BOILER PUMP
BOILER PUMP BOILER PUMP
BOILER PUMP
Boiler Pump
NAME OF EACH COMPONENT
GENERAL FEATURES OF
INSTALLATION GUIDE
SPECIFICATIONS
Condensate Removal Pump Condensate Removal Pump Condensate Removal Pump
Cover
Check Valve
Main Plate
Inlet Hole of Drain Hose
Reservoir
The DiversiTech Boiler Pump is designed to automatically remove the water produced by
condensing furnace and boilers that produce high temperature condensate. Can also be
used for air conditioning evaporation coils, especially when high li is required. These pumps
can also be used for other types of fresh water removal from refrigeration equipment,
dehumidiers, water dispensers, etc. where gravity drainage is impossible.
High performance pump - up to 46’ of li
Up to 212 degrees Fahrenheit condensate
Flame retardant and high impact plastic construction
Low noise motor with thermal protector
Stainless steel pump sha
90 degree turn check valve for easy servicing
WARNING
1. DO NOT USE TO PUMP FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS GASOLINE, FUEL OIL, ALCOHOL, ETC.
2. DO NOT USE IN EXPLOSIVE ATMOSPHERES
3. DO NOT HANDLE PUMP WITH WET HANDS OR WHEN STANDING ON A WET OR DAMP SURFACE OR IN
WATER
4. RISK OF ELECTRIC SHOCK THIS PUMP IS SUPPLIED WITH A GROUNDING CONDUCTOR AND
GROUNDINGTYPE ATTACHMENT PLUG. TO REDUCE THE RISK OF ELECTRIC SHOCK, BE CERTAIN THAT IT IS
CONNECTED ONLY TO A PROPERLY GOUNDED, GROUNDINGTYPE RECEPTACLE.
5. CONNECT THE PUMP ONLY TO THE POWER SUPPLY SPECIFIED ON THE NAMEPLATE OF THE PUMP
6. IN ANY INSTALLATION WHERE PROPERTY DAMAGE AND/OR PERSONAL INJURY MIGHT RESULT FROM AN
INOPERATIVE PUMP, A BACKUP SYSTEM AND/OR ALARM SHOULD BE USED
7. DO NOT TWIST THE DRAIN HOSE AND DISCHARGE HOSE
8. BEFORE ANY MAINTENANCE OR REPAIR OF THE PUMP PLEASE DISCONNECT THE PUMP FROM THE
POWER SUPPLY TO AVOID AN ELECTRICAL SHOCK
9. KEEP CHILDREN AWAY FROM THE PUMP
10. THIS IS NOT A SUBMERSIBLE PUMP
11. ALL SERVICE AND INSTALLATION SHOULD BE DONE BY A QUALIFIED SERVICE TECHNICIAN
12. THE INTERMITTENT RATING OF THIS PUMP IS NOT LONGER THAN 5 MINUTES
BP-46
114 Gal/Hr
1. This condensate pump is designed for pumping away condensate from condensing
boilers, PRV discharge and high temperature water up to 212°F. The pump is controlled
by a oat / switch mechanism which turns the pump on to discharge the condensate
when approximately .7 gallons of condensate collects in the tank. The pump switches o
automatically when the tank drains to approximately .3 gallons, giving a drink cycle of .4
gallons.
2. This pump is carefully packaged, inspected and tested to ensure safe operation and
delivery. When you receive the pump, examine it carefully to determine that there are
no broken or damaged parts that may have occurred during shipment. If damage has
occurred, please contact your supplier. They will assist you in replacement or repair, if
required.
3. Read the instructions carefully before attempting to install, operate or service the pump.
Know the pump application, limitations and potential hazards. Protect yourself and
others by observing all safety information. Failure to comply with instructions could result
in personal injury and/or property damage! Please retain these instructions for future
reference. Installation and connections are to be made by a qualied person.
4. If installed for combined boiler condensate & PRV discharge, this pump is only suitable for
boilers up to 143MBH.
46’
Model
Max Flow
Max Head
Tank Capacity
Volts
Hz
Discharge Size
High-level Alarm
1 Gal
230V/1A
60 Hz
3/8”
240VAC , 3A dry contact
9.8”
Overall Height
4.5”
Inlet Height
12.8”
Length
Width
6.3”
Cable Length
5.9’
*Suitable for boilers up to 1,028 MBH (when used for boiler condensate only)
SAFETY
1. Do not use to pump ammable or explosive uids such as gasoline, fuel oil, kerosene, etc.
Do not use in explosive environments. This pump should be used with liquids compatible
with the pump component materials.
2. Do not handle the pump with wet hands or when standing on a wet or damp surface, or
in water. To reduce the risk of electrical shock, be certain that the electrical supply is
connected to a permanent EARTH ground.
3. For installations where property damage and/or personal injury might result from an
inoperative or leaking pump due to power cuts, discharge line blockage, or any other
reason, a backup system and/or alarm should be used.
4. Support the pump and piping when assembling and when installed. Failure to do so may
cause piping to break, pump to fail, motor bearing failures, etc.
INSTALLING THE PUMP
1. Carefully unpack the pump.
2. The pump is designed to be oor standing and it is essential that the pump must sit on a
level surface. If installing on bare oor boards, to reduce noise transmission, it is advisable
to place the pump onto a noise absorbing material (such as underlay or carpet).
3. The pump should not be installled in a manner that will subject it to splashing or spraying.
4. PRV discharge should be routed through a tundish before entering the pump.
ELECTRICAL CONNECTIONS
1. If desired, connect overow safety switch ter minals. Normally closed contact can be
used to shut down equipment and normally open contact can be used to activate
optional audible or visual alarm. The microswitch in the overow safety is rated for 240V, 3A.
2. Plug the pump into a suitable outlet based on the voltage specied on the label located
on the pump.
3. If a permanent wiring solution is preferred, the plug can be cut o and the pump can be
wired in accordance with NEC and local codes.
4. If pump is installed on a separate branch circuit, a 3.0 amp fuse is recommended.
115V
230V
BP-46-230
115V/2.7A
How to Use the Check Valve
To uninstall
Turn 90° counter-clock-wise
Pull up to remove check valve from hole
To install
Turn check valve 90° clockwise
Insert the check valve into the hole