The UPA-100 Power Alert reduces the risk of electrical arc flash by
pre-verifying the electrical isolation from outside of a control panel. Hard
wired to the circuit breaker or main disconnect, the UPA flashes whenever
voltage is present. Engineered with redundant circuitry, the Power Alert
is powered by the same voltage that it indicates.
OPERATION
The eight detector UPA-100 visually alerts to the presence of dangerous
AC or DC (Stored Energy) potentials occurring between any combination
of the four monitored input lines (L1, L2, L3, GND). Two LED indicators
are assigned to each input line and are designated “+” and “-”. For
each input line carrying an AC potential (bi-polar), both the “+” and “-”
LEDs will be active. A DC or Stored Energy potential will illuminate the
“+” LED for the positive line and the “-” LED for the negative line.
OSHA 1910.147 THE CONTROL OF HAZARDOUS ENERGY
(LOCKOUT/TAGOUT)
Following the application of lockout or tagout devices to energy isolating devices,
all potentially hazardous stored or residual energy shall be relieved, disconnected,
restrained, and otherwise rendered safe. (d)(5)(ii)
If there is a possibility of reaccumulation of stored energy to a hazardous level,
verication of isolation shall be continued until the servicing or maintenance is
completed, or until the possibility of such accumulation no longer exists. (d)(6)
“Verication of Isolation.” Prior to starting work on machines or equipment that
have been locked out or tagged out, the authorized employee shall verify that isolation and de-energization of the machine or equipment have been accomplished.
SPECIFICATIONS
OPERATIONAL AC Single 40 to 600 VAC, 50/60/400 Hz,
RANGE or 3-Phase (LINE-TO-LINE or LINE-TO-GND)
DC or Stored 30 to 1000 VDC,
Energy (LINE-TO-LINE or LINE-TO-GND)
MAXIMUM RATED 750 VAC/1000 VDC (LINE-TO-LINE or
VOLTAGE LINE-TO-GND)
DETECTION 29 VAC 3-Phase, 40 VAC SINGLE-Phase,
THRESHOLDS 27 VDC (TYP Cutoff)
POWER 1.2 Watts @ 750 VAC (Approximately)
CONSUMPTION
TEMPERATURE Operate -4° to 131°F (-20° to +55°C)
RATING Storage -40° to 185°F (-40° to +85°C)
ENCLOSURE NEMA 4X 105°C PVC, Totally Encapsulated
for Environment Protection
TERMINATIONS (4) 8 ft, 18 AWG 1000V, UL-1452
WEIGHT 9 oz.
IND. CONT. EQ.
496Y
UL TYPE
4X
Universal Power Alert
• Detects Single or 3-Phase
AC & DC Voltage or
Stored Energy
• Redundant Circuitry
ORDERING INFORMATION
MODEL NUMBER DESCRIPTION
UPA-100 Universal Power Alert
UPA-100S Universal Power Alert
Solid-ON Red
Accessories
UPA-WP100 ANSI WARNING Plate
The UPA-100 Series is UL Listed under UL File Number E55826.
UPA-100C UNIVERSAL POWER ALERT CAT III CAT IV
DIMENSIONS
(INCHES)
• Verification of Zero Energy
in a Panel
• Fits 1-1/4" Conduit
Knock-Out
POWER ALERTS UPA-100 Series
INDICATOR FLASH RATES (L1, L2, L3, GND)
3- Phase Line-To-Line (VAC) <29 30 120 240 480 600 750
Flashes/Sec (Typical) 0 1.3 4.2 5.8 7.3 8.0 8.8
DC or Stored Energy (VDC) <27 30 48 110 300 600 1000
Flashes/Sec (Typical) 0 1.6 2.5 4.5 6.9 8.8 9.1
GND DETECTOR THRESHOLDS (LEAKAGE ANY PHASE-TO-GROUND)
3- Phase Line-To-Line (VAC) 30 120 240 480 750
L1, L2, or L3 To Ground Continuity (OHMS
Detector Included Fault Current (µA) 7 26 38 60 67
DETECTOR INCLUDED FAULT CURRENT (PHASE-TO-GROUND SHORT)
3- Phase Line-To-Line (VAC) 30 120 240 480 750
0 OHM Phase-To-Ground Current (µA) 28 108 219 455 730
) 2M 2M 3M 5M 7M
215