This equipment generates and uses radio frequency energy and, if not installed and used properly in strict accordance
with the manufacturer’s instructions, may cause interference with radio and television reception. It has been type tested
and found to comply with the limits for a Class A computing device in accordance with the specication in Subpart J
of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential
installation. If this equipment does cause interference to radio or television reception, which can be determined by
turning the equipment o and on, the installer is encouraged to try to correct the interference by one or more of the
following measures:
Reorient the receiving antenna
Relocate the computer with respect to the receiver
Move the computer away from the receiver
Plug the compute into a dierent outlet so that computer and receiver are on dierent branch circuits
If necessary, the installer should consult the dealer or an experienced radio/television technician for additional suggestions.
The installer may nd the following booklet, prepared by the Federal Communications Commission, helpful:
“How to identify and Resolve Radio-TV Interference Problems.”
This booklet is available from the U.S. Government Printing Oce, Washington D.C. 20402
36.20 System Sensor 2-Wire Smoke Detectors ................................. 57
36.21 System Sensor i4 Series Smoke and CO Detectors
Using A Single COSMOD2W Module ....................................... 58
36.22 System Sensor i4 Series Smoke and CO Detectors
Using Multiple COSMOD2W Modules ...................................... 59
Revisions to This Document
Certications
Export Control
XR500 Series Installation Guide Digital Monitoring Products
v
Page 8
This page intentionally left blank
Page 9
INTRODUCTION
Product Specications Summary
1.1 Power Supply
Transformer Input: Model 327, plug-in — Primary input: 120 VAC, 60 Hz, Secondary output: 16.5 VAC 50 VA
Model 322/323, wire-in — Primary input: 120 VAC, 60 Hz, Secondary output: 16 VAC 56 VA
Model 324/324P, wire-in — Primary input: 120 VAC, 60 Hz, Secondary output: 16 VAC 100 VA
Standby Battery: 12 Vdc, 1.0 Amps Max. charging current
Models 364, 365, 366, 368, or 369
Replace every 3 to 5 years
Auxiliary: 12 Vdc output at 1.5 Amp Max*
12 Vdc output at 325mA used with two Model 364 batteries in the Model 341 enclosure
Bell Output: 12 Vdc at 1.5 Amp Max*
All circuits are inherent Power Limited except the red battery wire and AC terminal.
* For Commercial Burglary and Fire installations, see the Compliance Instructions section. See section 5.3 J12
3-Pin Header for Transformer Types for panel output 2 Amp or 3 Amp current limitations.
1.2 Communication
• Built-in network communication to DMP Model SCS-1R or SCS-VR Receivers (XR500N/XR500E only)
• Built-in encrypted communication to DMP Model SCS-1R Receivers (XR500E only)
• Built-in dialer communication to DMP Model SCS-1R Receivers
• Optional cellular communication to DMP Model SCS-1R or SCS-VR Receivers
• Built-in Contact ID communication to DMP Model SCS-1R Receivers
• Optional 893A Dual Phone Line Module with phone line supervision
• Can operate as a local panel
1.3 Panel Zones
Eight 1k Ohm EOL burglary zones (zones 1 to 8)
Two 3.3k Ohm EOL powered zone with reset (zones 9 and 10)
1.4 Keypad Bus
You can connect up to a total of 16 of the following supervised keypads and expansion modules to the keypad bus:
You can connect the following devices to the LX-Bus™ provided on the panel or by the DMP 481, 462N, 462P, 463C
464-263C and 464-263H Interface Cards up to the maximum number of LX-Bus™ addresses. See Accessory Devices in
section 3.4.
• Model 521LX or 521LXT Smoke Detectors with CleanMe • Relay output expansion modules
• Model 2W-BLX or 2WT-BLX Smoke Detectors
1.6 Outputs
The XR500 Series provide two Single Pole, Double Throw (SPDT) relay outputs which require the installation of two
Model 305 relays, each rated 1 Amp at 30 Vdc resistive (power limited sources only). A Model 431 Output Harness is
required to use these outputs.
The XR500 Series panels also provide four open collector outputs rated for 50mA each. The open collector outputs
provide ground connection for a positive voltage source. A Model 300 Output Harness is required to use these
outputs.
1.7 Enclosure Specications
The XR500 Series panels are shipped in an enclosure with a transformer, End-of-Line resistors, battery leads, user’s
guide, and programming sheets.
Enclosure
Model
35017.5”W x 13.5”H x 3.5”DGray (G) or Red (R)18-Gauge
350A17.5”W x 13.5”H x 3.75”DGray (G)18-Gauge with 16-Gauge door
34112.75”W x 6.55”H x 3.15”DGray (G)20-Gauge
352X14.5”W x 32.0”H x 4.0”DGray (G)16-Gauge
XR500 Series Installation Guide Digital Monitoring Products
SizeColor(s)Construction (Cold Rolled
Steel)
1
Page 10
INTRODUCTION
Panel Features
2.1 Description
The DMP XR500 Series panel is a versatile 12 Vdc, combined access control, burglary, and re communicator panel
with battery backup. The XR500 Series provides eight on-board burglary zones and two on-board 12 Vdc Class B
powered zones. The powered zones have a reset capability to provide for 2-wire smoke detectors, relays, or other
latching devices. The XR500 Series can communicate to DMP SCS-1R or SCS-VR Receivers using digital dialer, cellular,
network, or Contact ID communication.
2.2 Zone Expansion
Up to 574 additional zones are available on the XR500 Series using DMP LCD keypad remote zone capability and zone
expansion modules. The panel keypad data bus supports up to sixteen supervised device addresses with each address
supporting up to four programmable expansion zones.
Up to 500 zones are available using the on board LX-Bus, Model 461 Interface Adaptor with 481, 462N, 462P, 463C,
464-263C and 464-263H Interface Cards, and any combination of single, four, eight, or 16-zone expansion modules
and single-zone LX-Bus™ detectors.
Note: Do not use shielded wire for LX-Bus or Keypad Bus circuits.
2.3 Output Expansion
In addition to the two SPDT relays and four programmable open collector outputs on the XR500 Series, you can also
connect up to 25 programmable Model 716 Output Expansion Modules to each LX-Bus. These modules can provide an
additional 500 programmable SPDT relays.
The XR500 Series provides 100 Output Schedules for programming the 716 to perform a variety of annunciation and
control functions. Also assign the 716 outputs to any panel Output Options such as Fire Alarm, Communication Fail,
or Phone Trouble Outputs. Refer to the 716 Installation Guide (LT-0183).
The LX-Bus™ also supports the Model 717 Graphic Annunciator Module. Each 717 module supplies 20 switched ground
outputs that follow the state of their assigned zones.
Note: The 717 supports the rst eight Keypad Bus addresses. To follow Keypad Bus addresses nine through 16, install
multiple 716 modules. Refer to the 717 Installation Guide (LT-0235) and 716 Installation Guide (LT-0183).
2.4 Central Station Communication
You can program the XR500 Series panel for reporting to DMP SCS-1R or SCS-VR Receivers using digital dialer, cellular,
network, or Contact ID communication. The XR500 Series connects at the premises to a standard RJ31X or RJ38X
telephone jack. Use the DMP 893A Dual Phone Line Module when connecting the XR500 Series panel to two separate
phone lines in re or burglary applications.
2.5 Encrypted Communications (XR500N/XR500E only)
An XR500E panel communicates using AES encryption. If you currently have an XR500N panel installed, you may
contact DMP Customer Service with the panel serial number. The serial number(s) should be sent in writing via
e-mail or fax. A separate feature key is sent for each panel to activate encrypted communications using the Feature
Upgrade process. Encrypted communication cannot be enabled on a standard XR500 panel. For more information on
the Feature Upgrade process see the XR500 Series Programming Guide (LT-0679).
2.6 Caution Notes
Throughout this guide you will see caution notes containing information you need to know when installing the panel.
These cautions are indicated with a yield sign. Whenever you see a caution note, make sure you completely read
and understand its information. Failing to follow the caution note can cause damage to the equipment or improper
operation of one or more components in the system. See the example shown below.
Always ground the panel before applying power to any devices: The XR500 Series must be properly
grounded before connecting any devices or applying power to the panel. Proper grounding protects against
Electrostatic Discharge (ESD) that can damage system components.
2.7 Compliance Instructions
For applications that must conform to a local authorities installation standard or a National Recognized Testing
Laboratory certicated system, please see the Wiring Diagrams for Notication Appliances and the Listed Compliance
Specications section near the end of this guide for additional instructions.
Digital Monitoring Products XR500 Series Installation Guide
2
Page 11
INTRODUCTION
System Components
3.1 Description
The DMP XR500 Series system is made up of an alarm panel with a built-in communicator, an enclosure, battery,
one 16.5 VAC transformer, and keypads. You can use up to sixteen supervised 32-character LCD keypads; network
communications and expansion interface cards; zone and output expansion modules; and initiating and indicating
circuit modules. You can also connect auxiliary devices to the panel’s output relays to expand the basic system
control capability. Combined current requirements of additional modules may require an auxiliary power supply.
Refer to the XR500 Series Power Requirements section in this guide when calculating power requirements.
3.2 Wiring Diagram
The XR500 Series diagram below shows some of the accessory modules you can connect for use in various
applications. A brief description of each module follows in section 3.4.
NFPA 72 OPERATING
INSTRUCTIONS
The operating instructions should be
located adjacent to the control unit or
keypad.
HOUSEHOLD FIRE WARNING
Recognized limited energy cable must
be used for connection of all initiating,
indicating, and supplementary devices.
Commercial and Residential Fire,
Burglar, Holdup, and Access Protected
Premise Unit
Bell
12 VDC
Minimum cutoff time 5 min.
1.5 Amp Max
The plug-in transformer shall plug
into a 120 VAC 60 Hz outlet not
controlled by a switch and all
18 gauge wire
conduit.
USE MARKING
shall run through
16 to
TYPES OF SERVICE
Suitable for Local, Police
Station Connect, Mercantile,
and Proprietary with 350A
Enclosure.
Central Station DACT service
may be provided using 350A
Attack Resistant enclosure.
Suitable for Proprietary, PPU,
other technologies, local.
Suitable for Signaling and
Remote Station PPU DACT
Service.
Suitable for manual fire alarm,
automatic fire alarm, sprinkler
supervisory, or water flow
alarm.
Suitable for Standard or
Encrypted Central Station with
NET or CELL communication.
Suitable for Bank Safe and
Vault Service with 350A
Enclosure.
Suitable for Household Fire
and Household Burglary.
Suitable for Coded and March
Time signaling.
SIA CP-01-2010 minimum
system is XR500, listed local
Bell, and off premise DACT
communication to an SCS-1R
receiver plus listed compatible
keypads as indicated in the
installation guide.
Maximum AC Wire distance
with 16 gauge wire: 70 feet
with 18 gauge wire: 40 feet
1k Ohm 1k Ohm 1k Ohm
Use Listed Power Supervision
s
s
16 to 18 gauge wire
RED
BLACK
Earth Ground
For Standard Line
Security burglary
applications use
Ademco Model
AB12M bell and bell
housing.
Bell cutoff time
range is 5 to 99
minutes, non-coded.
ss
ss
DISARM
Intended Installation Environment - Indoor/Dry
THIS UNIT MAY BE PROGRAMMED TO USE AN ALARM VERIFICATION FEATURE THAT
RESULTS IN DELAY OF THE SYSTEM ALARM SIGNAL FROM THE INDICATED CIRCUITS.
THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT EXCEED 60
SECONDS. NO OTHER SMOKE DETECTOR SHALL BE CONNECTED TO THESE CIRCUITS
UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ).
AC Wiring must be in conduit and exit
out the left side of the enclosure.
Wiring on terminals 5 through 22 must
exit right and maintain 1/4" separation
from the AC and battery positive wiring.
OVC
Output 1Output 2
J2
K6K7
Zone 1
SS
1k
1k
Ohm
Ohm
Minimum voltage on Auxiliary output to
process Sensor trips is 10.2 VDC.
1.5 Amp Max 10.2 VDC to 14.0 VDC
When using (2) Model 364 Batteries
325 mA Max 10.2 VDC to 14.0 VDC
BLACK
GREEN
YELLOW
RED
RED
RED
YELLOW
GREEN
BLACK
¼"
1.0k Ohm - DMP Model 311
3.3k Ohm - DMP Model 309
J11
3
10K Ohm - DMP Model 308
4
5
6
Out1 Out2
Outputs 3-6
Zone 2
Zone 3
Zone 4
SS
SS
SS
1k
1k
Ohm
Ohm
Ohm
Auxiliary/Smoke Power
Total current combined from
terminals 7, 11, 25, and 27
Total Combined Current from
terminals 7, 11, 25, and 27
s
Zone Expander
Model 714
7mA @ 12 VDC
Models 714-8, 714-16
20mA @ 12 VDC
1k Ohm 1k Ohm 1k Ohm
S SS SS S
WARNING: Incorrect
connections may cause
damage to the unit.
The total current combined from Auxiliary and Bell Power cannot
exceed:
Burglary/Access/Household Fire: 1.3 Amps with a 50 VA transformer,
1.0 Amp Max for Auxiliary Power
Commercial Fire: 1.2 Amps with a 56 VA transformer, .5 Amp Max for
Auxiliary Power and .7 Amp Max for Bell
Form C Relays (J2)
Output Color Code–Model 431 Harness
Output 2 N/O Orange/White
Output 2 Com White/Gray
Output 2 N/C Violet/White
Output 1 N/O Orange
Output 1 Com Gray
Output 1 N/C Violet
Annunciator Outputs (J11)
Output Color Code
Output 3 Red
Output 4 Yellow
Output 5 Green
Output 6 Black
Listed Resistors
J16
Reset
Zone9Zone
Zone 8
Zone 7
Zone 5
Zone 6
SS
SS
SS
1k
1k
Ohm
Zone
Expander
Model 711
7mA @ 12
VDC
S S
1k Ohm
SS
1k
1k
Ohm
Ohm
S S S S
3.3k
3.3k
Ohm
Ohm
Resistor
Resistor
= Supervised Circuit
s
NO
S1
ON
C
J1
NC
RELAY
Interface
RED
ON
Modul
READ LED
WIEGAND
734
YEL
XMT LED
GRN
DATA
e
PROG
J2
Piezo
J4
J5
VDC
S
1k Ohm
LC ASRED WHT GRN BLKZ1 Z2 Z3 Z4+Z4–RA GND GND
S
RED
KYPD IN
RED
KYPD OUT
RED
+ –
Zone Expander
(up to 8 zones)
Model 712-8
19mA @ 12
CAUTION: DO NOT USE LOOPED WIRE
UNDER TERMINALS. BREAK WIRE RUN TO
PROVIDE SUPERVISION OF CONNECTIONS.
10
J3
1
2
3
4 5 6 7
8
9
10
11 12 13 14
S S S S S S S S
3.3k Ohm 3.3k Ohm 3.3k Ohm 3.3k Ohm
Front and Rear
tamper protection
included with
Model 350A
Attack Resistant
Enclosure.
Front
Tamper
Rear
Tamper
Heat detectors, pull
stations, or any other
contact devices listed
for Fire Protective
Signaling can be
connected to zones
9 and 10.
Zones 9 and 10 and
Model 715 compatibility
identifier: A
Maximum operating
range: 9.7 VDC to
14.0 VDC.
Class B (Style A).
Zones 9, 10, and all
expanded zones are
suitable for Class B (as
applicable for the
initiating and signaling
line circuits per ANSI/UL
864 Table 48.2 or 48.3).
Installation limits under
local Authority Having
Jurisdiction (AHJ).
Using verification delays
on zones 9 and 10 is
optional. Use the
delays marked on the
smoke detectors.
Red
White (Data 1)
Green (Data 0)
Black
Card Reader
Orange
Yellow
Zone Expander
Model 715
7mA @ 12 VDC
Models 715-8, 715-16
20mA @ 12 VDC
Figure 1: XR500 Series Wiring Diagram
XR500 Series Installation Guide Digital Monitoring Products
3
Page 12
INTRODUCTION
3.3 Lightning Protection
Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on XR500 Series input
and output circuits. Additional surge protection is available by installing the DMP 370 or 370RJ Lightning Suppressors.
3.4 Accessory Devices
Interface Adaptor and Interface Cards
461 Interface Adaptor CardAllows you to connect two or more expansion interface cards to the XR500 Series
462P Printer Interface CardAllows you to connect the XR500 Series to any compatible serial printer providing the
464-263C/464-263H Cellular
Communicator Card
481 Expansion Interface CardProvides one LX-Bus for connecting up to 100 zone and output expansion modules.
Expansion Modules
710 Bus Splitter/RepeaterAllows you to increase keypad or LX-Bus™ wiring distance to 2500 feet.
711 Single Point Zone Expanders Provides one Class B zone for connecting burglary devices.
714, 714-8, 714-16 Zone
Expanders
712-8 Zone ExpanderProvides Class B zones for connecting burglary devices.
715, 715-8, 715-16 Zone
Expanders
716 Output ExpanderProvides four Form C relays (SPDT) and four switched grounds (open collector) for use
717 Graphic Annunciator Module Provides 20 zone following annunciator outputs (open collector) for use in a variety of
734, 734N, 734N-WiFi Wiegand
Interface Modules*
DMP Two-Way Wireless Devices
1100X/1100XH ReceiverSupports up to 500 devices in residential or commercial wireless operation.
1100R RepeaterProvides additional range for wireless devices.
1101 Universal TransmitterProvides both internal and external contacts that may be used at the same time to
1102 Universal TransmitterProvides an external contact.
1103 Universal TransmitterProvides both internal and external contacts that may be used at the same time to
1106 Universal TransmitterProvides both internal and external contacts that may be used at the same time to
1107 Micro Window Transmitter* Provides a wireless window transmitter.
1114 Four-Zone Expander*Provides four wireless zones.
1115 Wireless Temperature
Sensor and Flood Detector*
1116 Relay Output*Provides one Form C relay.
1117 LED Annunciator*Provides a visual system status indicator.
1118 Remote Indicator Light*Provides a visual indication of a Panic situation.
1119 Door Sounder*Provides a battery powered sounder.
1121 PIR Motion Detector*Provides motion detection with pet immunity.
1126R PIR Motion Detector*Ceiling mount motion detector with panel programmable sensitivity and Disarm/Disable
1127C/1127W PIR Motion
Detector
1129 Glassbreak Detector*Detects the shattering of framed glass mounted in an outside wall and provides full-
* Security Device Only: This device has not been investigated and shall not be used in listed installations.
panel. The 461 is an expansion mother board that plugs into the panel J6 Interface
Connector and is required when using two or more Interface Cards. Use combinations
of Interface Cards for expanding zones, network interfacing, local printing, and
connecting wireless devices.
user with real-time event recording. The 462P also provides an LX-Bus™ for connecting
zone and output expansion modules.
Provides a fully supervised alarm communication path over the CDMA network or HSPA
+ network for XR500 Series panels. The 464-263C or 464-263H also provides an LX-Bus™
for connecting zone and output expansion modules to the panel.
Provides Class B zones for connecting burglary and non-powered re devices.
Provides 12 Vdc Class B powered zones for connecting smoke detectors, glassbreak
detectors, and other 2- or 4-wire devices.
in a variety of remote annunciation and control applications for use on the LX-Bus only.
remote annunciation and control applications for use on the LX-Bus only.
Provides system codeless entry, and arming and disarming using access control readers.
yield two individual reporting zones from one wireless transmitter.
yield two individual reporting zones from one wireless transmitter. Requires EOL
resistor for external contact. Provides Disarm/Disable functionality.
yield two individual reporting zones from one wireless transmitter.
Temperature and ood detector with an internal temperature sensor. Can be paired
with 470PB or T280R remote sensors.
functionality.
Wall mount motion detector with panel programmable sensitivity and Disarm/Disable
functionality.
pattern coverage and false-alarm immunity.
Digital Monitoring Products XR500 Series Installation Guide
4
Page 13
INTRODUCTION
3.4 Accessory Devices (continued)
DMP Two-Way Wireless Devices (continued)
1131 Recessed Contact*Provides a recessed contact option for door or window applications.
1135 Wireless Siren*Provides a wireless siren.
1137 Wireless LED Emergency
Light
1139 Bill Trap*Provides a silent alarm option for retail and banking cash drawers.
1141 Wall Button*One button wall mounted wireless transmitter.
1142BC Two-button Hold-up
Belt Clip Transmitter
1142 Two-button Hold-up
Transmitter
1144-4 (Four-Button)*
1144-2 (Two-Button)*
1144-1 (One-Button)*
1164NS Wireless Commercial
Smoke
1165 Commercial Smoke
Detector
1183-135F Heat DetectorFixed temperature heat detector.
1183-135R Heat DetectorFixed temperature and rate-of-rise heat detector.
1184 Carbon Monoxide
Detector
Indicating and Initiating Devices
860 Relay Module*Provides dry relay contacts that are programmable and controlled from the DMP panel
865 Supervised Style W or X
Notication Circuit Module
866 Style W Notication Circuit
Module
867 Style W LX-Bus Notication
Circuit Module
869 Dual Class A Style D
Initiating Module
Accessory Modules and Keypads
893A Dual Phone Line ModuleAllows you to supervise two standard phone lines connected to an XR500 Series panel.
LCD keypadsAllows you to control the panel from various remote locations. Connect up to sixteen
9000 Series Wireless keypadsAllows you to control the panel from various remote locations. Connect up to four
9800 Series Wireless
Touchscreen keypads
Addressable Smoke Detectors
2W-BLX, 2WT-BLXSingle-zone, addressable conventional smoke, smoke/heat detectors that connect to the
Graphic
* Security Device Only: This device has not been investigated and shall not be used in listed installations.
Provides path lighting in the event of an alarm or trouble such as Burglary Alarm Output
or can be activated simultaneously by the panel via the Trip with Panel Bell feature.
Provides two-button hold-up operation with a belt clip.
annunciator outputs. Includes one Form C (SPDT) relay rated 1 Amp @ 30 Vdc. Sockets
are provided to allow the addition of three Model 305 plug-in relays.
Provides supervised alarm current when using the XR500 Series panel bell output
and up to 5 Amps at 12 or 24 Vdc when using a listed auxiliary power supply. The 865
can supervise 2-wire or 4-wire style circuits for opens and shorts with individual LED
annunciation.
Provides supervised alarm current using the XR500 Series panel bell output and up to 5
Amps at 12 or 24 Vdc when using a listed auxiliary power supply. The 866 can supervise
2-wire Style W circuits for opens and shorts.
Provides supervised alarm current using the XR500 Series panel bell output and up to 5
Amps at 12 or 24 Vdc when using a listed auxiliary power supply. The 867 connects to the
XR500 Series panel LX-Bus™ and provides one 2-wire Style W notication circuit for open
and short conditions. Individual Bell Relay addresses Bell Ring styles.
Provides two Class A, Style D, 4-wire initiating zones for connecting waterow switches
and other non-powered re and burglary devices.
The 893A module monitors the main and backup phone lines for a sustained voltage drop
and alerts users when the phone line is bad.
supervised Model 630F Remote Fire Command Center, Model 7060, 7063, 7070, 7073,
7160, 7163, 7170, 7173 Thinline™ keypads, 7060A, 7063A, 7070A, 7073A Aqualite™
keypads, 7760 Clear Touch™ keypad, or 7872, 7873 Graphic Touchscreen keypads to the
keypad bus using terminals 7, 8, 9, and 10.
9060/9063 Wireless Keypads.
Allows you to control the panel from various remote locations. Connect up to four
keypads. 9862 Wireless Keypads.
LX-Bus. Includes drift compensation.
XR500 Series Installation Guide Digital Monitoring Products
5
Page 14
INTRODUCTION
Installation
4.1 Mounting the Enclosure
The metal enclosure for the XR500 Series must be mounted in a secure, dry place to protect the panel from damage
due to tampering or the elements. It is not necessary to remove the XR500 Series PCB when installing the enclosure.
Figure 2 shows the mounting hole locations for the Model 350/350A Enclosures. Figure 3 shows the Model 341 Kiosk
Enclosure. Figure 4 shows the Model 352X panel cabinet and 352S shelf cabinet for multiple batteries.
The 350A Attack Resistant enclosure is factory shipped with one knockout on the top left of the enclosure. As
needed, additional knockouts or antenna exits may be added at the time of installation. See Figure 2 for the
positions on the enclosure that can be added. Each additional knockout must be lled with conduit.
Note: When using the XR500 Series panel for listed applications, use the Model 350, 349, 341, or 352S enclosure for
standby batteries. When using the 352X or 352S in listed applications, the enclosure must be surface mounted
on the wall.
Figure 4: XR500 Series in Model 352X Enclosure and Separate 352S Enclosure with Shelves
XR500 Series Installation Guide Digital Monitoring Products
7
Page 16
INSTALLATION
RCV
4.2 Mounting Keypads and Zone Expansion Modules
DMP LCD keypads have removable covers that allow you to easily mount the keypad to a wall or other at surface
using the screw holes on each corner of the base. Before mounting the base, connect the keypad wire harness leads
to the keypad cable from the panel and to any device wiring run to that location. Then attach the harness to the pin
connector on the PC board, mount the base, and install the keypad cover making sure all of the keys extend through
their respective holes.
For mounting keypads on solid walls, or for applications where conduit is required, use the Model 695 1-1/2” deep or
the Model 696 1/2” deep backboxes.
The DMP 711, 712-8, 714, 715, 716, and 717 modules are each contained in molded plastic housings with removable
covers. The base provides you with mounting holes for installing the unit to a wall, switch plate, or other surface.
4.3 Connecting LX-Bus and Keypad Bus Devices
Several factors determine the DMP LX-Bus™ and keypad bus performance characteristics: the wire length and gauge
used, the number of devices connected, and the voltage at each device. When planning an LX-Bus™ and keypad bus
installation, keep in mind the following information:
1. DMP recommends using 18 or 22-gauge unshielded wire for all keypad and LX-Bus circuits. Do not use twisted
pair or shielded wire for LX-Bus and keypad bus data circuits.
2. On keypad bus circuits, to maintain auxiliary power integrity when using 22-gauge wire do not exceed 500
feet. When using 18-gauge wire do not exceed 1,000 feet. To increase the wire length or to add devices, install
an additional power supply that is listed for Fire Protective Signaling, power limited, and regulated (12 Vdc
nominal) with battery backup.
Note: Each panel allows a specic number of supervised keypads. Add additional keypads in the unsupervised
mode. Refer to the panel installation guide for the specic number of supervised keypads allowed.
3. Maximum distance for any one bus circuit (length of wire) is 2,500 feet regardless of the wire gauge. This
distance can be in the form of one long wire run or multiple branches with all wiring totaling no more than
2,500 feet. As wire distance from the panel increases, DC voltage on the wire decreases. Maximum number of
LX-Bus devices on the rst 2,500 foot circuit is 40 devices.
4. Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2.0 Vdc. If the voltage
at any device is less than the required level, add an auxiliary power supply at the end of the circuit. When
voltage is too low, the devices cannot operate properly.
For additional information refer to the LX-Bus/Keypad Bus Wiring Application Note (LT-2031).
The LX-Bus provided on these cards requires only a 4-wire cable between the card and any devices connected to the
bus. You can connect devices (zone or output expansion modules) together on the same cable or provide separate
runs back to the card. Each LX-Bus provides up to 100 zones or outputs.
4.4 Wireless Keypad Association
Enable Wireless Keypad Association operation on both the keypad and panel.
To enable association operation in the keypad, access the Installer Options Menu (3577
(INST)) and select RF Survey). The keypad logo LEDs turn on Red until association is
J8
XMIT
Programming
successful.
To enable association operation in the XR500 panel, reset panel 3 times within 12
seconds. Allow the keypad bus Transmit/Receive LEDs to turn back on between each
reset.
Figure 5: Keypad Bus LEDs
For 60 seconds the panel listens for wireless keypads that are in the Installer Options
Menu (3577 CMD) and have not been programmed, or associated into another panel. Those keypads are assigned to
the rst open device position automatically based upon the order in which they are detected. The keypad logo turns
Green to indicate it has been associated with the panel.
Digital Monitoring Products XR500 Series Installation Guide
8
Page 17
INSTALLATION
Primary Power Supply
5.1 AC Terminals 1 and 2
Connect the transformer wires to terminals 1 and 2 on the panel. Use no more than 70 ft. of 16 gauge or 40 ft. of 18
gauge wire between the transformer and the XR500 Series.
Always ground the panel before applying power to any devices: The XR500 Series must be properly
grounded before connecting any devices or applying power to the panel. Proper grounding protects against
Electrostatic Discharge (ESD) that can damage system components. See the Earth ground section.
5.2 Transformer Types
Use Model 327 (16.5 VAC 50 VA) plug-in or Model 322/323 (16 VAC 56 VA), or 324/324P (16 VAC 100 VA) wire-in
transformer. Use Model 322/323 or 324/324P wire-in transformers when required by the Authority Having Jurisdiction
(AHJ).
The transformer must be connected to an unswitched 120 VAC 60 Hz electrical outlet with at least .87A of
available current. Never share the transformer output with any other equipment.
5.3 J12 3-Pin Header for Transformer Types
Place the jumper on the left two pins labeled 50VA for a Maximum 2 Amp (Bell+Aux+Smoke=2 Amp) when using the
Model 322/323 56VA, or 327 50VA plug-in transformer (default).
Place the jumper on the right two pins labeled 75VA for a Maximum 3 Amp (Bell+Aux+Smoke=3 Amp) when using the
Model 324/324P 100 VA wire-in transformer.
Note: For UL Commercial Fire installations, refer to the Universal Fire Alarm Specications, Transformer section, for
more information.
Secondary Power Supply
To AC
Panel Red and
Black Battery Cables
Battery
Start
AC
1234
14 AWG to
Earth Ground
XR550
Panel
+BAC–B
To Bell
Circuit
BELLGND
56
6.1 Battery Terminals 3 and 4
Connect the black battery lead to the negative battery
terminal. The negative terminal connects to the enclosure
ground internally through the XR500 Series circuit board.
Connect the red battery lead to the battery positive
terminal. Observe polarity when connecting the battery.
You can add a second battery in parallel using the DMP
Model 318 Dual Battery Harness. DMP requires each battery
318 Battery
Harness
Battery
PTC
318 Battery
Harness
PTC
Red
Red
Black
Black
be separated by a PTC in the battery harness wiring to
protect each battery from a reversal or short within the
Battery
Battery
circuit. See Figure 6.
For listed installations, all batteries shall be installed
in a DMP Model 350 or Model 352S enclosure and all wiring shall run through conduit. The enclosure shall be
installed to the left of the XR500 Series enclosure to ensure Battery and AC wire separation.
Use sealed lead-acid batteries only: Use the DMP Model 364 (12 Vdc 1.3Ah), DMP Model 365 (12 Vdc 9
Ah), Model 366 (12 Vdc 18 Ah), Model 368 (12 Vdc 5.0 Ah), or Model 369 (12 Vdc 7 Ah) sealed lead-acid
rechargeable battery. Batteries supplied by DMP have been tested to ensure proper charging with DMP
products.
GEL CELL BATTERIES CANNOT BE USED WITH THE XR500 SERIES PANEL.
6.2 Earth Ground (GND)
To provide proper transient suppression, XR500 Series panel terminal 4 must be connected to earth ground using
14 gauge or larger wire. DMP recommends connecting to a cold water pipe, ground rod, or building ground only. Do
not connect to an electrical ground or conduit, sprinkler or gas pipes, or to a telephone company ground.
6.3 Battery Only Restart
When powering up the XR500 Series panel without AC power, briey short across the battery start pads to pull in
the battery cuto relay. The leads need a momentary short only. Once the relay has pulled in, the battery voltage
holds it in that condition. If the XR500 Series panel is powered up with an AC transformer, the battery cuto relay is
pulled in automatically. For more information refer to Figure 1.
XR500 Series Installation Guide Digital Monitoring Products
9
Page 18
INSTALLATION
6.4 Battery Replacement Period
DMP recommends replacing the battery every 3 to 5 years under normal use.
6.5 Discharge/Recharge
The XR500 Series battery charging circuit oat charges at 13.9 Vdc at a maximum current of 1.0 Amps using a
50 VA or 56 VA transformer. Listed below are the various battery voltage level conditions:
Battery Trouble: Below 11.9 Vdc
Battery Cuto: Below 10.2 Vdc
Battery Restored: Above 12.6 Vdc
6.6 Battery Supervision
The XR500 Series tests the battery when AC power is present. The test is done every three minutes and lasts for ve
seconds. During the test, the panel places a load on the battery; if the battery voltage falls below 11.9 Vdc a low
battery is detected. If AC power is not present, a low battery is detected any time the battery voltage falls below
11.9 Vdc.
If a low battery is detected with AC power present, the test repeats every two minutes until the battery charges
above 12.6 Vdc indicating the battery has restored voltage. If a weak battery is replaced with a fully charged
battery, the restored battery will not be detected until the next two minute test is completed.
6.7 Battery Cuto
The panel disconnects the battery any time the battery voltage drops below 10.2 Vdc. This prevents battery deep
discharge damage.
Digital Monitoring Products XR500 Series Installation Guide
10
Page 19
INSTALLATION
6.8 XR500 Series Power Requirements
During AC power failure, the XR500 Series panel and all connected auxiliary devices draw their power from the battery.
All devices must be taken into consideration when calculating the battery standby capacity. The following table lists
the XR500 Series panel power requirements. You must add the additional current draw of keypads, zone expansion
modules, smoke detector output, and any other auxiliary devices used in the system for the total current required. The
total is then multiplied by the number of standby hours required to calculate the total ampere-hours required.
Standby Battery Power CalculationsStandby CurrentAlarm Current
XR500 Series Control Panel
Relay Outputs 1-2 (ON)
Switch Grounds 3-6 (ON)
Active Zones 1-8
Active Zones 9-10
2-Wire Smoke Detectors
Sub-Totals this page only Sub-Total Standby ______ mASub-Total Alarm ______mA
Sub-Totals from previous page Sub-Total Standby ______ mASub-Total Alarm ______mA
*Based on 10% of active zones in alarmTotal Standby ______ mATotal Alarm ______mA
# For systems that are not central station monitored, multiply alarm current by 12.
Total Standby ______ mA x number of Standby Hours needed
Qty_______
Qty ______xx
Qty ______
Qty ______xx
Qty ______
Qty ______xx
Qty ______
Qty ______xx
Qty ______
Qty ______xx
Qty ______
Qty ______
Qty ______
Qty ______
Qty ______
Qty ______
___mA
1.6mA
1.6mA
1.6mA
1.6mA
x
x
x
x
x
x
25mA
11mA
7mA
17mA
20mA
7mA
4mA
.1mA
20mA
4mA
.1mA
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
Qty ______
Qty ______xx
Qty ______
Qty ______xx
Qty ______
Qty ______xx
Qty ______
Qty ______xx
Qty ______
Qty ______xx
Qty ______
Qty ______
Qty ______
Qty ______
Qty ______
Qty ______
Qty ______ x13mA ______Qty ______
Qty ______xx
Qty ______ x10mA ______Qty ______
Qty ______xx
Qty ______
Qty ______xx
45mA
1mA
______
______
Qty ______
Qty ______xx
______mA______mA
Total Alarm
______ =
______ mA
_______ mA-hours
+ _______ mA-hours
Total
_______ mA-hours
X .001
= _______ Amp-hrs Required
___mA
x
x
30mA*
x
x
x
30mA*
x
174mA*#
50mA*#
25mA
11mA
2mA*
7mA
2mA*
17mA
2mA*
20mA
2mA*
7mA
.1mA
20mA
.1mA
13mA
12mA
10mA
1mA
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
Refer to section 6.9 for standby battery selection.
Digital Monitoring Products XR500 Series Installation Guide
12
Page 21
INSTALLATION
6.9 Standby Battery Selection
To choose the type and number of batteries needed for 24, 60, or 72 hours of standby power based on the Amp Hours
Required calculation from section 6.8 XR500 Series Power Requirements, perform the following:
1. Select the desired standby hours required from the table below: 24, 60, or 72 hours
2. Select the desired battery size: Model 368 (12 Vdc 5.0 Ah), Model 369 (12 Vdc 7 Ah),
Model 365 (12 Vdc 9 Ah), Model 366 (12 Vdc 18 Ah), or Model 364 (12 Vdc 1.3 Ah) when used in the
Model 341 enclosure.
3. Select a Max. Ah Available number that is just greater than the number calculated in Amp Hours Required.
4. Install the number of batteries shown in the corresponding No. of Batteries required column.
Example: If the Amp Hours Required calculation equals 22 Ah for 24 hours of standby time and 4.5 Ah batteries are
desired, install six (6) Model 368 (12 Vdc, 5.0 Ah) batteries.
Note: You can use a Model 327 Plug-in 50 VA or Model 322/323 Wire-in 56 VA with up to 36 Ah of batteries. The Model
324/324P Wire-in 100 VA Transformer may be used with any of the battery choices listed below.
For listed installations, all batteries shall be installed in a DMP Model 341, 349, 350 or 352S enclosure and all wiring
shall run through conduit. The enclosure shall be installed to the left of the XR500 Series enclosure to ensure Battery
and AC wire separation.
Note: If the Amp Hours Required calculation is greater than any Max. Ah Available number shown on a table, then
No. of
Batteries
No. of
Batteries
No. of
Batteries
add power supply(s) to power some system devices allowing the Amp Hours Required calculation to be
reduced. See the 710 Bus Splitter/Repeater Installation Guide (LT-0310).
Max. Ah
Available
Note: 48 hours is the typical battery recharge time for any of the Number of Batteries
shown in this section.
Max. Ah
Available
Max. Ah
Available
Note: 72 hours is the typical battery recharge time required for any of the Number of
Batteries shown in this section.
No. of
Batteries
No. of
Batteries
No. of
Batteries
7.7 Ah Batteries
Max. Ah
Available
Max. Ah
Available
No. of
Batteries
No. of
Batteries
9 Ah Batteries18 Ah Batteries
Max. Ah
Available
Max. Ah
Available
Note: 48 hours is the typical battery
recharge time for any of the Number of
Batteries shown in this section.
No. of
Batteries
No. of
Batteries
Max. Ah
Available
No. of
Batteries
XR500 Series Installation Guide Digital Monitoring Products
13
Page 22
INSTALLATION
Bell Output
7.1 Terminals 5 and 6
Terminal 5 supplies positive 12 Vdc to power alarm bells or horns. This output can be steady, pulsed, or temporal
depending upon the Bell Action specied in Bell Options. Terminal 6 is the ground reference for the bell circuit. This
supervised output detects 1k Ohms or less as normal. The indicating appliance can supply this resistance. If using a
horn or siren, a 1k Ohm 1/2 W EOL resistor (provided) should be added across the bell circuit to provide supervision.
See the Notication Appliance section for a list of approved notication appliances and the Wiring Diagrams for
connections.
Keypad Bus
8.1 Description
XR500 Series panel terminals 7, 8, 9, and 10 are for the keypad bus. You can connect up to sixteen supervised
keypads and multiple unsupervised keypads to the XR500 Series. In addition to DMP LCD keypads, you can also
connect any combination of zone expansion modules to the data bus. Refer to the specic device installation sheet
for the maximum number of Keypad Bus devices.
Refer to the section titled LX-Bus for complete information about the LX-Bus 4-pin header and expansion slot.
Note: Do not use shielded wire for LX-Bus/Keypad Bus circuits.
8.2 Terminal 7 - RED
This terminal supplies positive 12 Vdc Regulated to power DMP LCD keypads and zone expansion modules. Terminal 7
also supplies power for any auxiliary device. The ground reference for terminal 7 is terminal 10.
The output current is shared with the smoke power output on terminal 11 and Zones 9 and 10. Current draw for all
connected devices must not exceed the panel maximum current rating. See Power Supply in the Compliance section
for maximum current in a re listed application.
8.3 Terminal 8 - YELLOW
Terminal 8 receives data from keypads and zone expansion modules. It cannot be used for any other purpose.
8.4 Terminal 9 - GREEN
Terminal 9 transmits data to keypads and zone expansion modules. It cannot be used for any other purpose.
8.5 Terminal 10 - BLACK
Terminal 10 is the ground reference for DMP LCD keypads, zone expansion modules, and all auxiliary devices being
powered by terminal 7.
8.6 J8 Programming Connection
A 4-pin header (J8) is provided to connect a keypad when using a DMP Model 330 Programming Cable. This provides a
quick and easy connection for panel programming.
You may also use the J8 Programming Header to connect Keypad Bus devices. This is an alternative to connecting
keypad bus devices to terminals 7, 8, 9, and 10.
8.7 OVC LED
The Overcurrent LED (OVC) lights Red when the devices connected to the Keypad Bus and LX-Bus(es) draw more
current than the panel is rated for. The OVC is located above Outputs 1 and 2 on the panel and turns a steady Red
when lit. When the OVC LED lights Red, the LX-Bus(es) and Keypad bus are shut down.
Smoke and Glassbreak Detector Output
9.1 Terminals 11 and 12
Terminal 11 supplies positive 12 Vdc Regulated to power 4-wire smoke detectors and other powered devices. This
output can be turned o by the user for 5 seconds using the Sensor Reset User Menu option to allow latched devices
to reset. Terminal 12 is the ground reference for terminal 11.
9.2 Current Rating
The Output current from terminal 11 is shared with terminals 7, 25, and 27.
The total current draw of all devices powered from the panel must be included with terminal 11
calculations and must not exceed the maximum output rating.
Digital Monitoring Products XR500 Series Installation Guide
14
Page 23
INSTALLATION
1K Ohm
Normally
Closed
1K Ohm
Normally Open
1K Ohm
Combination Normally Open
and Normally Closed
Protection Zones
10.1 Terminals 13–24
Zones 1 to 8 (terminals 13 to 24) on the XR500 Series panel are all grounded burglary zones. For programming
purposes, the zone numbers are 1 through 8. Listed below are terminal 13 to 24 connection functions.
TerminalFunctionTerminalFunction
13Zone 1 voltage sensing19Zone 5 voltage sensing
14Ground for Zones 1 and 220Ground for Zones 5 and 6
15Zone 2 voltage sensing21Zone 6 voltage sensing
16Zone 3 voltage sensing22Zone 7 voltage sensing
17Ground for Zones 3 and 423Ground for Zones 7 and 8
18Zone 4 voltage sensing24Zone 8 voltage sensing
The voltage sensing terminal measures the voltage across a 1k Ohm End-of-Line resistor to ground. Use DMP Model
311 1k Ohm resistors. Dry contact sensing devices can be used in series (normally-closed) or in parallel (normallyopen) with any of the burglary protection zones.
Figure 6: Protection Zone Wiring
10.2 Operational Parameters
Each protection zone detects three conditions: Open, Normal, and Short. Listed below are voltage and resistance
parameters for each condition:
Condition Resistance on zone Voltage on positive terminal
Open over 1300 ohms over 2.0 Vdc
Normal 600 to 1300 ohms 1.2 to 2.0 Vdc
Short under 600 ohms under 1.2 Vdc
10.3 Zone Response Time
A condition must be present on a zone for 500 milliseconds before it is detected by the XR500 Series panel. Ensure
detection devices used on the protec tion zones are rated for use with this delay. Zones 1-10 can also be programmed
for a fast response delay of 160 milliseconds.
10.4 Keyswitch Arming Zone
Using a keyswitch on an Arming type zone allows you to arm and disarm selected areas without having to enter a
user code.
Powered Zones for 2-Wire Smoke Detectors
11.1 Terminals 25–26 and 27–28
Panel terminals 25 through 28 provide two resettable Class B, Style A, 2-wire powered zones. For programming
purposes the zone numbers are 9 and 10.
Note: The maximum wire length for either zone 9 or zone 10 is 3000 feet using 18 AWG or 1000 feet using 22 AWG.
The maximum voltage is 14 Vdc and the maximum normal standby current is 1.25mA DC. The maximum line
impedance is 100 Ohms. The maximum short circuit current is 56mA.
When using all other zone expansion modules, use listed Model 309 EOL resistors. The compatibility identier
for the zones is A.
Note: Do not mix detectors from dierent manufacturers on the same zone.
Caution: Performing a Sensor Reset momentarily drops power to the devices on Terminal 11 (SMK), Zones 9
and 10. The panel views these zones (9 and 10) as “Open” while the power is absent.
XR500 Series Installation Guide Digital Monitoring Products
15
Page 24
INSTALLATION
11.2 Compatible 2-Wire Smoke Detector Chart
ManufacturerModelDetector
ID
Hochiki
EST
SLR-835B-2
SLR-835BH-2
521B, 521BXT,
521NB, 521NBXT
HD-6N/A8-3514
S09A6.5-2012
BaseBase IDDC
Voltage
Range
Detectors
(12V/24V)
System Sensor2W-B, 2WT-BA8.5-3510
System Sensor 2WTA-BA (*)8.5-35 12
System Sensor 2WTR-BA(*)8.5-35 1
System Sensor 1151, 2151 A
B110PL,
B401
8.5-35 10
COSMO-2W
System Sensor
(using
A8.5-3512
COSMOD2W)
(*) = Must be used in conjunction with System Sensor Polarity Reversal Module model RRS-M0D.
Figure 7: Compatible 2-Wire Smoke Detectors
# of
Zone
Expansion
Modules
715, 715-8,
715-16
715, 715-8,
715-16
715, 715-8,
715-16
715, 715-8,
715-16
715, 715-8,
715-16
715, 715-8,
715-16
714, 714-8,
714-16,
715, 715-8,
715-16
Panel
Zones
9 & 10
9 & 10
9 & 10
9 & 10
9 & 10
9 & 10
1-10
Digital Monitoring Products XR500 Series Installation Guide
16
Page 25
INSTALLATION
Dry Contact Relay Outputs
12.1 Description
The XR500 Series panel provides two programmable auxiliary SPDT relays when equipped with two DMP Model 305
relays in sockets K6 (Output 1) and K7 (Output 2) and a Model 431 Output Harness on the J2 6-pin Header. Each relay
provides one SPDT set of contacts that can be operated by any of the functions listed below:
1) Activation by zone condition: Steady, Pulsing, Momentary, and Follow
2) Activation by 24-hour 7-day schedule: One on and one o time a day for each relay
3) Manual activation from the DMP LCD keypad menu
4) Communication failure 8) Exit and Entry timers
5) Armed area annunciation 9) System Ready
6) Fire Alarm, Fire Trouble or Supervisory 10) Late to Close
7) Ambush Alarm
Refer to the XR500 Series Programming Guide (LT-0679) for specic information.
12.2 Contact Rating
The Model 305 relay contacts are rated for 1 Amp at 30 Vdc (allows .35 power factor). Connect auxiliary power
to the Relay Output 1 common terminal by installing the gray harness wire to terminal 7. Current draw for all
connected devices must not exceed the panel maximum current rating.
12.3 Model 431 Output Harness Wiring
The relay contacts are accessible by installing the DMP 431 Output Harness on the 6-pin header labeled J2. Output
2 uses the top three prongs, and Output 1 uses the bottom three prongs. The wire harness and contact locations are
shown below:
ContactColor
Output 1 normally closedViolet
Output 1 commonGray
Output 1 normally openOrange
Output 2 normally closedViolet with white stripe
Output 2 commonWhite with gray stripe
Output 2 normally openOrange with white stripe
The relay contacts must be connected to devices located within the same room as the XR500 Series panel.
Annunciator Outputs
13.1 Description
The four programmable annunciator outputs can be programmed to indicate the activity of the panel zones or
conditions occurring on the system. Annunciator outputs do not provide a voltage but instead switch-to-ground a
voltage from another source. The outputs can respond to any of the conditions listed in the Description section for
Dry Contact Relays. Maximum voltage is 30 Vdc @ 50mA.
13.2 Model 300 Harness Wiring
Access the open collector outputs by installing DMP 300 Harness on the 4-pin header labeled J11. The output
locations are shown below. For listed applications, devices connected to the outputs must be located within the
same room as the panel.
Output ColorWireOutputColorWire
3Red15Green3
4Yellow26Black4
13.3 Model 860 Relay Module
Connect a Model 860 Relay Module to the J11 on the XR500 Series panel to provide relays for outputs 3-6. Use these
relays for electrical isolation between the alarm panel and other systems or for switching voltage to control various
functions. Power is supplied to the relay coils from a single wire connected to the panel auxiliary power terminal 7.
The module includes one relay and provides three additional sockets for expansion of up to four relays. Mount the
860 inside the panel enclosure using the 3-hole pattern and plastic standos. Refer to the 860 Module Install Sheet
(LT-0484) as needed.
Relay Contact Rating: 1 Amp at 30 Vdc (allows .35 power factor)
XR500 Series Installation Guide Digital Monitoring Products
17
Page 26
INSTALLATION
J23 6-Pin Header
14.1 Description
The XR500 Series panel supports RS-232, LX-Bus, and DMP Wireless operation. Only one operation can function at a
time. Install a jumper on one pair of J23 headers to indicate how the panel is programmed to operate. Refer to the
table below when installing a jumper on J23. When a jumper is installed or moved on the 6-pin header, briey reset
the panel using the J16 jumper to activate the selected operation.
Note: Only one operation, RS-232, LX-Bus, or DMP Wireless can function at a time.
J23 6-Pin Header
LetterOperation
RStandard RS-232
LLX-Bus
X1100 Series DMP Wireless
J23
R
L
X
J21
RS-232
J22
LX
LEDs
Xmit
Rec
Overcurrent
(OVC) LED
Figure 8: J23 6-Pin Header
J22 LX-Bus Expansion Connector
15.1 Description
The XR500 Series panel supports up to 500 wireless bus zones or up to ve LX-Bus circuits. Each Interface card
LX-Bus circuit provides 100 expansion zones. The maximum number of LX-Bus zones available on a fully populated
panel is 500. Use LX-Bus J22 Header for 100 zones. Install a single Interface Card Connector on the board to support
100 additional zones for a total of 200 zones. To install up to ve Interface Cards install a Model 461 Interface
Adaptor Card.
15.2 J22 LX-Bus Header
Note: Only one connector, J21 or J22 can function at a time. Either use J21 to connect a serial device for PC Log
Reporting, or use J22 to connect an LX-Bus or DMP Wireless device. Operation is determined by where you
install the jumper on the J23 6-Pin header. See the Connecting LX-Bus and Keypad Bus Devices section for
maximum wiring distances.
For each connection, respect wire colors when connecting devices and use all four wires. After placing the
jumper on the J23 6-Pin header to enable the required operation, briey reset the panel using the J16 jumper
to activate operation.
Wireless Bus Operation: Place a jumper on the two pins next to the letter “X” on the J23 6-Pin header. When
using J22 as a wireless bus, connect a DMP Model 300 4-wire Harness to the J22 4-pin header labeled LX. Connect
the other end to the J3 header on the 1100X or 1100XH Wireless Receiver. This provides up to 500 wireless zones
numbered 500 to 999. Refer to the 1100X Wireless Receiver Install Guide (LT-0708) or the 1100XH Wireless Receiver
Install Guide (LT-0970).
LX-Bus Operation: Place a jumper on the two pins next to the letter “L” on the J23 6-Pin header. When using J22 as
an LX-Bus, connect a DMP Model 300 4-wire Harness to the J22 4-pin header labeled LX. This provides the rst 100
LX-Bus zones numbered 500-599. No LX-Bus Interface Card is required.
Note: Do NOT use shielded wire when using the J22 LX-Bus Header.
RS-232 Operation: Place a jumper on the two pins next to the letter “R” on the J23 6-Pin header and refer to J21
Serial Connector.
Digital Monitoring Products XR500 Series Installation Guide
18
Page 27
INSTALLATION
15.3 LX-Bus Interface Cards
You can add one Interface Card (Model 481, 462N, 462P, 463C, 464-263C or 464-263H) to the XR500 Series using
J6 Interface Card Connector located on the board right edge. To add more than one Interface Card install a 461
Interface Adaptor Card using J6 Interface Card Connector on the board right edge. The 461 Adaptor Card allows up
to ve Interface Cards to be installed. Refer to the 461 Installation Sheet (LT-0736). Each Interface card provides up
to 100 LX-Bus Zones. Refer to the following tables to identify zone locations and numbers relative to J22 operation.
J22 LX-Bus Enabled
(Set J23 to “L”)
One Interface Card
461 Adaptor Card and
Multiple Interface Cards
LX-Bus Zone NumbersLX-Bus Zone NumbersLX-BusZone Numbers
The two LEDs, located near the bottom-right corner of J21 indicate data transmission and receipt. The top LED
ashes green to indicate the panel is transmitting LX-Bus data. The bottom LED ashes yellow to indicate the panel
is receiving LX-Bus data.
15.5 OVC LED
The Overcurrent LED (OVC) lights Red when the devices connected to the Keypad Bus and LX-Bus(es) draw more
current than the panel is rated for. The OVC is located above Outputs 1 and 2 on the panel and turns a steady Red
when lit. When the OVC LED lights Red, the LX-Bus(es) and Keypad bus shut down.
J21 Serial Connector
16.1 Description
Note: Only one connector, J21 or J22 can function at a time. Either use J21 to connect a serial device for PC Log
Reporting, or use J22 to connect a DMP Wireless device or an LX-Bus device. Operation is determined by where
you install the jumper on the J23 6-Pin header. The maximum line impedance is 100 Ohms.
To enable J21 to operate in RS-232 mode, place a jumper on the two pins next to the letter “R” on the J23 6-Pin
header and briey reset the panel using the J16 jumper to activate the selected operation. Panel programming using
Remote Link™ can be set up through a direct connection to a computer. The Serial Connector allows the following
operation options.
XR500 PanelXR500N/XR500E Panel
PC Log ReportsPC Log Reports
Remote Link™
Programming
J23
R
L
X
16.2 Computer Connection to J21
Use a straight through RS-232 Serial cable with a DB-9 female connector on one end and a DB-9 male connector on
the other end. Plug the DB-9 male connector end of the cable onto the XR500 Series panel J21 RS-232 connector.
Plug the DB-9 female connector end of the cable onto the DB-9 male connector located at the back of the computer.
Program the XR500 Series panel as needed then disconnect the computer.
J21
RS-232
DB-9 Female Connector
Serial Data Xmit LED
Serial Data Rec(eive) LED
J22
Figure 9: J21 Serial Connection
XR500 Series Installation Guide Digital Monitoring Products
19
Page 28
INSTALLATION
16.3 Serial Connector LEDs
The two LEDs, located near the bottom-right corner of J21 indicate data transmission and receipt. The top LED
ashes green to indicate the panel is transmitting serial data. The bottom LED ashes yellow to indicate the panel is
receiving serial data.
J1 Ethernet Connector (XR500N/XR500E only)
17.1 Description
The J1 Ethernet Connector is available on the XR500N/XR500E Network version to connect directly to an Ethernet
network using a standard patch cable. The maximum impedance is 100 Ohms.
17.2 Ethernet LEDs
The two LEDs, located to the left of J1 Ethernet Connector, indicate network
connection. The top, Link LED lights up green to indicate a valid receive
connection from the host network. The bottom, Activity LED ashes yellow to
indicate messages are being sent and received.
Link LED
Activity LED
Figure 10: J1 Header and LEDs
J1
ETHERNET
J3 Telephone RJ Connector
18.1 Description
Connect the panel to the public telephone network by installing a DMP 356 RJ Cable between the panel J3 connector
and the RJ31X or RJ38X phone block. The maximum impedance is 100 Ohms. CAUTION - To reduce the risk of re,
use only No. 26 AWG or larger telecommunication line cord, such as DMP Model 356 Series Phone Cords.
18.2 J10 893A Connector
Connect an 893A Dual Phone Line Module to J10 on the XR500 Series. Refer to the 893A Installation Sheet (LT-0135)
for complete information.
18.3 Notication
The user must not repair registered terminal equipment. In case of trouble, immediately unplug the device from the
telephone jack. The factory warranty provides for repairs. Registered terminal equipment may not be used on party
lines or in connection with coin telephones. No tify the telephone company with the following information:
a. The particular line(s) where the service is connected
b. The FCC registration number as listed in Section 18.5
c. The ringer equivalence
d. The device make, model, and serial number
18.4 Phone Line Monitor
The XR500 Series panel has a built-in telephone monitor that monitors the phone line voltage to verify the
connection to the central oce. Figure 11 and the table below identify the phone block pin layout, wire numbers,
The wires on the RJ31 that feed pins 4 and 5 should be the ONLY wires on the D-marc. All other house phone wiring
should be tied to pins 1 and 8 coming back from the RJ31.
Dial tone must come into RJ31X on pins 4 and 5 and go back to house phones from pins 1 and 8. Follow these steps
to determine if panel is seizing the line:
1. Unplug phone cord from RJ31X
2. Place butt-set on pins 4 and 5
3. Listen for dial tone. With dial tone present, lift either wire from pins 1 or 8
4. Listen for dial tone again. If the dial tone is present, RJ31X wiring is correct. If no dial tone is present, the
RJ31X wiring is backwards. Rewire so dial tone is coming IN on 4 and 5.If you still have trouble with the phone
line, you may need to replace the RJ cord. If the dial tone is still not present, swap out the RJ31X phone block.
To Telephone
Line
To Premise
Phone
RingTip
54
6
3
7
2
8
Ring 1
Tip 1
Figure 11: Phone Jack Wiring
RJ31X or RJ38X
Phone Block
1
Digital Monitoring Products XR500 Series Installation Guide
20
Page 29
INSTALLATION
18.5 FCC Registration
The Model XR500 Series complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the
outside of the enclosure of this equipment is a label that contains, among other information, a product identier in
the format US:CCKAL00BXR500. If requested this number must be provided to the telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the
applicable FCC Part 68 rules and requirements adopted by the ACTA. See installation instructions for details.
The Ringer Equivalence Number (REN) is used to determine the number of devices that may be connected to a
telephone line. xcessive RENs on a telephone line may result in the devices not ringing in response to an incoming
call. In most but not all areas, the sum of RENs should not exceed ve (5.0). To be certain of the number of devices
that may be connected to a line, as determined by the total RENs, contact the local telephone company.
If the XR500 Series causes harm to the telephone network, the telephone company will notify you in advance that
temporary discontinuance of service may be required. But if advance notice isn’t practical, the telephone company
will notify the customer as soon as possible. Also, you will be advised of your right to le a complaint with the FCC if
you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could aect
the operation of the equipment. If this happens the telephone company will provide advance notice in order for you
to make necessary modications to maintain uninterrupted service.
If trouble is experienced with the Model XR500 Series, for repair or warranty information, please contact DMP at
the address and telephone number listed on the back of this document. If the equipment is causing harm to the
telephone network, the telephone company may request that you disconnect the equipment until the problem is
resolved.
If your premises has specially wired alarm equipment connected to the telephone line, ensure the installation of the
XR500 Series does not disable your alarm equipment. If you have questions about what will disable alarm equipment,
consult your telephone company or a qualied installer.
Caution: To ensure proper operation, this equipment must be installed according to the installation instructions in
this manual. To verify that the equipment is operating properly and can successfully report an alarm, this equipment
must be tested immediately after installation, and periodically thereafter, according to the test instructions in this
document and the XR500 Series Programming Guide (LT-0679). Additionally, verication of Line Seize capability
should be made immediately after installation, and periodically thereafter, in order to ensure that this equipment
can initiate a call even when other equipment (telephone, answering system, computer modem, etc.) connected to
the same line is in use.
XR500 Series Installation Guide Digital Monitoring Products
21
Page 30
INSTALLATION
92
Reset and Tamper Headers
19.1 J16 Reset Header
The reset header is located just above the terminal strip on the right side of the circuit board and is used to reset
the XR500 Series microprocessor. To reset the panel when rst installing the system, install the reset jumper before
applying power to the panel. After connecting the AC and battery, remove the reset jumper.
To reset the panel while the system is operational, for example, prior to reprogramming, install the reset jumper
without powering down the system. Remove the reset jumper after one or two seconds.
After resetting the panel, begin programming within 30 minutes. If you wait longer than 30 minutes, you must reset
the panel again.
Momentarily place the Reset
jumper over both of the J16
pins to reset the panel.
J11
3
4
5
6
02122232425262728
J6
Interface
Card
Expansion
Connector
J16
Reset
Figure 12: XR500 Series Panel Showing the Reset Jumper
19.2 J4 Tamper Header
The J4 header is for use with the optional DMP 306 Tamper Harness. The harness connects to one or more tamper
switches mounted inside the panel enclosure to supervise against unauthorized enclosure opening or removal. Refer
to the wiring diagram on the enclosure door for correct tamper switch wiring.
How the Tamper Works
If the enclosure is opened or removed while one or more of the system areas are armed, a panel tamper alarm is
indicated. If all areas are disarmed, a panel tamper trouble is indicated.
Digital Monitoring Products XR500 Series Installation Guide
22
Page 31
COMPLIANCE
Listed Compliance Specications
20.1 Introduction
For applications that must conform to a local authorities installation standard or a National Recognized Testing
Laboratory certicated system, please see the following sections.
Universal Burglary Specications
21.1 Introduction
The programming and installation specications contained in this section must be completed when installing the
XR500 Series panel in accordance with any of the burglary standards. Additional specications may be required by a
particular standard. See the XR500 Series Programming Guide (LT-0679).
21.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70, ANSI/UL 681, and ANSI/UL 827 for all burglary
installations. All transformer wires must be installed in conduit.
21.3 Transformer
The total combined Auxiliary and Bell outputs cannot exceed 1.3 Amps with a 50 VA Transformer. The total combined
Auxiliary and Bell outputs cannot exceed 1.9 Amps with a 56 VA Transformer.
21.4 Control Outside of Protected Area
A Potter EVD or Sentrol 5402 should be used in place of a lined cabinet when the panel is installed outside of the
protected area. Front and rear tamper switches are required. Refer to the system wiring diagram.
21.5 Police Station Phone Numbers
The digital dialer telephone number programmed for communication must not be a police station phone number.
21.6 Bypass Reports
The Bypass Reports option must be programmed as YES for all listed burglary applications.
21.7 System Maintenance
To ensure continuous satisfactory operation of any alarm system, proper installation and regular maintenance by
the installing alarm company and frequent testing by the end user is essential. Oering a maintenance program and
acquainting the user with the correct procedures for system use and testing is also the responsibility of the installing
alarm company.
21.8 Listed Receivers
Operation has been veried with the DMP SCS-VR and SCS-1R receivers and any Central Station Receiver that accepts
industry standard Contact ID (DTMF) format. It is the installer’s responsibility to verify compatibility between the
panel and the receiver used during installation. The installer shall verify the compatibility of the receiver and the
system on a yearly basis.
21.9 Power Supply Supervision
For commercial burglary applications the power supply for all local bells shall be under 24-hour protection. Refer to
the Secondary Power Supply section in this document.
21.10 Wireless Tamper
The Zone Information Disarmed Open Message to Transmit must be programmed Trouble (T). (Not applicable to ANSI/
UL 1023).
21.11 Wireless External Contact
When used, the External Contact of 1101 or 1102 must be programmed Normally Closed.
21.12 Wireless Supervision Time
The Zone Information Supervision Time cannot be set to 0 (zero).
21.13 Detect Wireless Jamming
The Detect Wireless Jamming option must be programmed YES. (Not applicable to ANSI/UL 1023).
21.14 Standby Batteries
Use battery Models 365 (12 Vdc 9Ah), 366 (12 Vdc 18Ah), 368 (12 Vdc 5.0Ah), and 369 (12 Vdc 7Ah) with the XR500
panel when installed in the 341, 350, 350A, or 352 enclosures. The Model 364 (12Vdc 1.3Ah) battery is for use with
the XR500 panel when using the 341 enclosure with the optional 341B Battery Bracket. The Model 364 battery is
rated for 4 hours of standby time.
XR500 Series Installation Guide Digital Monitoring Products
23
Page 32
COMPLIANCE
Area Information
22.1 Ownership
The control unit system shall be under one ownership.
22.2 Annunciation
The System shall be installed so that when arming any area from any keypad, the local bell shall annunciate.
22.3 Trouble Display
The Status List programming shall be set to annunciate all trouble messages at all keypads.
22.4 Closing Wait
The Closing Wait option must be programmed YES.
22.5 Local Bell Supervision
When a local bell is employed, the power supply for the bell shall be under 24-hour protection. Proper personnel for
maintenance or security of the system shall be able to disarm that area.
Household Burglar-Alarm System Units
ANSI/UL 1023
23.1 Audible Devices
At least one listed audible device (Ademco AB12M) rated to operate over the voltage rate of 11.7 Vdc to 12.8 Vdc
and rated at 85 DB minimum must be used.
23.2 Auxiliary Circuits
At least one burglary alarm initiating device shall be used on the system. If the voltage for the device is applied
by the control unit the burglary alarm initiating device shall be rated to operate over the range of 11.5 Vdc to
12.7 Vdc.
23.3 Bell Cuto
The Bell Cuto time cannot be less than ve minutes.
23.4 Entry Delay
The maximum entry delay used must not be more than 45 seconds.
23.5 Exit Delay
The maximum exit delay used must not be more than 60 seconds.
23.6 Weekly Test
The product should be tested weekly.
23.7 Wireless Audible Annunciation Option
The Wireless Audible option must be selected as DAY for residential applications.
Digital Monitoring Products XR500 Series Installation Guide
24
Page 33
COMPLIANCE
Central-Station and Proprietary Burglar-Alarm Units
ANSI/UL 1610 AND ANSI/UL 1076
24.1 Opening/Closing Reports
The Opening/Closing Reports option must be programmed as YES.
24.2 Closing Wait
The Closing Wait option must be programmed YES.
24.3 Entry Delay
The maximum entry delay used must not be more than 60 seconds when using Model 350A or 350H Attack Resistant
Housing.
24.4 Exit Delay
The maximum exit delay used must not be more than 60 seconds.
24.5 Proprietary Dialer
The Model XR500 Series provides proprietary service when congured as a digital dialer.
24.6 DACT Central Station
DACT Central Station service can be provided under by adding an Ademco AB12M bell and bell housing and placing
the Model XR500 Series panel into Model 350A or 350H Attack Resistant Housing.
24.7 Bell Cuto
The Bell Cuto time cannot be less than 15 minutes.
24.8 Standard or Encrypted Line Security
Standard Line Security is provided when congured as a Path 1 NET system using an XR500N panel. The NET Check-in
time must be set to 03 minutes or RND. When programmed for Standard Line Security, Exit Time Restart is disabled.
When a dialer is required for 06 minute check-in time, an attack resistant enclosure (DMP Model 350A or 350H) is
required. When the check-in time is set to a number less than 200 seconds, an attack resistant enclosure is not
required.
To provide Encrypted Line security, install an XR500E panel.
For Encrypted Line security operation, communication between the Premise and Supervising Station provides 128 bit
encryption when using an XR500E panel.
The XR500 Series Protected Premises Control Unit is suitable for Standard Line Security service when congured for
NET communication with SCS-1R receiving system. This conguration is approved for the following:
AMCX - Central Station Alarm Units
APOU - Proprietary Alarm Units
24.9 Wireless Audible Annunciation Option
The Wireless Audible option must be selected as ANY for commercial applications.
24.10 CELL Only, Standard or Encrypted Line Security
Standard or Encrypted Line Security is provided when programmed using Model 463C, 464-263C or 464-263H for CELL
with no backup. XR500 cellular communication is used as primary with a 3 minute check-in when armed or disarmed.
Path 1 programming
Comm Type: = CELLCheckin: = 3 minute
Path Type: = PrimaryFail Time: = 3 minute
Encrypt: = NO or YES*Test Rpt: = NO
Sub Code: = NO or YES
*For Encrypted Line Security, program a Passphrase in Network Options.
XR500 Series Installation Guide Digital Monitoring Products
25
Page 34
COMPLIANCE
24.11 NET with CELL as Alternate Primary and Dialer Backup, Standard
or Encrypted Line Security
Standard or Encrypted Line Security is provided using NET communication with Model 463C, 464-263C or 464-263H
for CELL as an alternate primary and with digital dialer as a backup. XR500 network communication is used as
primary with a 6 minute check-in when armed, and a random check-in over a 60 minute period when disarmed. CELL
is the backup path and set to daily test. Should the NET primary path become disabled, CELL adapts the same checkin time programmed for the primary communication and becomes an alternate primary path. The dialer path is used
as the backup if both NET and CELL fail to receive acknowledgement from the receiver.
This method of operation causes the CELL alternate primary to adapt to the 6 minute NET primary check-in rate
when the NET primary is unavailable maintaining line supervision and precludes the need for a central station runner
to respond to the NET primary failure.
primary)
Test Rpt: = NOTest Rpt: = YESTest Rpt: = YES
Checkin: = 6 minute, or RND
(random)
Fail Time: = 6 minute, or RND
(random)
Encrypt: = NO or YES* Encrypt: = NO or YES*
Sub Code: = YESSub Code: = Shared
*For Encrypted Line Security, program a Passphrase in Network Options.
Test Freq: = DailyTest Freq: = Daily
Checkin: = ADAPTDuplicate Alarms: =
Path Type: = Backup
(operates as second
method)
YES
24.12 NET with CELL as Backup and Adaptive Primary, Standard
or Encrypted Line Security
Standard or Encrypted Line Security is provided when programmed using NET communication and Model 463C,
464-263C or 464-263H for CELL as backup and as needed adapts and takes over as primary. XR500 network
communication is used as primary with a 6 minute check-in when armed, and a random check-in over a 60 minute
period when disarmed. CELL is the backup path and set to daily test. Should the primary path become disabled, the
CELL adapts to a special 3 minute check-in time and because of that check-in rate becomes the primary without the
requirement of an additional backup. This method of operation causes the CELL backup to adapt to the 3 minute
check-in rate when the NET primary is unavailable becoming a standalone primary without the need for a backup.
This maintains line supervision and precludes the need for a central station runner to respond to the NET primary
failure.
Path 1 programmingPath 2 programming
Comm Type: = NETComm Type: = CELL
Path Type: = PrimaryPath Type: = Backup (operates as second
method)
Test Rpt: = NOTest Rpt: = YES
Checkin: = 6 minute, or RND
(random)
Fail Time: = 6 minute, or RND
(random)
Encrypt: = NO or YES* Encrypt: = NO or YES*
Sub Code: = YES Duplicate Alarms: = YES
*For Encrypted Line Security, program a Passphrase in Network Options.
Test Freq: = Daily
Checkin: = ADAPT3
Sub Code: = Shared
Digital Monitoring Products XR500 Series Installation Guide
26
Page 35
COMPLIANCE
Holdup Alarm Units
ANSI/UL 636
25.1 ANSI/UL 1610 Required
The programming and installation specications contained in this section must be completed in addition to
ANSI/UL 1610 Specications when installing a Model 1142 with a Model XR500 Series panel.
25.2 1100X/1100XH Wireless Receiver
The Model 1100X/1100XH Wireless Receiver in conjunction with the Model 1142 Holdup Alarm Transmitter must be
installed in the system.
25.3 Wireless Supervision Time
The Zone Information Supervision Time must be a maximum of 240 minutes.
25.4 LED Display
The LED Operation option display must be set to NO when using a Model 1142 Holdup Alarm Transmitter.
25.5 Jamming Detection
The Detect Wireless Jamming option must be set to YES.
25.6 Local Alarm
The Bell Action for a PN (Panic) type zone must be programmed as N (None).
25.7 Message to Transmit
The Armed Open and Armed Short messages for a PN (Panic) type zone must be programmed to A (Alarm).
25.8 Wireless Audible Annunciation Option
The Wireless Audible option must be selected as ANY for commercial applications.
Digital Burglar Alarm Communicator System Units
ANSI/UL 1635
26.1 System Trouble Display
The Status List Display must include at least one keypad that displays system monitor troubles.
26.2 Digital Dialer Telephone Number
Both programmed telephone numbers must begin with a P.
26.3 Test Time
The Test Time option must be programmed so that the XR500 Series sends a report once every 24 hours.
26.4 Closing Wait
The Closing Wait option must be programmed YES.
Police Station Connected and Local Burglar Alarm Units
ANSI/UL 365
27.1 System Trouble Display
The Status List Display must include at least one keypad that displays system monitor troubles.
27.2 Entry Delay
The maximum entry delay used must not be more than 60 seconds when using Model 350A or 350H Attack housing.
27.3 Exit Delay
The maximum exit delay used must not be more than 60 seconds.
XR500 Series Installation Guide Digital Monitoring Products
27
Page 36
COMPLIANCE
27.4 Bell
A local audible signal appliance must be used such as Ademco AB12M bell and bell housing.
The alarm housing for a mercantile alarm system without a remote alarm transmission connection shall be mounted
on the outside of the building, visible from a public street or highway. It shall be accessible for examination and
repair. It shall also be located not more than four stories above the street level unless:
a) A second alarm sounding device and housing, intended for outside service, is mounted adjacent to the premises
or area of the building in which the alarm system is installed or
b) A second alarm sounding device, intended for inside service, is mounted within the premises.
In either case, the outside alarm sounding device and housing may be mounted as high as the seventh oor.
27.5 Bell Cuto
The Bell Cuto time cannot be less than 15 minutes.
27.6 Automatic Bell Test
The Automatic Bell Test option must be programmed as YES.
27.7 Standard or Encrypted Line Security
Standard Line Security is provided when congured as a Path 1 NET system using an XR500N panel or an XR500 panel
with an iCOM™ Network Alarm Router. The NET Check-in time must be set to 06 minutes or RND When programmed
for Standard Line Security, Exit Time Restart is disabled. When a dialer is required for 06 minute check-in time, an
attack resistant enclosure (DMP Model 350A) is required. When the check-in time is set to a number less than 200
seconds, an attack resistant enclosure is not required.
To provide Encrypted Line security, install an XR500E panel or an XR500 panel with an iCOM-E™ Encrypted Network
Alarm Router.
For Encrypted Line security operation, communication between the Premise and Supervising Station provides 128 bit
encryption when using an XR500E panel or an XR500 panel with an iCOM-E Encrypted Network Alarm Router.
27.8 Wireless Audible Annunciation Option
The Wireless Audible option must be selected as ANY for commercial applications.
27.9 Model 463C, CELL Only, Standard or Encrypted Line Security
Standard or Encrypted Line Security is provided when programmed using CELL with no backup. XR500 cellular
communication is used as primary with a 3 minute check-in when armed or disarmed.
Path 1 programming
Comm Type: = CELLCheckin: = 3 minute
Path Type: = PrimaryFail Time: = 3 minute
Encrypt: = NO or YES*Test Rpt: = NO
Sub Code: = NO or YES
*For Encrypted Line Security, program a Passphrase in Network Options.
Digital Monitoring Products XR500 Series Installation Guide
28
Page 37
COMPLIANCE
27.10 Model 463C, NET with CELL as Alternate Primary and Dialer Backup,
Standard or Encrypted Line Security
Standard or Encrypted Line Security is provided using NET communication with CELL as an alternate primary and
with digital dialer as a backup. XR500 network communication is used as primary with a 6 minute check-in when
armed, and a random check-in over a 60 minute period when disarmed. CELL is the backup path and set to daily
test. Should the NET primary path become disabled, CELL adapts the same check-in time programmed for the
primary communication and becomes an alternate primary path. The dialer path is used as the backup if both NET
and CELL fail to receive acknowledgement from the receiver.
This method of operation causes the CELL alternate primary to adapt to the 6 minute NET primary check-in rate
when the NET primary is unavailable maintaining line supervision and precludes the need for a central station runner
to respond to the NET primary failure.
primary)
Test Rpt: = NOTest Rpt: = YESTest Rpt: = YES
Checkin: = 6 minute, or RND
(random)
Fail Time: = 6 minute, or RND
(random)
Encrypt: = NO or YES* Encrypt: = NO or YES*
Sub Code: = YESSub Code: = Shared
*For Encrypted Line Security, program a Passphrase in Network Options.
Test Freq: = DailyTest Freq: = Daily
Checkin: = ADAPTDuplicate Alarms: =
Path Type: = Backup
(operates as second
method)
YES
27.11 Model 463C, NET with CELL as Backup and Adaptive Primary,
Standard or Encrypted Line Security
Standard or Encrypted Line Security is provided when programmed using NET communication and CELL as backup
and as needed adapts and takes over as primary. XR500 network communication is used as primary with a 6 minute
check-in when armed, and a random check-in over a 60 minute period when disarmed. CELL is the backup path and
set to daily test. Should the primary path become disabled, the CELL adapts to a special 3 minute check-in time and
because of that check-in rate becomes the primary without the requirement of an additional backup. This method
of operation causes the CELL backup to adapt to the 3 minute check-in rate when the NET primary is unavailable
becoming a standalone primary without the need for a backup. This maintains line supervision and precludes the
need for a central station runner to respond to the NET primary failure.
Path 1 programmingPath 2 programming
Comm Type: = NETComm Type: = CELL
Path Type: = PrimaryPath Type: = Backup (operates as second
method)
Test Rpt: = NOTest Rpt: = YES
Checkin: = 6 minute, or RND
(random)
Fail Time: = 6 minute, or RND
(random)
Encrypt: = NO or YES* Encrypt: = NO or YES*
Sub Code: = YES Duplicate Alarms: = YES
*For Encrypted Line Security, program a Passphrase in Network Options.
Test Freq: = Daily
Checkin: = ADAPT3
Sub Code: = Shared
XR500 Series Installation Guide Digital Monitoring Products
29
Page 38
COMPLIANCE
Police Station Connected and Local Burglar Alarm Units
ANSI/UL 609
28.1 Mercantile
For Mercantile and Police Station Connect operation the Model XR500 Series must be mounted in an Attack Resistant
Housing, (DMP Model 350A or 350H).
28.2 Entry Delay
The maximum entry delay used must not be more than 60 seconds when using the Model 350A or 350H housing.
28.3 Exit Delay
The maximum exit delay used must not be more than 60 seconds.
28.4 Mercantile Safe and Vault
When the DMP Model 350A or 350H Attack housing is used, the XR500 Series provides operation as a mercantile
safe and vault alarm. Bell Supervision and wiring must be in accordance with ANSI/UL 681. When the XR500 Series
is mounted outside the safe or vault, tamper protection and the Sentrol Model 5402 or Potter EVD listed vibration
detectors should be used.
28.5 Bell
A local audible signal appliance must be used such as Ademco AB12M bell and bell housing.
In a mercantile burglar alarm system, a mercantile alarm sounding device located within a building but outside the
protected area, is acceptable, provided it is rated for outside service and alarm conditions are transmitted to:
a) The dispatch location of the law enforcement agency having jurisdiction over the protected property or
b) A central station or residential monitoring station complying with the Standard for Central Station Alarm
Services, UL 827.
In a mercantile burglar alarm system, an alarm sounding device located within the area of greatest protection, or
outside the area of greatest protection but within an area protected by an alarm system and that shares a common
control unit with the system installed in the area of greatest protection, is acceptable provided it is rated for inside
service and alarm conditions are transmitted to:
a) The dispatch location of the law enforcement agency having jurisdiction over the protected property or
b) A central station or residential monitoring station complying with the Standard for Central Station Alarm
Services, UL 827.
An inside sounding device shall be mounted at least 10 feet (3.05 m) above the oor or at the surface of the ceiling.
When there is xed construction within the area that could provide access for an intruder, the alarm sounding
device shall also be mounted at least 4 feet (1.2 m), as measured horizontally, away from the edges of the xed
construction or at least 10 feet (3.05 m) above it so as to minimize access by an intruder.
28.6 Bank Safe and Vault (XR500N/XR500E only)
The Bank Safe and Vault option must be programmed as YES. The 72 hour battery standby must be provided. A
Rothenbuhler Model 5110 High Security Bell must be used.
28.7 Wireless Audible Annunciation Option
The Wireless Audible option must be selected as ANY for commercial applications.
Digital Monitoring Products XR500 Series Installation Guide
30
Page 39
COMPLIANCE
Access Control System Units
ANSI/UL 294
29.1 Panel Designation
The XR500 Series panels are designated stand alone units.
29.2 Tamper Protection
For listed Access Control installations, a tamper switch must be used.
29.3 Transformer
The total combined Auxiliary and Bell outputs cannot exceed 1.3 Amps with a 50 VA Transformer. The total combined
Auxiliary and Bell outputs cannot exceed 1.9 Amps with a 56 VA Transformer.
29.4 Compatible Devices
The following devices are compatible with the XR500 Series panels.
Access Control
734/734N/734N-WIFI* Wiegand
Interface Module
OP-08CB Motion DetectorInfrared sensor
PB-2 REX Button* Exit control push button
PP-6005B Proxpoint Plus® Reader Proximity reader
MP-5365 Miniprox® ReaderSlimline proximity reader
PR-5455 ProxPro® II ReaderLong range reader with sounder
MX-5375 Maxi-Prox™ ReaderLong range reader compatible with 1351 Prox Pass
* This device has not been investigated and shall not be used in listed
installations.
Proximity reader connector
Universal Fire Alarm Specications
30.1 Introduction
The programming and installation specications contained in this section must be completed when installing the
Model XR500 Series in accordance with any of the ANSI/UL or NFPA re standards. Additional specications may be
required by a particular standard. See the XR500 Series Programming Guide (LT-0679).
30.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70.
30.3 Transformer
Use the Model 322/323 wire-in 16 VAC 56 VA or Model 324/324P wire-in transformer mounted within 20 feet of the
panel and connected by conduit.
For UL Commercial Fire installations, the total current combined from Auxiliary and Bell Power cannot exceed: 1.2
Amps with a 56 or 100 VA transformer; .5 Amp Max for Auxiliary Power and .7 Amp Max for Bell
For UL Residential Fire installations, the total combined Auxiliary and Bell outputs cannot exceed 1.3 Amps with a 50
VA Transformer. The total current combined from Auxiliary and Bell Power cannot exceed: 1.9 Amps with a 56 VA or
100 VA transformer
30.4 End-of-Line Resistor
The DMP Model 310 1k Ohm EOL resistor should be used on all 1k Ohm EOL re zones.
30.5 System Trouble Display
The Status List Display must include at least one keypad that displays system monitor troubles.
30.6 Fire Display
The Status List Display must include at least one keypad that displays troubles and alarms on re type zones.
XR500 Series Installation Guide Digital Monitoring Products
31
Page 40
COMPLIANCE
30.7 Police Station Phone Number
The digital dialer telephone number programmed for communication must not be a police station phone number,
unless that phone number is specically provided for that purpose.
30.8 System Maintenance
To ensure continuous satisfactory operation of any alarm system, proper installation and regular maintenance by
the installing alarm company and frequent testing by the end user is essential. Oering a maintenance program and
acquainting the user with the correct procedures for system use and testing is also the responsibility of the installing
alarm company.
30.9 Audible Alarm
Fire Type zones must be programmed to activate an audible alarm. The Bell Action for Fire Type zones must not be
programmed as N (None).
30.10 Fire Zone Programming
If a retard delay is used on a waterow zone, it cannot exceed 90 seconds and any retard delay in the waterow
initiating devices must be subtracted from the 90 seconds al lowed. The retard delay should not be used on a zone
with smoke detectors.
30.11 Class A Style D Zones
If required, the DMP 869 Dual Style D Initiating Module provides for connection of two Class A Style D zones to the
Model XR500 Series. See the 869 Installation Guide (LT-0186) and this guide for wiring information.
30.12 Listed Receivers
Operation has been veried with the DMP SCS-VR and SCS-1R receivers and any Central Station Receiver that accepts
industry standard Contact ID (DTMF) format. It is the installer’s responsibility to verify compatibility between the
panel and the receiver used during installation. The installer shall verify the compatibility of the receiver and the
system on a yearly basis.
30.13 Standby Batteries
For UL listed applications, the panel must have 24 hour battery standby operation. The Model 364 battery should not
be used for re installations.
Digital Monitoring Products XR500 Series Installation Guide
32
Page 41
COMPLIANCE
Control Units for Fire-Protective Signaling Systems
ANSI/UL 864, NFPA 72
31.1 Power Supply
For listed Commercial Fire installations, the 50 VA Plug-in transformer cannot be used.
The total combined current from Terminals 7, 11, 25, and 27 cannot exceed 1.2 Amps.
31.2 Zone Restoral Reports
The Restoral Reports option must be selected as YES or Disarm.
31.3 Power Fail Delay
The Power Fail Delay option must be selected as required by the service of the panel. For Central Station service:
6-12, for Remote Station service: 12-15.
31.4 Sprinkler Supervisory
Any zone used for sprinkler supervisory must be programmed with “SPRINKLR XXX” as the zone name. The last three
characters in the zone name may be assigned a number to identify the zone. The Model 893A Dual Phone Line Module
must be used on all sprinkler supervisory systems.
31.5 DACT Systems
A DACT system may be congured as one of the following:
Path 1 Type DD Primary and Path 2 Type DD Backup
Path 1 Type DD Primary and Path 2 Type CELL Backup
Path 1 Type DD Primary and Path 2 Type NET Backup
Path 1 Type DD Primary and Path 2 Type DD Backup
Use two telephone lines and the Model 893A Dual Phone Line Module to provide two phone line connections to the
system. Two dierent telephone numbers must be programmed for digital communication. Do not connect to ground
start or party lines.
Path 1 ProgrammingPath 2 Programming
Comm Type = DDComm Type = DD
Path Type = PrimaryPath Type = Backup
Test Rpt = YesTest Rpt = Yes
Test Freq = 1 DyTest Freq = 1 Dy
893A = Yes
Path 1 Type DD Primary and Path 2 Type CELL Backup
Path 1 ProgrammingPath 2 Programming
Comm Type = DDComm Type = CELL
Path Type = PrimaryPath Type = Backup
Test Rpt = YesTest Rpt = Yes
Test Freq = 1 DyTest Freq = 1 Dy
Receiver IP Address
First GPRS APN
Path 1 Type DD Primary and Path 2 Type NET Backup
Path 1 ProgrammingPath 2 Programming
Comm Type = DDComm Type = NET
Path Type = PrimaryPath Type = Backup
Test Rpt = YesTest Rpt = Yes
Test Freq = 1 DyTest Freq = 1 Dy
Receiver IP Address
31.6 Local Protective Signaling Systems
The DMP Model 865, 866, or 867 Notication Circuit Module must be used on the bell circuit for detection of shorts
and grounds. Any burglary or other o premises communication must be done with the Model 893A Dual Phone Line
Module. For local commercial re installations, the 893A is required.
XR500 Series Installation Guide Digital Monitoring Products
33
Page 42
COMPLIANCE
31.7 Remote Station Protective Signaling Systems
You must provide 60 hours of standby battery. See section 6.9 in this guide for standby battery calculations. Two
Radionics Model D127 Reversing Relay Modules provide two reversing polarity telephone connections. See the D127
Installation Instruction sheet for wiring details. A DMP Model 893A is used to provide two line dialer communication.
31.8 Fire Protective Signaling Systems using Internet/Intranet/Cell Networks
An Other Transmission Technologies system as dened in UL 864 9th Edition, Section 40.7 may be congured as
NET Primary using a hardwire IP network or CELL Primary using a Model 463C CDMA Cellular Communicator with or
without a backup path. The system may be congured as one of the following:
Path 1 Type NET or CELL Primary with no Backup
Path 1 Programming
Comm Type = NET or CELL Checkin Min = 5
Path Type = PrimaryFailtime Min = 5
Test Rpt = NoSub Code = Yes
Checkin = YesSend Comm Trbl = Yes
Path 1 Type NET Primary and Path 2 Type DD Backup
Path 1 ProgrammingPath 2 Programming
Comm Type = NETComm Type = DD
Path Type = PrimaryPath Type = Backup
Test Rpt = YesTest Rpt = Yes
Test Freq = 1 DyTest Freq = 1 Dy
Send Comm Trbl = YesSend Comm Trbl = Yes
Comm Path Trbl = Yes (Status List Programming)
Path 1 Type NET Primary and Path 2 Type CELL Backup
Path 1 ProgrammingPath 2 Programming
Comm Type = NETComm Type = CELL
Path Type = PrimaryPath Type = Backup
Test Rpt = YesTest Rpt = Yes
Test Freq = 1 DyTest Freq = 1 Dy
Send Comm Trbl = YesSend Comm Trbl = Yes
Comm Path Trbl = Yes (Status List Programming)
Path 1 Type CELL Primary and Path 2 Type NET Backup
Path 1 ProgrammingPath 2 Programming
Comm Type = CELLComm Type = NET
Path Type = PrimaryPath Type = Backup
Test Rpt = YesTest Rpt = Yes
Test Freq = 1 DyTest Freq = 1 Dy
Send Comm Trbl = YesSend Comm Trbl = Yes
Comm Path Trbl = Yes (Status List Programming)
31.9 Combination Systems
For combination re and burglary systems, powered burglary devices (PIR, Glassbreak, etc.) must be powered from a
separate listed power supply (DMP Model 505-12). This requirement is not needed for non-powered burglary devices
(door contacts, etc.) which only connect to the zone input of zone expanders or keypads. Refer to Powered Burglary
Devices later in this document.
For combination re and burglary systems, burglary sounding devices such as sirens and bells must be energized
using panel relays, 860 relays, or 716 relays. Programming the output to activate the relay must occur using the
Burglary Bell Output option in Area Information or by the Alarm Action output option of Zone Information. The
Burglary Bell Action option of the panel Bell Options must be programmed as None.
31.10 Remote Annunciators
At least one Model 630F Remote Annunciator must be used on the system. All re alarms, re troubles and
supervisory alarms or troubles must be annunciated only on the 630F. All burglary alarms or troubles must only be
annunciated on non-re keypads. See Status List options of the XR500 Series Programming Guide (LT-0679).
Digital Monitoring Products XR500 Series Installation Guide
34
Page 43
COMPLIANCE
31.11 Notication Appliances
The following table indicates the approved notication appliances that can be used with the XR500 Series system.
Wheelock Model No.DescriptionMax No. of Appliances using 56 VA/100 VA
When using cross zoning, there must be a minimum of two detectors installed in each protected space and the detector
installation spacing must be 0.7 times the linear spacing in accordance with National Fire Alarm Code, NFPA 72.
31.13 Ground Fault
For supervised circuits, ground fault is detected at 0 (zero) Ohms.
31.14 Wireless Testing
When using the 1100X or 1100XH Wireless Receiver for Fire Protective Signaling, after all transmitters are in
position, the WLS option of the panel’s Walk Test must be operated and all transmitters programmed for Fire (FI) or
Supervisory (SV) must show that their checkin message was received.
31.15 Wireless Supervision
When using the 1103 Universal Transmitter for Fire Protective Signaling, supervision time must be set for 3 minutes.
Supervision time cannot be set to 0 (zero).
Household Fire Warning System Units
ANSI/UL 985, NFPA 72
32.1 Bell Output Denition
The Model XR500 Series panel Bell Output must be programmed to operate steady on burglary alarms and pulsed or
temporal on re alarms.
32.2 Audible Devices
At least one listed audible device rated to operate over the voltage rate of 11.7 Vdc to 12.8 Vdc and rated at 85 DB
minimum must be used.
32.3 Auxiliary Circuits
At least one re alarm initiating device shall be used on the system. If the voltage for the device is applied by the
control unit the re alarm initiating device shall be rated to operate over the range of 11.5 Vdc to 12.7 Vdc.
32.4 Bell Cuto
The Bell Cuto time cannot be less than ve minutes.
32.5 Detect Wireless Jamming
The Detect Wireless Jamming option must be programmed YES.
32.6 Wireless Supervision Time
The Zone Information Supervision Time must be 240 minutes.
32.7 Wireless Fire Verication
When used, the Model 1161 and 1162 wireless smoke detectors must not be programmed as Fire Verication (FV)
zone type.
California State Fire Marshal Specications
33.1 Bell Output Denition
The Model XR500 Series panel Bell Output must be programmed to operate steady on burglary alarms and pulsed,
temporal, or California School Code on re alarms.
XR500 Series Installation Guide Digital Monitoring Products
35
Page 44
COMPLIANCE
New York City (FDNY) Specications
34.1 Introduction
The programming specications contained in section 34.2 or 34.3 must be completed when installing the XR500
Series panel for New York City (FDNY) re alarm installations for IP communication applications. Refer to the FDNY
Certicate of Approval #6123 or #6145 for the complete conditions of approval.
Note: Fire alarm installations that use two digital dialer telephone lines do not need to comply with these two
sections.
34.2 Network and Cellular Communication, Primary and Secondary
When installed as a central station Internet (Network) communicator or slave transmitter both primary
and secondary channels of communication shall be required and shall meet the conditions below. Network
communication shall be used as primary channel of communication with Central Station and a 463C Cellular
Communicator shall be used as the secondary channel of communication or in reverse order: 463C Cellular
Communicator as primary and Network connection as the secondary channel.
Path 1 Type NET Primary and Path 2 Type CELL Backup Programming
Path 1 ProgrammingPath 2 Programming
Comm Type = NETComm Type = CELL
Path Type = PrimaryPath Type = Backup
Checkin Min = 5Checkin Min = 5
Failtime Min = 5Failtime Min = 5
Test Rpt = YesTest Rpt = Yes
Test Freq = 1 DyTest Freq = 1 Dy
Send Comm Trbl = YesSend Comm Trbl = Yes
Comm Path Trbl = Yes (Status List Programming)
Path 1 Type CELL Primary and Path 2 Type NET Backup Programming
Path 1 ProgrammingPath 2 Programming
Comm Type = CELLComm Type = NET
Path Type = PrimaryPath Type = Backup
Checkin Min = 5Checkin Min = 5
Failtime Min = 5Failtime Min = 5
Test Rpt = YesTest Rpt = Yes
Test Freq = 1 DyTest Freq = 1 Dy
Send Comm Trbl = YesSend Comm Trbl = Yes
Comm Path Trbl = Yes (Status List Programming)
34.3 Digital Dialer Primary and Network Secondary Communication
When used with a central oce communicator or a transmitter, the installation and operation of the equipment and
devices shall comply with 3RCNY 17-01. The installation shall employ the digital dialer as the primary communicator
(using telephone line) with network IP communication as backup or secondary means of communication. It shall
have the capability of transmitting separate and distinct signals to indicate manual pull station alarm, automatic
detection alarm, sprinkler waterow alarm, supervisory signal indications and trouble indications.
34.3.1 Communication Programming
For digital dialer communication with supervised network backup, program the following:
PRIMARY COMM TYPE = DD
FIRST PHONE NUMBER = Central Station Receiver Phone Number
BACKUP COMM TYPE = NET
RECEIVER
ALARMS = YES
34.4 Wiring
All wiring must be in accordance with NEC, ANSI, and NFPA 70. All network cabling must be installed in accordance
with NFPA 70 for communication circuits.
34.5 Additional Requirements
Program and install the equipment to comply with NFPA basic re requirements. Refer to the Universal Fire Alarm
Specications and ANSI/UL 864 NFPA 72 Specications in this document.
Digital Monitoring Products XR500 Series Installation Guide
36
Page 45
COMPLIANCE
False Alarm Reduction Programmable Options *
35.1 Shipping Defaults and Recommended Programming for ANSI/SIA CP-01-2010
SIA CP-01 FEATURE
PARAGRAPH # AND
DESCRIPTION
4.2.2.1 Exit Time15.2 Exit Delay
4.2.2.2 Progress
Annunciation
4.2.2.3 Exit Time Restart 15.2 Exit DelayRequired Option
4.2.2.5 Auto Stay Arm on
Unvacated Premises
4.2.4.4 Exit Time and
Progress Annunciation/
Disable - for Remote Arm
4.2.3.1 Entry Delay(s)8.3 Entry Delay
4.2.5.1 Abort Window –
for Non-Fire Zones
4.2.5.1 Abort Window
Time – for Non-Fire
Zones
4.2.5.1.2 Abort
Annunciation
4.2.5.4.1 Cancel
Annunciation
4.2.6.1 & 4.2.6.2 Duress
Feature
4.3.1 Cross Zoning16.22 Cross ZoneRequired Option
4.3.1 Programmable
Cross Zoning Time
4.3.2 Swinger Shutdown
4.3.2 Swinger Shutdown
Disable
4.3.3 Fire Alarm
Verication
4.5 Call Waiting Cancel
4.6.3 System Test17.5 Walk TestAllowed
4.6.5 Communications17.5 Walk TestNot AllowedN/AN/AN/a
* Programming at installation may be subordinate to other listed requirements for the intended application.
** For listed Installations, combined Entry Delay and Transmit Delay should not exceed 1 minute.
DMP XR500
PROGRAMMING
GUIDE LT-0679
REQUIREMENTRANGE
SHIPPING
DEFAULT
SECTION #
Required
(Programmable)
15.2 Exit DelayAllowed
33.3 Occupied Premise
- See XR500 Install
Guide (LT-0681)
Not Available on
Remote Arming
3.7 Transmit DelayRequired Option
3.7 Transmit Delay
3.7 Transmit DelayRequired Option
Always Enabled - Not
Programmable
User Code + 1 =
Ambush Code Not
Available
8.4 Cross Zone TimeAllowed4 sec. - 250 sec.4 Seconds
8.7 Swinger Bypass
Trips
16.16 Swinger BypassAllowed
16.4 Zone TypeRequired Option FV Type ZoneNo
3.19 Telephone
Number
Required Option
(except for
remote arming)
Allowed Option
Required
(Programmable)
Required
(Programmable
Required Option
Allowed Option
Required
(Programmable)
Required Option
45 sec. - 250 sec.
Individual keypads
may be disabled per
zone
For re-entry during
exit time
Area 1 = Perimeter
Area 2 = Interior
Progress Annunciation
Always disabled for
Remote Arming
30 sec. – 240 Sec. **
Disable by zone or
zone type
15 sec. - 45 sec. **
Annunciate that no
alarm was transmitted
(S45)
Annunciate that
a Cancel was
transmitted (S49)
No 1 + derivative of
another user code/no
duplicates with other
user codes
Yes/No Zone
Programming
1-6 trips2 trips2 trips
For non-police
response zones
Include *70P in
Telephone Number
Test all protection
devices
60
Seconds
All
keypads
enabled
EnabledEnabled
Enabled
Not
Available
30
Seconds
Enabled
NT DY EX
Zone
30
Seconds
YesYes
Always
Enabled
Code +1
Always
Disabled
No
YesEnabled (all zones)
Disabled
N/AN/A
60 Seconds
All keypads enabled
Enabled for Residential
Applications
Remote Arming not
allowed for CP-01
installations.
At least 30 Seconds **
Enabled
At least 15 Seconds **
Yes
Not Programmable
Enabled using two or
more programmed
zones
Per walk path in
protected premises
Yes as required (unless
sensors can self verify)
Enabled if user has
call waiting
RECOMMENDED
PROGRAMMING*
XR500 Series Installation Guide Digital Monitoring Products
The Call Waiting default setting is disabled. To cancel the Call Waiting feature, program * (star) 7 0 P (pause), the
standard telephone code prex that cancels call waiting, into the telephone number string. Cancel Call Waiting for
telephone lines that have Call Waiting operational on the telephone line. See the XR500 Series Programming Guide
(LT-0679).
Caution: A call waiting cancel programmed on a non-call waiting telephone line, would prevent
communication to the central station.
35.3 Occupied Premise
When only two areas are used, and area one is named Perimeter, and area two is named Interior, and no exit type
zone transition occurs during the exit delay because the premise continues to be occupied, the Interior area will
automatically disarm at the end of the exit delay.
35.4 Entry Delay
Only use Entry Delay 1. Do not use Entry Delay 2, 3, or 4. See the XR500 Series Programming Guide (LT-0679).
35.5 Minimum Installation Requirements
SIA CP-01-2010 minimum system installation requirements include an XR500, a listed local Bell, and o premise
DACT communication to an SCS-1R receiver plus one of the following compatible keypads.
630F Fire Command™ Center
7060, 7063, 7070, or 7073 Thinline™ keypads
7060A, 7063A, 7070A, or 7073A Aqualite™ keypads
7160, 7163, 7170, or 7173 Thinline™ keypads
Digital Monitoring Products XR500 Series Installation Guide
38
Page 47
36.1 866 with NAC Extender
WIRING DIAGRAMS
Wiring Diagrams
To panel terminal 7
To panel terminal 10
DMP Model 866
45mA @ 12 VDC
The 866 Notification
Appliance Circuit
Module in alarm draws
up to 31mA through
its Terminal 3 Alarm
Input and 45mA from
its Terminal 1 Aux
Power Input.
See the 866
Installation (LT-0059)
To panel zone
Normal/Silence Switch
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out 7 Bell Trouble
8 Bell Trouble
Normal/Silence Switch
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out 7 Bell Trouble
8 Bell Trouble
Model 310
1K EOL
Note: Terminals 3
and 4 jumper together
to supply Bell Power
from the panel
To panel alarm output
To panel zone
Model 310
1K EOL
PowerPath NAC Extender
Models
PS-8
PS-8E
PS-6
PS-6E
See PowerPath installation for
detailed connection
instructions
The Bell Output programming for Fire type zones must be set to Steady
XR500 Series Installation Guide Digital Monitoring Products
39
Page 48
WIRING DIAGRAMS
36.2 866 Class B Style W using Single Notication Appliance
DMP Model 866
45mA @ 12 VDC
The 866 Notification
Appliance Circuit
Module in alarm draws
up to 31mA through
its Terminal 3 Alarm
Input and 45mA from
its Terminal 1 Aux
Power Input.
MAIN BACKUP
J4
J5
K2
–
DS1
Buzzer
F2
J1
P3
F1
J2
K1
P10
+
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out 7 Bell Trouble
8 Bell Trouble
Auxiliary Power Supply must be regulated, power
limited, and listed for Fire Protective Signaling
Service. Power Supplies must have battery backup.
Note: If an auxiliary power supply is not used,
terminals 3 and 4 can be jumpered together to
supply Bell Power from the panel.
When using a separate power supply, the
maximum current is 3 Amps.
505-12 Power
Green
LED
AC
AC
J11
3
4
5
6
Supply
Red
LED
DC
+ BAT -
Battery
AC
J3J2
Start
Trouble
12 VDC @ 5 Amps
Batt
Trouble
J4
J6 Interface
Card
Expansion
Connector
J6
+ DC -
The Auxiliary Power Supply and Notification Circuit
Module trouble contact zone must be programmed
as a Supervisory Type zone and must be selected
for display in the keypad status list.
Sync module required when
using multiple notification
appliances
Model 308
10K EOL
The maximum voltage drop
Polarized Notification
Appliances
between the panel Bell Output and
the Model 308 is 1 VDC when a
separate power supply is not used.
See the Notification Appliance
section for a list of appliances.
XR500 Series Installation Guide Digital Monitoring Products
41
Page 50
WIRING DIAGRAMS
36.4 866 Class B Style W Dual Notication Appliance Circuits
Sync module required when
using multiple notification
appliances
Normal
S1
Bell
J2
Silence
CR6
CR5
J1
1
AUX PWR
2
GND
Alarm In
3
Bell Out A -
Bell Out B Bell Trouble
Bell Trouble
4
5
6
7
8
9
10
11
Bell PWR In +
Bell PWR In -
Bell Out A +
Bell Out B +
DSM-12/24 Module
MINUS 2MINUS 1+OUT 1 +IN 1+IN 2-AUD+AUD +OUT 2
TRBL
GND
FAULT
Model 310
1K EOL
When using a separate
power supply, the
maximum current is 3
Amps.
The Bell Output
programming for Fire
type zones must be set
to Steady.
Auxiliary Power Supply must be regulated, power
limited, and listed for Fire Protective Signaling
Service. Power Supplies must have battery backup.
Note: If an auxiliary power supply is not used,
terminals 3 and 4 can be jumpered together to
supply Bell Power from the panel.
505-12 Power
Supply
Green
Red
LED
LED
AC
DC
AC
J3J2
+ BAT -
Battery
Start
AC
Trouble
12 VDC @ 5 Amps
Batt
Trouble
J4
J6
+ DC -
The Auxiliary Power Supply and Notification
Circuit Module trouble contact zone must be
programmed as a Supervisory Type zone and
must be selected for display in the keypad
status list.
Model 308
10K EOL
The maximum voltage drop
between the panel Bell Output and
the Model 308 is 1 VDC when a
separate power supply is not used.
Model 308
10K EOL
See the Notification Appliance section for a list of appliances.
Polarized Notification Appliances
Digital Monitoring Products XR500 Series Installation Guide
42
Page 51
WIRING DIAGRAMS
36.5 865 Class B Style W using Single Notication Appliance
J1
Ethernet
J21
RS-232
J22
LX-Bus
J10
1K EOL
PROG
Tamper
J8
J4
XR500 Series Command
Processor™ Panel
Output 2
Output 1
J2
K6K7
Out2
J11
3
4
5
6
The Bell Output programming for Fire
type zones must be set to Temporal.
Note: Terminals 3 and 4 jumper together to
supply Bell Power from the panel.
Sync module required when
using multiple notification
appliances
S1
J2
CR6
CR5
1
AUX PWR
2
GND
Alarm In
3
Bell Out A -
Bell Out B Bell Trouble
Bell Trouble
4
5
6
7
8
9
10
11
Bell PWR In +
Bell PWR In -
Bell Out A +
Bell Out B +
SM-12/24 Module
Regulated
12 VDC
Normal
Bell
Silence
TRBL
GND
FAULT
J1
Model 310
1K EOL
The Bell Output
programming for Fire
type zones must be set
to Steady.
When using a separate power supply, the
maximum current is 3 Amps.
Auxiliary Power Supply must be regulated, power
limited, and listed for Fire Protective Signaling
Service. Power Supplies must have battery backup.
Note: If an auxiliary power supply is not used,
terminals 3 and 4 can be jumpered together to
supply Bell Power from the panel.
505-12 Power
Supply
Green
Red
LED
LED
AC
DC
AC
J3J2
+ BAT -
Battery
Start
AC
Trouble
12 VDC @ 5 Amps
Batt
Trouble
J4
J6
+ DC -
The Auxiliary Power Supply and Notification
Circuit Module trouble contact zone must be
programmed as a Supervisory Type zone and
must be selected for display in the keypad
status list.
Model 308
10K EOL
The maximum voltage drop
between the panel Bell Output and
Polarized Notification Appliances
See the Notification Appliance section for a list of appliances.
the Model 308 is 1 VDC when a
separate power supply is not used.
Digital Monitoring Products XR500 Series Installation Guide
44
Page 53
WIRING DIAGRAMS
36.7 865 Class B Style W Dual Notication Appliance Circuits
Sync module required when
using multiple notification
appliances
Normal
S1
Bell
J2
Silence
CR6
CR5
J1
1
AUX PWR
2
GND
Alarm In
3
Bell Out A +
Bell Out A -
Bell Out B +
Bell Out B Bell Trouble
Bell Trouble
4
5
6
7
8
9
10
11
Bell PWR In +
Bell PWR In -
DSM-12/24 Module
MINUS 2MINUS 1+OUT 1 +IN 1+IN 2-AUD+AUD +OUT 2
TRBL
GND
FAULT
Model 310
1K EOL
When using a separate
power supply, the
maximum current is 3
Amps.
The Bell Output
programming for Fire
type zones must be set
to Steady.
Auxiliary Power Supply must be regulated, power
limited, and listed for Fire Protective Signaling
Service. Power Supplies must have battery backup.
Note: If an auxiliary power supply is not used,
terminals 3 and 4 can be jumpered together to
supply Bell Power from the panel.
505-12 Power
Supply
Green
Red
LED
LED
AC
DC
AC
J3J2
+ BAT -
Battery
Start
AC
Trouble
12 VDC @ 5 Amps
Batt
Trouble
J4
J6
+ DC -
The Auxiliary Power Supply and Notification
Circuit Module trouble contact zone must be
programmed as a Supervisory Type zone and
must be selected for display in the keypad
status list.
Model 308
10K EOL
The maximum voltage drop
between the panel Bell Output and
the Model 308 is 1 VDC when a
separate power supply is not used.
Model 308
10K EOL
See the Notification Appliance section for a list of appliances.
Polarized Notification Appliances
XR500 Series Installation Guide Digital Monitoring Products
45
Page 54
WIRING DIAGRAMS
Module in alarm dr
36.8 865 Class A Style X using Single Notication Appliance
J1
Ethernet
J21
RS-232
J22
LX-Bus
J10
1K EOL
PROG
Tamper
J8
J4
XR500 Series Command
Processor™ Panel
Output 2
Output 1
J2
K6K7
Out2
J11
3
4
5
6
Note: Terminals 3 and 4 jumper together
to supply Bell Power from the panel
Terminals 2 and 5 jumper together to
provide Ground from the panel
Only one notification appliance may be used
when not using a sync module.
The Bell Output programming for Fire type
zones must be set to Temporal.
Auxiliary Power Supply must be Listed for Fire
Protective Signaling Service. Power Supplies
must have battery backup.
505-12 Power
Supply
Green
Red
LED
LED
AC
DC
AC
J3J2
+ BAT -
Battery
Start
Trouble
AC
12 VDC @ 5 Amps
Batt
Trouble
J4
The Auxiliary Power Supply and Notification
Circuit Module trouble contact zone must be
programmed as a Supervisory Type zone and
must be selected for display in the keypad
status list.
J6
+ DC -
XR500 Series Installation Guide Digital Monitoring Products
47
Page 56
WIRING DIAGRAMS
36.10 867 Class B Style W Multiple Notication Appliance Circuit
Sync module required when using multiple notification appliances
Auxiliary Power Supply must be Listed for Fire
Protective Signaling Service. Power Supplies
must have battery backup.
When using an SM Sync Module, the
maximum current is 3 Amps.
505-12 Power
Supply
Green
Red
LED
LED
AC
DC
AC
J3J2
+ BAT -
Battery
Start
Trouble
AC
12 VDC @ 5 Amps
Batt
Trouble
J4
+ DC -
The Auxiliary Power Supply and Notification
Circuit Module trouble contact zone must be
programmed as a Supervisory Type zone and
must be selected for display in the keypad
status list.
J6
Model 308
10K EOL
Listed, Polarized
Notification Appliances
See the Notification Appliance
section for a list of appliances.
Digital Monitoring Products XR500 Series Installation Guide
48
Page 57
WIRING DIAGRAMS
36.11 867 Class B Style W Multiple Notication Appliance Circuits
Sync module required when using
multiple notification appliances
Normal/Silence Switch
Ground Fault LED
Bell Trouble LED
Bell In + 1
Bell In - 2
Bell Out + 3
Bell Out - 4
Bell Trouble 5
Bell Trouble 6
PWR Mon. 7
Mon. RTN 8
TENS ONES
TENS ONES
LX-Bus Wiring
Model 310
1K EOL
Bell Ring Style (Steady)
Power Supply Monitor LED
Data LED
DSM-12/24 Module
MINUS 2MINUS 1+OUT 1 +IN 1+IN 2-AUD+AUD +OUT 2
Auxiliary Power Supply must be Listed for Fire
Protective Signaling Service. Power Supplies
must have battery backup.
When using an DSM Sync Module, the
maximum current is 3 Amps.
505-12 Power
Supply
Green
Red
LED
LED
AC
DC
AC
J3J2
+ BAT -
Battery
Start
Trouble
AC
12 VDC @ 5 Amps
Batt
Trouble
J4
+ DC -
The Auxiliary Power Supply and Notification
Circuit Module trouble contact zone must be
programmed as a Supervisory Type zone and
must be selected for display in the keypad
status list.
Model 308
10K EOL
J6
Model 308
10K EOL
Listed, Polarized Notification Appliances
See the Notification Appliance section
for a list of appliances.
XR500 Series Installation Guide Digital Monitoring Products
49
Page 58
WIRING DIAGRAMS
36.12 Panel Slave Communicator for FACP using 630F Annunciator
Program forFire Protective Signaling communication to the
Central Station.
Program Fire Alarm zone as type FI and set Fire Panel Slave
Input option as YES.
Program General Trouble zone as type FI.
Program Supervisory zone as type SV and set the Latch
Supervisory option in System Options as NO.
Main Fire Alarm
Fire Alarm
Form C alarm contacts activate
short on General Fire Alarm.
General Trouble
Form C trouble contacts activate
open on General Trouble.
General Trouble must not be
used to indicate AC power fail
unless it can be delayed at least
1 hour.
Supervisory
Form C contacts activate short on
Supervisory condition.
Control Panel (FACP)
COMMAND
Normally Open
{
Normally Closed
Normally Open
{
Normally Closed
Normally Open
{
Normally Closed
Program Bell Options
fire type as None.
Zone 3
Common
Common
1.0k Ohm
Zone 4
Common
1k Ohm EOL
1.0k Ohm
Zone 6
Digital Monitoring Products XR500 Series Installation Guide
50
Page 59
WIRING DIAGRAMS
92
36.13 Panel Slave Communicator for FACP using Outputs
XR500 Series
Command Processor™ Panel
J1
J22
LX-Bus
J10
PROG
Tamper
J8
J4
Communication Fail
Output 1 must be programmed
as a Comm Fail output in Output
Options.
Fire Trouble
Output 2 must be programmed
as a Fire Trouble output in
Output Options.
Program at least one Device in Device Setup as a Fire Type although a keypad is
not actually connected.
Program for Fire Protective Signaling communication to the Central Station.
Program Fire Alarm zone as type FI and set Fire Panel Slave Input option as YES.
Program General Trouble zone as type FI.
Program Supervisory zone as type SV and set the Latch Supervisory option in
System Options as NO.
1234567810 11 12 13 14 15 16 17 18 19
Program Bell Options
Model 311
1K EOL
fire type as None.
Main Fire Alarm
Fire Alarm
Form C alarm contacts activate
short on General Fire Alarm.
General Trouble
Form C trouble contacts activate
open on General Trouble.
General Trouble must not be
used to indicate AC power fail
unless it can be delayed at least
1 hour.
Supervisory
Form C contacts activate short on
Supervisory condition.
Control Panel (FACP)
Normally Open
{
{
{
Common
Normally Closed
Normally Open
Common
Normally Closed
Normally Open
Common
Normally Closed
Normally Open
Common
Normally Closed
02122232425262728
Must be
installed
in conduit
and located
within 20 feet.
Zone 3
1.0k Ohm
Zone 4
1k Ohm EOL
1.0k Ohm
Zone 6
Communication Fail
Program FACP Zone Input to
indicate a communication trouble
locally.
Fire Trouble
Program FACP Zone Input to
indicate a trouble locally.
XR500 Series Installation Guide Digital Monitoring Products
Output Color Code–Model 431 Harness
Output 2 N/O Orange/White
Output 2 Com White/Gray
Output 2 N/C Violet/White
Output 1 N/O Orange
Output 1 Com Gray
Output 1 N/C Violet
Output Header J2 for K6 and K7 Dry Contact
Relays. All outputs must be connected to devices
located within the same room as the panel.
J2
K6
J11
K7
J6
Interface
Card
Expansion
Connector
J16
Reset
+ 12V
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
COMM
P2
Panel Terminal 7 Wire
Panel Common Wire
1 2 3
JP4
1 2 3
JP3
1 2 3
JP1
1 2 3
JP2
1 2 3 4 5 6 7 8
SW1 (MSB)SW2 (LSB)
OPEN
1 2 3 4 5 6 7 8
OPEN
Output 2 Common Wire
Output 1 Common Wire
J2
J1
+12 VDC Out
CONT OUT
D8122
Interfacing D8122 to the XR500 Series Panels
The D8122 may only be used in conjunction with telephone systems that support Derived Channel network.
For installation instructions, see the Derived Channel STUD8121A/D8122 Operation and Installation Guide.
• For Standard Line Security applications, the panel must be installed and programmed to meet burglary
alarm system requirements.
• The panel must be installed and programmed for reporting all alarm conditions through the integral
DACT or network connection to the same central station that monitors the D8122.
• The D8122 must be installed in the same enclosure as the XR500 Series panel using the supplied
mounting hardware. Refer to the STUD8121A/D8122 Operation and Installation Guide.
• Derived Channel Communication is not applicable for ULC Canadian Installations.
XR500 Series Installation Guide Digital Monitoring Products
53
Page 62
WIRING DIAGRAMS
36.16 Rothenbuhler 5110 High Security Bell Wiring.
XR500 Series Installation Guide Digital Monitoring Products
57
Page 66
WIRING DIAGRAMS
36.21 System Sensor i4 Series Smoke and CO Detectors
Using A Single COSMOD2W Module
See i4 Series Interface Module Installation and Maintenance Instructions for additional information.
To Panel SMK or Optional Power Supply
To GND from Panel or Power Supply
Program Smoke zone
as type Fire (FI)
Program Maintenance zone
as type Auxiliary (AUX)**
Program CO zone as type
Emergency (EM) and
To Panel or Zone Expander
To Panel or Zone Expander GND
To Panel or Zone Expander Zone
To Panel or Zone Expander GND
To Panel or Zone Expander Zone
To Panel or Zone Expander GND
include CO in Zone name.
** The COSMOD2W sends a smoke maintenance inquiry to the
smoke detectors every 24 hours. If a response indicating a
maintenance condition is received, such as the detector
needs cleaning, the maintenance zone will indicate a
trouble condition.
The CO detector reports any maintenace conditions on the
Emergency zone.
To next
Install 3.9K EOL Resistor
at last detector
(supplied with
COSMOD2W)
To silence detectors
perform a Sensor Reset
COSMO-2W. Up
to 12 detectors
can be installed
for each
COSMOD2W
*
Zone EOL
Power In +
Power In -
Smoke +
Smoke -
Maint +
Maint CO Alarm +
CO Alarm -
COSMOD2W
Zone EOL
Zone EOL
IDC +
IDC -
Loop Style D wiring
To detector (+)
To detector (-)
COSMO-2W
*Optional Power Supply connection
J1
Power Supply
+ DC —
***
716
Output Expander
E
T
N
S
8
7
9
6
0
5
1
4
Rotary
2
3
Switches
8
7
9
6
0
5
1
4
2
3
ONE
S
TXD
K1
K2
K3
K4
To Panel
LX-Bus
N/C to COSMOD2W
Power In (+) (Violet)
To COSMOD2W Power In (-)
To 716 Output Common (Gray)
If using optional Power supply, program Output
Options Fire Output for the 716 relay to provide
Sensor Reset capability.
*** Listed for Fire Applications, output limited power, regulated
Digital Monitoring Products XR500 Series Installation Guide
58
Page 67
WIRING DIAGRAMS
Connect the Bell In
Connect the CO Trigger
36.22 System Sensor i4 Series Smoke and CO Detectors
Using Multiple COSMOD2W Modules
See i4 Series Interface Module Installation and Maintenance Instructions for additional information.
N/O to CO Trigger
Common
N/O to Bell In
RELAY
To Panel power SMK terminal
If installing multiple COSMOD2W Interface
modules, connect the Bell In terminal to a N/O
relay output to turn on ALL COSMOD2W smoke
detector sounders during a fire alarm. Connect
the Output Common to the panel SMK or
optional Power Supply positive terminal (+). In
Bell Options, program Bell Output for the relay
output number. Program the Bell Output Bell
Action as Temporal (T).
Common
or Optional Power Supply
Power In +
Power In -
Smoke +
Smoke -
Maint +
Maint CO Alarm +
CO Alarm -
CO Trigger
COSMOD2W
Zone EOL
Zone EOL
IDC +
IDC -
Bell In
To turn on ALL CO detector sounders installed
on multiple COSMOD2W modules during a CO
alarm, connect the CO Trigger to a N/O relay
output. Connect the Output Common to the
panel SMK or optional Power Supply positive
terminal (+). In Zone Information Alarm Action,
program each COSMOD2W Emergency Zone
(CO Alarm) for the COSMO-2W to turn on the
relay output Steady (STD) when the zone is in a
shorted condition.
Power In +
Power In -
Smoke +
Smoke -
Maint +
Maint CO Alarm +
CO Alarm -
CO Trigger
COSMOD2W
Zone EOL
Zone EOL
IDC +
IDC -
Bell In
XR500 Series Installation Guide Digital Monitoring Products
59
Page 68
REVISIONS
Revisions to This Document
This section explains the changes that were made to this document during this revision. This section lists the
version, section number with heading, and a quick summary of the change.
Version Section Number and Heading Summary of Changes
1.29 11.2 Compatible 2-Wire Smoke Updated to current devices
Detector Chart
36.21 System Sensor i4 Series Smoke Added Wiring Diagram
and CO Detectors Using A Single
COSMOD2W Module
36.22 System Sensor i4 Series Smoke Added Wiring Diagram
and CO Detectors Using Multiple
COSMOD2W Modules
1.28 1.5 LX-Bus Added Model 2W-BLX and 2WT-BLX Smoke Detector references
3.4 Accessory Devices Added Model 2W-BLX and 2WT-BLX Smoke Detector references
6.8 XR500 Series Power Requirements Added Model 2W-BLX and 2WT-BLX Smoke Detector references
1.27 Complete Guide Added 464 Series References
3.4 Accessory Devices Updated for current product
6.8 XR500 Series Power Requirements Updated for current product
24.10 CELL Only, Standard or Added 464-263C, 464-263H
Encrypted Line Security
24.11 NET with CELL as Alternate Added 464-263C, 464-263H
Primary and Dialer Backup,
Standard or Encrypted
Line Security
24.12 NET with CELL as Backup and Added 464-263C, 464-263H
Adaptive Primary, Standard or
Encrypted Line Security
1.26 6.1 Battery Terminal 3 and 4 Updating model 368
6.9 Standby Battery Selection Updating model 368
21.14 Standby Batteries Updating mosel 368
1.25 21.8 Listed Receivers Claried listed receivers for contact ID
30.12 Listed Receivers Claried listed receivers for contact ID
Listings and Approvals Added California Stare re Marshal (CSFM)
1.24 3.2 Wiring Diagram Add 734 to Wiring Diagram
32.6 Wireless External Contact Removed 1101, 1102, and 1105 section
Digital Monitoring Products XR500 Series Installation Guide
60
Page 69
XR500 Series Installation Guide Digital Monitoring Products
61
Page 70
Certications
California State Fire Marshal (CSFM)
ANSI/SIA CP-01-2010 False Alarm Reduction
FCC Part 15
FCC Part 68 Registration ID CCKAL00BXR500
NIST Validated XR500E Encrypted Command
Processor Panel Certificate #130
New York City (FDNY COA #6167)
ANSI/UL 294 Access Control System Units
ANSI/UL 365 Police Connected Burglar
ANSI/UL 609 Local Burglar
ANSI/UL 1023 Household Burglar
ANSI/UL 1076 Proprietary Burglar
ANSI/UL 1610 Central Station Burglar
ANSI/UL 1635 Digital Burglar
ANSI/UL 2017 General Purpose Signaling
Devices and Systems
ANSI/UL 985 Household Fire Warning
ANSI/UL 864 Fire Protective Signaling 9th
Edition
Compatible with Devices listed for
ANSI/UL 268 Smoke-Automatic Fire Detectors
ANSI/UL 346 Waterow Indicators for Fire
Protective Signaling Systems
ANSI/UL 636 Holdup Alarm Units and
Systems Accessory
UL Bank, Safe, and Vault
UL Standard Line Security
UL Encrypted Standard Line Security
Export Control
The XR500E uses AES encryption and any export beyond
the United States must be in accordance with Export
Administration Regulations.