dixell COOL MATE XLH360 Operating Instructions Manual

dIXEL
Temperature and humidity controller
Operating Instructions
for seasoning-maturing cabinets
cod. 1592017410
XLH360
COOL MATE
Operating Instructions
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 1/16
dIXEL
Operating Instructions
cod. 1592017410
COOLMATE
XLH360
INDICE
1. GENERAL WARNING__________________________________________________________ 3
2. GENERAL DESCRIPTION ______________________________________________________ 3
3. TEMPERATURE REGULATION__________________________________________________ 3
4. HUMIDITY REGULATION ______________________________________________________ 3
5. FA NS ______________________________________________________________________ 4
6. EXTRACTOR FAN ____________________________________________________________ 4
7. MATURING CYCLE WITH DRIPPING, RUNNING AND STOPPING PHASE. ______________ 5
8. THE DISPLAY________________________________________________________________ 6
9. PARAMETER LIST ____________________________________________________________ 8
10. DIGITAL INPUT _____________________________________________________________ 10
11. INSTALLATION AND MOUNTING _______________________________________________ 11
12. DIMENSIONS _______________________________________________________________ 13
13. ELECTRICAL CONNECTIONS _________________________________________________ 13
14. HOW TO USE THE HOT KEY __________________________________________________ 13
15. ALARM SIGNALLING _________________________________________________________ 14
10. TECHNICAL DATA ___________________________________________________________ 14
16. XLH360 WIRING CONNECTIONS _______________________________________________ 15
17. DEFAULT SETTING VALUES __________________________________________________ 15
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 2/16
dIXEL
Operating Instructions
cod. 1592017410
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device.
Check the application limits before proceeding.
1.2
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high
atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.” (see address) with a detailed description of
the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough from each other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with inductive loads could be useful.
2. GENERAL DESCRIPTION
The XLH360 is microprocessor controller, suitable for applications on medium or low temperature refrigerating units. It has 6 output relays to control compressor, heating elements, defrost/extractor fan, fan, de-humidifier/light and humidifier. It has 2 NTC inputs one for thermostat the other one for defrost. It’s also present a 4÷20mA input for humidity. There is one digital input (free contact) configurable by parameter. An output allows the user to program the parameter list with the “Hot Key”.
3. TEMPERATURE REGULATION
The temperature regulation is performed through neutral zone using compressor and heater output relays.
ON
OFF
Heating output: CUT IN is “SET TEMP-dbt”, CUT OUT is when the temperature reaches the set point.
Set point
Compressor output CUT IN is “ SET TEMP +dbt”, CUT OUT is when the temperature reaches the set point.
3.1 DEFROST
During defrost the temperature control is disabled.
If the second relay is configured as defrost: oA2=dEF then two defrost modes are available through the “tdF” parameter: defrost with electrical heater (tdF=rE) or hot gas (tdF= in). The defrost interval is control by means of parameter “EdF”: (EdF=in) the defrost is made every “IdF” time, (EdF=Sd) the interval “IdF” is calculate through Smart Defrost algorithm (only when the compressor is ON). At the end of defrost dripping time is started, set by “Fdt” parameter. To disable the defrost set the MdF parameter to zero
If oA2 is different from dEF, defrost is made only by stopping compressor (tdF=rE). To disable defrosts set MdF=0.
Humidity regulation during defrost depends on the Hud parameter. With Hud=no humidity regulation is disabled. Con Hud=yES humidity regulation is performed also during defrost.
4. HUMIDITY REGULATION
The humidity regulation is performed through neutral zone, by humidifying dehumidifying actions. Humidity control can be disabled setting the SET %RH to “nu” value. In this case only the temperature control is perform.
4.1 HUMIDIFYING ACTION
The humidifying action is done enabling the humidifier relay when the humidity is lower than the “SET %RH-dbH” value. The relay is switch off when humidity reaches the set values.
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 3/16
dIXEL
Operating Instructions
cod. 1592017410
4.2 DEHUMIDIFYING ACTION WITHOUT DEHUMIDIFIER RELAY, OA1 DIFFERENT FROM DEH
In this case the dehumidifying action is performed by setting the following parameters in this way:
tHu = c-H kind of dehumidifying by means of heating and compressor relays oA1 different from dEH:
The heating and compressor outputs are activated together when humidity is higher than SET %RH+dbH value. Outputs are disabled when humidity comes back to the SET %RH value.
4.2.1 Relation between cooling, heating and dehumidifying
1. If is simultaneously present a request of cooling (temp>SET TEMP+dbt) and dehumidifying (RH > SET %RH+dbH): the cooling action has the priority over the dehumidifying action: only the compressor relay is energised till the SET TEMP is reached at this point also the heating relay is enabled.
2. If is simultaneously present a request of heating (temp< SET TEMP-dbt) and dehumidifying (RH > SET %RH+dbH): the dehumidifying action has the priority over the heating action: both the compressor and the heating relays are energised till the humidity set is reached at this point only the heating relay is enabled.
4.3 DEHUMIDIFYING ACTION WITH DEHUMIDIFIER RELAY, OA1 = DEH
The configurable relay is used, setting the parameter oA1 =dEH. NOTE: the LIGHT button is not more available; Two kinds of de-humidifying are available:
4.3.1 Dehumidifying action with ONLY de-humidifier relay
By setting the parameter tHu = db the de-humidifying action is performed by enabling the de-humidifier relay when the humidity is higher than SET %RH + dbH. The relay is switch off when humidity comes back to the SET %RH value.
4.3.2 Dehumidifying action with de-humidifier and compressor relays
By setting the parameter tHu = cHu the de-humidifying action is performed by enabling the de-humidifier and compressor relays together. when the humidity is higher than SET %RH + dbH. The relays are switched off when humidity comes back to the SET %RH value.
If is simultaneously present a request of cooling (temp>SET TEMP+dbt) and dehumidifying (RH > SET %RH+dbH): the cooling action has the priority over the dehumidifying action: only the compressor relay is energised till the SET TEMP is reached at this point also the de-humidifier is enabled.
5. FA NS
The fan control mode is selected by means of the “FnC” parameter: FnC=C-n fans will switch ON and OFF with the compressor and not run during defrost:; FnC= O-n fans will run continuously, but not during defrost FnC=C-y fans will switch ON and OFF with the compressor and run during defrost; FnC=O-y fans will run continuously also during defrost
6. EXTRACTOR FAN
6.1 EXTRACTOR FAN CYCLES
The second relay is configured as extractor fan, oA2= ESt, then it is possible to make extraction cycles, both manually and automatically.
Extraction cycle can be activated both manually by pushing the UP key for 3s, and automatically by the internal time rFi. Cycle duration is set by the rFd parameter. The cycle can be stopped also by key.
If rFI = 0 only manual cycle can be activated. If rFd = 0 the cycle is stopped only by pushing the key.
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 4/16
dIXEL
7. MATURING CYCLE WITH DRIPPING, RUNNING AND STOPPING PHASE.
Operating Instructions
cod. 1592017410
The diagrams displays a typical maturing cycle with the starting dripping phase.
DRIPPING PHASE lasts for the “dri” time, without humidity control, temperature set is SETG RUNNING PHASE lasts for the “on” time, both temperature and humidity are controlled. STOPPING PHASE lasts for the “off” time, without any control of temperature and humidity.
The end of the stopping phase is signalled by the internal buzzer and by the “End” message on the display.
After the STOPPING PHASE the behaviour of the controller depends on the parameter trc, according to the following settings:
7.1 HOW TO SET THE DURATION OF THE DRIPPING, RUNNING AND STOPPING PHASES
1. Push the CLOCK key, the display shows on the bottom display the “dri” message, while the “hourglass” start flashing.
2. Push again the CLOCK the duration of the dipping phase is shown, hh:mm.
3. To set the duration push the UP and DOWN keys.
4. Push again the CLOCK to confirm the time and pass to the setting of the running phase: the “on” message is displayed.
5. Push the CLOCK key to see its duration and use the UP and DOWN keys to set it.
6. Push again the CLOCK to confirm the time and pass to the setting of the stopping phase: the “oFF” message is displayed.
7. Push the CLOCK key to see its duration and use the UP and DOWN keys to set it.
8. Confirm the value by pushing again the CLOCK key and pass to the humidity display.
7.2 HOW TO SET THE TARGET HUMIDITY OF THE RUNNING CYCLE
1. Push the SET %RH key, the display shows on the bottom display the “SH1” message, while the “set” icon starts flashing.
2. Push again the SET %RH the humidity set point of the running phase is shown. Set it using the UP and DOWN keys. To disable the
3. Push again the SET %RH to confirm the value and pass to the humidity display.
7.3 HOW TO SET THE TARGET TEMPERATURE OF THE DRIPPING AND RUNNING PHASES
1. Push the SET TEMP key, the display shows on the upper display the “StG” message, while the “set ” icon starts flashing.
2. Push again the SET TEMP the temperature set point of the running phase is shown. Set it using the UP and DOWN keys.
3. Push again the SET TEMP to confirm the value and pass to the setting of the dripping phase: the “St1” message is displayed.
4. Push the SET TEMP key to see its value and use the UP and DOWN keys to set it.
7.4 HOW TO START THE CYCLE
Push and release START key: the led will be turned ON.
The
7.5 END OF THE CYCLE
When the timer has expired, the buzzer starts sounding and the bottom display shows the “End” message. To mute the buzzer push a key: The display come back to show the humidity and the LED of the START key is turned off.
7.6 HOW TO STOP THE CYCLE MANUALLY
To stop the cycle manually push the ON/OFF key
7.7 HOW TO MODIFY THE SETTING OF THE CURRENT CYCLE WHILE IT’S RUNNING
To modify the setting of the running cycle temperature (SET TEMP), humidity (SET %RH) or remaining time (CLOCK):
Dripping Running Stoppi ng Running Stopping
trc = co controller maintains the set points of the running phase trc = in controller stop the regulation at all. trc = cL controller performs the running and stopping phase till is stopped manually. trc = cLE as (trc = cL) plus at the end of each cycle the End label is displayed and the buzzer is switched on.
humidity control during the freezing phase set it to “nu”.
led flashes during the proving phase
.
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 5/16
dIXEL
1. Push twice the corespondent key: the setting value of the current phase (dripping or running) will be displayed.
2. Modify it using the UP and DOWN keys
3. Confirm the value using the corespondent key: temperature (SET TEMP), humidity (SET %RH) or remaining time (CLOCK).
NOTE: the changes made will be memorised. So the next cycle will start with the new values.
Operating Instructions
cod. 1592017410
8. THE DISPLAY
C
F
%RH
SET SET
To display and modify target temperature set point. (SET TEMP) for the running (St1)and the dripping (StG) phase.
To display and modify target humidity set point (SET %RH) of the running (SH1) phase; in programming mode it selects a parameter or confirm an operation.
In programming mode it browses the parameter codes or increases the displayed value. If oA2=ESt hold it pressed for 3s to start a extraction cycle
To start a manual defrost: hold it pressed for at least 3s. In programming mode it browses the parameter codes or decreases the displayed value.
Switch ON and OFF the light, if present (oA1=lig)
Start: to start the cycle
Clock: to set the duration of the dripping (dri), running (on) and stopping (off) phases
Switch ON and OFF the instrument.
KEY COMBINATIONS
+
+
+
8.1 ICONS AND SYMBOLS
Each LED function is described in the following table.
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 6/16
To lock and unlock the keyboard
To enter the programming mode.
To exit the programming mode.
dIXEL
LED MODE FUNCTION
°C °C °F °F
(umid)
ON
ON °C
FLASHING If measurement unit is °C, it flashing on programming mode
ON °F
FLASHING If measurement unit is °F, it flashing on programming mode
ON The compressor is running
FLASHING - Anti-short cycle delay enabled
ON The defrost is enabled
ON Heating enabled
FLASHING Temperature Set programming phase
ON - ALARM signal
ON Fan is running
ON RH%
ON Dehumidifying enabled
ON Humidifying enabled
FLASHING Humidity Set programming phase
ON Running phase is in progress FLASHING Dripping or stopping phase is in progress
FLASHING Setting of the duration of the cycle
Operating Instructions
- Instrument in stand by.
- In “Pr2” indicates that the parameter is also present in “Pr1”.
cod. 1592017410
8.2 HOW TO SEE AND MODIFY THE SET POINT (TEMPERATURE AND HUMIDITY)
1. Push and immediately release the SET key: the display will show the Set point
Or
valueand the correspondant set icon starts flashing;
2. To change the Set value push the o or n arrows within 10s.
3. To memorise the new set point value push the SET key again or wait 10s.
8.3 TO START A MANUAL DEFROST
1. Push the DEF key for more than 2 seconds and a manual defrost will start.
8.4 TO START A EXTRACTION CYCLE MANUALLY
Hold pushed the UP key for more than 2 sec. To stop manually the cycle: when the cycle is running, hold pushed the UP key for more than 2 sec.
8.5 TO ENTER IN PARAMETERS LIST “PR1”
To enter the parameter list “Pr1” (user accessible parameters) operate as follows:
1. Enter the Programming mode by pressing the SET %RH+ n for few
+
seconds. (°C or °F start flashing)
2. The instrument will show the first parameter present in “Pr1”
8.6 TO ENTER IN PARAMETERS LIST “PR2”
To access parameters in “Pr2”:
1. Enter the “Pr1” level.
2. Select “Pr2” parameter and press the “ SET %RH ” key.
3. The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero.
4. Use o or n to input the security code in the flashing digit; confirm the figure by pressing “ SET %RH ”.
The security code is “321“.
5. If the security code is correct the access to “Pr2” is enabled by pressing “ SET %RH ” on the last digit.
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 7/16
dIXEL
Another possibility is the following: after switching ON the instrument the user can push SET %RH + n keys within 30 seconds.
NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing SET %RH + n. When a parameter is present in “Pr1”
icon is on.
8.7 TO CHANGE PARAMETER VALUES
1. Enter the Programming mode.
2. Select the required parameter with o or n.
3. Press the “ SET %RH ” key to display its value (°C or °F icon start blinking).
4. Use o or n to change its value.
5. Press “ SET %RH ” to store the new value and move to the following parameter.
To exit: Press SET %RH + UP or wait 15s without pressing a key. NOTE: the new programming is stored even when the procedure is exited by waiting the time-out.
8.8 HOW TO LOCK THE KEYBOARD
8.9 ON/OFF FUNCTION
1. Keep the o and n keys pressed together for more than 3 s the o and n keys.
2. The “POF” message will be displayed and the keyboard is locked. At this point it is
only possible the viewing of the set point or the MAX o Min temperature stored and to switch ON and OFF the light, the auxiliary output and the instrument.
TO UNLOCK THE KEYBOARD
Keep the o and n keys pressed together for more than 3s.
By pushing the ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED is switched ON. During the OFF status, all the relays are switched OFF and the regulations are stopped;
N.B. During the OFF status the
Operating Instructions
icon is lighted.
cod. 1592017410
9. PARAMETER LIST
REGULATION
dbt half dead band width for temperature: (0,1÷25,5°C; 1÷45°F) this band is place below and above the temperature set point (SET
TEMP). The compressor is enabled when the temperature increases and reaches the SET TEMP + dbt value. It is turned off when it comes back to the SET TEMP. The heating output is enabled when temperature is less than SET TEMP -dbt value and disabled when the SET TEMP is reached.
dbH half dead band width for humidity: (0,5÷25,5RH) this band is place below and above the humidity set point (SET %RH). The
dehumidifying action is enabled when the humidity increases and reaches the SET %RH + dbH value. It is stopped when it comes back to the SET %RH. The humidifying output is enabled when humidity is less than SET %RH -dbH value and disabled when the SET %RH is reached.
LS Minimum temperature set point limit: (-50,0°C US Maximum temperature set point limit: (SET OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of the instrument and inhibits any output
activation for the period of time set in the parameter. (Light can work)
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following restart. tHu Kind of de-humidifying: db: only with de-humidifier relay (oA1= dEH); cHu with de-humidifier and compressor relay (oA1= dEH); c-H:
without de-humidifier relay, by means of compressor and heating relays (oA1 dEH). LSH Minimum humidity set point limit: (Lci ÷ Set H) Sets the minimum acceptable value for the humidity set point. uSH Maximum humidity set point limit: (Set H ÷ uci) Set the maximum acceptable value for humidity set point.
DISPLAY AND KIND OF REGULATION CF Measurement unit: °C= Celsius; °F= Fahrenheit
rES Resolution (for °C): allows decimal point display. dE = 0,1°C; in = 1 °C rEH Resolution for RH%: in = integer; Hd= half digit. trC Kind of behaviour after the end of the cycle trC=co the controller goes on working, and maintains the temperature and humidity of the running phase, till the controller is stopped. trC=in at the end of the stopping phase the controller gives the “End” message, the buzzer is turned on, and the regulation is stopped. trC=cL at the end of the stopping phase the controller gives the “End” message, the buzzer is turned on, and the regulation restarts from
the running phase
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 8/16
÷SET; -58°F÷SET) Sets the minimum acceptable value for the set point.
÷110°C; SET÷230°F) Set the maximum acceptable value for set point.
dIXEL
trC=cLE at the end of the stopping phase the regulation restarts from the running phase.
Operating Instructions
cod. 1592017410
DEFROST tdF Defrost type: rE = electrical heater (Compressor OFF); in = hot gas (Compressor and defrost relays ON)
EdF Defrost mode: in = interval mode. The defrost starts when the time “Idf” is expired; Sd=Smartfrost mode. The IdF time (interval
between defrosts) is increased only when the compressor is running (even non consecutively). SdF Set point for SMARTFROST: (-30
÷30 °C/ -22÷86 °F) evaporator temperature which allows the IdF counting (interval between defrosts) in
SMARTFROST mode. dtE Defrost termination temperature: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator probe is present) sets the
temperature measured by the evaporator probe which causes the end of defrost.
IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two defrost cycles. MdF Duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the defrost duration, when P2P = y, defrost end based on
temperature, it sets the maximum length for defrost.
dFd Display during defrost: rt = real temperature; it = temperature reading at the defrost start; Set set point; dEF = “dEF” label; dEG = “dEG” label; dAd Defrost display time out: (0
÷255 min) Sets the maximum time between the end of defrost and the restarting of the real room temperature
display. Fdt Drain down time: (0÷60 min.) time interval between reaching defrost termination temperature and the restoring of the control’s normal
operation. This time allows the evaporator to eliminate water drops that might have formed due to defrost.
dPO First defrost after start-up: y = Immediately; n = after the IdF time Hud Humidity control during defrost: no: the humidity control is stopped during the defrost; yES the humidity control works also during the
defrost.
FANS FnC Fan operating mode: C-n = running when a load is on, OFF during the defrost; C-y = running when a load is on, ON during the defrost;
O-n = continuous mode, OFF during the defrost; O-y = continuous mode, ON during the defrost; EXTRACTOR FANS rFi Interval between 2 cycles of change of air (0÷120 ore; 0 = only manual starting)
rFd Duration of change of air cycle (0÷250min; 0 = only manual stopping)
TEMPERATURE ALARMS ALC Temperature alarm configuration: rE = High and Low alarms related to Set Point; Ab = High and low alarms related to the absolute
temperature. ALL Low temperature alarm setting: ALC = rE , 0
÷ 50 °C or 90°F; ALC = Ab , - 50°C or -58°F ÷ ALU; when this temperature is reached
and after the ALd delay time, the LA alarm is enabled,. ALU High temperature alarm setting: ALC= rE, 0
after the ALd delay time the HA alarm is enabled. ALH Temperature alarm recovery differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for recovery of temperature alarm.
÷ 50°C or 90°F; ALC= Ab, ALL ÷ 110°C or 230°F; when this temperature is reached and
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition and the corresponding alarm signalling. dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection of the temperature alarm condition after
the instrument power on and the alarm signalling. EdA Alarm delay at the end of defrost: (0
÷255 min) Time interval between the detection of the temperature alarm condition at the end of
defrost and the alarm signalling. dot Delay of temperature alarm after closing the door : (0
÷255 min) Time delay to signal the temperature alarm condition after closing the
door.
HUMIDITY ALARMS AHC Humidity alarm configuration: rE = High and Low alarms related to humidity Set Point ; Ab= High and low alarms related to the
“absolute” humidity. AHL Low humidity alarm setting: (with AHC = rE: 0 ÷ 50. With AHC = Ab: Lci ÷ AHu) when this humidity is reached and after the AHd delay time, the HLA alarm is enabled,. AHu High humidity alarm setting: (with AHC = rE: 0÷50°C. with AHC = Ab: AHL ÷ uci when this humidity is reached and after the AHd delay time the HHA alarm is enabled.
AHH Humidity alarm recovery differential: (0.5÷20.0) Intervention differential for recovery of humidity alarm. AHd Humidity alarm delay: (0÷255 min) time interval between the detection of an alarm condition and the corresponding alarm signalling. dHo Delay of humidity alarm at start-up: (0min÷23h 50min) time interval between the detection of the humidity alarm condition after the
instrument power on and the alarm signalling. doH Alarm delay at the end of defrost: (0
÷255 min) Time interval between the detection of the humidity alarm condition at the end of defrost
and the alarm signalling. doA Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and its alarm signalling: the flashing
message “dA” is displayed.
tbA Alarm relay status after pushing a key: on= the relay remains on; off= the relay is switched off. nPS Pressure switch number: (0
(I1F= PAL). If the nPS activation in the “did” time is reached, switch off and on the instrument to restart normal regulation.
÷15) Number of activation of the pressure switch, during the “did” interval, before signalling the alarm event
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 9/16
dIXEL
Operating Instructions
cod. 1592017410
PROBE INPUTS Ot Thermostat probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offset of the thermostat probe.
OE Evaporator probe calibration: (-12.0
÷12.0°C/ -21÷21°F) allows to adjust possible offsets of the evaporator probe.
O3 Humidity probe calibration: (-10÷10 RH) allows to adjust possible offsets of the humidity probe. P2P Evaporator probe presence: n= not present: the defrost stops only by time; y= present: the defrost stops by temperature and time. P3P Humidity probe presence: n= not present; y= present. LCI Readout with 4 mA : (-999 ÷ 999). Adjustment of read out corresponding to 4mA signal. UCI Readout with 20 mA : (-999 ÷ 999). Adjustment of read out corresponding to 20mA signal.
DIGITAL INPUTS i1P Configurable digital input polarity: CL : the digital input is activated by closing the contact; OP : the digital input is activated by
opening the contact; i1P Door switch digital input polarity: CL : the digital input is activated by closing the contact; OP : the digital input is activated by
opening the contact i1F Digital input operating mode: configure the digital input function: EAL = generic alarm; bAL = serious alarm mode; PAL = Pressure
switch; Ht = heating relay safety; dor = door switch
odc Outputs status when open door: on = normal; Fan = Fan OFF; oFF = all the loads off rrd Outputs restarting after doA alarm: no = outputs not affected by the doA alarm; yES = outputs restart with the doA alarm; did Time interval/delay for digital input alarm:(0
÷255 min.) Time interval to calculate the number of the pressure switch activation when
I1F=PAL. If I1F=EAL or bAL (external alarms), “did” parameter defines the time delay between the detection and the successive signalling
of alarms.
OTHER oA1 Light relay configuration: ALr = alarm; dEH = dehumidifier; onF = on/off relay: close with instrument on, open with instrument off; Lig =
light, ESt, dEF not select oA2 Configuration of the defrost / extractor fans relay dEH = not select; onF = on/off relay: close with instrument on; open with instrument
on; Lig =Light , ESt = extractor fan; dEF = defrost relay. Adt RS485 serial address for temperature loads (0÷247) identifies the instrument within a control or supervising system. AdH RS485 serial address for humidity loads (0÷247) identifies the instrument within a control or supervising system. Ptb Parameter table: (read only) it shows the original code of the dIXEL parameter map. rEL Software release: (read only) Software version of the microprocessor. Prd Probes display: (read only) display the temperature values of the evaporator probe Pb2. Pr2 Access to the protected parameter list (read only).
10. DIGITAL INPUT
One digital input is present configurable by user by means of the i1F parameter according to the following descriptions.
10.1 DOOR SWITCH (I1F = dor)
It signals the door status and the corresponding relay output status through the “odc” parameter: no = normal (any change); Fan = Fan OFF; oFF = all the loads are switched off.
Since the door is opened, after the delay time set through parameter “dOA”, the alarm output is enabled and the display shows the message “dA”. The status of loads depends on the “rrd” parameter:
with rrd=no outputs are not affected by the doA alarm;
with rrd=yES = outputs restart with the doA alarm; The alarm stops as soon as the external digital input is disabled again. During this time and then for the delay “dot” and “doH” after closing the door, the temperature and humidity alarms are disabled.
10.2 GENERIC ALARM (I1F = EAL)
As soon as the digital input is activated the unit will wait for “did” time delay before signalling the “EAL” alarm message. The outputs status don’t change. The alarm stops just after the digital input is de-activated.
10.3 SERIOUS ALARM MODE (I1F = BAL)
When the digital input is activated, the unit will wait for “did” delay before signalling the “bAL” alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated.
10.4 PRESSURE SWITCH (I1F = PAL)
If during the interval time set by “did” parameter, the pressure switch has reached the number of activation of the “nPS” parameter, the “PAL” pressure alarm message will be displayed. The compressor and the regulation are stopped. When the digital input is ON the compressor is always OFF.
If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation.
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 10/16
dIXEL
Operating Instructions
cod. 1592017410
10.5 HEATING RELAY SAFETY (i1F=Ht)
With i1F=Ht as soon as the digital input is activated for “did” time heating relay is disabled. The alarm will stop as soon as the digital input is de-activated.
10.6 DIGITAL INPUTS POLARITY
The digital input polarity depends on the “i1P” parameters. CL : the digital input is activated by closing the contact; OP : the digital input is activated by opening the contact
11. INSTALLATION AND MOUNTING
The temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let the air circulate by the cooling holes.
Thanks to the case XLH360. See the following instructions for details.
GF
F
G
D E
A BC
FIG. 1
87
H
M
A
X
3
7
C
B
D
A
FIG. 2
230
I
M
130
120
210
A
2
X
8
FIG. 3
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 11/16
dIXEL
A
Operating Instructions
200
cod. 1592017410
61
1
0
6
.
4
4
°
0
0172
Fig. 6
200
0
11.1 WALL MOUNTING
1. Unscrew the 4 frontal screws (Fig. 1, A, B, F, G) and remove the cover (Fig. 1, C).
2. Unscrew the 2 screws (Fig. 1, D, E) that keep connected the frontal and lower parts of Cool Mate and separate the 2 parts.
3. Make the proper holes for cablepresses or pipepresses using the centres signed in the bottom cover of the Cool Mate, (Fig. 3, H, I, ). Then
make 3 holes in the wall, as indicated in (Fig. 3, L, M, N), to fix the Cool Mate
4. Fix the cablepresses and the pipepresses..
5. Insert the wall-nugs, contained in the kit, into the holes made in the wall. Then use the o-rings and fix the back part of the Cool Mate (Fig. 3,
L, M, N) by means of the 3 screws to the wall itself.
6. Insert the wiring cables in cablepresses or in the pipepresses.
7. Mount the frontal part using the previous 4 screws Fig. 1, D, E, F, G. (do not press excessively in order to avoid plastic deformation).
8. After connecting the wires to the terminal blocks close the cover (Fig. 2, c) and fix it by the screws.
185
192.5
61
12
6
14.5
22.5
29.5
1
0
6
.
4
4
°
8.5
0 4
11
Fig. 5
Fig. 4
8
.
5
5
R
R
5
190 186 179
175.5
167.5
160.55
19018
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 12/16
dIXEL
11.2 PANEL MOUNTING
1. Make a hole in the panel with dimensions described in Fig. 4 (simplified) or Fig. 5 (completed)
2. Unscrew the 4 frontal screws (Fig. 1, A, B, F, G) and remove the cover (Fig. 1, C).
3. Unscrew the 2 screws (Fig. 1, D, E) that keep connected the frontal and lower parts of Cool Mate and separate the 2 parts.
4. Cut from the back part of the Cool Mate the teeth indicated in Fig. 6, A.
5. Make the proper holes for cablepresses or pipepresses using the centres signed in the bottom cover of the Cool Mate, (Fig. 3, H, I, ).
6. Fix the cablepresses and the pipepresses..
7. Insert the wiring cables in cablepresses or in the pipepresses.
8. Join the back and frontal parts, with the panel in the middle, and fix them screwing the 4 screws taken previously away (dimensions 4x35
mm), in the holes of Fig. 1, A, B, D, E. Maximum panel thickness: 6mm.
9. After connecting the wires to the terminal blocks close the cover (Fig. 2, c) and fix it by the screws.
Operating Instructions
cod. 1592017410
12. DIMENSIONS
210 87
230
13. ELECTRICAL CONNECTIONS
The instruments are provided with screw terminal block to connect cables with a cross section up to 2,5 mm2. Heat-resistant cables have to be used. Before connecting cables make sure the power supply complies with the instrument’s requirements. Separate the probe cables from the power supply cables, from the outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external relay.
13.1 PROBE CONNECTIONS
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature.
14. HOW TO USE THE HOT KEY
14.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
2. When the controller is ON
3. Push “SET” key and the End will stop flashing.
4. Turn OFF
NOTE: the “Err” message is displayed for failed programming. In this case push again o key if you want to restart the upload again or remove the “Hot key” to abort the operation.
14.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON.
3. Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the “doL” message is blinking followed a by
4. After 10 seconds the instrument will restart working with the new parameters.
5. Remove the “Hot Key”..
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 13/16
the instrument remove the “Hot Key”, then turn it ON again.
flashing “End”.
, insert the “Hot key” and push o key; the "uPL" message appears followed a by flashing “End”
dIXEL
NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then on if you want to restart the download again or remove the “Hot key” to abort the operation.
Operating Instructions
cod. 1592017410
15. ALARM SIGNALLING
Message Cause Outputs
“P1” Thermostat probe failure Compressor and heating outputs off “P2” Evaporator probe failure Defrost and by time “P3” Humidity probe failure Humidity regulation off
“HA” High temperature alarm Outputs unchanged
“LA” Low temperature alarm Outputs unchanged “HHA” High humidity alarm Outputs unchanged “HLA” Low humidity alarm Outputs unchanged
“dA” Door switch alarm Outputs depending on the odC parameter “EAL” External alarm Other outputs unchanged “BAL” Serious external alarm Outputs OFF “PAL” Pressure switch alarm Outputs OFF
The alarm message is displayed until the alarm condition recoveries. All the alarm messages are showed alternating with the room temperature except for the “P1” which is flashing. To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is displayed for about 3s.
15.1 SILENCING BUZZER
Once the alarm signal is detected the buzzer, if present, can be silenced by pressing any key.
15.2 ALARM RECOVERY Probe alarms : “P1” (probe1 faulty), “P2”, “P3”; they automatically stop 10s after the probe restarts normal operation. Check connections before
replacing the probe.
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal values or when the defrost starts. Humidity alarms “HHA” and “LHA” automatically stop as soon as the humidity returns to normal values. Door switch alarm “dA” stop as soon as the door is closed. External alarms “EAL”, “BAL” stop as soon as the external digital input is disabled Pressure switch alarm PAL” alarm is recovered by switching OFF the instrument.
10. TECHNICAL DATA
Housing: self extinguishing ABS; Case: frontal 210x230 mm; depth 87mm; Mounting: See par. 11; Protection: IP65 Connections: Screw terminal block 2,5 mm Power supply: 230Vac 50/60Hz Display:3 digits, red LED, 30.5 mm high. 3 digits, yellow LED low. Inputs: 2 NTC, 1 input 4 ÷ 20mA;
Digital inputs : Door switch and configurable, free voltage. Max. distance 10m;
Relay outputs:
compressor: relay SPST 20(8) A, 250Vac; defrost or extraction fans: relay SPDT 16(3) A, 250Vac fans: relay SPST 8(3) A, 250Vac;
heater control: relay SPDT 20 A, 250Vac; Humidifying: relay SPST 8 A, 250Vac Light / De- humidifying: relay SPST 16 A, 250Vac Other output :
Alarm buzzer (Standard) Direct RS485 (optional)
Serial output : TTL standard Communication protocol: Modbus - RTU Data storing: on the non-volatile memory (EEPROM). Internal clock back-up: 24 hours Kind of action: 1B; Pollution grade: normal; Software class: A. Operating temperature: 0÷60 °C. Storage temperature: -25÷60 °C. Relative humidity: 20 Measuring and regulation range: NTC probe: -40÷110°C (-58÷230°F) Resolution: 0,1 °C or 1°C or 1 °F (selectable). Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 14/16
± 10% or 110Vac 50/60Hz ± 10%; Power absorption: 10VA max.
÷85% (no condensing)
2
wiring.
dIXEL
16. XLH360 WIRING CONNECTIONS
Operating Instructions
cod. 1592017410
HO T K E Y
1234567891011121314 1516 17 18 19 2021 222 3 24 25 26 2728 29 30 31 33 34
Conf. Do o r
35 36
RS 48 5
12 V§ gnd
4÷20mA
Input
In
Evap.
20A 250V
16 F LA (9 6LRA)
20 A 2 50 V
16 FLA ( 96L RA)
Room
Co m p
Heater Hum
NC
16A
250V~
Extr.
Def
16A
250V~8A250V~
Light
De-
Hu m
2 50V
8A
Fa n
~
NC
Supply
120/230V~
NLine
110 Vac Power Supply: connect to 33-34 terminals
17. DEFAULT SETTING VALUES
Set temperature Set humidity Duration
Dripping Phase 5.0 °C - - 5.00 h Running Phase 5.0 °C 50.0 RH% 5.00 h Stopping Phase - - 5.00 h
Label Value Menu Description Range
dbt
dbH
LS uS
odS
Ac
tHu c-H Pr2 Humidity regulation
LSH uSH
cF rES rEH
trC
tdF EdF SdF
dtE
idF
MdF
dFd dAd
Fdt dPo Hud Fnc
rFi
rFd ALc ALL ALu
ALH
ALd dAo
EdA
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 15/16
2.0 Pr1 Half dead band width for temperature 0.1°C o 1°F ÷ 25°C o 77°F
5.0 Pr1 Half dead band width for humidity 0.5 ÷ 50
-40.0 Pr2 Minimum temperature set point limit -50.0°C o –58°F ÷ Set T 110 Pr2 Maximum temperature set point limit Set T ÷ 110°C o 230°F
1 Pr2 Outputs activation delay at start up 0 ÷ 250 min 1 Pr1 Anti-short cycle delay 0 ÷ 30 min
db = dehumidifier relay.; cHu = dehum+
compr.; c-H= without dehum. relay
0.0 Pr2 Minimum humidity set point limit Lci ÷ Set H
100 Pr2 Maximum humidity set point limit Set H ÷ uci
°C Pr2 Measurement unit °C ÷°F dE Pr2 Resolution (for °C): in = integer / dE = decimal Hd Pr2 Resolution for RH%: in = integer / Hd = half digit
co=start holding, in=stop regulation,
co Pr2 Instrument behaviour at the end of the cycle
cL=restart the first phase+End message; cLE
= restart the first phase
rE Pr2 Defrost type rE, rT, in
in Pr2 Defrost mode In, Sd
0.0 Pr2 Set point for SMART DEFROST -30 ÷ +30°C / -22÷+86°F
8.0 Pr2 Defrost termination temperature -50,0÷110°C/ -58÷230°F
6 Pr1 Interval between defrosts 1 ÷ 120 h
20 Pr1 Duration of defrost 0 ÷ 250 min
it Pr2 Display during defrost rt / it / SEt / dEF / dEG
30 Pr2 Defrost display time out 0 ÷ 250 min
0 Pr2 Draining time 0÷60 min. no Pr2 First defrost after start up n ÷ y no Pr2 Humidity control during defrost no; yES
c-n Pr2 Fan operating mode c-n / c-Y / o-n / o-Y
0 Pr2 Interval between 2 cycles of change of air 1 ÷ 120 h (0 = manual start)
0 Pr2 Duration of cycle of change of air 1 ÷ 250 min (0 = manual stop)
Ab Pr2 Temperature alarm configuration rE = relative / Ab = absolute
-40.0 Pr1 Low temperature alarm setting 0°C ÷ 50.0°C / -50.0°C ÷ ALu 110 Pr1 High temperature alarm setting 0°C ÷ 50.0°C / ALL ÷ 110°C
1.0 Pr2 Temperature alarm recovery differential 0.1°C o 1°F ÷ 25°C o 77°F 15 Pr2 Temperature alarm delay 0 ÷ 250 min
1.3 Pr2 Delay of temperature alarm at start-up 0.0 ÷ 23.5 h 20 Pr2 Alarm delay at the end of defrost 0 ÷ 250 min
dIXEL
Label Value Menu Description Range
dot AHc AHL AHu AHH AHd
dHo doH doA
tbA
nPS
ot oE o3
P2P P3P
Lci uci i1P i2P
i1F
odc
rrd
did
oA1 LiG Pr2 Light relay configuration 1
oA2 ESt Pr2 Light relay configuration 2
Adt
AdH
Ptb rEL Prd Pr2
20 Pr2 Delay of temperature alarm after closing the door 0 ÷ 250 min
Ab Pr2 Humidity alarm configuration rE = relative / Ab = absolute
0.0 Pr1 Low humidity alarm setting 0 ÷ 50 / Lci ÷ AHu
100 Pr1 High humidity alarm setting 0 ÷ 50 / AHL ÷ uci
2.0 Pr2 Humidity alarm recovery differential 0.5 ÷ 25 15 Pr2 Humidity alarm delay 0 ÷ 250 min
1.3 Pr2 Delay of humidity alarm at start-up 0.0 ÷ 23.5 h 20 Pr2 Alarm delay at the end of defrost 0 ÷ 250 min 20 Pr2 Open door alarm delay 0 ÷ 250 min ( 250 = nu )
oFF Pr2 Relay status after pushing a key on÷oFF
15 Pr2 Pressure switch number 0÷15
0.0 Pr1 Thermostat probe calibration -12.0 ÷ 12.0
0.0 Pr2 Evaporator probe calibration -12.0 ÷ 12.0
0.0 Pr1 Humidity probe calibration -10 ÷ 10
YES Pr2 Evaporator probe presence no = absent / YES = present YES Pr2 Humidity probe presence no = absent / YES = present
0.0 Pr2 Readout with 4 mA -999 ÷ 999
100 Pr2 Readout with 20 mA -999 ÷ 999
cL Pr2 Configurable digital input polarity cL =open / oP = close cL Pr2 Door switch digital input polarity cL =open / oP = close
dor Pr2 Digital input configuration dor / PAL / EAL / bAL / Ht FAn Pr2 Outputs status when open door on / Fan / oFF YES Pr2 Outputs restarting after doA alarm no = no / YES = yes
0 Pr2 Digital input alarm delay 0÷255 min.
1 Pr2 1 Pr2
- - - Pr2 Parameter table - - -
- - - Pr2 Software release - - -
- - - Pr2 Probes display Pb1÷Pb3
- - - Pr1 Access to the protected parameter list - - -
Operating Instructions
ALr = alarm; dEH = dehumidifier; onF =
on/off; Lig = light, ESt, dEF not select
ALr = alarm; dEH = not use; onF = on/off; Lig = light, ESt= extractor, dEF =defrost
Serial address for temperature 0÷247 num Serial address for humidity 0÷247 num
cod. 1592017410
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 16/16
Loading...