DMP Electronics 1168 Installation And Programming Manual

Page 1
1168 Wireless Smoke/CO/Low
Temp Detector
INSTALLATION AND PROGRAMMING GUIDE
Page 2
Page 3
TABLE OF CONTENTS
About the 1168 ............................... 1
Indicator LEDs................................................. 1
Power Supply .................................................. 1
Voice Annunciation ....................................... 1
Tamper Magnet ............................................... 1
Cadence Synchronization ......................... 1
Low Temp Sensor .......................................... 1
1168 Features ..................................2
Program the 1168 ...........................3
Install the 1168 .............................. 11
Mount the Base ...............................................11
Install the Battery ......................................... 12
Replace the Cover ....................................... 12
Mounting Guidelines ....................13
Authority Having Jurisdiction .................. 14
Locations to Avoid ....................................... 15
Commercial .................................................... 16
Multi-Family ....................................................16
Test the 1168 ..................................17
Smoke Test ...................................................... 17
CO Test.............................................................. 17
Additional Information ................21
Reset the Language Selection ................. 21
Supervision Message ................................... 21
Inspection Testing and Maintenance ..... 21
Replace The Batteries .................................22
NFPA 72 Guidelines .....................................23
Page 4
Compliance Specifications ........28
FCC Information ..........................30
Industry Canada Information ......31
Page 5

ABOUT THE 1168

The 1168 Wireless Smoke/CO/Low Temp Detector features multi-criteria smoke sensing using a combination of photoelectric, heat, IR flame flicker, and carbon monoxide indicators. The 1168 reports fire, CO, and low temp alarms to the control panel. Use the onboard wireless transmitter to connect the 1168 with DMP1100Series Wireless Receivers.

INDICATOR LEDS

The 1168 has a multi-color top LED that indicates the state of the device:
GREEN—Supervisory indication; blinks during power on, reset, and during normal operation
AMBER—Signal maintenance and trouble events
RED—Alarm (Smoke/CO/Low Temp)
Indicator lights on the side alarms (initiating detector only):
RED—Smoke
BLUE—CO

POWER SUPPLY

The 1168 is powered by four 3.0V lithium batteries. Battery life expectancy for the unit is at least three years under normal conditions.
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 1

VOICE ANNUNCIATION

The 1168 audibly announces alarm and maintenance requirements, enhancing occupant understanding and evacuation.

TAMPER MAGNET

The 1168 features a tamper magnet which sends a trouble message to the panel if the detector is removed from the mounting base.

CADENCE SYNCHRONIZATION

The 1168 provides cadence synchronization with other 1168 or 1164 units on the system.

LOW TEMP SENSOR

The 1168 includes a low temperature sensor that causes an alarm when inside temperature falls below 41°F (5°C).
Page 6

1168 FEATURES

CO Test Button Smoke Test Button
Indicator
Lights
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 2
CO Entry
Port
Figure 1: 1168 Features
Indicator
LED
IR Flame Detector
Indicator
Lights
Page 7

PROGRAM THE 1168

When programming an 1168 Wireless Smoke/CO/Low Temp Detector, refer to the appropriate panel programming guide as needed.
PROGRAMMER
ZONE INFORMATION
ZONE NO:
* UNUSED *
ZONE TYPE FI PN EM SV
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 3
PROGRAMMER MENU
Enter 6653 (PROG) at the keypad to enter the PROGRAMMER menu.
ZONE INFORMATION
Press CMD until ZONE INFORMATION displays. Press a select key or area to enter the menu.
ZONE NUMBER
Enter the zone number. Press CMD.
Note: The 1168 takes up to three zone numbers (Smoke,
CO, Temp). The zone numbers must be consecutive.
ZONE NAME
Denote the zone name as a fire zone. Press CMD.
ZONE TYPE
Press any select area. Press CMD to move to the next set of menu options. Select FI (fire) as the ZONE TYPE.
Page 8
FIRE BEL OUT: 0
FIRE BELL OUT
Default is 0. Press CMD.
NEXT ZONE? NO YES
WIRELESS? YES
TRANSMITTER SERIAL #: -
CONTACT: FIRE
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 4
NEXT ZONE
At the NEXT ZONE? prompt, select NO.
WIRELESS
At the WIRELESS? prompt, select YES.
Note: If you are programming the 1168 onto a zone that
can be either hardwired or wireless, then this prompt appears. If the zone you are programming is wireless-only, then the prompt does not appear.
SERIAL NUMBER
Enter the eight-digit SERIAL #: - found on the device and press CMD.
CONTACT TYPE
Enter the CONTACT type as FIRE and press CMD.
Page 9
SUPVSN TIME: 240
SUPERVISION TIME
Enter the SUPVSN TIME, and press CMD.
NEXT ZN? YES
ZONE NO:
* UNUSED *
ZONE TYPE CO IN
FIRE BEL OUT: 0
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 5
NEXT ZONE
At the NEXT ZONE? prompt, select YES.
ZONE NUMBER
Enter the zone number. This number must be consecutive with the previous zone. For example, if 500 was entered for Fire,501 should be entered here. Press CMD.
ZONE NAME
Denote the zone name as a carbon monoxide (CO) zone. Press CMD.
ZONE TYPE
Press any select area. Press CMD three times to move to the last set of menu options. Select CO (carbon monoxide) as the ZONE TYPE.
FIRE BELL OUT
Default is 0. Press CMD.
Page 10
NEXT ZONE? NO YES
NEXT ZONE
At the NEXT ZONE? prompt, select NO.
WIRELESS? YES
TRANSMITTER SERIAL #: -
CONTACT: CO
SUPVSN TIME: 240
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 6
WIRELESS
At the WIRELESS? prompt, select YES.
Note: If you are programming the 1168 onto a zone that
can be either hardwired or wireless, then this prompt appears. If the zone you are programming is wireless-only, then the prompt does not appear.
SERIAL NUMBER
Enter the eight-digit SERIAL #: - found on the device and press CMD.
CONTACT TYPE
Enter the CONTACT type as CO and press CMD.
SUPERVISION TIME
Enter the SUPVSN TIME, and press CMD.
Page 11
NEXT ZN? YES
NEXT ZONE
At the NEXT ZONE?, prompt, select YES.
ZONE NO:
ZONE NAME:
ZONE TYPE FI PN EM SV
FIRE BEL OUT: 0
NEXT ZONE? NO YES
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 7
ZONE NUMBER
Enter the zone number. This number must be consecutive with the previous zones. For example, if 51 was entered for Fire and 52 was entered for CO, 53 should be entered here. Press CMD.
ZONE NAME
Denote the zone name as a temperature (TEMP) zone. Press CMD.
ZONE TYPE
Press any select area. Press CMD to move to the next set of menu options. Select SV as the ZONE TYPE.
FIRE BELL OUT
Default is 0. Press CMD.
NEXT ZONE
At the NEXT ZONE? prompt, select NO.
Page 12
WIRELESS? YES
WIRELESS
At the WIRELESS? prompt, select YES.
Note: If you are programming the 1168 onto a zone that
can be either hardwired or wireless, then this prompt appears. If the zone you are programming is wireless-only, then the prompt does not appear.
TRANSMITTER SERIAL #: -
CONTACT: TEMP
SUPVSN TIME: 240
NEXT ZN? NO
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 8
SERIAL NUMBER
Enter the eight-digit SERIAL #: - found on the device and press CMD.
CONTACT TYPE
Enter the CONTACT type as TEMP and press CMD.
SUPERVISION TIME
Enter the SUPVSN TIME, and press CMD.
NEXT ZONE
At the NEXT ZONE?, prompt, select NO.
Page 13
BELL OPTIONS
BELL OPTIONS
Press CMD until BELL OPTIONS displays, and then press a select key or area.
FIRE BELL ACTION... FIRE TYPE: T
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 9
FIRE BELL ACTION
At FIRE BELL ACTION FIRE TYPE:, select T (temporal) as the action type.
Note: Program this option to enable cadence synchronization with other 1168 and 1164 units on the system.
Page 14

SELECT A LOCATION

Use the LED survey operation to select a proper location for the 1168. The LED survey operation allows one person to confirm communication with the wireless receiver or panel while the cover is removed. Because the transmitter LED on the 1168 is not visible, use a separate 1100 Series transmitter for the LED survey operation, such as the 1106 Universal Transmitter.
1. Hold the 1106 in the exact desired location.
2. Press the tamper switch on the 1106 to send data to the panel and determine if communication is confirmed or faulty.
Confirmed: If communication is confirmed, for each press or release of the tamper switch the LED blinks immediately on and immediately o.
Faulty: If communication is faulty, the LED remains on for up to eight seconds or flashes multiple times in a quick succession. Relocate the wireless receiver until the LED confirms clear communication.
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 10
Page 15

INSTALL THE 1168

MOUNT THE BASE

1
After selecting a location, mount the 1168 on a flat wall or ceiling. The ensure optimum performance, mount the 1168 away from large metal objects. See Mounting Guidelines for more information.
1. Grasp the detector and twist counterclockwise to remove the detector from the mounting base. See Figure 2.
2. Use the supplied screws and anchors to mount the base to the surface. See Figure3.
Mounting Hole
Mounting Hole
Figure 2: Remove
Detector from Base
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 11
Figure 3: Mounting
Hole Locations
Page 16

INSTALL THE BATTERY

2
The 1168 comes pre-installed with four 3.0V lithium batteries. Firmly grasp the battery pull-tab on the battery compartment and remove it. See Figure4.

REPLACE THE COVER

After installing the battery, replace the cover back
3
on the base. Follow the directions below:
1. Place the detector on the base, aligning the raised tab on the detector’s lip and the cover latch on the base’s lip.
2. Rotate the detector until it clicks into place.
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 12
Figure 4: Battery Location
Page 17

MOUNTING GUIDELINES

In addition to NFPA 72, use the following location guidelines to optimize performance and reduce false alarms. Refer to Figure5.
Place ceiling-mounted smoke detectors in the center of a room or hallway at least4inches from walls and partitions. If a ceiling is sloped, peaked, or gabled, place the detector 3 feet from the highest-point. If mounting to suspended ceiling tile, the tile must be secured with an appropriate fastener across ceiling panel supports.
Place wall-mounted smoke detectors at least 4 inches below the ceiling.
Mount smoke detectors on a firm, permanent surface.
Place in environmentally-controlled areas with a temperature range between41°Fand 100°F (5°C and 37.8°C) and humidity between0%and90%non-condensing.
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 13
Page 18

AUTHORITY HAVING JURISDICTION

A proper location is critical to ensuring proper operation. Equipment should be installed in accordance with the National Fire Protection Association’s (NFPA) Standard 72, Chapters2 and 8. You may need to reference other chapters of NFPA 72 or NFPA 101.
Smoke detector regulations vary from state to state, so contact the Authority Having Jurisdiction (AHJ). Where public safety is primary, the AHJ may be a federal, state, local, or other regional department or individual (such as a fire chief, fire marshal, chief of a fire prevention bureau, labor or health department, building ocial, electrical inspector, or others having statutory authority.
For insurance purposes, an AHJ may be an insurance inspection department, rating bureau, or other insurance company representative. Sometimes, a property owner or their designated agent assumes the role of the AHJ. At government installations, the commanding ocer or department ocial may be the AHJ.
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 14
Page 19

LOCATIONS TO AVOID

Smoke detectors should not be installed in or near the following locations:
In or near areas where combustion particles are common (kitchens, garages, furnaces, hot water heaters, or gas space heaters).
On ceilings in rooms next to kitchens if there is no transom between the room and the kitchen.
In damp or humid areas, such as bathrooms with showers.
In extremely cold or hot areas.
In dusty, dirty, or insect-infested areas.
Near air conditioners, heating registers, or any other ventilation source that may interfere with smoke entering the detector.
Near fresh air inlets or returns or excessively drafty areas (heating or air conditioning vents, fans, etc.).
In dead-air spaces at the top of peaked ceilings or corners where walls and ceiling meet.
Near fluorescent light fixtures (smoke detectors should be at least 10 feet away).
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 15
Page 20
Stair­well
Oce
Oce
Hall
Hall
Lobby
Oce
Oce
Stairwell
Men’s
Conference
Room
Hall
Closet
Women’s
Oce
OceOce
In commercial buildings,
place smoke detectors in
stairwells and every room on
each level.

COMMERCIAL

Stairwell
Third Floor
Second Floor
First Floor
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 16
Kitchen
Bathroom
ApartmentApartment
Stairwell
Apartment Apartment Apartment
Living Room
Dining
Hall
Figure 5: Smoke Detector Placement Locations
Bedroom
Apartment

MULTI-FAMILY

In multifamily buildings,
place smoke detectors in
hallways and stairwells on
each level.
Inside each apartment,
place smoke detectors in
the living area, hallway, and
each bedroom.
Page 21

TEST THE 1168

Note: If particulate like canned smoke is the only input to the detector, an alarm will
only occur after five minutes of alarm-level particulate exposure.

SMOKE TEST

For more information, refer to the LED Indication and Sounder table.
1. Press the Smoke Test button on the 1168 to initiate a smoke alarm test. The fire alarm will not sound at the panel.
2. To initiate a functional smoke test, press and hold the Smoke Test button for5seconds.
3. Hold a container of canned smoke close to the smoke entry openings. Spray the smoke directly into the detector for 1 second or until the unit goes into alarm. The fire alarm sounds at the panel.

CO TEST

For more information, refer to the LED Indication and Sounder table.
1. Press the CO Test button on the 1168 to initiate the CO test. The CO alarm will not sound at the panel.
2. To initiate a functional CO test, press and hold the CO Test button for 5 seconds.
3. Hold a container of Solo C6 CO Detector Tester (or similar) close to the CO Gas Entry Port. See Figure 1 for port location. Spray the can directly into the detector for 1second or until the unit goes into alarm. The CO alarm sounds at the panel.
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 17
Page 22
LED Indication and Sounder
Mode Status LED
(Top)
Smoke Alarm
Smoke System (functional)
CO Test
1;2
Blink RED once every sec
Blink RED once every 10 secs
1;2
Blink GREEN once a sec
Side LED
Sounder Speaker
Windows
Dark Temp-3 Voice smoke sensor
test result and remaining battery life
Blink RED once every 10
Temp-3 No voice
announcement
secs
Dark Temp-4 Voice CO sensor test
result, remaining sensor life, and remaining battery life
CO Test— Successful gas
Blink RED every 10 secs
entry
Low Battery Blink AMBER
every 10 secs
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 18
Blink BLUE
Temp-4 “Warning: Carbon
every 10 secs
Dark Chirp
every 45 secs after 7 days
Monoxide. Move to fresh air.”
Voice instructions when chirp is hushed by pressing either test button
Page 23
LED Indication and Sounder
Mode Status LED
(Top)
Smoke Maintenance
CO Trouble Double Blink
CO End of Life3—First 29 days
CO End of Life3—First 30 days
Freeze Warning: Temp lower than 41°F (5°C)
Blink AMBER every 5 secs
AMBER every 5 secs
Double Blink AMBER every 3 secs
Double Blink AMBER every 3 secs
Blink RED every 10 secs
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 19
Side LED
Sounder Speaker
Windows
Dark Silent Voice smoke
maintenance instructions if either test button is pressed
Dark Silent No voice
announcement
Dark Silent Voice end of life
instructions when either test button is pressed
Dark Chirp
every 45 secs
Voice end of life instructions when either test button is pressed
Dark Silent No voice
announcement
Page 24
1
Test activated by the test switch or from the controller. Detector is functioning properly
(within proper sensitivity).
2
If Test mode is activated and the LED and Sounder do not function, check for
maintenance or trouble conditions.
3
Starts chirping after 30 days, continues until the batteries are replaced or die.
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 20
Page 25

ADDITIONAL INFORMATION

RESET THE LANGUAGE SELECTION

Press and hold both the Smoke and CO test switch simultaneously for 10seconds, then release. The green light will flash rapidly. Press and hold both buttons again for one second and release. The sensor begins speaking a welcome message. Language selection can now be made. The options are English and Spanish.

SUPERVISION MESSAGE

When a wireless receiver is installed, a receiver is restarted, the panel is reset, or if programming is complete, then the supervision time is reset. If the receiver has been powered down for more than one hour, then the 1168 may take up to an additional hour to send a supervision message. A missing message may display on the keypad until the supervision message is sent.

INSPECTION TESTING AND MAINTENANCE

The 1168 is designed for easy field service and maintenance. When installed and used properly, the 1168 requires minimal maintenance. The device should be functionally tested per NFPA 72 for system type smoke detectors. When a smoke detector requires maintenance, the red LED blinks every 5 seconds.
Caution: Smoke alarms cannot provide warnings for fires resulting from explosions, smoking in bed or other furniture, ignition of flammable liquids, vapors and gases, children playing with matches or lighters. Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 21
Page 26

REPLACE THE BATTERIES

Caution: The batteries used in this device may present a fire or chemical burn hazard if mistreated. Do not recharge, disassemble, heat above 212°F (100°C) or dispose of in fire. Use only Panasonic CR123A Lithium batteries. Use of other batteries may present a risk of fire or explosion. Keep used batteries away from children. Dispose of used batteries properly.
Remove old batteries. Wait 10 seconds and then replace with four new batteries. To avoid a low battery indication when installing new batteries, all four batteries must be installed within 15seconds of installing the first one. Any low battery condition that may have occurred should clear when the backplate is installed.
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 22
Page 27

NFPA 72 GUIDELINES

Total (Complete) Coverage
If required, total coverage shall include all rooms, halls, storage areas, basements, attics, lofts, spaces above suspended ceilings, and other subdivisions and accessible spaces; and the inside of all closets, elevator shafts, enclosed stairways, dumbwaiter shafts, and chutes. Inaccessible areas shall not be required to be protected by detectors. (For exceptions, refer to NFPA 72.)
Partial Coverage
If required, partial detection systems shall be provided in all common areas and work spaces, such as corridors, lobbies, storage rooms, equipment rooms, and other tenant-less spaces in those environments suitable for proper detector operation in accordance with this code.
Selective Coverage
Where codes, standards, laws, or authorities having jurisdiction require the protection of selected areas only, the specified areas shall be protected in accordance with this code.
Supplementary (Non required) Coverage
Where installed, detection that is not required by an applicable law, code, or standard, whether total (complete), partial, or selective coverage, shall conform to the requirements of this code. (For exceptions, refer to NFPA 72 Spacing Requirements.) Where non required detection devices are installed for a specific hazard, additional non required detection devices shall not be required to be installed throughout an entire room or building.
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 23
Page 28
Heat-Sensing Fire Detectors
Heat-sensing fire detectors shall be installed in all areas where required by the NFPA codes and standards or by the authority having jurisdiction.
Detection in New Apartment Buildings
Approved, single-station smoke alarms shall be installed in accordance with 7-6.2.10 of NFPA 101 outside every sleeping area in the immediate vicinity of the bedrooms and on all levels of the dwelling unit including basements. (For exceptions, refer to this section of NFPA 72.)
Detection in Existing Apartment Buildings
Approved, single-station smoke alarms shall be installed in accordance with 7-6.2.10 of NFPA 101 outside every sleeping area in the immediate vicinity of the bedrooms and on all levels of the dwelling unit including basements. (For exceptions, refer to this section of NFPA 72.)
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 24
Page 29
WARNING! Limitation of Smoke Detectors
Wireless smoke alarms are very reliable, but may not work under all conditions. No fire alarm provides total protection of life or property. Smoke alarms are not a substitute for life insurance.
Smoke alarms require a source of power to work. This smoke alarm will not operate and the alarm will not sound if the battery is dead or not installed properly.
Smoke alarms may not be heard. A sound sleeper or someone who has taken drugs or alcohol may not awaken if the alarm is installed outside a bedroom. Closed or partially closed doors and distance can block sound. This alarm is not designed for the hearing impaired.
Smoke alarms may not always activate and provide warning early enough. Smoke alarms only activate when enough smoke reaches the alarm. If a fire starts in a chimney, wall, roof, on the other side of closed doors, or on a dierent level of the property, enough smoke may not reach the alarm for it to alarm.
Smoke alarms are a significant help in reducing loss, injury, and even death. However, no matter how good a detection device is, nothing works perfectly under every circumstance and we must warn you that you cannot expect a smoke alarm to ensure that you will never suer any damage or injury.
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 25
Page 30
Fire Prevention and Escape
The purpose of an early warning smoke alarm is to detect the presence of fire in its early stages and sound an alarm, giving the occupants time to exit the premises safely.
Avoid Fire Hazards
Do not smoke in bed.
Do not leave children home alone.
Never clean with flammable liquids such as gasoline.
Properly store materials.
Use general good housekeeping techniques to keep your home neat and tidy. A cluttered basement, attic, or other storage area is an open invitation to fire.
Use combustible materials and electrical appliances carefully and only for their intended uses.
Do not overload electrical outlets.
Do not store explosive and/or fast burning materials in your home.
Even after proper precautions have been taken, fires can start. Be prepared.
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 26
Page 31
Operation Modes
Mode Status LED
(Top)
Power Up Blink GREEN
every 2 secs
Normal (Standby)
Smoke Alarm Blink RED
Single blink GREEN every 10 secs
every 10 secs
Side LED
Sounder Speaker
Windows
Dark Silent Voice welcome,
instructions after first time power-up or after default
Dark Silent No voice
announcement
Blink RED Temp-3 Voice smoke warning
CO Alarm Blink RED
Blink BLUE Temp-4 Voice CO warning
every 10 secs
Powered Down Dark Dark Silent No voice
announcement
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 27
Page 32

COMPLIANCE SPECIFICATIONS

Specifications
Battery Life Expectancy ETL Rating: 1 Year
Under Normal Conditions: 3 Years
Battery Type 4 x 3.0 V, CR123A Lithium; Panasonic CR123A only
Sensitivity UL Limits 0.9 to3.50%/ft; ULC Limits 0.9 to 3.08%/ft
Audible Signal 85dBA
Frequency Range 905-924 MHz
Dimensions 16.002cm Diameter x 4.19cm Thick
6.3in Diameter x 1.65in Thick
Tamper Cover
Operating Temperature 32°F to 100°F; 0°C to 38°C
Storage Temperature 14°F to 158°F; -10°C to 70°C
Relative Humidity 20% to 95% RH (Agency Compliance is 93% max),
Non-condensing
Color White
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 28
Page 33
Patents
U.S. Patent No. 7,239,236
Compatibility
1100D Series Wireless Receiver with firmware version 203 or higher
1100X Series Wireless Receiver with firmware version 203 or higher
XT30/XT50 Series Panels with firmware version 1.92 or higher
XR150/XR550 Series Panels with firmware version 1.92 or higher
XTLplus Series Panels with firmware version 1.92 or higher
XTLtouch Series Panels with firmware version 1.92 or higher
Certifications
FCC Part 15 Registration ID CCKPC0204
IC Registration ID 5251A-PC0204
Intertek (ETL) Listed
ANSI/UL 268 Smoke-Automatic Fire Detectors
ANSI/UL 2075 Gas and Vapor Detectors and Sensors
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 29
Page 34

FCC INFORMATION

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
The antenna used for this transmitter must be installed to provide a separation distance of at least 20cm (7.874 in.) from all persons. It must not be located or operated in conjunction with any other antenna or transmitter. Changes or modifications made by the user and not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment o and on, the user is encouraged to try to correct the interference by one or more of the following measures:
1. Reorient or relocate the receiving antenna.
2. Increase the separation between the equipment and receiver.
3. Connect the equipment into an outlet on a circuit dierent from that to which the receiver is connected.
4. Consult the dealer or an experienced radio/TV technician for help.
1168 Wireless Smoke/CO/Low Temp Detector Installation and Programming Guide 30
Page 35

INDUSTRY CANADA INFORMATION

This device complies with Industry Canada License-exempt RSS standard(s). Operation is subject to the following two conditions:
1. This device may not cause interference, and
2. This device must accept any interference, including interference that may cause undesired operation of the device.
This system has been evaluated for RF Exposure per RSS-102 and is in compliance with the limits specified by Health Canada Safety Code 6. The system must be installed at a minimum separation distance from the antenna to a general bystander of 7.87 inches (20 cm) to maintain compliance with the General Population limits.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes:
1. l’appareil ne doit pas produire de brouillage, et
2. l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.
L’exposition aux radiofréquences de ce système a été évaluée selon la norme RSS-102 et est jugée conforme aux limites établies par le Code de sécurité 6 de Santé Canada. Le système doit être installé à une distance minimale de 7.87 pouces (20 cm) séparant l’antenne d’une personne présente en conformité avec les limites permises d’exposition du grand public.
Information furnished is believed to be accurate and reliable.
This information is subject to change without notice.
1168 Wireless Smoke/CO/Low Temp Combo Detector Installation and Programming Guide 31
Page 36
LT-1898 19354 1.01 © 2019 Digital Monitoring Products, Inc.
Loading...