Every precaution has been taken to ensure that this literature is accurate and complete. DITEK Corporation assumes no responsibility and disclaims all liability for damages resulting from the use of this information or for any errors or omissions.
One DITEK Center 1720 Starkey Road - Largo, FL 33771
Phone: 1-800-753-2345 Direct: 727-812-5000
Technical Support: 1-888-472-6100
www.diteksurgeprotection.com
Doc. Number: SPS-100005-006 Rev 1 11/16
©2016 DITEK Corp.
Page 1 of 1
120VAC Surge Protector
See DTK-120HW Datasheet
Multi-base system, 4 circuit pairs
See DTK-2MHLP Datasheet
Ground Bar Kit for Grounding
See 100-640 Datasheet
Mechanical Characteristics
Polycarbonate NEMA 4X (IP66)
UL Listed Industrial Control Panel Enclosure
UL94 Flammability Rating
-40°F - 175°F (-40°C - 80°C)
7.26”Lx 3.74”W x 10.43”H
(184mm x 95mm x 265mm)
Quality, Standards & Approval
UL1449 for DTK-120HW
UL497B for DTK-2MHLP
UL497A for DTK-2MHTP
IEEE C62.41.1 –2, IEEE C62.45
Ten Year Limited Warranty
Applications
Fire Alarm Panels
Control Panels
UL listed control panels
DITEK’s Total Surge Solution (TSS) is a range of
products that provide total surge protection for
addressable and conventional alarm systems.
The DTK-TSS6 protects 120V system power and up to
eight pairs of SLC, IDC/PIV, NAC or dialer circuits. The
TSS6 is equipped with a DTK-120HW for 120VAC surge
protection and a DTK-4MB mounting base. Adding DTK2MHLP/2MHTP modules for data/signal and dialer circuit
protection provides a complete solution for your fire alarm
system. The DTK-TSS6 includes an NFPA 72 2013
10.6.5.2 compatible lockout kit to prevent accidental
disconnect of the fire alarm system.
Example to protect 120V system power, two 24V data/signal pairs,
two 12V data/signal pairs and two telco pairs:
1 x DTK-TSS6 (DTK-120HW & DTK-4MB in NEMA enclosure)
1 x DTK-2MHLP24B (protect 2-data/signal pairs 24V)
1 x DTK-2MHLP12B (protect 2-data/signal pairs 12V)
1 x DTK-2MHTP (protect 2-telco pairs)
Product Features
120VAC power surge protection
Hard-wired base for 2MHLP/2MHTP modules,
protects up to 8 SLC, NAC, IDC, PIV and dialer
circuits pairs (must be ordered separately)
Complete protection, simple installation, high
quality, and field-replaceable modules make the
TSS6 a perfect, cost effective fit for alarm systems
or control panels.
Accessories
Test Module Kit – Part Number DTK-2MHLPTM