DMP Electronics CellCom series, CellComSLC, CellComSLCZ, CellComSLCF, CellCom-LTE-V Compliance Listing Manual

...
CellComTM SERIES UNIVERSAL ALARM
Use 18-22 AWG for Power Supply connection
Control Panel Tip
Control Panel Ring
12VDC Aux. Output
+
-
Ground
Control Panel
The panel or separate power supply must be 12 Volt Regulated and Power Limited.
Telephone Jack Connector
Bell -
Bell +
RESET S1
LOAD S2
BAT
S
N
+12 G Z1 Z2 Z4-Z4+GZ3 RTO2O1
RB
J8
J26
J9
S1
S2
S3
MODEL CellComSLC
COMMUNICATOR
Compliance Listing Guide
BEFORE YOU BEGIN
This guide provides compliance information for the CellCom Series Universal Alarm Communicator. The CellCom‑LTE‑V Series Universal Alarm Communicator provides a fully supervised alarm communication path for any burglary, commercial fire, or residential fire control panel. DMP recommends that you read through the contents of this guide before starting the installation process. It describes the functions along with available installation options. Information contained in this guide allows you to learn the operation, functionality, and programming features of the communicator to meet specific applications. This guide covers all the requirements for installing the CellComSLCF and CellComF‑LTE‑V Universal Alarm Communicators for Commercial Fire installations. This document applies to the following models:
CellComSLC CDMA Cellular Communicator
CellComSLCZ CDMA Cellular Communicator with Z‑Wave
CellComSLCF CDMA Cellular Communicator for Commercial Fire
CellCom‑LTE‑V LTE Cellular Communicator
CellComZ‑LTE‑V LTE Cellular Communicator with Z‑Wave
CellComF‑LTE‑V LTE Cellular Communicator for Commercial Fire
PROGRAMMING REQUIREMENTS
System Programming Option Requirements
Notice to users, installers, authorities that have jurisdiction, and other involved parties: This product incorporates field‑programmable software. In order for the product to comply with the requirements of a certificated installation, certain programming features or options must be limited to specific values or not used at all as indicated below.
PROGRAM FEATURE OR OPTION STANDARD PERMITTED? POSSIBLE SETTINGS SETTINGS PERMITTED
System Reports, RESTORAL ANSI/UL 864 Y NO, YES, DISARM YES, DISARM
Communication, CHECKIN MINUTES ANSI/UL 864 Y 3‑250 3‑58
Output Options, COMM FAIL OUT ANSI/UL 864 Y 0, 1, 2 1, 2
APPLICATIONS
CID
Dialer Connection
Directly connect the tip and ring from the control panel to the communicator. See Figure 1. This connection captures Contact ID messages from any fire panel that are based on the SIA communication standard DC‑05‑1999.09‑DCS. Messages are then formatted into a Serial 3 message and sent to a DMP Model SCS‑1R Receiver or SCS‑VR Receiver.
Note: CID Dialer Connection cannot be used when using Zone 4 Bell Connection. Do not connect telephone company wires to the communicator. Remove any connected telephone company wires from the control panel.
Figure 1: CellCom Series Wiring Diagram for Tip and Ring Connection
COMPLIANCE
For Future Use
# 6 Screws Included
with Backbox
CellComSLCF and CellComF-LTE-V Commercial Fire Communicator Installation ANSI/UL 864
Fire Protective Signaling Systems using Internet/Intranet/Cell Networks
A Performance Based Technologies system as defined in UL 864 10th Edition may be configured as CELL Primary with or without a backup path. The system may be configured as the following:
Path 1 Type CELL Primary with no Backup
PATH 1 PROGRAMMING
Comm Type = CELL Checkin Min = 58 Path Type = Primary Failtime Min = 60 Test Rpt = No Checkin = Yes
Model 685-R Back Box Installation
For Commercial Fire applications using the CellComSLCF or the CellComF‑LTE‑V and the included red plastic Model 685‑R Back Box, mount the Back Box to the wall with the 1” #6 screws included with the fire communicator. Mount the fire communicator to the back box with the 1/2” #6 screws. See Figure 2. Locate the fire communicator within 20 feet of the control panel and route all wire in conduit.
CellComSLCF and CellComF-LTE-V for FACP Communication Fail Output
24VDC Applications:
For 24VDC applications using the fire communicator, connect a keypad using a Model 330‑24 4‑wire programming harness with in‑line resistor.
Output 1:
Output 1 must be programmed as a Comm Fail output in Output Options.
Installation Length:
Must be installed in conduit from the fire panel to the 685‑R conduit box and located within 20 feet.
FACP Zone Input:
Program FACP Zone Input to indicate a communication trouble locally.
Figure 2: Model 685-R Back Box Installation
S1
RESET
S2
LOAD
CellComSLCF/
CellComF-LTE-V
CellComF-LTE-V
J8
RB
Main Fire Alarm
Control Panel (FACP)
+DC G Z1 Z2 Z3 G Z4+ Z4- O1 O2 T R
J9
S3
+DC G Z1 Z2 Z3 G Z4+ Z4- O1 O2 T R
12/24VDC Aux Output
Ground
FACP Zone Input
{
FACP Zone Input
{
Use EOL specified
by FACP
Connect to terminal with lowest voltage
Output 1
2 CellCom SERIES COMPLIANCE LISTING GUIDE | DIGITAL MONITORING PRODUCTS
Figure 3: CellComSLCF and CellComF-LTE-V
Wiring Diagram for FACP
Loading...