DMP Electronics 734N Installation Manual

Page 1
Annunciator Outputs
INSTALLATION GUIDE
734N Wiegand Interface Module
Description
The 734N Wiegand Interface Module
Door Relay Wiegand Inputs
allows you to add IP network access control capability to XR100/XR500, XR150/ XR550, and XR150INT/XR550INT Series panels using proximity or mag-stripe card readers. The 734N provides a fast, safe and secure 10/100 Mbps connection to your local network for AES encrypted TCP communication with the control panel. It
Green
LED
Piezo
Reset Header
734N
Interface
Module
also allows fast verication of user codes
presented at the reader for door access.
Four input zones are provided to allow connection of nearby burglary devices.
Yellow
LED
Network
Connection
Green Power
LED
For local annunciation, a programmable speaker and a variety of switched ground annunciators are provided to connect
DC Input
sounders. In addition, he 734N provides LEDs to indicate door strike, Wiegand
Figure 1: 734N Wiegand Interface Module
inputs, and power to the module.
The 734N provides a keypad programming connection to use a standard DMP LCD keypad for initial network setup. Programming can be completed using the keypad or from the panel.
Zones
Red
Door Strike
LED
Yellow
Wiegand
LED
Mounting the 734N
The 734N ships installed in a decorative, high-impact plastic housing that mounts directly to walls, backboards, or other at surfaces. For easy installation, the 734N housing back and ends have wire entrances. The bottom contains multiple screw holes for mounting on single-gang switch boxes. It is recommended to mount the 734N near the protected door.
Magnetic Lock and Door Strike Wiring
Control door strikes and magnetic locks by using the Form C relay on the 734N module. Use an additional power supply to power door strikes and magnetic locks. Refer to Figures 2 and 3 for wiring information.
Normally Open
+
12/24VDC
Power
Supply
Model 333 Supressor
734N
Interface
Module
DC Input
+
Magnetic Lock
12/24VDC
Power
Supply
Normally Closed
Model 333 Supressor
734N
Interface
Module
DC Input
DC Door Strike
Figure 2: 734N Magnetic Lock Wiring
Figure 3: 734N Door Strike Wiring
Page 2
Network Connection
734N
Interface
Module
Model 333 Supressor
Model 333 Suppressor
Wire the Suppressor to the Common and Normally Open or Normally Closed depending upon which terminals are used for the device.
Connect an IP network cable from the LAN/WAN connection to the 734N Network connector. The 734N communicates
AES encrypted TCP with panels with Network installed.
Two LED's are located on the ethernet jack.
• The green LED indicates data sent to the panel.
• The yellow LED indicates the speed of the transmission. A solid yellow LED indicates the network is connected
at 100 Base-T. A ashing yellow LED indicates the network is connected at 10 Base-T.
NO/C/NC (Dry Contact Relay)
The 734N provides a Form C (SPDT) relay for controlling door strikes or magnetic locks. The three relay terminals marked NO C NC allow you to connect the device wiring to the relay for module control. See Figures 2 and 3 for proper door strike and magnetic lock wiring.
The Form C relay draws up to 35mA of current and contacts are rated for 10 Amps (resistive) at 12/24VDC. When connecting multiple locks to the Form C relay, the total current for all locks cannot exceed 10 Amps. If the total current for all locks exceeds 10 Amps, problems may arise and an isolation relay may be needed.
See the Isolation Relay section for information.
Install the 333 Suppressor
One Model 333 Suppressor is included with the 734N module. Install the suppressor across the 734N Common (C) and Normally Open (NO) or Normally Closed (NC) terminals. If the device being controlled by the relay is connected to the NO and C terminals, install the suppressor on the NO and C terminals. Conversely, if the device is connected to the NC and C
Figure 4: Model 333 Installation on the 734N Module
terminals, install the 333 Suppressor on NC and C terminals. The suppressor wire is non-polarized. Install the suppressor as shown in Figure 4.
Isolation Relay
The Form C Relay can control a device that draws less than 10 Amps of current. If a device draws more than 10 Amp of current, or the sum of all devices controlled by the Form C Relay exceeds 10 Amps, an isolation relay must be used. Refer to Figures 5 and 6 for isolation relay wiring.
Normally Open
Model 333 Supressor
Normally
Closed
12/24VDC
Power
Supply
Isolation Relay
NCCNO
Figure 5: Isolation Relay with Magnetic Lock Figure 6: Isolation Relay with Door Strike
Digital Monitoring Products 734N Installation Guide
2
+
Magnetic Lock
+
Model 333 Supressor
12/24VDC
Power
Supply
Normally Open
Normally
Open
Isolation Relay
+
NCCNO
DC Door Strike
+
Page 3
Connection to Reader
Figure 7 shows a reader with wire colors red, white, green, and black. The wire colors may be different for the reader being installed. Connect the reader wires to terminals 1, 2, 3, and 4. As shown in Figure 7, the green wire carries D0, or Data Zero, and the white wire carries
12/24VDC
Card Reader
Black
Green (Data 0)
White (Data 1)
Red
Shield
D1, or Data One. The red wire carries 12/24VDC, 200mA power limited output and the black wire is ground.
Status LEDs
The 734N provides three status LEDs and two ethernet LEDs. See Figure 1 for locations of the LEDs.
• The red LED turns on for the duration of the door strike.
• The yellow LED turns on for one second to indicate a Wiegand read.
• The green LED is constant to indicate power.
Figure 7: Card Reader Wiring
734N Interface Module
Zone Terminals
Terminals 5-11 connect grounded zones 1 through 3. These zones have
a grounded side and cannot be used for re-initiating devices. Zones
2 and 3 can also be used for access control with Zone 2 providing a bypass option and Zone 3 providing Request to Exit functionality. Zone 4 terminals provide a non-powered Class B, Style A zone. Use the supplied, DMP Model 311 1K Ohm End-of-Line resistors on each zone. Refer to the
panel programming guide for programming instructions.
Zone # Recommended Device Residential Fire Devices?
1 Any burglary device No 2 Door Contact No 3 REX (PIR or Button) No 4 Any device Yes
734N Interface Module
Figure 8: 734N Zone Terminals
Note: Use 1K Ohm EOL for each zone.
Zone 1
Zone 2
Zone 3
Zone 4
Annunciator Header
The 4-pin header located on the far right of the circuit board is used to wire the Armed Status, Remote Annunciation, and the Remote LED Control 30VDC. Connect a Model 300 4-wire harness to the 4-pin header for connection of the following indicators:
--
AS (Armed Status)
Armed Status provides an unsupervised switched ground for a visual or audible armed status indicator that turns on when the burglary areas are armed, such as SYSTEM ON or ALL SYSTEM ON. Connect the wire from the 4-wire harness to an Armed Status output.
--RA (Remote Annunciation)
Remote Annunciation provides an unsupervised switched ground for a remote annunciator that turns on when the 734N on-board piezo turns on. the wire from the 4-wire harness to a annunciator silences when the RA restores. The remote annunciator (RA) switched ground operates even if the speaker is programmed not to operate.
--LC (Remote LED Control)
Remote LED Control provides an unsupervised switched ground for a visual indicator that turns on when the 734N relay activates. Connect the wire from the 4-wire harness to an LED. The LED turns on for the duration the door strike relay is on. HID readers optionally provide a connection for LED reader control.
. The open collectors supply a ground for a maximum current of 50mA
Remote LED Control Remote Audible Annunciator Armed Status Output
Connect
remote annunciator. The remote
Figure 9: 734N Annunciator Outputs
Output 2
Output 1
@
Auxiliary Outputs 1 & 2
The 734N controls Auxiliary Outputs 1 and 2 when the Activate Zone 2 Bypass programming option is enabled and the Zone 2 Bypass Time is set. When the door contact (Zone 2) is opened while the door strike is activated, the Zone 2 Bypass Time starts. If the door has not closed at the end of the timer, Aux Output 1 is turned on and the timer starts again. If the door is still open at the end of the second timer, Aux Output 2 is turned on. Aux Outputs 1 and 2 turn off when the door contact is closed. Use the Model 431 Relay Harness for connection of Output 1 and Output 2 as shown in Table 1.
734N Installation Guide Digital Monitoring Products
Form C Relays (J2)
Output Color Code–Model 431 Harness Output 2 N/O Orange/White Output 2 Com White/Gray Output 2 N/C Violet/White Output 1 N/O Orange Output 1 Com Gray Output 1 N/C Violet
Table 1: Harness Wiring
3
Page 4
Reset Header
The reset header is located just above and to the right of the network connector (see Figure 1) and is used to reset the
734N module. To reset the module when rst installing the system, short the two pins on the reset header before applying
power to the module. To reset the module while the system is operational, short the two pins on the reset header for one or two seconds without
powering down the system.
Addressing the 734N
Keypad Bus Addresses
DMP XR550 Series panels use keypad bus addresses 2 through 16. XR150 Series panels can only use keypad bus addresses 2 through 8. Address 1 is reserved for hardwired keypads on both XR150 and XR550 Series panels. Each keypad bus address can accommodate 1 door output and 4 expansion zones. The 734N operates using addresses 2-16, with address 1 being reserved for panel keypad operation. A 734N with an address of 2 on the keypad bus would represent Door 2 and zones 21-
24. A 734N with a keypad address of 14 would represent Door 14 and zones 141-144.
AX-Bus Addresses (XR550 only)
DMP XR550 panels are capable of access control expansion using any of the ve AX/LX-Bus headers (AX/LX500, 600, 700,
800, and 900). An AX-Bus address can accommodate 1 door output and 1 expansion zone. Because the 734N has a built-in 4-zone expander, 3 extra zones must be mapped to the 734. A 734N with an address of 501 on AX500 would represent Door 501 and zones 501-504. A 734N with an address of 505 on AX500 would represent Door 505 and zones 505-508. A 734N with an address of 701 on AX700 would represent Door 701 and zones 701-704.
Note: Hardwired zone expanders and addressable points and modules do not communicate on an AX-Bus. AX-Bus doors do not have programmable device or communication types and do not have assignable display areas.
Setting the 734N Addresses
To set the 734N address, refer to Table 2.
Only valid door numbers can be assigned to 734Ns in device setup. For complete keypad and AX-Bus address mapping, see the chart below.
Table 2: Device Addresses and 734N Zone Numbers
Device/
Door
2 21-24 505 505-508 605 605-608 705 705-708 805 805-808 905 905-908
3 31-34 509 509-512 609 609-612 709 709-712 809 809-812 909 909-512
4 41-44 513 513-516 613 613-616 713 713-716 813 813-816 913 913-916
5 51-54 517 517-520 617 617-620 717 717-720 817 817-820 917 917-920
6 61-64 521 521-524 621 621-624 721 721-724 821 821-824 921 921-924
7 71-74 525 525-528 625 625-628 725 725-728 825 825-828 925 925-928
8 81-84 529 529-532 629 629-632 729 729-732 829 829-832 929 929-932
9 91-94 533 533-536 633 633-636 733 733-736 833 833-836 933 933-936
10 101-104 537 537-540 637 637-640 737 737-740 837 837-840 937 937-940
11 111-114 541 541-544 641 641-644 741 741-744 841 841-844 941 941-944
12 121-124 545 545-548 645 645-648 745 745-748 845 845-848 945 945-948
13 131-134 549 549-552 649 649-652 749 749-752 849 849-852 949 949-952
14 141-144 553 553-556 653 653-656 753 753-756 853 853-856 953 953-956
15 151-154 557 557-560 657 657-660 757 757-760 857 857-860 957 957-960
16 161-164 561 561-564 661 661-664 761 761-764 861 861-864 961 961-964
Zones
Device/
Door
501 501-504 601 601-604 701 701-704 801 801-804 901 901-904
Zones
Device/
Door
Zones
Device/
Door
Zones
Device/
Door
Zones
Device/
Door
Note: The 734N is a supervised module and cannot operate in unsupervised mode.
Zones
Digital Monitoring Products 734N Installation Guide
4
Page 5
PROG (Programming)
To program a 734N you must complete the programming process in two places: the panel and the 734N. First, refer to the Network Options and Device Setup sections of the XR150/XR550 Series Programming Guide (LT-1232) to set up the device in the panel. Then, step through the programming directions below to program the 734N.
The rst time a 734N is programmed, you must use a 32-character keypad connected directly to the 734N and set to
address one. For 12 Volt applications, connect the keypad to the module using a Model 330 4-wire harness. For 24 Volt applications, connect the keypad to the module using a 330-24 4-wire programming harness with an in-line resistor. While in programming mode, no 734N communication with the panel can occur.
Caution: Do not connect a keypad using a Model 330 harness if you are using a 24 volt power supply! Damage to the keypad could occur.
Note: Before programming the 734N, obtain the Service Set Identication (SSID), the Wireless Security Type, and the
Wireless Network Key from the router or a network administrator.
VER 101 02/01/17
date display.
734N ZONE: 1 -OKAY
734N DOOR ZONE: 2 -OPEN
zone number followed by the CMD key.
734N
734N REX
ZONE: 3 -SHORT
MENU? NO YES
return to Version Display.
CONNECT STATUS
CONNECT STATUS NOT CONNECTED
CONNECT STATUS
programmed in the panel.
BAD PASSPHRASE
CONNECT STATUS
Device Number in the panel.
DEVICE NOT PROG
Duplicate Device: There is another device on the network with the same device number.
CONNECT STATUS
Transmit Time XXX: The speed in milliseconds in which the last message was sent and received
DUPLICATE DEVICE
between the 734N and the panel.
CONNECT STATUS XMIT TIME xxx mS
Press the CMD key to enter programming and display initialization options. Initialization Options
in preparation for programming. Press any select key to enter the initialization menu.
Initialization Communications
INITIALIZATION COMMS? NO YES
Select YES to initialize the communication options back to factory defaults. Select NO to
leave communication options unchanged.
INITIALIZATION
Initialize Conrm Option
SURE? YES NO
for conrmation to clear the memory. This is a safeguard against accidentally erasing the
programming. No memory is cleared from the programming until you answer YES to the SURE? option. Selecting NO leaves communication options unchanged.
Initialization Access
INITIALIZATION
Select YES to initialize the Access Options back to factory defaults. Select NO to return to
ACCESS? NO YES
the INITIALIZATION menu.
734N
PROGRAMMER
734N
INITIALIZATION
Version Display
When you connect the keypad to the 734N module, the version number and release
• Press keys 1, 2, 3, or 4 then the CMD key to show zone status of that zone.
• Press CMD key to enter the Diagnostic Menu.
• Press 6653 (PROG) then CMD to enter the Programming Menu.
Zone Status Display
The status of the entered zone number displays. To display another zone, enter the
Diagnostic Menu
Select YES to display the Panel Communication Connect Status display. Select NO to
Connect Status
To display the connection status of the 734N to the panel, select any top row key.
Not Connected: The 734N cannot connect to the panel on the network. Bad Passphrase: The passphrase programmed in the 734N device does not match the passphrase
Device Not Programmed: The device number programmed in the 734N is not programmed as a
Programming Menu
These options can set the 734N module programming memory back to factory defaults
After selecting YES to clear the Communication settings, the 734N displays SURE? YES NO
734N Installation Guide Digital Monitoring Products
5
Page 6
INITIALIZATION SURE? YES NO
conrmation to clear the memory. This is a safeguard against accidentally erasing the
programming. No memory is cleared from the programming until you answer YES to the SURE? option. Selecting NO
734N
Press any select key to enter the Communication menu. Press the CMD key to advance to
COMMUNICATION
the Access Options menu. Press the back arrow to display the 734N Initialization menu.
734N DEVICE NO:
Enter a device number from 2-16 for the 734N. The device number must also be
7
programmed as a device in the panel. Default is 7.
734N DHCP? NO YES
Select YES (fourth select key) to use dynamic IP address information for the 734N IP
Address, Subnet Mask, and Gateway Address. Select NO (third select key) to enter static IP information.
734N IP ADDRESS:
192.168.0.201
SUBNET MASK:
Enter the local subnet mask assigned to the 734N. Default is 255.255.255.0
255.255.255.0
GATEWAY ADDRESS:
Enter the local gateway address of the 734N. Default is 192.168.0.1
192.168.0.1
PANEL IP ADDR:
Enter the IP address of the panel. Default is 0.0.0.0.
0.0.0.0
Address option in Network Options. The DHCP programming in the panel must be set to NO.
PANEL IP PORT:
Enter the port number that the 734N uses to send communication to the panel. This must
2002
be the same port that is programmed in 734N Listen Port in Network Options programming of the panel.
Note: The Panel IP Port cannot be the same as the panel network programming port.
734N PASSPHRASE
Enter an 8 to 16-character alphanumeric Passphrase to encrypt communication with the
panel. The 734N Passphrase must match the 734N Passphrase entered in Network Options programming of the panel. The Passphrase is blank by default.
734N
Press any select key to enter the Access Options menu. Press the CMD key to advance to the
ACCESS OPTIONS
Stop option. Press the back arrow to display the Communication menu.
ACTIVATE ZONE 2
Select YES to activate the Zone 2 Bypass operation. Selecting NO allows standard zone
BYPASS? NO YES
operation on Zone. Default setting is NO. protected (contact installed), you can provide a programmable bypass entry/exit timer by connecting its contact wiring to the 734N module Zone 2. When the on-board Form C relay activates and the user opens the door connected to Zone 2, the zone fault is delayed for the number of seconds programmed in ZONE 2 BYPASS TIME allowing the user to enter/exit during an armed period.
If Zone 2 does not restore (door closed) within the programmed time, the piezo sounds every other second during the last ten seconds. If Zone 2 restores prior to the end of the programmed time, the piezo silences. If the zone does not restore before the programmed time, the 734N ends the bypass and indicates the open or short zone condition to the panel.
ZONE 2 BYPASS TIME: 40
Enter the number of seconds to elapse before the Bypass Timer expires. Range is from 20
to 250 seconds. Press any top row select key to enter the number of seconds. If the door remains open when the timer expires a zone open/short is sent to the panel for Zone 2. The default is 40 seconds. Figure 10 shows how the Bypass option works.
Initialize Conrm Option
After selecting YES to clear the Access Options, the 734N displays SURE? YES NO for
leaves communication options unchanged.
Communication Menu
734N Device Number
734N DHCP
734N IP Address
Enter the static IP address of the 734N if the DHCP is set to NO. Default is 192.168.0.201.
Subnet Mask
Gateway Address
Panel IP Address
Note: This IP address must match the address programmed in the panel at the Local IP
Panel IP Port
734N Passphrase
Note: A passphrase is required for communication to occur with the panel.
Access Options
Activate Zone 2 Bypass
If the door being released by the 734N module is
Zone 2 Bypass Time
Digital Monitoring Products 734N Installation Guide
6
Page 7
01110101101101010001100111
5 Second
Strike
40
Seconds
10 seconds before the bypass time expires, the device beeps if the door is still open.
40-Second Zone 2 Bypass entry/exit timer.
End of timer.
A zone open/short is indicated if the door remains open.
Figure 10: Zone 2 Bypass Timeline using default time
RELOCK ON ZONE 2
Selecting YES turns the relay off when Zone 2 returns to normal during the bypass. Selecting
CHANGE? NO YES
NO leaves the relay on when Zone 2 faults to an open or short condition during bypass. Turning off the relay at Door Closed allows a long strike time to be automatically ended and relocks the door. The default is NO.
ACTIVATE ZONE 3 REX? NO YES
Selecting NO allows standard zone operation on Zone 3. Default setting is NO. Connect a PIR (or other motion sensing device) or a mechanical switch to Zone 3 to provide REX capability to the system. When Zone 3 shorts, the on-board Form C relay activates for the programmed number of seconds (see Zone 3 REX Strike Time). During this time, the user can open the protected door to start the programmed Zone 2 Bypass entry/exit timer. After the programmed number of seconds, the relay restores the door to its locked state. The 734N module provides a bypass-only option for REX on Zone 3. When Zone 3 OPENS from a NORMAL state, only a bypass occurs: the on-board relay does not activate. This
bypass-only option uses two methods of REX. The rst REX device provides the programmed
bypass entry/exit timer. The second REX, or manual device such as a door knob, unlocks the door.
An example of the shunt-only conguration is a door to an ofce that is locked 24 hours
a day. Users pass a REX motion detector positioned by the door to begin the programmed exit timer. Within the programmed number of seconds the user must then manually activate a second device, such as a REX device or manual door knob, to unlock the door. If the door is opened after the programmed number of seconds, an open condition is indicated to the panel.
ZN 3 REX STRIKE
Enter the number of REX seconds to elapse. Range is from 5 to 250 seconds. Press any
TIME: 5
select key to enter the number of seconds. The default is 5 seconds.
ACTIVATE ONBOARD SPEAKER? NO YES
annunciations. Select NO to turn the speaker off for all operations. This does not affect remote annunciator open collector (RA) operation. The default is NO.
Card Options
CARD OPTIONS:
DMP
CARD OPTIONS: DMP CUSTOM ANY
Note: When set to DMP, the 734N converts 17 bits of the 26 to 45-bit data string into a 5-digit number.
Relock on Zone 2 Change?
Activate Zone 3 Request to Exit
Selecting YES activates the Zone 3 Request to Exit (REX) option.
Zone 3 REX Strike Time
Activate Onboard Speaker
Select YES to enable the onboard speaker for local annunciation, such as alarm and trouble
Typically, an access card contains data bits for a site code, a user code, and start/stop/
parity bits. The starting position location and code length must be determined and programmed into the 734N Module. Select DMP to indicate the reader sends a 26-45 bit data
string. To select the DMP option, press the rst Select key under DMP. Default is DMP.
Select CUSTOM if using a non-DMP card with a user code length of 4 to 12 digits. Select ANY to allow all card reads to activate the door strike relay. The door strike relay is activated for the length of time programmed in ZN 3 REX TIME. No user code information is sent to the panel.
First Bit
Received
Position = 1
Figure 11: HID 26-bit Wiegand Data Stream Bit Location
734N Installation Guide Digital Monitoring Products
Site Code
Position = 2
Length = 8
In this example the Wiegand Code Length = 26 bits.
User Code Position = 9 Length = 16
Last Bit
Received
Position = 26
7
Page 8
Custom Card Denitions Wiegand Code Length
WIEGAND CODE
When using a custom product, enter the total number of bits to be received in Wiegand
LENGTH: 26
code including parity bits. Press any top row Select key to enter a number between 1-255 to equal the number of bits. Default is 26 bits.
SITE CODE POSITION: 1
between 0-255. Default is 1. Press the CMD key to save the entry.
SITE CODE LENGTH: 8
1-16. Default is 8. Press the CMD key to save the entry.
USER CODE
Dene the User Code start bit position. Press any Select Key to enter a number between
POSITION: 9
0-255. Default is 9. Press the CMD key to save the entry.
USER CODE
Dene the total number of User Code bits used. Press any Select Key to enter a number
LENGTH: 16
between 1-255. The default is 16.
REQUIRE SITE
Press the top row Select key under YES to use a site code and press the CMD key to
CODE: NO YES
view the site code entry display. In addition to User Code verication, door access is only
granted when any one site code programmed at the SITE CODE ENTRY option matches the site code received in the Wiegand string.
Site Code Display
SITE CODE 1: (1 - 65,535) 127
SITE CODE 2:
To change the site code, press a select key, then enter the new code. Press the CMD
(1 - 65,535) -
key to save and to display the next site code. Site Codes 2-8 default to blank.
SITE CODE 8:
Site Code Position
Enter the site code start position in the data string. Press any Select Key to enter a number
Site Code Length
Enter the number of Site Code bits used.
Press any Select Key to enter a number between
User Code Position
User Code Length
Require Site Code
You can program up to eight ve-digit site codes. Site code range is 1-65535.
SITE CODE 1 displays rst. Any previously programmed site code displays. Default is 127.
(1 - 65,535) ­NO. OF USER CODE
DIGITS: 5
Select key to enter a user code digit length between 3-12 digits. This number must match the user code number length being programmed in the panel. Default is 5. All bits are read and converted into a decimal number string. The number string is left padded with '0' if needed for long user code lengths. When selecting '4' the right digit is dropped and the next four sent. Example: # decoded 1234567 10 digits 0001234567
No Communication with Panel
NO COMM WITH PNL
This option denes the relay action when communication with the panel has not occurred
OFF
for approximately ten seconds. Default is OFF. Press any top row Select key to change the default relay action. Choose the action required when the 734N cannot establish communication with the panel:
NO COMM WITH PNL OFF SITE ANY ON
If communication is lost during a door strike, relay remains on for the door strike duration, but turns off at the end of the door strike timer. Press the second Select key to choose SITE (Accept Site Code) — Door access is granted when the Wiegand site code string received matches any site code programmed at SITE CODE 1-8. For details refer back to the REQUIRE SITE CODE option. Press the third Select key to choose ANY (Any Wiegand Read) — Door access is granted when any Wiegand string is received. Press the fourth Select key to choose ON (Relay Always On) — The relay is always on. Press the CMD key to display the next action. Press the rst Select key to choose LAST (Keep Last State) — The relay remains in the same
NO COMM WITH PNL
state and does not change when communication is lost. If communication is lost during a
LAST
door strike, the relay remains on for the door strike duration, but then returns to it's last state prior to doing the door strike.
734N
Press any select key to start the stop routine. When programming in complete, the Version
displays and the keypad can now be removed.
STOP
Number of User Code Digits
The 734N module recognizes user codes from one to ten digits in length. Press any top row
5 digits 34567 4 digits 3456
Press the rst Select key to choose OFF (Relay Always Off) — The relay does not turn on when any Wiegand string is received. OFF does not affect any REX operation.
Stop
Digital Monitoring Products 734N Installation Guide
8
Page 9
734N Network Specications
The 734N was designed to have minimum impact on network performance. The 734N is supervised in the panel by
exchanging two data packets every ve seconds. The payload of the data packets exchanged between the XR100/XR500, XR150/XR350/XR550 or the XR150INT/XR350INT/XR550INT Series and the 734N is a very small 18 bytes. The total trafc for
all supervision, including network overhead, is roughly two kilobytes per minute per 734N. This would be equivalent to a very small e-mail message.
If required, all of the trafc between the 734N(s) and the panel can be completely isolated from the rest of the existing
network by connecting all of the 734N modules and the panel to the same switch, then connecting the switch to the
remainder of the network. All trafc between the 734N and the panel would then be conned to the switch where they are
connected, while still allowing the panel to communicate with the central station through the normal network.
The security of the 734N is multi-faceted. Most importantly, the 734N is a single purpose network device. What this means is that all of the ports in the TCP/IP stack used in the 734N are disabled and allow no inbound connections. This prevents a potential intruder from making any type of connection with the 734N through the network. The 734N communicates with the control panel by establishing an outbound only connection to the panel. All communication between the 734N and the control panel is encrypted using 128-bit AES encryption. This is the same encryption standard approved and used by the U.S. government, including the National Security Agency for encrypting Secret information.
Packet Communication Outline:
• The 734N module establishes panel communication using the TCP/IP protocol.
At start up, the 734N opens a TCP/IP connection that remains open indenitely.
• The socket can be closed by the 734N or panel after a time-out.
• The connection is re-established by the 734N after the time-out.
• A pair of supervision packets are sent every 5 seconds.
- The payload for each packet is 18 bytes and the total trafc, including overhead, is approximately 2 kilobytes
per minute for each 734N.
- Non-Supervision messages have a payload range of 18-50 bytes.
Compliance Listing Specications
UL Access Control
The access relay must be congured as fail-safe or fail-secure as determined by the local Authority Having Jurisdiction (AHJ). This system is not intended to be used in place of listed panic hardware.
The power supply must be a listed commercial burglary/household re, power limited, Class 2 with a compatible voltage
range for the product. The 734N requires a listed 12 or 24VDC power source.
ULC Commercial Burglary (XR100/XR500 and XR150/XR350/XR550 Series Panels)
When using the zones of the 734N in a listed application, place the module in a listed enclosure and connect a DMP Model 307 Clip-on Tamper Switch to the enclosure programmed as a 24-Hour zone.
The 734N Access Control features have not been investigated by ULC.
The 734N zones can be used in a Low Risk application. For Medium or High Risk applications, refer to the Dual Zone Protection diagram in the XR100/XR500 or XR150/XR350/XR550 Canadian installation guides.
734N Installation Guide Digital Monitoring Products
9
Page 10
Specications
Primary Power 8.5VDC to 28.5VDC Current Draw
Standby 346mA (Includes 200mA for Proximity Reader) + 1.6mA per active zone Alarm 348mA (Includes 200mA for Proximity Reader)
+ 10mA with Annunciator ON
+ 2mA per faulted zone
Form C Relay 35mA at 12/24VDC Zones 5VDC, 2mA max Dimensions 4.5” W x 2.75” H x 1.75” D Weight 8 oz .23 Kg
Compatibility
XR150/XR550 Series panels XR150INT/XR550INT Series panels
Accessories
Proximity Readers
PP-6005B ProxPoint® Plus Proximity Reader
MP-5365 MiniProx™ Proximity Reader
PR-5455 ProxPro® II Proximity Reader
MX-5375 MaxiProx® Proximity Reader
TL-5395 ThinLine II® Proximity Reader Proximity Credentials
1306P DMP Prox Patch
1306PW Prox Patch™
1326 ProxCard II® Card
1346 ProxKey III® Access Device
1351 ProxPass®
1386 ISOProx II® Card
Certications
FCC Part 15 California State Fire Marshall (CSFM)
NIST AES Algorithm Certicate #1937
ANSI/UL 294 Access Control System Units ANSI/UL 1610 Central-Station Burglar-Alarm Units ANSI/UL 609 Local Burglar Alarm Units And Systems ANSI/UL 1076 Proprietary Burglar Alarm Units And
Systems ANSI/UL 1023 Household Burglar-Alarm System Units ULC S304 Central And Monitoring Station Burglar
Alarm ULC C1076 Proprietary Burglar Alarm Units And
Systems ULC C1023 Household Burglar Alarm System Units
International Certications
Security Grade: 3 Environmental Class: II Intertek (ETL)
EN 50130-4 EMC Product Family Standard: Immunity Requirements for Componenets of Fire, Intruder and Social Alarm Systems
EN 50130-5 Environmental Standards EN 50131-1:2006+A1 Intrusion and Hold-up Systems EN 50131-3:2009 Control and Indicating Equipment EN 50133-1:1997 Access Control Systems EN 61000-3-2 Limits - Limits for Harmonic Current Emissions (Equip.Input Current up to and including 16 A per Phase) Includes
A1 & A2 July 1, 2009
EN 61000-3-3 Limitations of Voltage Fluctuations & Flicker in Low-Voltage Supply Systems for Equip. with Rated Current Less Than or Equal to 16 A per Phase & Not Subject to Conditional Connection EN 61000-6-4 Generic Standards - Emissions Standard for Industiral Environments
Export Control
The 734N uses AES encryption and any export beyond
the United States must be in accordance with Export Administration Regulations.
17072
800-641-4282
www.dmp.com 2500 North Partnership Boulevard
Designed, Engineered and
Assembled in U.S.A.
INTRUSION • FIRE • ACCESS • NETWORKS
Springeld, Missouri 65803-8877
LT-1197 1.03 © 2017 Digital Monitoring Products, Inc.
Loading...