DMP Electronics 1100R SERIES Installation Manual

DESCRIPTION
Figure 1: 1100R Wireless
Repeater
WALL
TAMPER
ENABLE DISABLE
BAT
1
PROGRAM THE PANEL
Refer to the panel programming guide as needed.
1. Reset the panel.
2. At a keypad, enter 6653 (PROG) to access the PROGRAMMER menu.
3. In ZONE INFORMATION, enter the wireless zone number.
4. Enter the ZONE NAME.
5. Select AUX 1 (auxiliary) as the ZONE TYPE.
6. Select YES when WIRELESS? displays.
7. At SERIAL NO:, enter the repeater's eight-digit serial number. If using multiple repeaters, they must be programmed as sequential zone numbers.
8. At SUPRVSN TIME, press CMD to accept the default time of 240 minutes. Press any select key or area to select the supervision time required for the wireless repeater. When an 1100 Series receiver is installed, powered up, or the panel is reset, the supervision time for any programmed repeaters and transmitters are reset.
9. At the NEXT ZONE prompt, select NO for more programming options.
10. Program ARMED OPEN and DISARMED OPEN as TROUBLE.
11. Program ARMED SHORT and DISARMED SHORT as ALARM.
12. Press CMD until STOP displays. Press a top row select key or area to save programming.
The 1100R Series Wireless
Repeaters provide an increased
communication range by
forwarding messages from the
transmitter to the wireless receiver.
The 1100RE features
128-bit AES encryption.
Up to eight repeaters can be
installed on a wireless system.
The repeater is powered from a
12VDC power supply and includes
a 24-hour battery backup.
The 1100R Wireless Repeater
provides a built-in survey
capability to allow for single-
person installations, eliminating
the requirement for an external
survey kit.
Compatibility
All DMP 1100 Series Wireless
Receivers using Version 106 or
higher software.
All DMP panels with a built-in
wireless receiver.
Encryption requires panel
version183 or higher and wireless
receiver version 300 or higher.
What is Included
One Model 1100R Repeater
800 mAh Lithium Polymer Rechargeable Battery
Hardware Pack
One Model 376L Plug-In DC Power Supply
2
SELECT A LOCATION
Mount the 1100R on a flat surface and away from large, metal objects. Mounting on or near metal surfaces impairs performance.
The 1100R is typically mounted between the 1100 Series wireless receiver and the 1100 Series wireless transmitters that are out of range. Mount the 1100R as far from the 1100 Series receiver as needed to provide the required system range.
If the repeater is powered from an auxiliary power supply, mount the 1100R away from the metal power supply enclosure.
1100R SERIES WIRELESS REPEATER
Installation Guide
2 1100R INSTALLATION GUIDE | DIGITAL MONITORING PRODUCTS
LED Survey Operation
The 1100R provides a survey capability to allow one person to confirm communication with the receiver while the cover is removed. Apply DC power to the terminal block on the 1100R with the battery connected. It can then be operated on litium battery only for survery operation.
The 1100R automatically establishes communication with the receiver when it's powered up. Use the table below to determine good communication between the 1100R and the receiver. Relocate the 1100R until it establishes good communication with the receiver.
Note: The 1100R green/red Survey LED operation is dierent from the standard single red LED flash for the 1100 Series transmitters.
3
ENABLE/DISABLE THE TAMPERS
The 1100R is equipped with a case and wall tamper. When the housing cover is removed, the case tamper activates and the 1100R sends a tamper trouble to the panel. A two-position header is provided to enable or disable the wall tamper.
If a wall tamper isn't required for the installation, place the jumper across both header pins.
If a wall tamper is required for the installation, place the jumper on the top two pins to enable or the bottom two pins to disable. When faulted, the 1100R immediately sends a wireless zone short to the panel.
MOUNT THE 1100R
1. Remove the cover.
2. Secure the 1100R to the wall using the supplied screws in the mounting hole locations. See Figure 1 for mounting hold locations.
3. If the wall tamper is enabled, ensure a screw is placed through the 5th hole located behind the circuit board to secure the carbon spacer to the wall.
4. Snap the cover back on the unit after observing LED operation.
4
POWER THE 1100R
The 1100R can be powered from a 12 VDC external power supply such as the included DMP model 376L or an optional external DC power supply such as the DMP model 505-12. In addition to powering the 1100R, the power supply also charges the back-up battery on the 1100R that should be connected at the time of the installation. If the DC power source is removed, the power failure is indicated as an open condition on the 1100R zone.
5
LED SURVEY OPERATION
Status (See LED
labels on the PCB)
Operation
GOOD
Green indicates reliable communication is established with the receiver. Reliable communication is defined as the last five messages sent by the 1100R have been acknowledged immediately by the receiver. A message can be sent by pressing or releasing the tamper switch on the 1100R.
BAD
Red indicates the 1100R has not established reliable communication with the receiver. Communication is not considered reliable when the last 5 out of 15 messages sent by the 1100R have not been acknowledged immediately by the receiver. Messages may still be communicated, however the communication link between the repeater and the receiver is not optimum. In this case, the 1100R should be relocated until the GOOD LED lights green.
PWR Green indicates there is power to the 1100R.
Loading...
+ 2 hidden pages