Ditek DTK-MRJPOEX Installation

INSTALL INSTRUCTIONS
DITEK Corporation
DTK-MRJPOEX
ONE DITEK CENTER
1720 Starkey Road
Largo, FL 33771
This Surge Protection Device (SPD) is a high performance device, designed to provide protection for sensitive electronic loads connected to service panels, fire panels, or where the SPD is directly connected to the electronic device. Maximum protection will only be achieved if the SPD is properly installed. Please read and follow the installation instructions carefully.
NOTICE: This SPD should be installed by a licensed contractor in accordance with the National and Local Electrical Codes and the following instructions.
APPLICATION
Surge suppression for externally mounted PoE devices using CAT 5e cable and RJ45 connectors.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of
the unit. Improper installation voids the warranty. This unit must be connected in series with the equipment to be protected.
1. Disconnect the power to the circuit before beginning installation.
2. Mount the device in the desired location close to the equipment to be protected using the included self tapping screws. Make sure the openings of the Liquid Tight Cordgrips are facing downward.
3. If using pre-existing cabling, cut the supply cable going to the externally mounted device.
4. Using RJ45 plugs, tip each cable prior to inserting into the cordgrips, using best practice.
5. Remove the internal sealing compression glands from the cordgrips.
6. Feed the SUPPLY/FIELD cable into the left hand side cordgrip (IN UNPROTECTED).
7. Feed the TO EQUIPMENT cable, to the equipment to be protected, into the right hand side cordgrip (OUT PROTECTED).
8. Insert each RJ45 plug into their respective RJ jacks.
9. Position the compression gland around the cable, insert into the cordgrip and tighten all hardware to assure a water tight connection.
10. If using factory pre-terminated patch cables, repeat #5 above and continue.
11. Push the ground wire through the center hole of the Liquid Tight Break-Thru Plug.
12. Crimp the included spade terminal (#12-10 AWG) onto the grounding conductor. Connect the ground lead to the ground terminal on the MRJPOEX using a #12 AWG ground conductor. Make sure to provide enough conductor length to allow for an adequate ground termination. Gently pull the wire back 1/2”. The gland will seal itself. Make sure the ground wire is as short as possible. Ground Resitance Rule: Max ground resistance is 25 Ohms, 5 Ohms or less is optimum. This cannot be an assumed value and must be measured to assure proper grounding. Note: If using STP (shielded twisted pair) it is not required to ground the MRJPOEX. As long as the shield from the STP is bonded at one end of the cable run, this will serve as the grounding point.
13. After all connections have been made and no hazards exist, restore power.
GROUND WIRE 14AWG MINIMUM
IN UNPROTECTED
OUT PROTECTED
GND
SUPPLY/FIELD CABLE
TO EQUIPMENT
INSTALLATION
Drawn By: R. Mitchell 5/22/17 Approved By: R. Mitchell 5/22/17
1-888-472-6100 www.ditekcorp.com
DITEK Technical Support Available 24/7
Doc # INT-100164-001 Part No. 191595 Rev. 2