The 1168 Wireless Smoke/CO/Low Temp Detector features multi-criteria smoke sensing
using a combination of photoelectric, heat, IR flame flicker, and carbon monoxide
indicators. The 1168 reports fire, CO, and low temp alarms to the control panel. Use the
onboard wireless transmitter to connect the 1168 with DMP1100Series Wireless Receivers.
INDICATOR LEDS
The 1168 has a multi-color top LED that
indicates the state of the device:
• GREEN—Supervisory indication; blinks
during power on, reset, and during
normal operation
• AMBER—Signal maintenance and
trouble events
• RED—Alarm (Smoke/CO/Low Temp)
Indicator lights on the side alarms (initiating
detector only):
• RED—Smoke
• BLUE—CO
POWER SUPPLY
The 1168 is powered by four 3.0V lithium
batteries. Battery life expectancy for the
unit is at least three years under normal
conditions.
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide1
VOICE ANNUNCIATION
The 1168 audibly announces alarm and
maintenance requirements, enhancing
occupant understanding and evacuation.
TAMPER MAGNET
The 1168 features a tamper magnet which
sends a trouble message to the panel if the
detector is removed from the mounting
base.
CADENCE SYNCHRONIZATION
The 1168 provides cadence synchronization
with other 1168 or 1164 units on the system.
LOW TEMP SENSOR
The 1168 includes a low temperature
sensor that causes an alarm when inside
temperature falls below 41°F (5°C).
1168 FEATURES
CO Test ButtonSmoke Test Button
Indicator
Lights
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 2
CO Entry
Port
Figure 1: 1168 Features
Indicator
LED
IR Flame
Detector
Indicator
Lights
PROGRAM THE 1168
When programming an 1168 Wireless Smoke/CO/Low Temp Detector, refer to the
appropriate panel programming guide as needed.
PROGRAMMER
ZONE INFORMATION
ZONE NO:
* UNUSED *
ZONE TYPE
FI PN EM SV
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide3
PROGRAMMER MENU
Enter 6653 (PROG) at the keypad to enter the PROGRAMMER
menu.
ZONE INFORMATION
Press CMD until ZONE INFORMATION displays. Press a select
key or area to enter the menu.
ZONE NUMBER
Enter the zone number. Press CMD.
Note: The 1168 takes up to three zone numbers (Smoke,
CO, Temp). The zone numbers must be consecutive.
ZONE NAME
Denote the zone name as a fire zone. Press CMD.
ZONE TYPE
Press any select area. Press CMD to move to the next set of
menu options. Select FI (fire) as the ZONE TYPE.
FIRE BEL OUT: 0
FIRE BELL OUT
Default is 0. Press CMD.
NEXT ZONE? NO YES
WIRELESS? YES
TRANSMITTER
SERIAL #: -
CONTACT: FIRE
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 4
NEXT ZONE
At the NEXTZONE? prompt, select NO.
WIRELESS
At the WIRELESS? prompt, select YES.
Note: If you are programming the 1168 onto a zone that
can be either hardwired or wireless, then this prompt
appears. If the zone you are programming is wireless-only,
then the prompt does not appear.
SERIAL NUMBER
Enter the eight-digit SERIAL #: - found on the device and press
CMD.
CONTACT TYPE
Enter the CONTACT type as FIRE and press CMD.
SUPVSN TIME: 240
SUPERVISION TIME
Enter the SUPVSN TIME, and press CMD.
NEXT ZN? YES
ZONE NO:
* UNUSED *
ZONE TYPE
CO IN
FIRE BEL OUT: 0
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide5
NEXT ZONE
At the NEXT ZONE? prompt, select YES.
ZONE NUMBER
Enter the zone number. This number must be consecutive
with the previous zone. For example, if 500 was entered for
Fire,501 should be entered here. Press CMD.
ZONE NAME
Denote the zone name as a carbon monoxide (CO) zone. Press
CMD.
ZONE TYPE
Press any select area. Press CMD three times to move to the
last set of menu options. Select CO (carbon monoxide) as the
ZONETYPE.
FIRE BELL OUT
Default is 0. Press CMD.
NEXT ZONE? NO YES
NEXT ZONE
At the NEXTZONE? prompt, select NO.
WIRELESS? YES
TRANSMITTER
SERIAL #: -
CONTACT: CO
SUPVSN TIME: 240
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 6
WIRELESS
At the WIRELESS? prompt, select YES.
Note: If you are programming the 1168 onto a zone that
can be either hardwired or wireless, then this prompt
appears. If the zone you are programming is wireless-only,
then the prompt does not appear.
SERIAL NUMBER
Enter the eight-digit SERIAL #: - found on the device and press
CMD.
CONTACT TYPE
Enter the CONTACT type as CO and press CMD.
SUPERVISION TIME
Enter the SUPVSN TIME, and press CMD.
NEXT ZN? YES
NEXT ZONE
At the NEXT ZONE?, prompt, select YES.
ZONE NO:
ZONE NAME:
ZONE TYPE
FI PN EM SV
FIRE BEL OUT: 0
NEXT ZONE? NO YES
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide7
ZONE NUMBER
Enter the zone number. This number must be consecutive with
the previous zones. For example, if 51 was entered for Fire and
52 was entered for CO, 53 should be entered here. Press CMD.
ZONE NAME
Denote the zone name as a temperature (TEMP) zone. Press
CMD.
ZONE TYPE
Press any select area. Press CMD to move to the next set of
menu options. Select SV as the ZONETYPE.
FIRE BELL OUT
Default is 0. Press CMD.
NEXT ZONE
At the NEXTZONE? prompt, select NO.
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.