INSTALL INSTRUCTIONS
DTK-PVPIP
This Surge Protection Device (SPD) is a high performance device, designed to provide protection for sensitive electronic loads connected to service panels, fire panels, or where the SPD is directly connected to the electronic device. Maximum protection will only be achieved if the SPD is properly installed. Please read and follow the installation instructions carefully.
NOTICE: This SPD should be installed and grounded, by a licensed contractor, per the applicable requirements of the NEC. These devices are only to be employed on the communication loop circuits which have been isolated from the Public Switched Telephone Network.
APPLICATION
DTK-PVPIP-Surge suppression for IP/PoE video where data circuits use an RJ45 connection and 12V/24V camera and accessory power use a seperate connection with a maximum wire gage of 12 AWG. This device is intended for indoor use or intended for outdoor use within an enclosure which has been evaluated for the application.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of
the unit. Improper installation voids the warranty. This unit must be connected in series with the equipment to be connected. TURN OFF ALL POWER BEFORE BEGINNING INSTALLATION. VIDEO / DATA CONNECTION:
1. Connect the incoming wires to the "INPUT" RJ45 connector.
2. Connect a CAT5e patch cable from the “OUTPUT” RJ45 connector to the equipment to be protected. NOTE: Patch cable should be 3-6 feet in length to allow for circuit reaction time.
12 / 24 VAC CAMERA AND ACCESORY CONNECTION:
1. Connect the incoming power wires to the “CAM” and/or “ACC” UNPROTECTED connector.
2. Connect the “CAM” and/or “ACC” PROTECTED connector to the camera or accesory to be protected. Circuit conductors must be 3-6 feet in length.
3. Always have one common ground per system to eliminate the possibility of a differential in ground potentials.
NOTE: The ground conductor should be a minimum #14 AWG wire, the length must be as short as possible.
Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum. This cannot be an assumed value and must be measured to assure proper grounding.
r.
4. After all connections have been made and no hazards exist, restore power.
SUPPLY (Field) PATCH CABLE
DTK-PVPIP
EQUIPMENT PATCH CABLE 3' LENGTH MINIMUM
TO EQUIPMENT
INPUT
VIDEO / DATA
12V/24V POWER
PROTECTION
GND
OUTPUT
PROTECTED
OUTPUT 2 PAIR ACCESSORY TO EQUIPMENT. 3' LENGTH MINIMUM
GROUND WIRE 14AWG
INPUT 2 PAIR ACCESSORY WIRES
UNPROTECTED
INSTALLATION
Drawn By: B. Aycock 6-6-16 Approved By: R. Mitchell 6-8-16
DITEK Technical Support Available 24/7 1-888-472-6100 www.ditekcorp.com
Doc # INT-100118-001 Part No. 191543 Rev. 5