
DUALCOMTM SERIES UNIVERSAL ALARM
LOAD RESET
ETHERNET
+DC- Z1 Z2 Z3 G +Z4- 01 02 T1 R1 T2 R2
Use 18-22 AWG for
power supply connection
CONTROL PANEL TIP
CONTROL PANEL RING
12/24 VDC Aux. Output +
-
Ground
Control Panel
The panel or separate power
supply must be listed for fire,
regulated, and power limited.
Telephone
Jack
Connector
BELL -
BELL +
CONTROL PANEL TIP
CONTROL PANEL RING
Telephone
Jack
Connector
NC (No Connection)
Switch
Connect the Ethernet within 20 ft and routed in
conduit to network equipment in the same room
(supervised, power limited).
+ DC -, T1 R1, and T2 R2 shall be connected
within 20 ft in the same room and routed in
conduit.
COMMUNICATOR
Compliance Listing Guide
BEFORE YOU BEGIN
This guide provides compliance information for the DualCom Series Universal Alarm Communicator. Read through the
contents of this guide before starting the installation process. It describes the functions along with available installation
options. Information contained in this guide allows you to learn the operation, functionality, and programming features of
the communicator to meet specific applications.
The DualCom Series Universal Alarm Communicator provides a fully supervised alarm communication path for
commercial fire control panels. This section applies to the following model:
• DualComNF Cellular Communicator with Network/LTE for Commercial Fire
PROGRAMMING REQUIREMENTS
Notice to users, installers, authorities that have jurisdiction, and other involved parties: This product incorporates
field-programmable software. In order for the product to comply with the requirements of a certificated installation,
certain programming features or options must be limited to specific values or not used at all as indicated below.
Program feature or option Standard Permitted? Possible settings Settings permitted
System Reports, RESTORAL ANSI/UL 864 Y NO, YES, DISARM YES, DISARM
Communication, CHECKIN MINUTES ANSI/UL 864 Y 3-240
Communication, FAILTIME MINUTES ANSI/UL 864 Y 3-240
3-238 (Dual Path)
3-58 (Single Path)
3-240 (Dual Path)
3-60 (Single Path)
COMMERCIAL FIRE INSTALLATION
CID Dialer Connection
Directly connect both tip and ring terminals from the control panel to the communicator. See Figure 1. This
connection captures Contact ID messages from any fire panel that are based on the SIA communication standard
DC-05-1999.09-DCS. Messages are then formatted into a Serial 3 message and sent to an SCS-1R Receiver or
SCS-VRReceiver.
Communication Failure
The phone line voltage on the second tip and ring will drop when DualComNF is in a communication failure state. This
triggers the host panel to annunciate a communication failure. When communications have restored on DualComNF,
voltage will be restored on the second tip and ring terminal, allowing the host panel to see a restoral on the phone line.
DIGITAL MONITORING PRODUCTS | DUALCOM SERIES COMPLIANCE LISTING GUIDE 1
Figure 1: Wiring Diagram for Tip and Ring Connection

ANSI/UL 864
For Future Use
# 6 Screws Included
with Backbox
Network Cable
Routing Locations
Fire Protective Signaling Systems using Internet/Intranet/Cell Networks
A Performance Based Technologies system as defined in UL 864 10th Edition may be configured as the following:
Network Primary and Cellular Backup Programming
Network Programming Cellular Programming
Comm Type = NET Comm Type = CELL
Checkin Min = 238 Checkin Min = 238
FailTime Min = 240 FailTime Min = 240
Cellular Primary with no Backup
Path 1 Programming
Comm Type = CELL Checkin Min = 58
Path Type = Primary FailTime Min = 60
Test Rpt = No Checkin = Yes
Network Primary with no Backup
Path 1 Programming
Comm Type = NET Checkin Min = 58
Path Type = Primary FailTime Min = 60
Test Rpt = No Checkin = Yes
Figure 2: Model 685-R Backbox Installation
Model 685-R Backbox Installation
For Commercial Fire applications using DualComNF and the included red plastic Model 685-R backbox, mount the
backbox to the wall with the 1” #6 screws included with the fire communicator. Mount the fire communicator to the
backbox with the 1/2” #6 screws. See Figure2. Locate the fire communicator within 20 feet of the control panel and
route all wire in conduit.
Refer to the DualCom Series Programming and Installation Guide (LT-1859) for communication test procedure.
For Remote Station, route supervisory and trouble messages to a separate receiver programmed in Receiver 2. See
Communication in LT-1859 for more information.
DUALCOM SERIES UNIVERSAL
ALARM COMMUNICATOR
Specifications
Primary Power Nominal 12 - 24VDC
Current Draw at 12VDC
Standby 75mA
Alarm 95mA Peak Cellular Communication
Current Draw at 24VDC
Standby 45mA
Alarm 85mA Peak Cellular Communication
Dimensions and Color
Housing Dimensions 5.5”W x 3.75”L x 1”H
Housing Color Red
Designed, engineered, and
manufactured in Springfield, MO
using U.S. and global components.
LT-1899 19164 1.01
Certifications
Cellular
FCC Part 15: XMR201707BG96
IC: 10224A-201709BG96
Underwriters Laboratories (UL) Listed
ANSI/UL 864 Fire Protective Signaling Systems
(CID Capture)
INTRUSION • FIRE • ACCESS • NETWORKS
2500 North Partnership Boulevard
Springfield, Missouri 65803-8877
800.641.4282 | DMP.com