DMP Electronics XR100, XR500 Installation Manual

Page 1
INSTALLATION GUIDE
734W Wiegand Interface Module
Description
The 734W Wiegand Interface Module allows you to add WiFi network access control capability to XR100/XR500 panels using proximity or mag-stripe card readers. The 734W provides a fast, safe and secure connection to your local WiFi network
for AES encrypted TCP communication with the control panel and allows fast verication of user codes presented at the
reader for door access. The 734W operates at 12/24 Vdc from the power supply supporting the magnetic lock or door­strike at the door and provides a 10 Amp Form C relay contact for lock control. Four input zones are provided to allow connection of nearby burglary devices. For local annunciation, a programmable speaker and a variety of switched ground annunciators are provided to connect to sounders. In addition, the 734W provides LEDs to indicate door strike, Wiegand inputs, and power to the module.
The 734W provides a keypad programming connection to use a standard DMP LCD keypad for initial WiFi network setup. Programming can be completed using the keypad or from the XR100/XR500 panel.
Mounting the 734W
The 734W ships installed in a decorative, high­impact plastic housing that mounts directly
to walls, backboards, or other at surfaces.
For easy installation, the 734W housing back and ends have wire entrances. The bottom contains multiple screw holes for mounting on single-gang switch boxes. It is recommended to mount the 734W near the protected door.
Magnetic Lock and Door Strike Wiring
You can control door strikes and magnetic locks by using the Form C relay on the 734W module. Use an additional power supply to power door strikes and magnetic locks. Refer to Figures 2 and 3 for wiring information.
Figure 2: 734W Magnetic Lock Wiring
Figure 1: 734W Wiegand Interface Module
Figure 3: 734W Door Strike Wiring
12/24 VDC Power
Power to the 734W module can be provided by a Listed 12 or 24 VDC power source connected to the J27 terminal block.
Page 2
NO/C/NC (Dry Contact Relay)
The 734W provides a Form C (SPDT) relay for controlling door strikes or magnetic locks. The three relay terminals marked NO C NC allow you to connect the device wiring to the relay for module control. See Figures 2 and 3 for proper door strike and magnetic lock wiring.
The Form C relay draws up to 35mA of current and its contacts are rated for 10 Amps (resistive) at 12/24 VDC. When connecting multiple locks to the Form C relay, the total current for all locks cannot exceed 10 Amps. If the total current for all locks exceeds 10 Amps, problems may arise and an isolation relay may be needed.
See the Isolation Relay section for information.
Install the 333 Suppressor
One Model 333 Suppressor is included with the 734W module. Install the suppressor across the 734W Common (C) and Normally Open (NO) or Normally Closed (NC) terminals. If the device being controlled by the relay is connected to the NO and C terminals, install the suppressor on the NO and C terminals. Conversely, if the device is connected to the NC and C terminals, install the 333 Suppressor on NC and C terminals. The suppressor wire is non-polarized. Install the suppressor as shown in Figure 4.
Isolation Relay
The Form C Relay can control a device that draws less than 10 Amps of current. If a device draws more than 10 Amp of current, or the sum of all devices controlled by the Form C Relay exceeds 10 Amps, an isolation relay must be used. Refer to Figures 5 and 6 for isolation relay wiring.
Figure 4: Model 333 Installation on the 734W Module
Figure 5: Isolation Relay with Magnetic Lock
Connection to Reader
The 734W provides direct 12/24 VDC, 200mA output to the reader on the J9 Red terminal connection.
Figure 7 shows a reader with wire colors Red, White, Green, and Black. The wire colors may be different for the reader being installed. Connect the reader wires to J9 terminals 1, 2, 3, and 4. As shown in Figure 7, the Green wire carries D0, or Data Zero, and the White wire carries D1, or Data One. The Red wire carries 12/24 VDC, 200mA power limited output and the Black wire is ground.
Status LEDs
The 734W provides two status LEDs. See Figure 1 for locations of the LEDs.
The Red LED turns on for the duration of the door strike.
The Yellow LED turns on for one second to indicate a Wiegand read.
The Green LED is constant to indicate power.
Digital Monitoring Products 734W Installation Guide
2
Figure 6: Isolation Relay with Door Strike
Figure 7: Card Reader Wiring
Page 3
Zone Terminals
Terminals 5-11 on J9 connect grounded zones 1 through 3. These zones
have a grounded side and cannot be used for re-initiating devices. Zones
2 and 3 can also be used for access control with Zone 2 providing a bypass option and Zone 3 providing Request to Exit functionality. Zone 4 terminals provide a non-powered Class B, Style A zone. Use the supplied, DMP Model 311 1K Ohm End-of-Line resistors on each zone. Refer to the panel programming guide for programming instructions.
Zone # Recommended Device Residential Fire Devices?
1 Any burglary device No 2 Door Contact No 3 REX (PIR or Button) No 4 Any device Yes
Figure 8: 734W Zone Terminals
Annunciator Header
The 4-pin J26 header located on the far right of the circuit board is used to wire the Armed Status, Remote Annunciation, and the Remote LED Control maximum current of 50mA the 4-pin header for connection of the following indicators:
--
AS (Armed Status)
Armed Status provides an unsupervised switched ground for a visual or audible armed status indicator that turns on when the burglary areas are armed, such as SYSTEM ON or ALL SYSTEM ON. Connect the wire from the 4-wire harness to
. The open collectors will supply a ground for a
@ 30 VDC. Connect a Model 300 4-wire harness to
Remote LED Control Remote Audible Annunciator Armed Status Output
Output 2
Output 1
an Armed Status output.
--RA (Remote Annunciation)
Remote Annunciation provides an unsupervised switched ground for a remote annunciator that turns on when the Model 734W on-board piezo turns on. Connect the wire from the 4-wire harness to a
remote annunciator. The
Figure 9: 734W Annunicator Outputs
remote annunciator silences when the RA restores. The remote annunciator (RA) switched ground will operate even if the speaker is programmed not to operate.
--LC (Remote LED Control)
Remote LED Control provides an unsupervised switched ground for a visual indicator that turns on when the Model 734W relay activates. Connect the wire from the 4-wire harness to an LED. The LED turns on for the duration the door strike relay is on. HID readers optionally provide a connection for LED reader control.
Auxiliary Outputs 1 & 2
The 734W controls Auxiliary Outputs 1 and 2 when the Activate Zone 2 Bypass programming option is enabled and the Zone 2 Bypass Time is set. When the door contact (Zone 2) is opened while the door strike is activated, the Zone 2 Bypass Time starts. If the door has not closed at the end of the timer, Aux Output 1 is turned on and the timer starts again. If the door is still open at the end of the second timer, Aux Output 2 is turned on. Aux Outputs 1 and 2 turn off when the door contact is closed. Use the Model 431 Relay Harness for connection of Output 1 and Output 2 as shown in Table 1.
Reset Header
Form C Relays (J2)
Output Color Code–Model 431 Harness Output 2 N/O Orange/White Output 2 Com White/Gray Output 2 N/C Violet/White Output 1 N/O Orange Output 1 Com Gray Output 1 N/C Violet
Table 1: Harness Wiring
The reset header is located just above and to the right of the WiFi network connector (see Figure 1) and is used to reset
the 734W module. To reset the module when rst installing the system, install the reset jumper before applying power to
the module. After connecting the power, remove the reset jumper. To reset the module while the system is operational, for example, prior to reprogramming, install the reset jumper
without powering down the system. Remove the reset jumper after one or two seconds.
PROG (Programming)
The 734W module is programmable from a 32-character keypad set to address one. For 12 Volt applications, connect the keypad to the module using a Model 330 4-wire harness.
For 24 Volt applications, connect the keypad to the module using the included WR-0235 4-wire programming harness with in-line resistor.
Do not connect a keypad using a Model 330 harness if using a 24 volt power supply! Damage to the keypad could occur.
While programming the 734W module with a keypad, advance to the next programming option by pressing the CMD key. Return to the previous programming option or erase an incorrect entry by pressing the Back Arrow key. Make a selection by pressing the Select key below the option you wish to select. While in programming mode no 734W communication with the panel can occur.
734W Installation Guide Digital Monitoring Products
3
Page 4
VER vvv mm/dd/yy
date display.
734W ZONE: 1 -OKAY
734W DOOR ZONE: 2 -OPEN
734W
Version Display
When you connect the keypad to the 734W module, the version number and release
Press keys 1, 2, 3, or 4 then the CMD key to show zone status of that zone.
Press CMD key to enter the Diagnostic Menu.
zone number followed by the CMD key.
Press 6653 (PROG) then CMD to enter the Programming Menu.
Zone Status Display
The status of the entered zone number displays. To display another zone, enter the
734W REX
ZONE: 3 -SHORT
MENU? NO YES
return to Version Display.
CONNECT STATUS
CONNECT STATUS NOT CONNECTED
CONNECT STATUS
passphrase programmed in the panel.
BAD PASSPHRASE
CONNECT STATUS
Device Number in the panel.
DEVICE NOT PROG
Duplicate Device: There is another device on the WiFi network with the same device number.
CONNECT STATUS
Diagnostic Menu
Select YES to display the Panel Communication Connect Status display. Select NO to
Connect Status
To display the connection status of the 734W to the panel, select any top row key.
Not Connected: The 734W cannot connect to the panel on the WiFi network.
Bad Passphrase: The passphrase programmed in the 734W device does not match the
Device Not Programmed: The device number programmed in the 734W is not programmed as a
DUPLICATE DEVICE
Transmit Time XXX: The speed in milliseconds in which the last message was sent and received
CONNECT STATUS
between the 734W and the panel.
XMIT TIME xxx mS
734W
Press the CMD key to enter programming and display initialization options.
PROGRAMMER
Initialization Options
in preparation for programming. Press any select key to enter the initialization menu.
Initialization Communications
INITIALIZATION
Select YES to initialize the communication options back to factory defaults. Select NO to
COMMS? NO YES
leave communication options unchanged.
InitializeConrmOption
INITIALIZATION SURE? YES NO
for conrmation to clear the memory. This is a safeguard against accidentally erasing the
programming. No memory is cleared from the programming until you answer YES to the SURE? option. Selecting NO leaves communication options unchanged.
734W
INITIALIZATION
Programming Menu
These options can set the 734W module programming memory back to factory defaults
After selecting YES to clear the Communication settings, the 734W displays SURE? YES NO
Initialization Access
INITIALIZATION
Select YES to initialize the Access Options back to factory defaults. Select NO to return to
ACCESS? NO YES
the INITIALIZATION menu.
INITIALIZATION SURE? YES NO
conrmation to clear the memory. This is a safeguard against accidentally erasing the
programming. No memory is cleared from the programming until you answer YES to the SURE? option. Selecting NO
734W
Press any select key to enter the Communication menu. Press the CMD key to advance to
COMMUNICATION
the Access Options menu. Press the back arrow to display the 734W Initialization menu.
734W Installation Guide Digital Monitoring Products
InitializeConrmOption
After selecting YES to clear the Access Options, the 734W displays SURE? YES NO for
Communication Menu
leaves communication options unchanged.
4
Page 5
734W DEVICE NO:
Enter a device number from 2-16 for the 734W. The device number must also be
7
programmed as a device in the panel. Default is 7.
734W DHCP? NO YES
Select YES (fourth select key) to use dynamic IP address information for the 734W IP
Address, Subnet Mask, and Gateway Address. Select NO (third select key) to enter static IP information.
734W IP ADDRESS:
192.168.0.201
SUBNET MASK:
Enter the local subnet mask assigned to the 734W. Default is 255.255.255.0
255.255.255.0
GATEWAY ADDRESS:
Enter the local gateway address of the 734W. Default is 192.168.0.1
192.168.0.1
PANEL IP ADDR:
Enter the IP address of the panel. Default is 0.0.0.0.
0.0.0.0
Address prompt in Network Options. The DHCP programming in the panel must be set to NO.
PANEL IP PORT:
Enter the port number that the 734W uses to send communication to the panel. This must
2002
be the same port that is programmed in 734W Listen Port in Network Options programming of the panel.
734W PASSPHRASE
Enter an 8 to 16-character alphanumeric Passphrase to encrypt communication with the
panel. The 734W Passphrase must match the 734W Passphrase entered in Network Options programming of the panel. The Passphrase is blank by default.
Press any select key to enter the Access Options menu. Press the CMD key to advance to the
ACCESS OPTIONS
Stop prompt. Press the back arrow to display the Communication menu.
ACTIVATE ZONE 2
Select YES to activate the Zone 2 Bypass operation. Selecting NO allows standard zone
BYPASS? NO YES
operation on Zone. Default setting is NO. protected (contact installed), you can provide a programmable bypass entry/exit timer by connecting its contact wiring to the 734W module Zone 2. When the on-board Form C relay activates and the user opens the door connected to Zone 2, the zone is delayed for the number of seconds programmed in ZONE 2 BYPASS TIME allowing the user to enter/exit during an armed period.
other second during the last ten seconds. If Zone 2 restores prior to the end of the programmed time, the piezo silences. If the zone does not restore before the programmed time, the 734W ends the bypass and indicates the open or short zone condition to the panel.
ZONE 2 BYPASS TIME: 40
Enter the number of seconds to elapse before the Bypass Timer expires. Range is from 20
to 250 seconds. Press any top row select key to enter the number of seconds. If the door remains open when the timer expires a zone open/short is sent to the panel for Zone 2. The default is 40 seconds. Figure 10 shows how the Bypass option works.
734W
734W Device Number
734W DHCP
734W IP Address
Enter the IP address of the 734W. Default is 192.168.0.201.
Subnet Mask
Gateway Address
Panel IP Address
Note: This IP address must match the address programmed in the panel at the Local IP
Panel IP Port
734W Passphrase
Note: A passphrase is required for communication to occur with the panel.
Access Options
Activate Zone 2 Bypass
If the door being released by the 734W module is
If Zone 2 does not restore (door closed) within the programmed time, the piezo sounds every
Zone 2 Bypass Time
734W Installation Guide Digital Monitoring Products
5 Second
Strike
40
Seconds
40-Second Zone 2 Bypass entry/exit timer.
Figure 10: Zone 2 Bypass Timeline using default time
10 seconds before the bypass time expires, the device beeps if the door is still open.
End of timer.
A zone open/short is indicated if the door remains open.
5
Page 6
RELOCK ON ZONE 2
Selecting YES turns the relay off when Zone 2 returns to normal during the bypass. Selecting
CHANGE? NO YES
NO leaves the relay on when Zone 2 faults to an open or short condition during bypass. Turning off the relay at Door Closed allows a long strike time to be automatically ended and relocks the door. The default is NO.
ACTIVATE ZONE 3 REX? NO YES
Selecting NO allows standard zone operation on Zone 3. Default setting is NO. You can connect a PIR (or other motion sensing device) or a mechanical switch to Zone 3
to provide REX capability to the system. When Zone 3 shorts, the on-board Form C relay activates for the programmed number of
seconds (see Zone 3 REX Strike Time). During this time, the user can open the protected door to start the programmed Zone 2 Bypass entry/exit timer. After the programmed number of seconds, the relay restores the door to its locked state.
The 734W module provides a bypass-only option for REX on Zone 3. When Zone 3 OPENS from a NORMAL state, only a bypass occurs: the on-board relay does not activate. This
bypass-only option uses two methods of REX. The rst REX device provides the programmed
bypass entry/exit timer. The second REX, or manual device such as a door knob, unlocks the door.
An example of the shunt-only conguration is a door to an ofce that is locked 24 hours
a day. Users pass a REX motion detector positioned by the door to begin the programmed exit timer. Within the programmed number of seconds the user must then manually activate a second device, such as a REX device or manual door knob, to unlock the door. If the door is opened after the programmed number of seconds, an open condition is indicated to the panel.
ZN 3 REX STRIKE
Enter the number of REX seconds to elapse. Range is from 5 to 250 seconds. Press any
TIME: 5
select key to enter the number of seconds. The default is 5 seconds.
ACTIVATE ONBOARD SPEAKER? NO YES
annunciations. Select NO to turn the speaker off for all operations. This does not affect remote annunciator open collector (RA) operation. The default is NO.
CARD OPTIONS:
DMP
CARD OPTIONS: DMP CUSTOM ANY
Note: When set to DMP, the 734W converts 17 bits of the 26 to 45-bit data string into a 5-digit number.
Relock on Zone 2 Change?
Activate Zone 3 Request to Exit
Selecting YES activates the Zone 3 Request to Exit (REX) option.
Zone 3 REX Strike Time
Activate Onboard Speaker
Select YES to enable the onboard speaker for local annunciation, such as alarm and trouble
Card Options
Typically, an access card contains data bits for a site code, a user code, and start/stop/
parity bits. The starting position location and code length must be determined and programmed into the 734W Module. Select DMP to indicate the reader sends a 26-45 bit data
string. To select the DMP option, press the rst Select key under DMP. Default is DMP.
Select CUSTOM if using a non-DMP card or user code length of 6 to 10 digits. Select ANY to allow all card reads to activate the door strike relay. The door strike relay is activated for the length of time programmed in ZN 3 REX TIME. No user code information is sent to the panel.
First Bit
Received
Position = 0
Figure 11: HID 26-bit Weigand Data Stream Bit Location
WIEGAND CODE
When using a custom product, enter the total number of bits to be received in Wiegand
LENGTH: 26
code including parity bits. Press any top row Select key to enter a number between 0-255 to equal the number of bits.
Default is 26 bits.
SITE CODE POSITION: 1
between 0-255. Default is 1. Press the COMMAND key to save the entry.
734W Installation Guide Digital Monitoring Products
CustomCardDenitions
Site Code Position
Enter the site code start position in the data string. Press any Select Key to enter a number
01110101101101010001100111
Site Code
Position = 2
Length = 8
In this example the Wiegand Code Length = 26 bits.
User Code
Position = 10
Length = 16
Last Bit
Received
Position = 25
6
Page 7
SITE CODE LENGTH: 8
1-16. Default is 8. Press the COMMAND key to save the entry.
USER CODE
Dene the User Code start bit position. Press any Select Key to enter a number between
POSITION: 9
0-255. Default is 9. Press the COMMAND key to save the entry.
USER CODE
Dene the total number of User Code bits used. Press any Select Key to enter a number
LENGTH: 16
between 1-255. The default is 16.
REQUIRE SITE
Press the top row Select key under YES to use a site code and press the COMMAND key to
CODE: NO YES
view the site code entry display. In addition to User Code verication, door access is only
granted when any one site code programmed at the SITE CODE ENTRY option matches the site code received in the Wiegand string.
SITE CODE 1: (1 - 65,535) 127
SITE CODE 2:
To change the site code, press a select key, then enter the new code. Press the COMMAND
(1 - 65,535) -
key to save and to display the next site code.
SITE CODE 8:
Site Codes 2-8 default to blank.
(1 - 65,535) ­NO. OF USER CODE
DIGITS: 5
Select key to enter a user code digit length between 1-10 digits. This number must match the user code number length being programmed in the panel. Default is 5.
All bits are read and converted into a decimal number string. The number string is left padded with '0' if needed for long user code lengths. When selecting '4' the right digit is dropped and the next four sent. Example: # decoded 1234567 10 digits 0001234567
No Communication with Panel
NO COMM WITH PNL
This option denes the relay action when communication with the panel has not occurred
OFF SITE ANY ON
for ve seconds. Default is OFF. Press any top row Select key to change the default relay action.
Choose the action required when the 734W cannot establish communication with the panel:
NO COMM WITH PNL
Press the rst Select key to choose OFF (Relay Always Off) — The relay does not turn on
LAST
when any Wiegand string is received. OFF does not affect any REX operation. If communication is lost during a door strike, relay remains on for the door strike duration, but turns off at the end of the door strike timer.
Press the second Select key to choose SITE (Accept Site Code) — Door access is granted when the Wiegand site code string received matches any site code programmed at SITE CODE 1-8. For details refer back to the REQUIRE SITE CODE option.
Press the third Select key to choose ANY (Any Wiegand Read) — Door access is granted when any Wiegand string is received.
Press the fourth Select key to choose ON (Relay Always On) — The relay is always on. Press the COMMAND key to display the next action. Press the rst Select key to choose LAST (Keep Last State) — The relay remains in the same
state and does not change when communication is lost. If communication is lost during a door strike, the relay remains on for the door strike duration, but then returns to it's last state prior to doing the door strike.
734W
Press any select key to start the stop routine. When programming in complete, the Version
displays and the keypad can now be removed.
STOP
Site Code Length
Enter the number of Site Code bits used.
Press any Select Key to enter a number between
User Code Position
User Code Length
Require Site Code
Site Code Display You can program up to eight ve-digit site codes. Site code range is 1-65535.
SITE CODE 1 displays rst. Any previously programmed site code displays. Default is 127.
Number of User Code Digits
The 734W module recognizes user codes from one to ten digits in length. Press any top row
5 digits 34567 4 digits 3456
Stop
FCC Information
Electronic Emission
This device complies with CFR47 Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation.
734W Installation Guide Digital Monitoring Products
7
Page 8
FCC Frequency Interference
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to CFR47 Part 15. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a residential environment, not withstanding use in commercial, business and industrial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. There is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Changes or modications to this equipment not expressly approved by the party responsible for compliance could void the user’s
authority to operate the equipment.
FCC Radiation Exposure
To comply with FCC Radio Frequency exposure requirements in section 1.1307, a minimum separation distance of 20 cm. is required between the antenna and all occupational persons, and a minimum separation distance of 20 cm. is required between
the antenna and all public persons.
Antenna Installation
WARNING: It is installer’s responsibility to ensure that when using the authorized antennas in the United States (or where FCC rules apply); only those antennas certied with the product are used. The use of any antenna other than those certied with the product is expressly forbidden in accordance to FCC rules CFR47 part 15.204. The installer should congure the output power
level of antennas, according to country regulations and per antenna type. Professional installation is required of equipment with connectors to ensure compliance with health and safety issues.
Industry Canada Information
Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (e.i.r.p.) is not more than that necessary for successful communication.
This radio transmitter (identify the device by certication number, or model number if Category II) has been approved by Industry
Canada to operate with the antenna provided with the maximum permissible gain and required antenna impedance. Antenna types not included, having a gain greater than the maximum gain indicated for that type, are strictly prohibited for use with this device.
This device complies with Industry Canada Licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may
cause undesired operation of the device.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes : (1) l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l’appareil
doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.
Specications
Primary Power 8.5 VDC to 28.5 VDC Current Draw
Standby 100mA + 1.6mA per active zone Alarm 100mA + 10mA with Annunciator ON + 2mA per faulted zone
Form C Relay 35mA at 12/24 VDC Zones 5 VDC, 2mA max Dimensions 4.5” W x 2.75” H x 1.75” D
Compatibility
XR100/XR500 Series panels
800-641-4282
www.dmp.com
Made in the USA
Accessories
Proximity Readers
PP-6005B ProxPoint® Plus Proximity Reader MP-5365 MiniProx™ Proximity Reader PR-5455 ProxPro® II Proximity Reader MX-5375 MaxiProx® Proximity Reader TL-5395 ThinLine II® Proximity Reader
Proximity Credentials
1306P DMP Prox Patch 1306PW Prox Patch™ 1326 ProxCard II® Card 1346 ProxKey II® Access Device 1351 ProxPass®
1386 ISOProx II® Card
Listings and Approvals
FCC Part 15 ID: CCKPC0110 Industry Canada ID: 5251A-PC0110
INTRUSION • FIRE • ACCESS • NETWORKS
2500 North Partnership Boulevard
Springeld, Missouri 65803-8877
12055
LT-1213 © 2012 Digital Monitoring Products, Inc.
Loading...