DTK-TSS1 Series Total Surge Solution
Complete Fire Panel Protection for AC Power and Loop Circuits
DITEK’s Total Surge Solution (TSS) is a range of
products that provide total surge protection for
addressable and conventional alarm systems.
The TSS1 protects 120V AC power and up to ten
pairs of SLC, IDC/PIV, NAC and dialer circuits.
The TSS1 is equipped with DTK-120SRD
120VAC surge protection and a prewired DTK5MB mounting base for loop protection. Adding
DTK-2MHLP modules or 2MHTP telco modules
provides a custom solution for your system.
Complete protection, simple installation, high
quality, and field-replaceable modules make the
TSS1 a perfect fit for addressable alarm systems
or control panels. For alarm panels with
network connections, use DTK-TSS1IP.
DTK-TSS1
Product Features
• 20A current rated, 54kA surge rated AC protection
• 20kA surge rated low voltage suppression
• Dry contacts for remote monitoring of surge
protection status
• Field replaceable surge modules for NAC, IDC/PIV
and SLC circuits
• Ten Year Limited Warranty
Specifications
• NEMA TYPE 1 steel enclosure with latching cover
• UL Listed - Industrial Control Panel Enclosure
• Weight: ≈ 11 lb. (5 kg)
• Dimensions: 12” x 12” x 4” (305mm x 305mm x 102mm)
• Operating temperature: -40° F to 175° F (-40°C to 80°C)
Options
• DTK-TSS1IP same as TSS1 with IP network
protector, DTK-MRJ45C5E
• DTK-TSS2 120V AC and four-line low voltage
transient surge protection
• DTK-TSS3 four-line low voltage protection for
building-to-building runs
• Voice/Data protection modules: DTK-2MHLP
(select required voltage), DTK-2MHTP (Telco lines)
General Product Specifications
DTK-120SRD AC Protection Features
• Agency Approvals: UL1449 3rd Edition,
cUL, UL1283 EMI/RFI filtering
• Protector Type: Type 4 SPD, for Type 2 Application
• Nominal Discharge Current Rating (In): 3kA
• SCCR: 10kA
• Operating Voltage: 120VAC
• MCOV: 150VAC
• Peak Surge Current: 54,000 Amps
• LED function indicators
• Form C dry contact circuit
Low Voltage Protection Features
• Hard-wire base for replaceable suppression modules
• DTK-2MHLP modules are UL497B listed
• DTK-2MHTP telco modules are UL497A listed
• 2MHLP low voltage modules protect two data/signal
pairs each. The TSS1, with 2MHLP modules, can
protect power and up to ten data/signal pairs.
• Available voltages: 5VDC – 130VDC
• Maximum continuous current: 5A per module
• DTK-2MHLPTM Test/Bridging module is included
One DITEK Center
1720 Starkey Road
Largo, FL 33771
NOTE: See DTK-2MHLP/DTK-2MHTP/DTK-120SRD/DTK-MRJ45C5E
Datasheets for detailed specifications on SLC, IDC/PIV, NAC, Dialer &
AC Power Protection
1-800-753-2345 Direct 1-727-812-5000
Technical Support: 1-888-472-6100
www.ditekcorp.com
Doc Number: SPS-100004-001 Rev 11 04-13
Specification Subject to Change
©2013 DITEK Corp.