INSTALL INSTRUCTIONS
DTK-RM16-C5
This Surge Protective Device (SPD) is a high performance device, designed to provide protection
for sensitive electronic loads connected to service panels, fire panels, or where the SPD is directly
connected to the electronic device. Maximum protection will only be achieved if the SPD is properly
installed.
Please read and follow the installation instructions carefully.
NOTICE: This SPD should be installed by a qualified electrician in accordance with the National
and Local Electrical Codes and the following instructions.
APPLICATION
Surge suppression for rack mountable data circuits using an RJ45 connection.
WIRING INSTRUCTIONS:
Caution
module. Improper installation voids the warranty.
This unit must be connected in series with the field wiring and the equipment to be protected.
1. Connect a #10 AWG minimum gage ground wire to the ground lug on back of face plate and connect
this to an appropriate ground point.
Note: Make sure the #10 AWG ground wire is as short as possible.
2. Mount this device using your preferred method of install.
3. Connect the incoming wires to the “IN” connector.
4. Connect a 3’ - 6’ minimum CAT5e patch cable from the “OUT” connector to the equipment being
protected.
Note: Always have one common ground per system to eliminate the possibility of a differential in
ground potentials.
Ground Resistance Rule: Max ground resistance is 25 Ohms, 5 Ohms or less is optimum.
This cannot be an assumed value and must be measured to assure proper grounding.
: Measure all voltages to insure applied voltage does not exceed the voltage rating of the
DTK-RM16C5M SURGE MODULE REPLACEMENT INSTRUCTIONS:
1. Lay faceplate face down on a flat surface with the ground lug on the left hand side.
2. Select the desired module positon number (1-16)
3. Remove damaged surge module.
4. Remove hardware kit and surge module from plastic bag.
5. Place the silver spacer onto the threaded standoff.
6. Place split (lock) washer on top of silver standoff.
7. Place surge module pc board over threaded standoff with “J1” at output side and “J2” at input side.
Make sure the connectors and threaded standoff line up with their perspective holes and seat properly.
8. Place 2nd split (lock) washer over threaded standoff.
9. Place the hex-nut over the threaded standoff. using a 3/16” hex socket, tork the nut
to 10 Inch Pounds Maximum.
10. Re-install the DTK-RM16C5
INSTALLATION
Revised By: K. Nguyen 5-12-16
Approved By: R. Mitchell 6-3-16
DITEK Technical Support Available 24/7
1-888-472-6100
www.ditekcorp.com
Doc # INT-100061-001
Part No. 191044 Rev. 4
DITEK Corporation
ONE DITEK CENTER
1720 Starkey Road
Largo, FL 33771
INSTALL INSTRUCTIONS
DTK-RM16C5
Illustrations Page
Network Equipment
EQUIPMENT CABLES
ALLOW 3’ MIN.
LENGTH
OUTPUT
Ground
wire
10awg. Min
SUPPLY
CABLES
INPUT
OUT
IN
1 2
1 2
3
3 4
5 6
4
5
6 7 8 9 10
7
8 9 10
11 12
11 12
13
13
15 16
14
15 16
14
INSTALLATION
Drawn By: K. Nguyen 5-12-16
Approved By: R. Mitchell 6-3-16
DITEK Technical Support Available 24/7
1-888-472-6100 www.ditekcorp.com
Doc # INT-100061-001
Part No. 191044 Rev. 4