Diversified Electronics UPA-100 Series Data Sheet

The UPA-100 Power Alert reduces the risk of electrical arc flash by pre-verifying the electrical isolation from outside of a control panel. Hard wired to the circuit breaker or main disconnect, the UPA flashes whenever voltage is present. Engineered with redundant circuitry, the Power Alert is powered by the same voltage that it indicates.
OPERATION
The eight detector UPA-100 visually alerts to the presence of dangerous AC or DC (Stored Energy) potentials occurring between any combination of the four monitored input lines (L1, L2, L3, GND). Two LED indicators are assigned to each input line and are designated “+” and “-”. For each input line carrying an AC potential (bi-polar), both the “+” and “-” LEDs will be active. A DC or Stored Energy potential will illuminate the “+” LED for the positive line and the “-” LED for the negative line.
OSHA 1910.147 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT/TAGOUT)
Following the application of lockout or tagout devices to energy isolating devices, all potentially hazardous stored or residual energy shall be relieved, disconnected, restrained, and otherwise rendered safe. (d)(5)(ii)
If there is a possibility of reaccumulation of stored energy to a hazardous level, verication of isolation shall be continued until the servicing or maintenance is completed, or until the possibility of such accumulation no longer exists. (d)(6)
“Verication of Isolation.” Prior to starting work on machines or equipment that have been locked out or tagged out, the authorized employee shall verify that isola­tion and de-energization of the machine or equipment have been accomplished.
SPECIFICATIONS
OPERATIONAL AC Single 40 to 600 VAC, 50/60/400 Hz, RANGE or 3-Phase (LINE-TO-LINE or LINE-TO-GND)
DC or Stored 30 to 1000 VDC, Energy (LINE-TO-LINE or LINE-TO-GND)
MAXIMUM RATED 750 VAC/1000 VDC (LINE-TO-LINE or VOLTAGE LINE-TO-GND)
DETECTION 29 VAC 3-Phase, 40 VAC SINGLE-Phase, THRESHOLDS 27 VDC (TYP Cutoff)
POWER 1.2 Watts @ 750 VAC (Approximately) CONSUMPTION
TEMPERATURE Operate -4° to 131°F (-20° to +55°C) RATING Storage -40° to 185°F (-40° to +85°C)
ENCLOSURE NEMA 4X 105°C PVC, Totally Encapsulated
for Environment Protection
TERMINATIONS (4) 8 ft, 18 AWG 1000V, UL-1452
WEIGHT 9 oz.
IND. CONT. EQ.
496Y
UL TYPE
4X
Universal Power Alert
• Detects Single or 3-Phase AC & DC Voltage or Stored Energy
• Redundant Circuitry
ORDERING INFORMATION
MODEL NUMBER DESCRIPTION
UPA-100 Universal Power Alert UPA-100S Universal Power Alert Solid-ON Red
Accessories UPA-WP100 ANSI WARNING Plate
The UPA-100 Series is UL Listed under UL File Number E55826.
UPA-100C UNIVERSAL POWER ALERT CAT III CAT IV
DIMENSIONS
(INCHES)
• Verification of Zero Energy in a Panel
• Fits 1-1/4" Conduit Knock-Out
POWER ALERTS UPA-100 Series
INDICATOR FLASH RATES (L1, L2, L3, GND)
3- Phase Line-To-Line (VAC) <29 30 120 240 480 600 750 Flashes/Sec (Typical) 0 1.3 4.2 5.8 7.3 8.0 8.8 DC or Stored Energy (VDC) <27 30 48 110 300 600 1000 Flashes/Sec (Typical) 0 1.6 2.5 4.5 6.9 8.8 9.1
GND DETECTOR THRESHOLDS (LEAKAGE ANY PHASE-TO-GROUND) 3- Phase Line-To-Line (VAC) 30 120 240 480 750 L1, L2, or L3 To Ground Continuity (OHMS Detector Included Fault Current (µA) 7 26 38 60 67
DETECTOR INCLUDED FAULT CURRENT (PHASE-TO-GROUND SHORT) 3- Phase Line-To-Line (VAC) 30 120 240 480 750 0 OHM Phase-To-Ground Current (µA) 28 108 219 455 730
) 2M 2M 3M 5M 7M