dixell COOL MATE XLH360 Operating Instructions Manual

dIXEL
Temperature and humidity controller
Operating Instructions
for seasoning-maturing cabinets
cod. 1592017410
XLH360
COOL MATE
Operating Instructions
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 1/16
dIXEL
Operating Instructions
cod. 1592017410
COOLMATE
XLH360
INDICE
1. GENERAL WARNING__________________________________________________________ 3
2. GENERAL DESCRIPTION ______________________________________________________ 3
3. TEMPERATURE REGULATION__________________________________________________ 3
4. HUMIDITY REGULATION ______________________________________________________ 3
5. FA NS ______________________________________________________________________ 4
6. EXTRACTOR FAN ____________________________________________________________ 4
7. MATURING CYCLE WITH DRIPPING, RUNNING AND STOPPING PHASE. ______________ 5
8. THE DISPLAY________________________________________________________________ 6
9. PARAMETER LIST ____________________________________________________________ 8
10. DIGITAL INPUT _____________________________________________________________ 10
11. INSTALLATION AND MOUNTING _______________________________________________ 11
12. DIMENSIONS _______________________________________________________________ 13
13. ELECTRICAL CONNECTIONS _________________________________________________ 13
14. HOW TO USE THE HOT KEY __________________________________________________ 13
15. ALARM SIGNALLING _________________________________________________________ 14
10. TECHNICAL DATA ___________________________________________________________ 14
16. XLH360 WIRING CONNECTIONS _______________________________________________ 15
17. DEFAULT SETTING VALUES __________________________________________________ 15
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 2/16
dIXEL
Operating Instructions
cod. 1592017410
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device.
Check the application limits before proceeding.
1.2
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high
atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.” (see address) with a detailed description of
the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough from each other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with inductive loads could be useful.
2. GENERAL DESCRIPTION
The XLH360 is microprocessor controller, suitable for applications on medium or low temperature refrigerating units. It has 6 output relays to control compressor, heating elements, defrost/extractor fan, fan, de-humidifier/light and humidifier. It has 2 NTC inputs one for thermostat the other one for defrost. It’s also present a 4÷20mA input for humidity. There is one digital input (free contact) configurable by parameter. An output allows the user to program the parameter list with the “Hot Key”.
3. TEMPERATURE REGULATION
The temperature regulation is performed through neutral zone using compressor and heater output relays.
ON
OFF
Heating output: CUT IN is “SET TEMP-dbt”, CUT OUT is when the temperature reaches the set point.
Set point
Compressor output CUT IN is “ SET TEMP +dbt”, CUT OUT is when the temperature reaches the set point.
3.1 DEFROST
During defrost the temperature control is disabled.
If the second relay is configured as defrost: oA2=dEF then two defrost modes are available through the “tdF” parameter: defrost with electrical heater (tdF=rE) or hot gas (tdF= in). The defrost interval is control by means of parameter “EdF”: (EdF=in) the defrost is made every “IdF” time, (EdF=Sd) the interval “IdF” is calculate through Smart Defrost algorithm (only when the compressor is ON). At the end of defrost dripping time is started, set by “Fdt” parameter. To disable the defrost set the MdF parameter to zero
If oA2 is different from dEF, defrost is made only by stopping compressor (tdF=rE). To disable defrosts set MdF=0.
Humidity regulation during defrost depends on the Hud parameter. With Hud=no humidity regulation is disabled. Con Hud=yES humidity regulation is performed also during defrost.
4. HUMIDITY REGULATION
The humidity regulation is performed through neutral zone, by humidifying dehumidifying actions. Humidity control can be disabled setting the SET %RH to “nu” value. In this case only the temperature control is perform.
4.1 HUMIDIFYING ACTION
The humidifying action is done enabling the humidifier relay when the humidity is lower than the “SET %RH-dbH” value. The relay is switch off when humidity reaches the set values.
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 3/16
dIXEL
Operating Instructions
cod. 1592017410
4.2 DEHUMIDIFYING ACTION WITHOUT DEHUMIDIFIER RELAY, OA1 DIFFERENT FROM DEH
In this case the dehumidifying action is performed by setting the following parameters in this way:
tHu = c-H kind of dehumidifying by means of heating and compressor relays oA1 different from dEH:
The heating and compressor outputs are activated together when humidity is higher than SET %RH+dbH value. Outputs are disabled when humidity comes back to the SET %RH value.
4.2.1 Relation between cooling, heating and dehumidifying
1. If is simultaneously present a request of cooling (temp>SET TEMP+dbt) and dehumidifying (RH > SET %RH+dbH): the cooling action has the priority over the dehumidifying action: only the compressor relay is energised till the SET TEMP is reached at this point also the heating relay is enabled.
2. If is simultaneously present a request of heating (temp< SET TEMP-dbt) and dehumidifying (RH > SET %RH+dbH): the dehumidifying action has the priority over the heating action: both the compressor and the heating relays are energised till the humidity set is reached at this point only the heating relay is enabled.
4.3 DEHUMIDIFYING ACTION WITH DEHUMIDIFIER RELAY, OA1 = DEH
The configurable relay is used, setting the parameter oA1 =dEH. NOTE: the LIGHT button is not more available; Two kinds of de-humidifying are available:
4.3.1 Dehumidifying action with ONLY de-humidifier relay
By setting the parameter tHu = db the de-humidifying action is performed by enabling the de-humidifier relay when the humidity is higher than SET %RH + dbH. The relay is switch off when humidity comes back to the SET %RH value.
4.3.2 Dehumidifying action with de-humidifier and compressor relays
By setting the parameter tHu = cHu the de-humidifying action is performed by enabling the de-humidifier and compressor relays together. when the humidity is higher than SET %RH + dbH. The relays are switched off when humidity comes back to the SET %RH value.
If is simultaneously present a request of cooling (temp>SET TEMP+dbt) and dehumidifying (RH > SET %RH+dbH): the cooling action has the priority over the dehumidifying action: only the compressor relay is energised till the SET TEMP is reached at this point also the de-humidifier is enabled.
5. FA NS
The fan control mode is selected by means of the “FnC” parameter: FnC=C-n fans will switch ON and OFF with the compressor and not run during defrost:; FnC= O-n fans will run continuously, but not during defrost FnC=C-y fans will switch ON and OFF with the compressor and run during defrost; FnC=O-y fans will run continuously also during defrost
6. EXTRACTOR FAN
6.1 EXTRACTOR FAN CYCLES
The second relay is configured as extractor fan, oA2= ESt, then it is possible to make extraction cycles, both manually and automatically.
Extraction cycle can be activated both manually by pushing the UP key for 3s, and automatically by the internal time rFi. Cycle duration is set by the rFd parameter. The cycle can be stopped also by key.
If rFI = 0 only manual cycle can be activated. If rFd = 0 the cycle is stopped only by pushing the key.
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 4/16
dIXEL
7. MATURING CYCLE WITH DRIPPING, RUNNING AND STOPPING PHASE.
Operating Instructions
cod. 1592017410
The diagrams displays a typical maturing cycle with the starting dripping phase.
DRIPPING PHASE lasts for the “dri” time, without humidity control, temperature set is SETG RUNNING PHASE lasts for the “on” time, both temperature and humidity are controlled. STOPPING PHASE lasts for the “off” time, without any control of temperature and humidity.
The end of the stopping phase is signalled by the internal buzzer and by the “End” message on the display.
After the STOPPING PHASE the behaviour of the controller depends on the parameter trc, according to the following settings:
7.1 HOW TO SET THE DURATION OF THE DRIPPING, RUNNING AND STOPPING PHASES
1. Push the CLOCK key, the display shows on the bottom display the “dri” message, while the “hourglass” start flashing.
2. Push again the CLOCK the duration of the dipping phase is shown, hh:mm.
3. To set the duration push the UP and DOWN keys.
4. Push again the CLOCK to confirm the time and pass to the setting of the running phase: the “on” message is displayed.
5. Push the CLOCK key to see its duration and use the UP and DOWN keys to set it.
6. Push again the CLOCK to confirm the time and pass to the setting of the stopping phase: the “oFF” message is displayed.
7. Push the CLOCK key to see its duration and use the UP and DOWN keys to set it.
8. Confirm the value by pushing again the CLOCK key and pass to the humidity display.
7.2 HOW TO SET THE TARGET HUMIDITY OF THE RUNNING CYCLE
1. Push the SET %RH key, the display shows on the bottom display the “SH1” message, while the “set” icon starts flashing.
2. Push again the SET %RH the humidity set point of the running phase is shown. Set it using the UP and DOWN keys. To disable the
3. Push again the SET %RH to confirm the value and pass to the humidity display.
7.3 HOW TO SET THE TARGET TEMPERATURE OF THE DRIPPING AND RUNNING PHASES
1. Push the SET TEMP key, the display shows on the upper display the “StG” message, while the “set ” icon starts flashing.
2. Push again the SET TEMP the temperature set point of the running phase is shown. Set it using the UP and DOWN keys.
3. Push again the SET TEMP to confirm the value and pass to the setting of the dripping phase: the “St1” message is displayed.
4. Push the SET TEMP key to see its value and use the UP and DOWN keys to set it.
7.4 HOW TO START THE CYCLE
Push and release START key: the led will be turned ON.
The
7.5 END OF THE CYCLE
When the timer has expired, the buzzer starts sounding and the bottom display shows the “End” message. To mute the buzzer push a key: The display come back to show the humidity and the LED of the START key is turned off.
7.6 HOW TO STOP THE CYCLE MANUALLY
To stop the cycle manually push the ON/OFF key
7.7 HOW TO MODIFY THE SETTING OF THE CURRENT CYCLE WHILE IT’S RUNNING
To modify the setting of the running cycle temperature (SET TEMP), humidity (SET %RH) or remaining time (CLOCK):
Dripping Running Stoppi ng Running Stopping
trc = co controller maintains the set points of the running phase trc = in controller stop the regulation at all. trc = cL controller performs the running and stopping phase till is stopped manually. trc = cLE as (trc = cL) plus at the end of each cycle the End label is displayed and the buzzer is switched on.
humidity control during the freezing phase set it to “nu”.
led flashes during the proving phase
.
1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 5/16
Loading...
+ 11 hidden pages