INSTALL INSTRUCTIONS
DTK-DP4P-BP
DITEK Corporation
ONE DITEK CENTER
1720 Starkey Road
Largo, FL 33771
This Surge Protection Device (SPD) is a high performance device, designed to provide protection
for sensitive electronic loads connected to service panels, fire panels, or where the SPD is
directly connected to the electronic device. Maximum protection will only be achieved if the SPD
is properly installed.
Please read and follow the installation instructions carefully.
NOTICE: This SPD should be installed by a qualified electrician in accordance with the National
and Local Electrical Codes and the following instructions.
APPLICATION
Surge suppression for video connections using UTP to BNC convertions.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of
the unit. Improper installation voids the warranty.
This unit must be connected in series with the equipment to be connected.
1. Connect the UTP wires to the positive and negative terminal of the DTK-DP4P-BP.
2. Connect a BNC Patch cable to the equipment to be protected.
3. Connect the ground wire to the ground terminal. (use a minimum of 14 AWG)
4. Always have one common ground per system to eliminate the possibility of a differential in
ground potentials.
Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum.
This cannot be an assumed value and must be measured to assure proper grounding.
5. For mounting, use double sided tape (supplied), or two (2) #8 screws (not supplied).
UTP
UN PROT ECT ED
TWI STED PAIR
VI DEO
PROT ECTED
BNC CONNECTOR
VI DEO
BNC
-
+
VI DEO
D TK- D P4 P- BP
P
R
O
T
E
C
T
E
D
24V POW ER,
5V D ATA
CONN ECTION
OUTPUTS
INSTALLATION
DrawnBy: J.Ramirez 12-15-08
ApprovedBy: R.Mitchell 12-15-08
DITEK Technical Support Available 24/7
1-888-472-6100
www.ditekcorp.com
5V D ATA
5V D ATA
5V D ATA
5V D ATA
24V PWR
24V PWR
OUT IN
GND
U
N
P
R
O
T
E
C
T
E
D
GROUND
CONNECTOR
24V POW ER,
5V D ATA
CONN ECTION
IN PUTS
Doc # INT-100077-001
Part No. 191134 Rev. 2