fire alarms D9000 series
Fig.2 Fig.3 Fig.4
Place the detector base and rotate it .
If the detector is locked to the base, to unlock it , insert first the key to the specified location
(Fig. 4) and rotate the detector counterclockwise;
Test the detector to check the correct operation of the LED indication; During normal operation, the LEDs blink for 16 seconds.
2. Testing and Maintenance
Testing
Apply power; Wait about a minute or until the detector begins to blink; Activate the detector test spray and / or temperature sonda. The two red LEDs must illuminate
permanently.
Service maintenance
Visual inspection for mechanical damage and pollution - once a year; – Verification of performance - once a year; Prophylactic cleaning - depending on the environment in which it is located.
Optical detectors D9000 SR/MSR are software tested and when the detector is contaminated, it is signaled by flashing LEDs for 2 seconds to 2 seconds .
D9000 Series detectors are compatible with all conventional power plants, that have met the requirements of a standards EN54.
The detectors are available with three types of bases:
In 9000 - a standard basis; – In 9000D - standard base with diode for recording damage detector down;In 9000R - standard base with relay output 12V for security panels.
3. Warranty obligations
The manufacturer guarantees the conformity of the device with standards EN 54-5 and EN54-7. The warranty period is 24 months from the date of sale , provided that:
the conditions of storage and transport have been followed; release is performed by authorized persons; the requirements for operation stated in this instruction have been abode. defects are not caused by natural phenomena and accidents of the plug socket.
When there is the need of warranty repair , please contact us by phone or email to give you guidelines for the warranty obligations of the company. Repairs are carried out in the company's service company.