Power outages, surges, and voltage transients on
data lines can be deadly to critical data/comm
equipment. DITEK’s DTK-MRJTLC surge
protector is designed specifically to protect the
Rauland-Borg Telecenter VI communications/
safety system. The MRJTLC protects Telecenter
VI Telco, Clock and Call Circuits for each portable
classroom.
NOTE:To ensure optimum Telecenter VI system
protection, apply primary lightning arresters at
each building entrance and surge protection in
each remote classroom.
DTK-MRJTLC
Features
• Protects Telecenter VI runs from the controller to
the classroom
• Voltage-matched pairs protect all four circuits in
one product
• SAD technology provides optimal circuit protection
• Single point ground improves protection and
speeds installation
• Ten Year Limited Warranty
DTK-MRJTLC
Telecenter VI Surge Protector
General Product Specifications
Specifications
• Connection Method: RJ45 (8-wire) In/Out
• Continuous Current: 0.5A Telco,
1.0A Speaker, Clock, Call In
• Max. Surge Current: 100A per line
(10/1000µs impulse)
• Protection Modes: All Lines – Ground
• Dimensions: 1.3 ”H x 2.4” W x 3.0”D
(33mm x 61mm x 76mm)
• Weight: 4 oz. (113g)
• Housing: ABS
Telecenter VI and Rauland-Borg areTMRauland-Borg Corporation
One DITEK Center
1720 Starkey Road
Largo, FL 33771
1-800-753-2345 Direct 1-727-812-5000
Technical Support: 1-888-472-6100
www.ditekcorp.com
DTK-MRJTLC
Telco
(Pins 4 & 5)
Speaker
(Pins 1 & 2)
Clock
(Pins 7 & 8)
Call In
(Pins 3 & 6)
Service
Voltage
MCOV
Clamping
Voltage
48V 180V 250V
25V
25V
12V
Doc. Number: SPS-100042-004 Rev 1 3/08
45V 60V
20V 28V
Specification Subject to Change
60V45V
©2008 DITEK Corp.