by the
thermostat probe with a positive
differential from the set point: if the
started and then turned off when the
LED
MODE
FUNCTION
ON
Compressor enabled
Flashing
Anti-short cycle delay enabled
ON
Defrost enabled
Flashing
Drip time in progress
ON
Fans enabled
Flashing
Fans delay after defrost in progress.
ON
An alarm is occurring
ON
Continuous cycle is running
ON
Energy saving enabled
°C/°F
ON
Measurement unit
°C/°F
Flashing
Programming phase
n
n
o
o
refrigeration applications
XW60LS
1. GENERAL WARNING
Functioning: i f the difference of temper ature between the evaporator and the room probes is more
than the value of the Fct parameter, the fans are switched on. With Fct=0 the function is disabled.
3.3.2 Cyclical activation of the fans with compressor off.
When Fnc = c-n or c-Y ( fans in parallel to t he c om pr es s or) , by means of the Fon and FoF parameters
the fans can carry out on and off c ycl es ev en if the compressor is s wi tc hed of f. W hen the c om pr es s or
is stopped the fans go on worki ng for the F on tim e. Wi th Fon =0 t he fans rem ain al ways off, when the
compressor is off.
4. FRONT PANEL COMMANDS
1.1 PLEASE READ BEFORE USING THIS MANUAL
• This manual is part of the product and should be kept near the instrument for easy and quick
reference.
• The instrument shall not be used for purposes different from those described hereunder. It cannot be
used as a safety device.
• Check the application limits before proceeding.
• Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring
the same and unchanged functionality .
1.2
• Check the supply voltage is correct before connecting the ins trument.
• Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden
• Warning: disconnect all electr ical connections before any kind of mai ntenance.
• Fit the probe where it is not accessible by the End User. The instrument must not be opened.
• In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” (see
• Consider the maximum current which can be applied to each relay (see Technical D ata).
• Ensure that the wires for probes, loads and the power supply are separated and far enough from each
• In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel
SAFETY PRECAUTIONS
temperature changes with high atmospheric humi di ty to prevent formation of condensation
address) with a detailed descript i on of the fault.
other, without crossing or i ntertwining.
with inductive loads could be useful.
2. GENERAL DESCRIPTION
Model XW60LS, format 38x185mm, is microprocessor based controller, sui table for applicati ons on
medium or low tem peratur e venti lated r efri gerati ng units . It has 3 relay outputs to control com pres sor,
fan and defrost, which c an be either electri cal or rever se cycle (hot gas ) It could be provided with a
Real Time Clock which allows programmi ng of up to 6 daily defrost cy cles, divi ded into holidays and
workdays. A “Day and Night” func tion wit h two different s et points is f itted for energy savi ng. It i s al so
provided with up to three NTC or PTC probe inputs, the f irst one for temperatur e control , the second
one, to be located onto the evaporator, to c ontrol the defros t term inat ion tem peratur e and to m anaged
the fan. Third probe can operates as digital input.
The HOT KEY output allows to connect the unit, by means of t he external module X J485-CX, to a
network line ModBUS-RTU compatible such as the dIXEL monitoring units of X-WEB family. It
allows to program the controller by means the HOT KEY programming keyboard.
The instrument is fully configurable through special parameters that can be easily programmed
through the keyboard.
3. CONTROLLING LOADS
3.1 COMPRESSOR
4.1 STANDARD FRONTAL PANEL
4.2 STEEL FINISHING
: To display target set point; in programming mode i t selects a parameter or confirm an
operation.
(DEF) To start a manual defrost
(UP): To see the max. stored temperatur e; in programming mode i t browses the parameter
codes or increases the displayed value.
(DOWN) To see the min s tored temperature; in pr ogramming mode i t browses the parameter
codes or decreases the displayed value.
To switch the instrument off, if onF = oFF.
NOT USED.
KEY COMBINATIONS:
+
+To enter in programming mode.
+
To lock & unlock the keyboard.
To return to the room temperature display.
4.3 USE OF LEDS
Each LED function is described in the following table.
the temperature measured
temperature increases and reaches set
point plus di fferential the compress or is
temperature reaches the set point val ue
again.
In case of fault i n the thermostat probe the start and stop of the compress or are timed through
parameters “COn” and “COF”.
3.2 DEFROST
Two defrost modes ar e avail able t hrough the “tdF” param eter: defr ost thr ough elec tri cal heater ( tdF =
EL) and hot gas defrost (tdF = in).
The defrost interval depends on the pres enc e of t he RTC (opt i onal ) . I f the RT C i s pr es ent i s c ont rolled
by means of parameter “EdF”:
- with EdF=in the defrost is made every “IdF” time – standard way for controller without RTC.
- with EdF = “rtc”, the defros t is made i n real tim e depending on the hour s set in the par ameters
Ld1..Ld6 on workdays and in Sd1…Sd6 in holidays;
Other parameters are used to control defrost cycles: its maximum length (MdF) and two defrost
modes: timed or controlled by the evaporator’s probe (P2P).
At the end of defrost drippi ng time is started, its l ength is set in the F dt parameter. Wit h Fdt =0 the
dripping time is disabled.
3.3 CONTROL OF EVAPORATOR FANS
The fan control mode is selected by means of the “FnC” parameter:
FnC = C_n: fans will switch ON and OFF with the compressor and not run during defrost;
FnC = o_n fans will run even if the compressor is off, and not run during defrost; After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter.
FnC = C_Y fans will switch ON and OFF with the compressor and run during defrost;
FnC = o_Y fans will run continuously also during defrost
An additional parameter “FSt” provides the s etting of temper ature, detected by the evaporator probe,
above which the fans are always OFF. This is used to make sure circulation of air only if his
temperature is lower than set in “FSt”.
3.3.1 Forced activation of fans
This function managed by the Fct parameter is designed to avoid s hort cycles of fans, that coul d
happen when the control l er is switched on or after a defrost, when the r oom ai r war m s the ev apor ator .
5. MAX & MIN TEMPERATURE MEMORIZATION
5.1 HOW TO SEE THE MIN TEMPERATURE
1. Press and release the
key.
2. The “Lo” message will be displayed followed by the minimum temperature recorded.
3. By pressing the
key again or by waiting 5s the normal display will be restored.
5.2 HOW TO SEE THE MAX TEMPERATURE
1. Press and release the
key.
2. The “Hi” message will be displayed followed by the maximum temperature recorded.
3. By pressing the
key again or by waiting 5s the normal display will be restored.
5.3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
1. Hold press the SET k ey for more than 3s , while the max . or min tem perature is dis played. (rSt
message will be displayed)
2. To confirm the operati on the “rSt” message starts blinking and the normal temperature will be
displayed.
1. Push and immediatel y r elease the SET key: the di s pl ay w i l l s how t he S et
2. Push and immediately release the SET key or wait for 5 seconds to
Push the DEF key for more than 2 seconds and a manual defrost will start.
n
o
With “onF = oFF”, pushing the ON/OFF key, the instr ument is swi tched off. The “OFF”
6.1 TO SET THE CURRENT TIME AND DAY (ONLY FOR INSTRUMENTS
WITH RTC)
When the instrument is switched on, it’s necessary to program the time and day.
1. Enter the Pr1 programming menu, by pushing the SET + n keys for 3s.
2. The rtc parameter is displayed. Push the SET key to enter the real time clock menu.
3. The Hur (hour) parameter is displayed.
4. Push the SET and set current hour by the UP and Down keys, then push SET to confirm
the value..
5. Repeat the same operations on the Min (minutes) and dAy (day) parameters.
To exit: Push SET+UP keys or wait for 15 sec without pushing any keys.
6.2 HOW TO SEE THE SET POINT
point value;
display the probe value again.
6.3 HOW TO CHANGE THE SET POINT
1. Push the SET key for more than 2 seconds to change the Set point value;
2. The value of the set point will be displayed and the “°C” or “°F” LED starts blinking;
3. To change the Set value push the o or n arrows within 10s.
4. To memorise the new set point value push the SET key again or wait 10s.
6.4 HOW TO START A MANUAL DEFROST
6.5 HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:
1. Enter the Programm ing mode by pres sing the Set + n keys for 3s (the “°C” or “°F” LED starts
blinking).
2. Select the required parameter. Press the “SET” key to display its value
3. Use “UP” or “DOWN” to change its value.
4. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key.
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.
6.6 THE HIDDEN MENU
The hidden menu Includes all the parameters of the instrument.
6.6.1 HOW TO ENTER THE HIDDEN MENU
1. Enter the Programm ing mode by pres sing the Set + n keys for 3s (the “°C” or “°F” LED starts
blinking).
2. Released the keys, then push agai n the Set+n keys for more than 7s. The Pr2 label will be
displayed immediately followed from the HY parameter.
NOW YOU ARE IN THE HIDDEN MENU.
3. Select the required parameter.
4. Press the “SET” key to display its value
5. Use o or n to change its value.
6. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + o or wait 15s without pressing a key.
NOTE1: i f none parameter is pres ent in Pr 1, after 3s the “noP ” message is displ ayed. Keep the k eys
pushed till the Pr2 message is displayed.
NOTE2: the set value is stored even when the procedure is exited by waiting the time-out to expire.
6.6.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE
FIRST LEVEL AND VIC EVER SA.
Each parameter pres ent i n the HI DDE N M E NU can be r em ov ed or put into “THE FIRST LEVEL” (user
level) by pressing “SET +
In HIDDEN MENU when a parameter is present in First Level the decimal point is on.
”.
6.7 HOW TO LOCK THE KEYBOARD
1. Keep pressed for more than 3 s the UP + DOWN keys.
2. The “POF” message will be displayed and the keyboard wil l be locked. At this point it will be
possible only to see the set point or the MAX o Min temperature stored
3. If a key is pressed more than 3s the “POF” message will be displayed.
6.8 TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the o and n keys , till the “Pon” message wil l be
displayed.
6.9 THE CONTINUOUS CYCLE
When defrost is not in progress, i t can be activated by holding the “o” key pressed for about 3
seconds. The compressor operates to mai ntain the “ccS” set point for the tim e set through the “CCt”
parameter. The cycl e can be term inated before the end of the s et tim e using the sam e activ ation key
“
” for 3 seconds.
6.10 THE ON/OFF FUNCTION
message is displayed. In this configuration, the regulation is disabled.
To switch the instrument on, push again the ON/OFF key.
WARNING: Loads connected to t he nor mally clo sed cont acts of t he r elays are always supplied
and under voltage, even if the instrument is in stand by mode.
7. PARAMETERS
rtc Real time clock menu (only for controller with RTC): to set the time and date and defrost start
time.
REGULATION
Hy Differential: (0,1 ÷ 25,5°C / 1÷ 255 °F) Int erventi on dif ferenti al for set point. Compr essor Cut IN is
Set Point + differenti al (Hy). Compressor Cut O UT is when the temperature reac hes the set
point.
LS Minimum set point: (- 50°C÷SET/-58°F÷SET): Sets the minimum value for the set point.
US Maximum set point: (SET÷110°C/ SET÷230°F). Set the maximum value for set point.
Ot Thermostat pr obe calibration: (-12.0÷12.0°C; -120÷120°F) al lows to adjust possi ble offset of
the thermostat probe.
P2P Evaporator pr obe presen ce: n= not pr esent: the defros t stops by time; y= present: the defrost
stops by temperature.
OE Evaporator probe calibration: (-12.0÷12.0°C; -120÷120°F). allows to adjust possi ble offset of
the evaporator probe.
P3P Third probe presence (P3): n= not present:, the termi nals 13-14 operate as digital input.; y=
present:, the terminals 13-14 operate as third probe.
O3 Third probe calibration (P3): (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of the
third probe.
OdS Outputs activat ion delay at start up: (0÷255mi n) Thi s funct ion i s enabl ed at the ini tial star t up
of the instrument and inhibits any output activation for the period of time set in the parameter.
AC Anti-short cycle delay: (0÷ 50 min) minimum inter val between the compressor stop and the
following restart.
rtr Percentage of the seco nd and f ir st p r o be for regulation (0÷100; 100 = P1, 0 = P2 ): it allows
to set the regulation ac cording to the percentage of the first and s econd probe, as for the
following formula (rtr(P1-P2)/100 + P2).
CCt Compressor ON time during continuous cycle: (0.0÷24.0h; res. 10min) Allows to set the
length of the continuous cyc le: compr essor stay s on without interruption for the CCt tim e. Can be
used, for instance, when the room is filled with new products.
CCS Set point for continuous cycle: (-50÷150°C) it sets the set point used during the conti nuous
cycle.
COn Compressor ON time with faulty probe: (0÷255 min) tim e during which the compr essor is
active in case of faulty thermostat probe. With COn=0 compressor is always OFF.
COF Compressor OFF time with faulty probe: (0÷255 min) time duri ng which the compressor is
OFF in case of faulty thermostat probe. With COF=0 compressor is always active.
DISPLAY
CF Temperature measurement unit: °C=Celsius; °F=Fahrenheit. WARNING: When the
measurement unit is changed the S ET point and t he values of t he parameters Hy, LS, US , Ot,
ALU and ALL have to be checked and modified if necessary).
rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display.
Lod Instrument display: (P1; P2, P3, P4, S ET, dtr): it selects whic h probe is displayed by the
instrument: P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe(only for model with
this option enabled); P4 = NOT SET IT, SET = set point; dtr = percentage of visualization.
rEd X- REP d isp lay ( optional): ( P 1; P 2, P 3, P 4, S E T, dtr ) : i t selects which probe is displ ay ed by X-
REP: P1 = Therm ostat probe; P2 = Evaporator probe; P3 = Third probe(only for model with t his
option enabled); P4 = NOT SET IT, SET = set point; dtr = percentage of visualization.
dLy Display delay: ( 0 ÷ 20.0m ; resul. 10s) when the temperature increases, the display is updated of
1 °C/1°F after this time.
dtr Percentage of th e second and first probe for visualization when Lod = d tr (0÷100; 100 =
P1, 0 = P2 ): if Lod = dtr it allows to s et t he visualization according to t he perc ent age of the fir s t
and second probe, as for the following formula (dtr(P1-P2)/100 + P2).
DEFROST
EdF Defrost mode (only for controller with RTC):
rtc = Real Time Clock mode. Defrost ti me follows Ld1÷Ld6 parameters on workdays and
Sd1÷Sd6 on holidays.
in = interval mode. The defrost starts when the time “Idf” is expired.
tdF Defrost type: EL = electrical heater; in = hot gas
dFP Probe selection for defrost termination: nP = no probe; P1 =thermostat probe; P2 =
evaporator probe; P3 =configurable probe; P4 = NOT SET IT.
dtE Defrost termination temperature: (-50÷50 °C/
-58÷122°F) (Enabled only when EdF=Pb) sets the temper ature measured by the evaporator
probe, which causes the end of defrost.
IdF Int erval bet ween def ro st cycles: ( 0÷ 120h) Deter m ines the time interval between the begi nni ng
of two defrost cycles.
MdF (Maximum) length for defrost: (0÷255min) When P2P = n, (not ev aporator probe: timed
defrost) it set s the defr os t dur at i on, when P2P = y ( defr os t end bas ed on tem per atur e) i t s ets the
maximum length for defrost.
dSd Start defrost delay: ( 0÷99min) This i s us eful when different defrost start times ar e nec es s ar y to
avoid overloading the plant.
dFd Temperature displayed during defrost: (rt = real temperature; it = temperature at defrost start;
SEt = set point; dEF = “dEF” label)
dAd MAX display delay after def rost: (0÷255min). Sets the m aximum time between the end of
defrost and the restarting of the real room temperature display.
Fdt Drip time: (0÷120 min) time interv al between reac hing defros t termi nation temper ature and the
restoring of the control ’s normal operation. T his time allows the ev aporator to eliminate water
drops that might have formed due to defrost.
dPo First defrost after start-up: (y = immediately; n = after the IdF time)
dAF Defr ost delay after continuous cycle: (0÷23.5h) t ime interval between the end of the fast
freezing cycle and the following defrost related to it.
FANS
FnC Fans operating mode: C-n= runs with the compressor, OFF during defrost;
o-n = continuous mode, OFF during defrost;
C-Y = runs with the compressor, ON during defrost;
o-Y = continuous mode, ON during defrost;
Fnd Fans delay after defrost: (0÷255min) Interval between end of defrost and evaporator fans start.
Fct Temper ature dif ferential avo iding short cycles of fans (0÷ 59°C; Fc t=0 functi on disabl ed). If
the difference of tem perature between the evaporator and the room probes is more than the
value of the Fct parameter, the fans are switched on.
FSt Fans stop temperature: (-50÷50°C/122°F) setting of temperature, detected by evaporator
Fon Fan ON time: (0÷15 mi n) with Fnc = C_n or C_y , (fan acti vated in par allel with com pressor) . it
To connect the X-REP to the
52F(2m), CAB-55F(5m),
sets the evaporator fan ON cy cling ti me when the compr essor is of f. With Fon =0 and FoF ≠ 0
the fan are always off, with Fon=0 and FoF =0 the fan are always off.
FoF Fan OFF time: (0÷15 m in) with Fnc = C_n or C_y, (fan acti vated i n paral lel with c ompr essor ). i t
sets the evaporator fan off cycling time when the compressor is off. With Fon =0 and FoF ≠ 0 the
fan are always off, with Fon=0 and FoF =0 the fan are always off.
FAP Probe selecti on for fan managemen t: nP = no probe; P1 =thermostat probe; P2 = evaporator
probe; P3 =configurable probe; P4 = NOT SET IT.
ALARMS
ALP Probe selecti on for alarm: nP = no probe, the tem perature al arms ar e disabl ed; P1 = Pr obe 1
(Thermostat probe); P 2 = Probe 2 ( evaporator pr obe); P3 = P robe 3 (dis play pr obe); P4 = NOT
SET IT.
ALC Temperature alarms configuration: (Ab; rE)
Ab= absolute temperature: alarm temperature is given by the ALL or ALU values. rE =
temperature alarms are referred to the set point. Temperature alarm is enabled when the
temperature exceeds the “SET+ALU” or “SET-ALL” values.
ALU MAXIMUM temperat ure alarm: (SE T÷110°C; SET÷ 230°F) when this temperatur e is reached
the alarm is enabled, after the “ALd” delay time.
ALL Minimum temp erature alarm: ( -50.0 ÷ SET °C; -58÷ 230°F when this temper ature is reached
the alarm is enabled, after the “ALd” delay time.
AFH Differential for temperature alarm/ fan recovery: (0,1÷25,5°C; 1÷45°F) Intervention
differential for recovery of temperatur e alarm. It’ s also used for the r estart of the fan when the
FSt temperature is reached
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm
condition and alarm signalling.
dAO Exclusion of temp eratur e alarm at start-up: (from 0.0 min to 23.5h) ti me i nterv al between the
detection of the temperature alarm condition after instrument power on and alarm signalling.
CONDENSER TEMPERATURE ALARM
AP2 Pr obe selectio n for temperat ure alarm o f condenser : nP = no probe; P1 =thermostat probe;
P2 = evaporator probe; P3 =configurable probe; P4 = Probe on Hot Key plug.
AL2 Low temperatur e alarm of condenser: (-55÷150°C) when this temperature is reached the LA2
alarm is signalled, possibly after the Ad2 delay.
Au2 High temperature alarm of condenser: (-55÷150°C) when thi s t em perat ur e i s r eached t he HA2
alarm is signalled, possibly after the Ad2 delay.
AH2 Differential for temperature condenser alarm recovery: (0,1÷25,5°C; 1÷45°F)
Ad2 Condenser temperature alarm delay: (0÷255 min) time interval betw een the detection of the
condenser alarm condition and alarm signalling.
dA2 Condenser temperature alarm exclusion at start up: (from 0.0 min to 23.5h, res. 10min)
bLL Compressor of f with low temperat ure alarm of condenser: n = no: compressor k eeps on
working; Y = yes, compressor i s switched off till the alarm is present, i n any case regulation
restarts after AC time at minimum.
AC2 Compressor off with high temperature alarm of condenser: n = no: compressor k eeps on
working; Y = yes, com pressor is swit ched off till the alarm i s present, in any case regul ation
restarts after AC time at minimum.
DIGITAL INPUTS
i1P Digital input p olarity: oP: the digital i nput is activ ated by opening the contact; CL: the digital
input is activated by closing the contact.
i1F Digital input configuration: EAL= external alarm: “EA ” message is displayed; bAL= s erious
alarm “CA” message i s displayed. PAL= pressure s witch alarm, “CA” message is dis played;
dor= door switch funct ion; dEF= activation of a defros t cycle; AUS=not enabl ed; Htr= kind of
action invers i on ( c ool i ng – heating); FAn= not set it; ES= Energy saving; HdF = Holiday defrost
(enable only with RTC); onF = to switch the controller off.
did (0÷255 min) withi1F= EAL or i1F = bAL digital input alarm delay (13-14): del ay between the
detection of the external alarm condition and its signalling.
with i1F= dor: door open signalling delay
with i1F= PAL: time for pressure switch function: time inter v al to c al c ul at e the num ber of t he
pressure switch activation.
nPS Pressure swi tch number : (0
interval, before signalling the alarm event (I2F= PAL).
If the nPS activatio n in t h e di d t im e is r each ed, swit ch of f an d o n t h e inst rument to restart
normal regulation.
odc Compressor and fan status when open door: no = normal; Fan = Fan OFF; CPr =
Compressor OFF; F_C = Compressor and fan OFF.
rrd Outputs restart after doA alarm : no= outputs not affected by the doA alarm; yES = outputs
restart with the doA alarm.
HES Temperature increase during the Energy Saving cycle:
(-30,0°C
TO SET CURRENT TIME AND WEEKLY HOLIDAYS (ONLY FOR MODELS WITH RTC)
Hur Current hour (0 ÷ 23 h)
Min Current minute (0 ÷ 59min)
dAY Current day (Sun ÷ SAt)
Hd1 First weekly holiday (Sun ÷ nu) Set the first day of the week which follows the holiday times.
Hd2 S eco nd weekl y ho lid ay (Sun ÷ nu) Set the second day of the week which follows the holiday
N.B. Hd1,Hd2 can be set also as “nu” value (Not Used).
TO SET ENERGY SAVING TIMES (ONLY FOR MODELS WITH RTC)
ILE Energy Saving cycle start during w orkdays: (0 ÷ 23h 50 min.) During the E nergy Savi ng
dLE Energy Saving cycle length during workdays: (0 ÷ 24h 00 min.) Sets the duration of the
ISE Energy Saving cycle start on holidays. (0 ÷ 23h 50 min.)
dSE Energy Saving cycle length on holidays (0 ÷ 24h 00 min.)
TO SET DEFROST TIMES (ONLY FOR MODELS WITH RTC)
Ld1÷Ld6 Workday def rost start (0 ÷ 23h 50 min.) These par ameters set the beginning of the 6
Sd1÷Sd6 Holiday defr ost start (0 ÷ 23h 50 min.) These paramet ers set the beginning of the 6
÷30,0°C) it sets the increasing value of the set point during the Energy Saving cycle.
times.
cycle the s et point is incr eased by the value i n HES s o that the operation s et point i s SET +
HES.
Energy Saving cycle on workdays.
programmable defrost c yc les during workdays. Ex. When Ld2 = 12.4 the second defrost starts at
12.40 during workdays.
programmable defrost cyc les on holi days. E x. W hen Sd2 = 3.4 the second defrost starts at 3.40
on holidays.
N.B. :To disable a defrost cycle set it to “ nu”(not used). Ex. If Ld6=nu ; the sixth defr ost
cycle is disabled
÷15) Number of ac tiv ation of the pres sure s wit ch, duri ng the “did”
OTHER
Adr Serial address (1÷244): Identifies the instrument address when connected to a ModBUS
compatible monitoring system.
PbC Type of probe: it allows t o set the k ind of pr obe used by the i nstr ument: PbC = PBC probe, ntc
= NTC probe.
onF on/off key enabling: nu = disabled; oFF = enabled; ES = not set it.
dP1 Thermostat probe display
dP2 Evaporator probe display
dP3 Third probe display- optional.
rSE Real set point: it shows the set point used during the energy saving cycle or during the
As soon as the digital input is activated the unit wi ll wait for “did” time delay before si gnalling the
“EAL” alarm message. The outputs stat us don’t change. T he alarm stops jus t after the di gital i nput is
de-activated.
8.2 SERIOUS ALARM MODE (i1F = bAL)
When the digital input i s activated, the unit wi ll wait for “did” delay before s ignalling the “CA” al arm
message. The relay output s are swi tched OFF. T he alarm w ill s top as soon as the digital input is deactivated.
8.3 PRESSURE SWITCH (i1F = PAL)
If during the interval time set by “did” parameter, the pressur e switch has reached the number of
activation of the “nPS” parameter, the “CA” pressure alarm message will be displayed. The
compressor and the regul ation are stopped. When the digi tal input is ON the compr essor is always
OFF. If the nPS activat io n i n t h e did t ime i s r each ed, sw it ch of f and on the instr u men t to rest ar t
normal regulation.
8.4 DOOR SWITCH INPUT (i1F = dor)
It signals the door status and the corresponding rel ay output st atus thr ough the “ odc” param eter : no =
normal (any change); Fan = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF.
Since the door i s opened, aft er the delay ti me set t hrough param eter “did”, the door alar m is enabled,
the display shows the m essage “dA” and the regulat ion restarts is r tr = yES. The alarm stops as
soon as the external digi tal input i s dis abled again. Wit h the door open, the high and low temperatur e
alarms are disabled.
8.5 START DEFROST (i1F = dEF)
It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will
restart only if the di gital input is di sabled otherwi se the instrum ent wil l w ait unti l the “M dF” safety tim e
is expired.
8.6 INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F =Htr)
This function allows to invert the regulation of the controller: from cooling to heating and viceversa.
8.7 ENERGY SAVING (i1F = ES)
The Energy Savi ng function allows to change the s et point value as the result of the SET + HES
(parameter) sum. This function is enabled until the digital input is activated.
8.8 HOLIDAY DEFROST (i1F = HDF) –ONLY FOR MODELS WITH RTC
This function enabled the holiday defrost setting.
8.9 ON OFF FUNCTION (i1F = onF)
To switch the controller on and off.
8.10 DIGITAL INPUTS POLARITY
The digital input polarity depends on the “i1P”parameter.
i1P or i2P =CL: the input is activated by closing the contact.
i1P or i2P=OP: the input is activated by opening the contact
9. TTL S ERIAL LINE – FOR MONITORING SYSTEMS
The TTL serial line, available thr ough the HOT KEY connector, all ows by means of the external
TTL/RS485 converter, XJ485-CX, to connect the instrument to a monitor ing system ModBUS-RTU
compatible such as the X-WEB500/3000/300.
10. X-REP OUTPUT – OPTIONAL
As optional, an X-REP can be connected to the instrument, trough the HOY KEY
connector. The X-REP output EXCLUDES the serial connection.
instrument the following connectors
must be used CAB-51F(1m), CAB-
11. INSTALLATION AND MOUNTING
The controller XW60LS, shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two
screws
∅ 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L).
The temperature r ange allowed for correct operation i s 0 - 60 °C. Avoid places subj ect to strong
vibrations, cor rosive gases , excessi ve dirt or hum idity. The same recommendations apply to probes.
Let the air circulate by the cooling holes.
Page 4
11.1 CUT OUT
1
1
2
23
3
4
4
RG-LX gascke
(optional)
Message
Cause
Outputs
“P1”
Room probe failure
Compressor output acc. to par. “Con” and “COF”
“P2”
Evaporator probe failure
Defrost end is timed
“P3”
Third probe failure
Outputs unchanged
“HA”
Maximum temperature alarm
Outputs unchanged.
“LA”
Minimum temperature alarm
Outputs unchanged.
"HA2"
Condenser high temperature
It depends on the “Ac2” parameter
"LA2"
Condenser low temperature
It depends on the “bLL” parameter
Message
Cause
Outputs
“dA”
Door open
Compressor and fans restarts
“EA”
External alarm
Output unchanged.
“CA”
Serious external alarm (i1F=bAL)
All outputs OFF.
“PA”
Pressure switch alarm (i1F=PAL)
All outputs OFF
“rtc”
Real time clock alarm
Alarm output ON; Other outputs unchanged;
has to be set
rtF
Real time clock board failure
Alarm output ON; Other outputs unchanged;
Defrosts according to par. “IdF” Contact the service
Pon
Keyboard unlocked.
PoF
Keyboard locked
noP
In programming mode: none parameter is present in Pr1
On the display or in dP2, dP3, dP4: the selected probe is nor enabled
Defrosts according to par. “IdF” Set real time clock
11.2 STEEL FINISHING MOUNTING
12. ELECTRICAL CONNECTIONS
The instruments are pr ovided with s crew termi nal block t o connect cables with a cross section up to
2
2,5 mm
for the digital and analogue i nputs. Relays and power supply have a Faston connection
(6,3mm). Heat-resi stant cables have to be used. Before connecting cables make sure the power
supply compl i es with the instrument’s requir em ents . S epar ate t he probe c ables from the power supply
cables, from the outputs and the power connecti ons. Do not exceed the maxim um current all owed on
each relay, in case of heavier loads use a suitable external relay.
N.B. Maximum current allowed for all the loads is 20A.
12.1 PROBE CONNECTION
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
infiltration. It is recommended to place the thermostat probe away from air streams to correctly
measure the average room temper ature. Place the defrost term ination probe among the evaporator
fins in the coldest pl ace, w here mos t ic e is form ed, far fr om heater s or f rom t he warmes t plac e duri ng
defrost, to prevent premature defrost termination.
13. HOW TO USE THE HOT KEY
13.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
2. When the controller i s ON, i ns er t the “Ho t key” and push o key; the "uPL" message appears
followed a by flashing “End”
3. Push “SET” key and the End will stop flashing.
4. Turn OFF the instrument remove the “Hot Key”, then turn it ON again.
NOTE: the “Err” message is di splayed for failed program ming. In this case push again o key if y ou
want to restart the upload again or remove the “Hot key” to abort the operation.
13.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY
(DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON.
3. Automatically the parameter li st of the “Hot Key” is downloaded into t he Controller memor y,
the “doL” message is blinking followed a by flashing “End”.
4. After 10 seconds the instrument will restart working with the new parameters.
5. Remove the “Hot Key”..
NOTE the message “Err” is di s pl ay ed for f ai l ed pr ogr am m i ng. I n thi s c as e tur n the unit off and then on
if you want to restart the download again or remove the “Hot key” to abort the operation.
14. ALARM SIGNALS
14.1 ALARM RECOVERY
Probe alarms P1”, “P2”, “P3” start some seconds after the fault in the related probe; they automatically
stop some seconds after the probe res tarts norm al operat ion. Chec k connec tions before repl acing the
probe.
Temperature alarms “HA”, “LA” “HA2” and “LA2” automatical ly stop as soon as the temperature
returns to normal values.
Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm “PA” (with i1F=PAL) recovers only by switching off and on the instrument.
14.2 OTHER MESSAGES
15. TECHNICAL DATA
Housing: self extinguishing ABS.
Case: facia 38x185 mm; depth 48mm
Mounting : panel mounting in a 150x31 mm panel cut-out with two screws.
Distance between the holes 165mm
Protection: IP20; Frontal protection: IP65 with frontal gasket mod RG-L. (optional)
Connections: Screw terminal block
Power supply: 230Vac or. 110Vac or 24Vac
Power absorption: 5VA max.
Display: 3 digits, red LED, 14,2 mm high.
Display: 3 digits, red LED, 14,2 mm high; Inputs: Up to 4 NTC or PTC probes.
Digital inputs: 2 free voltage
Relay outputs: Total current on loads MAX. 20A
compressor: relay SPST 20(8) A, 250Vac
light: relay SPST 8 or 16(3) A, 250Vac
fans: relay SPST 8(3) A, 250Vac
defrost: relay SPST 8(3) A, 250Vac
Other output : buzzer (optional)
Serial output : TTL standard; Communication protocol: Modbus - RTU
Data storing: on the non-volatile memory (EEPROM).
Internal clock back-up: 24 hours (only for model with RTC)
Kind of action: 1B; Pollution grade: 2;Software class: A.;
Rated impulsive voltage: 2500V; Over voltage Category: II
Operating temperature: 0÷60 °C; Storage temperature: -30÷85 °C.
Relative humidity: 20÷85% (no condensing)
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);
PTC probe: -50÷150°C (-58÷302°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit
2
≤ 2,5 mm
heat-resistant wiring and 6,3mm Faston
± 10%
∅ 3 x 2mm.
16. CONNECTIONS
16.1 XW60LS – DRY CONTACTS
Supply: 120Vac or 24Vac: connect to terminals 11-12
The X-REP output is optional