DITEK DP4P-TPV
Installation Instructions
1. Check the cable signal before and after the installation of the DP4P-TPV
to insure proper install and no signal distortion.
2. Securely mount this unit between the field wiring and the equipment to be
protected. Use a minimum #14 AWG wire from the ground connector to
the common Earth ground, with 25 ohms or less.
3. Connect the unprotected UTP wiring from the field to the IN + and IN - .
4. Connect the protected UTP wiring to the equipment to be protected to the
OUT+ and OUT- respectively. Allow a minimum of 3 wire feet between the
DP4P-TPV and the protected equipment. This will allow the unit time to react.
5. Make sure the wire distance from the surge protector to protected equipment
is greater than the wire distance from the surge protector to ground.
6. Always use one common ground per system to eliminate the possibility of a
differential in ground potentials.
7. For mounting, use double-sided tape (supplied), or two #8 screws
(not supplied).
8. For further information or technical support please call 1-888-472-6100.
TITLE:
Diversified Technology Group, Inc.
1720 Starkey Road Largo, Florida 33771
Tel. 727-812-5000 Fax 727-812-5026
MATERIAL:
FINISH:
DRAWN BY:
RWM
Installation Instructions For Ditek DP4P-TPV
DATE:
5-20-03
REVISED:
PROTECTED
TWISTED PAIR
VIDEO
24V POWER,
5V DATA
CONNECTION
OUTPUT
UTP OUT
-
+
DTK-DP4P-TPV
P
R
O
T
E
C
T
E
D
5V DATA
5V DATA
5V DATA
5V DATA
24V PWR
24V PWR
OUT IN
APPROVED BY:
DWG NO.
INT-100043-001
VIDEO
UTP IN
-
+
UNPROTECTED
TWISTED PAIR
VIDEO
GND
U
N
P
R
O
T
E
C
T
E
D
PART NO.
191501
GROUND
CONNECTOR
24V POWER,
5V DATA
CONNECTION
INPUT
REV.
0
DITEK DP4P-TPV
Installation Instructions
1. Check the cable signal before and after the installation of the DP4P-TPV
to insure proper install and no signal distortion.
2. Securely mount this unit between the field wiring and the equipment to be
protected. Use a minimum #14 AWG wire from the ground connector to
the common Earth ground, with 25 ohms or less.
3. Connect the unprotected UTP wiring from the field to the IN + and IN - .
4. Connect the protected UTP wiring to the equipment to be protected to the
OUT+ and OUT- respectively. Allow a minimum of 3 wire feet between the
DP4P-TPV and the protected equipment. This will allow the unit time to react.
5. Make sure the wire distance from the surge protector to protected equipment
is greater than the wire distance from the surge protector to ground.
6. Always use one common ground per system to eliminate the possibility of a
differential in ground potentials.
7. For mounting, use double-sided tape (supplied), or two #8 screws
(not supplied).
8. For further information or technical support please call 1-888-472-6100.
TITLE:
Diversified Technology Group, Inc.
1720 Starkey Road Largo, Florida 33771
Tel. 727-812-5000 Fax 727-812-5026
MATERIAL:
FINISH:
DRAWN BY:
RWM
Installation Instructions For Ditek DP4P-TPV
DATE:
5-20-03
REVISED:
PROTECTED
TWISTED PAIR
VIDEO
24V POWER,
5V DATA
CONNECTION
OUTPUT
UTP OUT
-
+
DTK-DP4P-TPV
P
R
O
T
E
C
T
E
D
5V DATA
5V DATA
5V DATA
5V DATA
24V PWR
24V PWR
OUT IN
APPROVED BY:
DWG NO.
INT-100043-001
+
VIDEO
UTP IN
-
UNPROTECTED
TWISTED PAIR
VIDEO
GND
U
N
P
R
O
T
E
C
T
E
D
PART NO.
191501
GROUND
CONNECTOR
24V POWER,
5V DATA
CONNECTION
INPUT
REV.
0