Diversified Electronics ISO Series, ISL Series Data Sheet

800.727.5646 atcdiversified.com Diversified Electronics
OPERATION
\\\
The ISO/ISL Series multiple channel devices are used to provide a
afe and reliable means of controlling loads from hazardous locations
s without releasing sufficient energy under normal or abnormal condi­tions to cause ignition of a flammable or combustible atmospheric
ixture while in its most easily ignited concentration. An isolated out-
m put turns on when the corresponding control switch input from the hazardous location is activated. When using normally closed control
witch inputs, a jumper should be installed between terminals 1 and 2.
s Normally open control switch inputs do not require the optional jumper. When the non-latching ISO Series control switch input is
ctivated, its corresponding output turns on. When the control switch
a input is deactivated, its output turns off. When the control switch input 2, 3 or 4 is activated, its corresponding output turns on. When control switch 2, 3 or 4 is deactivated, its corresponding output remains latched on as long as control switch input 1 is activated; otherwise it turns off immediately. Control switch input 1 also controls output 1 just as in the non-latching ISO Series.
DIMENSIONS (INCHES)
\\\
latching ISL Series
M
ISO, ISL Series
u
l
t
i
l
e
C
h
a
n
n
e
l
I
s
o
l
a
t
e
d
w
S
h
c
t
i
ORDERING INFORMATION
\\\
MODEL
NUMBER
ISL-24-AAE
ISL-24-ABE
ISL-24-ACE
ISL-120-AAE
ISL-120-ABE
ISL-120-ACE
ISO-24-AAE
ISO-24-ABE
ISO-24-ACE
ISO-120-AAE
ISO-120-ABE
ISO-120-ACE
CONTROL
VOLTAGE
24 VAC 2
24 VAC 3
24 VAC 4
120 VAC 2
120 VAC
120 VAC 4
24 VAC 2
24 VAC 3
24 VAC 4
120 VAC 2
120 VAC 3
120 VAC 4
CHANNELS
3
SPECIFICATIONS
\\\
CONTROL VOLTAGE
CONTROL SWITCH
RESPONSE TIMES
POWER REQUIRED
DUTY CYCLE CONTACT
RATING ISOLATION
LIFE EXPECTANCY
INDICATORS
TEMPERATURE RATING
ENCLOSURE
TERMINATIONS WEIGHT
24 or 120 VAC, ±10%, 50/60 Hz
Open Circuit
Voltage
Short Circuit
Current
Operate 6 mSEC (Approx.)
Release 2.5 mSEC (Approx.)
2.5 VA
Continuous SPST-N.O., 5 amps per channel @ 24 or 120
VAC, Resistive; 278 VA, Inductive 2500 Volts, Input to Output
Mechanical 20 Million Operations
Electrical
On When Corresponding Output is On
Operate -4° to 131°F (-20° to +55°C)
Storage -40° to 185°F (-40° to +85°C)
Style “E” Lexan®Surface Mounted
(12) #8-32 Screw Terminals 8 oz.
6.2 VDC
10 µAmps
50,000 Operations @ Rated Load
Isolated Switches // ISO & ISL Series
263