
The Master 500 controller is designed to
control the boiler operation with
automatic feeding of fuel, CH pump and
DHW pump in central heating systems.
Operating instructions
for screw feeder or piston feeder
maintaining the set temperature of the boiler by controlling the blower and the
feeder
ability to operate a boiler with an emergency grate
infinitely adjustable blower operation and adjustable power
programmable boiler blow
adjustable damping time and automatic disabling of control when boiler no fuel
is available
controlling the central heating circulating pump operation
ability to switch hot water priority on and off
control of the domestic hot water heater charging pump depending on the
required temperature
ability to operate the boiler and the DHW pump under one of several weekly
programs installed in the Master 500 controller
COMFORT SYSTEM function, which protects the pump against limescale
protection system – TERMIK thermal fuse
function protecting the system against freezing and overheating of the boiler
temperature sensor failure alarm
adjustable display brightness – increased during adjustment of settings
ability to connect remote control with a sound alarm system
ability to connect a room thermostat
1

Description of the controller components1
1 2 3 4 5
6
2
Operating screen description
Current temperature
of the boiler
Operation mode
Current time
Day of the week
DHW parameters
1.
2. Signal LEDs:
FEEDER
FAN
CH PUMP
DHW PUMP
3. The back button
4. Adjust setting UP button (+)
5. MENU button
6. Adjust setting DOWN button (-)
Display
Fig.1 Description of the controller components
Fig.2 Description of the operating screen

Installation Recommendations2
The controller is designed for use with boilers with automatic feeding of fuel.
The controller must be installed by an authorized person.
The controller must be connected to a socket with a protective contact.
It is required that the boiler had its own safeguards against excessive
temperature rise of the boiler caused e.g. boiler controller or related equipment
malfunction.
The controller should be placed in a location that prevents its heating to a
temperature higher than 40°C.
The controller must not be exposed to water and conditions causing
condensation (e.g. sudden changes in ambient temperature).
The device should be installed and operated as described in the assembly
description and rules for electrical equipment.
A blown fuse due to bad wiring or a short circuit in the electrical system does not
constitute grounds for a warranty repair.
Before starting the controller, you should check the electrical connections.
The controller is protected with two 5 A fuses.
Connection of the power cord and fuse replacement should be made with the
controller powered off (the controller power plug must be disconnected from the
mains). Connection of the receiving devices and replacement of fuses with the
mains plug of the controller plugged in creates an electric shock hazard.
The connection cables of the controller can be replaced only by the
manufacturer or their authorized service establishment.
You must not use a damaged controller.
3

Electrical connection and sensors diagram3
control
fuse 5 A
fuse 5 A
L
N
PE
L
N
L
N
PE
L
N
Room thermostat
DHW sensor
Reed relay
PE
PE
M
Fun
1~
M
Feeder
1~
M
CH Pump
1~
Power supply
~230 V
Thermal
fuse
CH boiler sensor
Feeder sensor
L
N
PE
M
DHW Pump
1~
Fig.3 Wiring diagram to connect power cables
Fig.4 Wiring diagram to connect sensors
Controller installation4
1. The controller is designed to be mounted on the boiler.
2. Using the provided template for positioning of the controller.
3. Install a screw in the boiler housing in the place indicated on the template.
4. Decide on the method of routing the cable from the controller (rear, bottom) and
remove the corresponding caps from the housing.
5. Slide the controller onto the fixed screw, use the other two screws to fasten it to
the boiler housing.
6. Install the optional cables at the appropriate connectors and put them through
the holes in the housing.
7. Protect the installed cables against pulling out, fixing then to the housing in
special sockets using the provided brackets and screws.
8. Install the controller door.
4

Note: If after the controller is switched on, the display is not lit up, check
whether there is voltage in the mains socket, then check the fuses and
replace if damaged with new ones 2 x 5 A. If, after the replacement of
fuses the display remains dark, please contact the maintenance provider.
!
Note: Always replace fuses with the unit switched off and the plug
removed from the socket.
!
Connection of the controller to the electrical system
1. Connect the fan, pump and feeder with the appropriate power cables (see Figure 3).
2. Install all necessary sensors (and reed relay for the piston feeder) acc. to Fig.4
and Fig.6.
3. Put the plug of the controller power supply cable in a ~ 230 V socket.
4. Switch the controller on, using the power switch.
Fan, feeder and pumps wiring diagrams5
5
M
N
L
blue wire N
brown wire L
yellow-green wire
M
Fig.5 Power supply cable wiring diagrams for the fan, feeder, pump, etc. (Depending on the version of the
controller).

~ 230 V
1. Master 500 controller
2. Feeder motor
3. Reed relay
4. Feeder temperature sensor
5.
6. TERMIK thermal fuse
7. CH boiler temperature sensor
8. Central heating pump
9. DHW pump
10. DHW heater sensor
11. Remote control
12. Room thermostat
CH boiler fan
Controller to hydraulic system connection diagram6
1
6
8
10
9
7
11 12
Fig.6 Master 500 wiring diagram
2
4
5
First start7
To set the correct time and date, press , and then use the "+", “-" keys to set the
desired day of the week and approve .
Proceed in the same way by setting the current time, and then the minute.
When you first run the controller, the display flashes the clock and day of the week.
3
6

Starting the boiler and setting the operating parameters
8
When the boiler temperature rises to the level specified by the "dt" parameter, the
controller switches to HEATING mode.
After finishing the settings and double-pressing of , you will be taken to the main
screen.
After reaching the required temperature, the controller will switch to the
MAINTAINING mode, until the temperature drops below the hysteresis – to find out
more, see Operating parameters - HYSTERESIS.
When you press the or button, the SETT symbol will show to inform about the
currently set temperature. Set the required value, using the same buttons: to
increase the setting or to reduce it.
Setting the parameters of the boiler
1. Open the ash pit door.
2. Start the feeder manually (see Manual operation - Testing outputs) and wait
until coal shows at the level of the blow holes.
3. Turn off the feeder and then ignite the coal in the furnace chamber.
4. After obtaining a stable flame, start automatic operation of the controller by
holding down for three seconds the , the display shows START, the controller
will start regular dosing fuel and will control the fan in order to obtain the desired
temperature in the boiler.
7

DHW heater operating parameters setting9
During operation of the controller press the button ; the HOT WATER display will
be shown.
Setting the temperature of the domestic hot water heater.
Pressing again will take you to the desired temperature setting for the boiler. Set
the required temperature, using the buttons: to increase the setting or to reduce
it. Change range: from 40 °C to 70 °C.
The parameter that specifies the minimum measured temperature difference
between the boiler and the domestic hot water heater that must occur for the heating
of domestic hot water to be cost effective and the domestic hot water pump to be
turned on. If this difference is less than the set point, the DHW pump will not switch
on (regardless of whether priority of hot water is turned on or not). Change range:
from 2 °C to 20 °C.
The temperature difference between the boiler and heater
8

A parameter that specifies the number of degrees Celsius by which the temperature
must fall on the domestic hot water heater below the set point for the domestic hot
water pump to turn on. Change range: from 2 °C to 9 °C.
Hysteresis of the DHW pump
Selecting or changing the CH and DHW operating mode10
To access the controller operation mode selection menu, press the ; the display
will show HOT WATER. Then use the or button to select the OPER. MODE
option and confirm with .
You can choose the mode in which the controller operates. The mode determines
whether the DHW pump is to be operated and whether it must run in the DHW priority
mode.
Selecting the desired mode using the or buttons. : only CH /
CH&DHW / DHW Priority / SUMM.
Change range
9

Note: SUMMER mode, indicated by the symbol on the screen means
that outside of the heating season the heating pump will not operate and
all the heat generated by the boiler is designed to heat domestic hot water.
!
ON / OFF. Operation of room thermostat11
You can connect a room thermostat (see Fig. 4) that controls the operation of the
central heating pump, depending on the room temperature. In order to operate the
pump the boiler must also reach its corresponding minimum temperature.
To access the room thermostat menu, press the button ; the display will show HOT
WATER. Then use the or button to select the ROOM THERMOSTAT and
confirm with .
Use the or buttons to select the desired setting. Change range: no / yes
In order to improve thermal comfort, the controller will periodically run the CH pump
when the room temperature is at a preset level.
In order to determine the conditions of this operation, set the operation time and
pause time for the central heating pump.
Pressing again takes you to the next setting.
10
The activated room thermostat function is indicated with the symbol on the display.

Pressing again takes you to the next setting.
Central heating pump - break time
This parameter specifies the time interval in the operation of the CH PUMP (calculated
in minutes) when interoperability with the room thermostat. Change range: from 5 min
to 60 min.
Shutting down the boiler
12
When the boiler is operating in HEATING or MAINTAINING mode, you can switch it to
the DAMPING mode - during which the fan and the feeder is not working.
DAMPING mode
The boiler may be shut down due to lack of fuel, the completion of the damping
process or manually switching to the STOP mode.
When there is no fuel, EMPTY BUNK will be displayed.
11
Central heating pump - operation time
A parameter that specifies the CH pump operation time (calculated in seconds) when
interoperability with the room thermostat. Change range: from 0 s to 240 s.

You can manually shut down the boiler and go to STOP mode.
To do this, press and hold for a few seconds the - the display will show STOP. If
the message is different (e.g. START / HEATING / MAINTAINING), then repeat the
action until STOP is displayed.
STOP mode
Operating parameters13
The OPERATING PARAMETERS functionality makes it possible to set the operating
parameters for the boiler, feeder, fan and CH pump.
To enter the operating parameters menu, press the button ; the display will show
HOT WATER. Then use the or buttons, select the OPER.PARAM. options and
confirm with .
When the temperature in the boiler drops below "dt damp", countdown to damping
will start (see - Adjustment of damping time), and then the boiler will shut down which will be indicated by the STOP message.
To switch on the DAMPING mode, press and hold for a few seconds the - the
screen will show DAMP.
12

The parameter defines the number of degrees Celsius by which the temperature
must fall below the setpoint, at which the controller will resume the HEATING mode –
at this point the feeder will start regular operation as set by the parameters Operating
parameters - HEATING - feeder operation and Operating parameters - HEATING
- feeder pause) ,fan will be switch on and will keep running until the boiler reaches the
required temperature. Change range: from 1 °C to 9 °C.
Operating parameters - HYSTERESIS
Operating parameters - HEATING - feeder operation
The parameter defines the time (in seconds) of the duration of fuel feeding (feeder
operation) in the START and HEATING mode. Change range: from 1 s to 250 s.
Operating parameters - HEATING- feeder pause
This parameter specifies the time (in seconds) of the interval between cyclic fuel
delivery (feeder operation) in START and HEATING mode.
250 s.
Change range: from 1s to
Pressing again takes you to the next setting.
Pressing again takes you to the next setting.
Pressing again takes you to the next setting.
If a piston feeder is used, feeding of fuel into the furnace will be performed in cycles
(i.e. stroke of the fuel drawer and its return). Change range: from 1 to 20.
13

Operating parameters - HEATING - blowing power
This parameter allows you to set the maximum power at which the fan will operate
during HEATING mode. Change range: from 1 % to 100 % of maximum fan power, set
in the maintenance menu - see Adjusting the maximum fan power.
Pressing again takes you to the next setting.
In the case of the piston feeder the scope and factory setting is changed. Change
range: from 10 s to 900 s.
14
Operating parameters - FAN - run-out
This parameter allows you to set the time (in seconds) of earlier switching on of the
fan relative to the switching on of the feeder.
Pressing again takes you to the next setting.
Operating parameters - FAN - delayed switch-off of the fan
This parameter allows you to set the time (in seconds) to delay the switching off of the
fan until the feeder is switched off.
Pressing again takes you to the next setting.

Pressing again takes you to the next setting.
This parameter specifies the time (in seconds) of the interval between cyclic fuel
delivery (feeder operation) in the MAINTAINING mode. Change range: from 1 min to
240 min.
Operating parameters - MAINTAINING - feeder pause
Pressing again takes you to the next setting.
This parameter specifies the time (in seconds) of the interval between cyclic fuel
delivery (feeder operation) in the MAINTAINING mode during summer. Change
range: from 5 min to 240 min.
Operating parameters - MAINT. SUMMER - feeder pause
15
Pressing again takes you to the next setting.
If the piston feeder is used, its time of operation in maintaining mode will be defined by
the number of cycles and not by seconds. Change range: from 1 to 20.
Operating parameters - MAINTAINING - feeder operation
This parameter specifies the time (in seconds) of the duration fuel feeding (feeder
operation) in the MAINTAINING mode. Change range: from 1s to 250 s.

Pressing again takes you to the next setting.
This parameter defines the time of interval in the operation of the fan (in seconds) in
the MAINTAINING mode. Change range: from 5 min to 240 min.
Operating parameters - MAINTAINING - fan pause
Pressing again takes you to the next setting.
Operating parameters - MAINTAINING - blowing power
This parameter allows you to set the power at which the fan will operate during the
MAINTAINING mode. Change range: from 1 % to 100 % of maximum fan power, set
in the maintenance menu - see Adjusting the maximum fan power.
16
Operating parameters - MAINTAINING - fan operation
This parameter defines the time of operation of the fan (in seconds) in the
MAINTAINING mode. Change range: from 0 s to 90 s.
Pressing again takes you to the next setting.
Note: In the MAINTAINING mode the fan starts at the same time as the
feeder.
!

A parameter that specifies the temperature above which the central heating pump
turns on and operates continuously. If the temperature of the boiler falls below this
setting, the pump is switched off. Change range: from 30 °C to 70 °C.
Operating parameters - CH pump oper. threshold control
Emergency grate14
The controller allows you to control the boiler also when it is burning fuel using the
emergency grate instead of the retort furnace. Boiler operation in this mode is
indicated by the GRATE message, displayed on the screen.
To access the menu of the emergency grate, press the ; the display will show HOT
WATER. Then use the or button to select the EMER. GRATE option and confirm
with .
17
The parameter enabling or disabling smooth operation of the fan. The principle of
smooth operation is that the fan progressively reduces its speed when the
temperature of the boiler approaches the desired setpoint. Change range: yes / no.
Fan - smooth operation
Pressing again takes you to the next setting.

Emergency grate - blowing power
This parameter allows you to set the maximum power at which the fan will operate
when the emergency grate is used. Change range: from 1 % to 100 % of maximum
fan power, set in the maintenance menu - see Adjusting the maximum fan power.
This parameter defines the time of interval in the operation of the fan (in seconds) in
the MAINTAINING mode. Change range: from 1 min to 60 min.
Emergency grate - MAINTAINING - fan pause
Emergency grate - MAINTAINING - fan operation
This parameter defines the time of operation of the fan (in seconds) in the
MAINTAINING mode. Change range: from 0 s to 90 s.
Pressing again takes you to the next setting.
18
Use the or buttons to select the desired setting. Change range: no / yes
Pressing again takes you to the next setting.

This parameter allows you to set the power at which the fan is to operate in manual
mode (testing). Change range: from 1% to 100% of maximum fan power, set in the
maintenance menu - see Adjusting the maximum fan power.
Manual operation - blowing power
Pressing again takes you to the next setting.
A window allowing testing the correctness of operation of individual outputs (feeder,
fan, CH pump, DHW pump).
Select the tested output with the button , and to enable/disable it press the or
button. The output currently being checked is indicated by a blinking symbol on the
screen and lighting up the appropriate LED.
.
Manual operation - testing outputs
A window indicating the currently measured temperature of the boiler (temperature),
the hot water heater (DHW), the feeder (Feed).
Temperatures16
19
Manual operation15
This function is used testing the correctness of the connected equipment. To enter the
manual operation menu, press the button ; the display will show HOT WATER.
Then use the or buttons to select the MANUAL OPERATION option and confirm
with .

In order to enter the temperatures window, press the button the display will show
HOT WATER. Then use the or button to select the TEMPERATURES option and
confirm .
No temperature rise17
Use the or buttons to set the desired value and confirm with . :
from 10 min to 240 min.
Change range
Clock18
The CLOCK function allows you to change the set time and day of the week, as
described in the Section Getting Started. To enter the time setting menu, press and
hold the button , the display will show HOT WATER Then use the or buttons
to select the CLOCK and confirm with .
This parameter defines the time (calculated in seconds), during which it is expected
that the temperature will rise during operation in the HEATING mode. To access the
no temperature rise menu, press the button ; the display will show HOT WATER.
Then use the or button and select the T NOT RISING option and confirm . If
the after specified time the temperature does not increase by 2 °C, then the message
EMPTY BUNKER will be displayed.
20

Weekly program19
The WEEKLY PROGRAM functionality enables boiler and DHW pump operation
according to one of several programs. To enter the weekly program menu, press the
button the display will show HOT WATER. Then use the or button to select
the WEEKLY PROGRAM and confirm with .
Weekly program - enabling
This parameter determines whether the weekly program applies to central heating or
hot water. Change range: disabled / only CH / only DHW / CH and DHW
Note: Starting the weekly program for CH will have the effect that in the
scopes indicated by the program the boiler operates according to set
temperature and outside of these ranges -it operates at reduced
temperature - see Weekly program - reduction of boiler temperature.
!
Pressing again takes you to the next setting.
Weekly program - reduction of boiler temperature
This parameter determines the level of the boiler temperature reduction during the
running of the weekly program for CH. Change range: from 5 °C to 30 °C.
Note: Starting the weekly program for DHW is indicated with the
symbol.
.
!
21

Pressing again takes you to the next setting.
Weekly program - program selection
This parameter allows you to select one of the available weekly programs. Change
range: family / work / senior / custom.
The parameters of available programs
Sun 07:00 - 22:00
Mon 05:30 - 22:00
Tue 05:30 - 22:00
Wed 05:30 - 22:00
Thu 05:30 - 22:00
Fri 05:30 - 23:00
Sat 06:30 - 23:30
Sun 08:00 - 22:00
Mon 06:00 - 08:00, 16:00 - 22:00
Tue 06:00 - 08:00, 16:00 - 22:00
Wed 06:00 - 08:00, 16:00 - 22:00
Thu 06:00 - 08:00, 16:00 - 22:00
Fri 06:00 - 08:00, 15:00 - 23:00
Sat 07:00 - 23:30
Family program
Work program
Sun 05:30 - 22:00
Mon 05:30 - 22:00
Tue 05:30 - 22:00
Wed 05:30 - 22:00
Thu 05:30 - 22:00
Fri 05:30 - 22:00
Sat 05:30 - 22:00
Senior program
Selection of the CUSTOM program makes it possible to create an individual program
- for each day of the week it is possible to set two time intervals.
22

Make the changes with the keys, and approve each setting with .
Setting the ON/OFF parameters to "--:--” means that in a specific period the pump ON
and OFF time was not set.
Language20
Nthis setting is used to set the language for displaying of messages. To enter the
language setting menu, press and hold the button , the display will show HOT
WATER Then use the or buttons to select the LANGUAGE option and approve
. .
Next maintenance21
This parameter informs the user of the time remaining until the next maintenance
inspection of the controller. To call up the screen with this information, press the
button ; the display will show HOT WATER. Then use the or to select the
MAINT. INSP. option and confirm with .
23

Factory settings22
This function is used to remove the parameters set by the user and return to the
factory settings. To access the factory settings menu, press the ; the display will
show HOT WATER. Then use the or to select the FACT. SETGS. option and
confirm with .
Confirmation of parameters change to factory settings is done with the button.
Maintenance parameters23
In this menu the maintenance technician can set specific parameters of the
equipment operation as regards the fan and feeder.
To enter the maintenance parameters menu, press and hold the button ; the
display will show MAINT.PARAM. Confirm selection by repeated pressing .
Enabling the piston feeder mode
This parameter switches the controller to work with the piston feeder. Change range:
yes/no.
Note: In the piston feeder mode, be sure to connect the reed relay to the
appropriate connector (see Fig. 4).
!
Pressing again takes you to the next setting.
24

Emergency stop of the piston feeder
The parameter defines the time (in seconds) ensuring a full cycle of the feeder
drawer. If, for some reasons, it is jammed, then, after that time the feeder and the fan
will be stopped in emergency mode, and the screen will indicate a feeder fault - see
more Alarms - piston feeder drawer fault. : from 10 s to 200 s.Change range
Pressing again takes you to the next setting.
This parameter allows you to set the maximum operating power of the fan.
range: from 40 % to 100 %.
Change
Adjusting the maximum fan power
Pressing again takes you to the next setting.
This parameter allows you to set the fan operating time during damping, i.e. after the
temperature drop at the boiler by the "dt" parameter. Change range: from 0 min to 45
min.
Adjustment of damping time
Pressing again takes you to the next setting.
25

A parameter that specifies at how many degrees Celsius below the temperature set on
the boiler for the damping countdown to start, and then to shut the boiler down, see
Adjustment of damping time. : from 10 °C to 30 °C. Change range
Starting the DAMPING process
Example:
- the temperature set on the boiler: 50 °C
- “dt”: 10 °C
During burning out of the boiler, when the temperature drops to the level of
40°C (50°C-10°C), the controller will start counting the time set - see item
Adjustment of damping time - and then the fan will stop running.
!
Pressing again takes you to the next setting.
Feeder and fan locking in the MAINTAINING mode
A parameter that specifies the boiler temperature rise above which the feeder and fan
operation will be locked in the MAINTAINING mode. Change range: from 5 °C to 20 °C.
Pressing again takes you to the next setting.
26

DHW - maintenance24
The effect of this parameter is that when the controller is in SUMMER mode, the
domestic hot water heater pump is working despite reaching the desired temperature
for domestic hot water. It is done to protect the boiler from rapid temperature
increases.
Select the desired setting using the or buttons. Change range: yes / no.
Note: The prerequisite for the pump to start is maintaining minimum
temperature difference between the temperature measured on the DHW
heater and that measured on the boiler.
!
To enter the DHW maintenance parameters menu, press and hold the button ; the
display will show MAINT.PARAM then use the or buttons to select the DHW
MAINT option and confirm with .
Ejection of fuel into the furnace in a critical situation
Parameter specifying the time (counted in minutes), during which the feeder will
press the fuel into the furnacein a situation when the temperature in the feeder
reaches a critical level - for more information see Alarm – feeder temperature.
Change range: from 1 min to 50 min.
27

Maintenance menu - Alarm25
The menu has settings for triggering the alarm for excessive temperature on the
boiler.The menu has settings for triggering the alarm for excessive temperature on
the boiler.
To access the alarm menu, press and hold for a few seconds the button, the
screen displays MAINT PARAM Then press or to select ALARM and confirm
with .
This parameter allows you to set the temperature above which both pumps will start in
emergency mode (hot water pump starts, provided that the controller will operate in
the domestic hot water mode). Change range: from 80 °C to 99 °C.
Alarm - pump temperature
Pressing again takes you to the next setting.
This parameter allows you to set the temperature above which an alarm is triggered.
Change range: from 80 °C to 99 °C.
Alarm - boiler temperature
Pressing again takes you to the next setting.
28

This parameter allows you to set the temperature above which an alarm is triggered.
Change range: from 30 °C to 99 °C.
Alarm - feeder temperature
Pressing again takes you to the next setting.
Parameter allowing enabling or disabling the boiler temperature rise monitoring
functionality No temperature rise. Change range: Yes / No.
Alarm - no temperature rise
Pressing again takes you to the next setting.
This parameter allows you to enable or disable the alarm sounds. Change range: yes
/ no.
Alarm - sound
Maintenance check26
Parameter to reset and change the countdown time to the next maintenance check.
To enter the maintenance check menu, press and hold for a few seconds the button
. ; the display will show MAINT.PARAM then use the or buttons to select the
MAINT CHECK option and confirm wiyh .
29

The controller will prompt you to enter the access code.
Use the buttons to set the access code and confirm with .
!
Note: The access code is known only to the maintenance technician.
A screen will be displayed for setting the number of months until the next
maintenance check Make the change using the buttons; and confirm the
selection .
Note: For the COMFORT SYSTEM function to be active after the end of
the heating season, leave the controller plugged in.
!
The controller protects the heating system from freezing, both pumps running all the
time when the temperature of water falls to 4 °C or lower (DHW pump will start,
provided that the controller runs in the DHW mode).
The protection against freezing function28
The COMFORT SYSTEM built-in in the controller prevents pump blockage by
deposition of scale between the rotor and stator of the pump. The controller
automatically switches the pump on for 30 seconds every 24 hours from its last run.
Pump operation in this mode is indicated by the blinking PUMP LED The function
takes effect after 24 hours from turning the controller on.
The COMFORT SYSTEM function27
30

The controller is designed for remote control (see Fig. 4), which enables control of the
current temperature of the boiler, changing the set temperature of the boiler and a
number of other features which improve user comfort. Built-in beeper emits a sound
when the temperature rises to a dangerous level specified by the user.
Remote control - optional
29
When the temperature in the boiler exceeds the value set in Alarm - boiler
temperature, the display will show Boiler T and an intermittent beep will be
generated (as long as it is turned on - see Alarm - sounds).
Over temperature on the boiler
Alarms - description
30
When the temperature in the feeder exceeds the value set in Alarm - feeder
temperature, the display will show Feeder T and an intermittent beep will be
generated (as long as it is turned on - see Alarm - sounds).
Over temperature on the feeder
When the boiler temperature sensor is damaged, the display shows Boil.Sens. (the
fan stops working), instead of the boiler temperature -- will be shown and a
continuous sound will be generated (as long as it is turned on - see Alarm - sound).
Damaged boiler temperature sensor
31

When the feeder temperature sensor is damaged, the display shows Feed Sens (fan
operation will stop and the feeder will continue for the time set in item Ejection of fuel
into the furnace in a critical situation), instead of the temperature -- will be
displayed and a continuous sound will be generated (as long as this option is enabled
- see Alarm - sound).
Feeder sensor damaged
When the DHW temperature sensor is damaged, the display shows DHW Sens.
(DHW stops working), instead of the DHW temperature -- will be shown and a
continuous sound will be generated (as long as it is turned on - see Alarm - sound).
Damaged DHW temperature sensor
In the event of an overrun on the boiler temperature above 90 °C, the fan will be
disabled in emergency mode. At the same time the display will show THERMAL
FUSE, and an intermittent beep will be generated (as long as it is turned on - see
Alarm - sound).
Thermal fuse
When the temperature drops below 90 °C, the thermal protection system is "off" and
the controller returns to normal operation.
32

When there is a fault / jamming of the piston feeder mechanism (the drawer will not
move), then the screen will show Feeder (the feeder and fan will be stopped) and a
continuous sound will be generated (as long as this option is enabled - see Alarm -
sound).
Piston feeder drawer fault
Note: Pressing the or buttons when the sound is generated will
cause it to turn off.
!
Additional notes
Note: When the fault is removed, press the - the error message will be
cleared from the screen.
!
33

Measured temperature range from - 9 °C to + 120 °C
Boiler temperature setting range from + 45 °C to + 80 °C
Hot water heater temperature range from + 40 °C to + 70 °C
Temperature setting range for the CH pump from + 30 °C to + 70 °C
Smooth start of the fan yes
Adjustable maximum fan power 40 - 100 %
Fan hysteresis (difference between ON - OFF) from 1 °C to 9 °C
DHW pump hysteresis (difference between ON - OFF) from 2 °C to 9 °C
Blowing control (option to completely operation: 0 - 90 seconds
disable blowing) break: 1 - 60 minutes
Adjustable boiler damping time 0 - 45 minutes
Allowable load on outputs fan: 100 VA (W) / 230 V
feeder: 200 VA (W) / 230 V
CH pump: 100 VA (W) / 230 V
DHW pump: 100 VA (W) / 230 V
Rated supply voltage ~ 230 V, 50 Hz
Electrical protection 2 x 5 A
Air relative humidity < 95 %
Enclosure protection grade IP 20
Ambient temperature from 0 °C to + 40 °C
Software class A
Operation type fan: 1Y
feeder: 1B
CH pump: 1B
DHW pump: 1B
Specifications31
34
Note: Depending on the software version, some setting ranges may differ from the above

Disposal of Waste Electrical and Electronic Equipment (Applicable in the
European Union and other European countries with separate collection
systems).
This symbol on the product or its packaging (pursuant to the Act of July 29, 2005
on Waste Electrical and Electronic Equipment) states that this product may not
be treated as household waste. It should be handed over to a facility for
collection of waste electrical and electronic equipment. By ensuring proper
storage of this product, you will help prevent negative consequences for the
environment and human health. Recycling helps conserve natural resources.
For more detailed information about recycling of this product, information about
the set up system to receive and collect waste electrical and electronic
equipment and a list of treatment facilities, please contact our office or our
distributors.
INFORMATION ON WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT
Made in Poland
ul.PrzyjaŸni 141
53-030 Wroc³aw, Poland
Phone (+48) 71 333 73 88, 71 333 74 36
fax. (+48) 71 333 73 31
biuro@dksystem.pl
Maint.
Phone (+48) 71 333 73 88
Manufacturer: