DMP Electronics 1168 Installation And Programming Manual

1168 Wireless Smoke/CO/Low
Temp Detector
INSTALLATION AND PROGRAMMING GUIDE
TABLE OF CONTENTS
About the 1168 ............................... 1
Indicator LEDs................................................. 1
Power Supply .................................................. 1
Voice Annunciation ....................................... 1
Tamper Magnet ............................................... 1
Cadence Synchronization ......................... 1
Low Temp Sensor .......................................... 1
1168 Features ..................................2
Program the 1168 ...........................3
Install the 1168 .............................. 11
Mount the Base ...............................................11
Install the Battery ......................................... 12
Replace the Cover ....................................... 12
Mounting Guidelines ....................13
Authority Having Jurisdiction .................. 14
Locations to Avoid ....................................... 15
Commercial .................................................... 16
Multi-Family ....................................................16
Test the 1168 ..................................17
Smoke Test ...................................................... 17
CO Test.............................................................. 17
Additional Information ................21
Reset the Language Selection ................. 21
Supervision Message ................................... 21
Inspection Testing and Maintenance ..... 21
Replace The Batteries .................................22
NFPA 72 Guidelines .....................................23
Compliance Specifications ........28
FCC Information ..........................30
Industry Canada Information ......31

ABOUT THE 1168

The 1168 Wireless Smoke/CO/Low Temp Detector features multi-criteria smoke sensing using a combination of photoelectric, heat, IR flame flicker, and carbon monoxide indicators. The 1168 reports fire, CO, and low temp alarms to the control panel. Use the onboard wireless transmitter to connect the 1168 with DMP1100Series Wireless Receivers.

INDICATOR LEDS

The 1168 has a multi-color top LED that indicates the state of the device:
GREEN—Supervisory indication; blinks during power on, reset, and during normal operation
AMBER—Signal maintenance and trouble events
RED—Alarm (Smoke/CO/Low Temp)
Indicator lights on the side alarms (initiating detector only):
RED—Smoke
BLUE—CO

POWER SUPPLY

The 1168 is powered by four 3.0V lithium batteries. Battery life expectancy for the unit is at least three years under normal conditions.
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 1

VOICE ANNUNCIATION

The 1168 audibly announces alarm and maintenance requirements, enhancing occupant understanding and evacuation.

TAMPER MAGNET

The 1168 features a tamper magnet which sends a trouble message to the panel if the detector is removed from the mounting base.

CADENCE SYNCHRONIZATION

The 1168 provides cadence synchronization with other 1168 or 1164 units on the system.

LOW TEMP SENSOR

The 1168 includes a low temperature sensor that causes an alarm when inside temperature falls below 41°F (5°C).

1168 FEATURES

CO Test Button Smoke Test Button
Indicator
Lights
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 2
CO Entry
Port
Figure 1: 1168 Features
Indicator
LED
IR Flame Detector
Indicator
Lights

PROGRAM THE 1168

When programming an 1168 Wireless Smoke/CO/Low Temp Detector, refer to the appropriate panel programming guide as needed.
PROGRAMMER
ZONE INFORMATION
ZONE NO:
* UNUSED *
ZONE TYPE FI PN EM SV
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 3
PROGRAMMER MENU
Enter 6653 (PROG) at the keypad to enter the PROGRAMMER menu.
ZONE INFORMATION
Press CMD until ZONE INFORMATION displays. Press a select key or area to enter the menu.
ZONE NUMBER
Enter the zone number. Press CMD.
Note: The 1168 takes up to three zone numbers (Smoke,
CO, Temp). The zone numbers must be consecutive.
ZONE NAME
Denote the zone name as a fire zone. Press CMD.
ZONE TYPE
Press any select area. Press CMD to move to the next set of menu options. Select FI (fire) as the ZONE TYPE.
FIRE BEL OUT: 0
FIRE BELL OUT
Default is 0. Press CMD.
NEXT ZONE? NO YES
WIRELESS? YES
TRANSMITTER SERIAL #: -
CONTACT: FIRE
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 4
NEXT ZONE
At the NEXT ZONE? prompt, select NO.
WIRELESS
At the WIRELESS? prompt, select YES.
Note: If you are programming the 1168 onto a zone that
can be either hardwired or wireless, then this prompt appears. If the zone you are programming is wireless-only, then the prompt does not appear.
SERIAL NUMBER
Enter the eight-digit SERIAL #: - found on the device and press CMD.
CONTACT TYPE
Enter the CONTACT type as FIRE and press CMD.
SUPVSN TIME: 240
SUPERVISION TIME
Enter the SUPVSN TIME, and press CMD.
NEXT ZN? YES
ZONE NO:
* UNUSED *
ZONE TYPE CO IN
FIRE BEL OUT: 0
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 5
NEXT ZONE
At the NEXT ZONE? prompt, select YES.
ZONE NUMBER
Enter the zone number. This number must be consecutive with the previous zone. For example, if 500 was entered for Fire,501 should be entered here. Press CMD.
ZONE NAME
Denote the zone name as a carbon monoxide (CO) zone. Press CMD.
ZONE TYPE
Press any select area. Press CMD three times to move to the last set of menu options. Select CO (carbon monoxide) as the ZONE TYPE.
FIRE BELL OUT
Default is 0. Press CMD.
NEXT ZONE? NO YES
NEXT ZONE
At the NEXT ZONE? prompt, select NO.
WIRELESS? YES
TRANSMITTER SERIAL #: -
CONTACT: CO
SUPVSN TIME: 240
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 6
WIRELESS
At the WIRELESS? prompt, select YES.
Note: If you are programming the 1168 onto a zone that
can be either hardwired or wireless, then this prompt appears. If the zone you are programming is wireless-only, then the prompt does not appear.
SERIAL NUMBER
Enter the eight-digit SERIAL #: - found on the device and press CMD.
CONTACT TYPE
Enter the CONTACT type as CO and press CMD.
SUPERVISION TIME
Enter the SUPVSN TIME, and press CMD.
NEXT ZN? YES
NEXT ZONE
At the NEXT ZONE?, prompt, select YES.
ZONE NO:
ZONE NAME:
ZONE TYPE FI PN EM SV
FIRE BEL OUT: 0
NEXT ZONE? NO YES
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 7
ZONE NUMBER
Enter the zone number. This number must be consecutive with the previous zones. For example, if 51 was entered for Fire and 52 was entered for CO, 53 should be entered here. Press CMD.
ZONE NAME
Denote the zone name as a temperature (TEMP) zone. Press CMD.
ZONE TYPE
Press any select area. Press CMD to move to the next set of menu options. Select SV as the ZONE TYPE.
FIRE BELL OUT
Default is 0. Press CMD.
NEXT ZONE
At the NEXT ZONE? prompt, select NO.
Loading...
+ 25 hidden pages