Dixon ADS Maintenance & Operating Instructions

Page 1
30471PA CAP. SENSOR TESTER KIT INSTRUCTIONS
REV A 2018/06/11 877.582.3569 1
Maintenance & Operating Instructions
dixonvalve.com
Page 2
REV A 2018/06/11 877.582.3569 2
30471PA, CAP. SENSOR TESTER KIT INSTRUCTIONS
Product Overview
The DIXON ADS capacitance sensor tester is designed to verify function and calibration on a selection of DIXON ADS brand liquid level sensors. The regular test and verification of sensors ensures the ongoing safe, reliable, and consistent operation for the life of the sensor. The capacitance sensor tester and go-gauge verify the output signals are within the factory accepted tolerances.
1. Capacitance sensor tester
2. 9V Battery
3. Trip window gauge
4. Storage Case
Page 3
REV A 2018/06/11 877.582.3569 3
30471PA, CAP. SENSOR TESTER KIT INSTRUCTIONS
Compatibility
The capacitance sensor tester is designed to test the output and trip point of A100 and A200 series sensors. It is necessary for the A100 and A200 to be partly disassembled before testing can be completed. The tester is limited to only single point sensors.
Technical Specifications
Size: [Case] 9.7” x 10.7” x 4.8” Weight: 5Lbs Battery Type: 9V of any chemistry Automatic Power Timeout: 5 minutes Approximate Battery Life: 15hrs continious
Procedure
A100 Disassembly
1. Remove the back of the A100 by
unscrewing these four screws:
Page 4
REV A 2018/06/11 877.582.3569 4
30471PA, CAP. SENSOR TESTER KIT INSTRUCTIONS
2. Unplug the sensor connection at the bottom of the unit.
3. Connect this to the capacitance sensor tester.
4. Continue to Testing the Sensor section.
A200 Disassembly
1. Unscrew the housing lid.
2. Once open, disconnect the sensor from the
external plug and connect it the Sensor Output Tester.
Page 5
REV A 2018/06/11 877.582.3569 5
30471PA, CAP. SENSOR TESTER KIT INSTRUCTIONS
Testing the Sensor
1. Unscrew the thumb screw and knob all the way.
2. Place the capacitance sensor tip into the go-gauge,
then pull the sensor back until the shoulder is captured.
3. Screw in the knob all the way.
4. Push the sensor towards the knob stem until the
sensor butts up against it.
5. Tighten the thumb screw to lock the sensor in
place.
Page 6
REV A 2018/06/11 877.582.3569 6
30471PA, CAP. SENSOR TESTER KIT INSTRUCTIONS
6. Turn on the capacitance sensor tester.
7. Verify the capacitance sensor tester shows closed.
If the capacitance sensor tester shows any of the following conditions, the sensor is considered bad: a. Closed b. No sensor c. Shorted Removed from service and contact Dixon technical support.
8. Begin unscrewing the knob.
9. Verify the capacitance sensor tester switches from
closed to open before the knob is completely unscrewed. Be sure to remove your hand from the knob as this will interfere with the gauges accuracy. If the knob is completely unscrewed and the sensor output tester shows any of the following conditions, the sensor is considered bad:
a. Closed b. No sensor c. Shorted
Remove from service and contact Dixon technical support.
Replacement Parts
9V Battery: Dixon 10261 Storage Case: Dixon 10491
Page 7
REV A 2018/06/11 877.582.3569 7
30471PA, CAP. SENSOR TESTER KIT INSTRUCTIONS
FAQ & Troubleshooting
The capacitance sensor tester is not turning on.
o The battery may be low. Try replacing the battery.
The capacitance sensor tester shows red momentarily
while adjusting the trip window gauge. o This is normal behavior. The sensor and tester are
working properly.
The capacitance sensor tester shows the sensor is
working correctly but the sensor doesn’t work when assembled back into the A100/A200. o This may be an indication that the A100, or A210
repeater is bad. Call Dixon Technical service for further troubleshooting.
The sensor tester changes states when touching it with
my hand. o This is normal behavior. Your hand should be removed
while not adjusting the knob to prevent interfering with the gauge’s capacitance.
Support
For questions, technical support, or to request an RGA to return products for warranty inspection, please call our 24 hour technical hotline at +1 (877) 582-3569
Page 8
REV A 2018/06/11 877.582.3569 8
30471PA, CAP. SENSOR TESTER KIT INSTRUCTIONS
dixonvalve.com
For Sales and Service Contact
Europe: Dixon Group Europe Ltd. Preston, England Phone: +44 (0) 1772 323529 Fax: +44 (0) 1772 314664 Email: enquiries@dixoneurope.co.uk
Mexico: Dixva, S. de R.L. de C.V. Monterrey, N.L Phone: 01-800-00-DIXON (34966) Fax: 01-81-8354-8197 E-mail: contactenos@dixonvalve.com.mx
Canada: Dixon Group Canada Limited Innisfil (Barrie), Ontario Phone: 705-436-1125 Fax: 705-436-6251 Toll Free: 877-963-4966 E-mail: isales@dixongroupcanada.com
USA: Dixon Bayco USA Chestertown, Maryland Phone: 410-778-2000 Fax: 410-778-4702 Toll Free: 800-355-1991 E-mail: dixonbayco@dixonvalve.com
Asia Pacific: Dixon (Asia Pacific) Pty Ltd Wingfield, South Australia Phone: +61 8 8202 6000 Fax: +61 8 8202 6099 E-mail: enquiries@dixonvalve.com.au