Ditek DTK-TSS1 Installation

DTK-2MHTP (2-Pair Modular Hybrid Telco Protector)
1. Connect the communication loop circuit from the field to the side marked UNPROTECTED. The first pair is connected to the terminals marked 1+ and 1- . If a second pair is used, connect to the terminals marked 2+ and 2- .
2. Connect the communication loop for the alarm panel supply wiring to the side marked PROTECTED.
DTK-TSS1
DTK-2MHLPXXB (2-Pair Modular Hybrid Line Protector)
1. Connect the IDC (Initiating) wiring from the field to the side marked INPUT. The first pair is connected to the terminals marked 1+ and 1- . If a second pair is used, connect to the terminals marked 2+ and 2- .
2. Connect the IDC for the alarm panel supply wiring to the side marked OUTPUT.
3. Connect the NAC (Notifying) wiring from the field to the side marked INPUT. The first pair is connected to the terminals marked 1+ and 1- . If a second pair is used, connect to the terminals marked 2+ and 2- .
4. Connect the NAC for the alarm panel supply wiring to the side marked OUTPUT. Repeat for the SLC (Signaling) circuit. Note: There are up to 4 modules available for protection of any combination of IDC (Initiating), NAC (Notifying), or SLC (Signaling) circuits. Each module will protect 2 pairs or circuits. Note: All modules have been factory pre-wired for ground. It is not necessary to make any additional ground connections. After all connections have been made and no hazards exist, restore power
1+ 1- 2+ 2-
DTK - 2MHLP
DITEK
DTK - 2MHTP
MADE IN THE USA
5
12 24 36 48
MODULAR SURGE PROTECTION
VOICE - DATA- SIGNAL
A B
75
130
1+ 1- 2+ 2-
Total Surge Solution
User Guide
UNPROTECTED PROTECTED
FIELD PAIRS TO EQUIPMENT. 3' MINIMUM
191519 INT-100099-001 Rev 5
DITEK CORPORATION
One DITEK Center 1720 Starkey Road Largo, Fl 33771 1-800-753-2345 www.ditekcorp.com
DITEK CORPORATION
One DITEK Center 1720 Starkey Road Largo, Fl 33771
Sales: 1-800-753-2345
Technical Support: 1-888-472-6100
DITEK TSS1 (Total Surge Solution)
System Overview
TSS1 (Total Surge Solution)
The TSS1 is an integrated surge protection solution for alarm panels. This device provides transient voltage surge protection for two pairs of communication circuits, up to eight pairs of any combination of initiating circuits and notifying circuits, and AC power protection. This product also features field replaceable modules and an edge card connection circuit that shields the AC power circuit from the loop and comminication circuits .
DTK-120SRD (120V Series Surge Protector)
Warning !! Turn power off at the main circuit breaker panel.
Note: Connect this device in series between the AC power supply wiring and the alarm panel AC inputs.
1. Crimp the supplied ring terminals to the connection wires.
2. Connect the Ground (green or bare) supply wire to the ground buss on the back plane. The GROUND on the DTK-120SRD has been factory pre-wired. It is not necessary to make any additional ground connections.
3. Connect the Neutral (white) supply wire to the NEUTRAL terminal on the Input side.
4. Connect the Phase (black) supply wire to the LINE terminal on the Input side.
5. Connect the Ground, Neutral and Phase wires from the Output side to the alarm panel AC inputs.
6. After all connections have been made and metal nuts have been torqued to 10 inch pounds, install the plastic protective cover and fasten with the included nylon nuts until snug, then restore power.
Installation
Cabinet
Caution: This installation should be performed by a licensed electrician. Note: Install this device between the field wiring and the alarm panel. Disconnect system power and loop circuits before beginning installation.
1. Locate an appropriate area for the cabinet near the alarm panel to be protected.
2. Position the TSS cabinet on the finished wall surface and fasten the cabinet to the wall.
3. Remove the appropriate knockouts from the cabinet to facilitate the routing of the field wiring and alarm panel supply wiring . Make sure the field wiring and the protected wiring to the alarm panel occupy separate conduit feeds.
4. Pull the field wiring and the alarm panel supply wiring through the appropriate knockouts on the cabinet. Make sure to route the AC power wires separately from the loop circuit wires.
4"
12"
11"
9"
GROUND WIRE TO GROUND BUSS (Chassis Ground) (Factory Pre-Wired)
GROUNDED 120 VAC POWER (Installer Provided)
Ground Buss
DRY CONTACT CIRCUIT INFORMATION
EXAMPLE MONITORING CIRCUIT
DTK-5MB Ground (Factory Pre-Wired)
Ground For Future Use On Additional Bases (Installer Provided)
DTK-120SRD
SURGE PROTECTIVE DEVICE
MADE IN USA
WWW.DITEKCORP.COM
CAUTION !!!
HIGH VOLTAGE
DRY CONTACT
NO C NC
NC C NO
120VAC(+)
GROUNDED 120 VAC POWER TO ALARM PANEL. (Installer Provided)
12”
191519 INT-100099-001 Rev 5
DITEK CORPORATION
One DITEK Center 1720 Starkey Road Largo, Fl 33771 1-800-753-2345 www.ditekcorp.com
EXAMPLE REMOTE MONITORING
USING FACP FOR NOTIFICATION
DTK-120SRD
NEUTRAL(-)
LOAD: 120VAC, 0.5AMP (MAX)