DINUY KNX User Manual

DINUY S.A. c/Auzolan 2, 20303 Irun (Guipuzcoa)
Tel.: 943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com
CONTROL OF BLIND CHANNELS
DINUY S.A. c/Auzolan 2, 20303 Irun (Spain)
Tel.: +34943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com 2
INTRODUCTION
- The following User Manual describes the operation and configuration of the Blind channels that incorporate different DINUY
Actuators
- These channels can control the motion of Roller Blinds or Awnings, Venetian Blinds (blinds or blinds with slats) and Ventilation
Gates.
- In the Actuators with this functionality, the control of the blind is carried out by means of two consecutive relays. The first
relay of each channel will send the raising telegrams, whereas the second channel will send the lowering ones.
CONFIGURATION
- Each Blind channel can be configured as:
· Venetian Blind (blind with or without slats):
· Roller Shutter/Awning:
DINUY S.A. c/Auzolan 2, 20303 Irun (Spain) Tel.: +34943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com 3
· Venting Louver:
Configuration Parameters
- Regardless of the parameterization, the following parameters are available:
· Behavior after recovering bus voltage: action to be performed when the KNX bus voltage or mains supply is
restored.
No action: the blind does nothing, it stays at the same position it was in before the supply fault.
Nevertheless, after the mains is reestablished, regardless of the current position of the blind, the Actuator considers that it is completely lowered (position = 100%) and it will be necessary to make a complete move up to carry out correctly the next positioning.
Up: the blind is moved-up.
Down: the blind is moved-down.
Go to position: the blind is moved completely up and then is moved to the set position.
· Blind/Roller/Louver Movement time (sec): movement time of the blind from upper position (0%) to lower (100%),
and vice versa. This time can be set between 1 and 3600 seconds.
· Slats Movement time (only Venetian Blind): movement time of the slats from fully open position (0%) to fully
closed one (100%), and vice versa. This time can be set between 2 and 600 tenths of a second. The number of steps of the slats will be calculated by dividing this time by the length of the step, sets in the general parameters.
· Reaction after bus failure: behavior of the blind after detecting a fault on the KNX bus.
· Extra time for Up movement (%): time added to the up movement to complete the raising course. Due to its
weight, the length of the raising course will be higher than the lowering course.
DINUY S.A. c/Auzolan 2, 20303 Irun (Spain) Tel.: +34943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com 4
· Reversion Pause time (msec): time delay to avoid any damage on the engine due to an instant direction change when
the blind was already in movement. The Actuator waits if it was in movement and a telegram to change the direction is received.
· Step operation possible: sets if the Step action is allowed, or just Stopping one, through the object “[BL] Stop / Step
Up / Down”.
· If the Step action is allowed, it will be necessary to set its length:
· Output Line phase respect to reference: allows the "zero-crossing-point" switching control of the relay. This type of
control makes it possible to switch high loads without risk of damaging the relay due to the high current peaks of the load at starting. The Reference Phase is that with which the Actuator is supply in L and N.
Reference
Phase
DINUY S.A. c/Auzolan 2, 20303 Irun (Spain) Tel.: +34943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com 5
Configuration Communication Objects
- Likewise, the following communication objects will be available by default:
Number
Name
Object Function
Description
244
[BL] Blind Move Up/Down
0 = Up, 1 = Down
1-Bit object for Move_Up (0) and
Move_Down (1) telegrams
245
[BL] Blind Stop / Step Up/Down
0 = Step Up, 1 = Step Down
When receiving a 0 on this object, the
shutter is Stopped or it makes a Step
Up (if enabled). If it receives a 1, the
shutter is Stopped or it makes a Step
Down (if enabled)
254
[BL] Blind position Input
0% = Open, 100% = Closed
La persiana se mueve a la posición
recibida (%) a través de este valor de 1
byte
255
[BL] Slats position Input
0% = Open, 100% = Closed
The slats are moved to the received
position (%) through this 1-byte value
DINUY S.A. c/Auzolan 2, 20303 Irun (Spain) Tel.: +34943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com 6
Advanced Parameters
- Moreover, advanced parameters and functions are also available:
· Enable object: Blind/Roller/Louver position Feedback (%): allows to know the position of the Blind through the 1-
byte object, "[BL] Blind / Roller / Louver position Feedback". By enabling this object, it will be necessary to set the period for cyclical sending: "Time to send "Blind / Roller / Louver position Feedback" (sec)". This time can be set between 60 and 3600 seconds.
· Enable object: Slats position Feedback (only Venetian Blinds): allows to know the position of the Slats through
the 1-byte object, "[BL] Slats position Feedback". By enabling this object, it will be necessary to set the period for cyclical sending: "Time to send Slats position Feedback" (sec)". This time can be set between 60 and 3600 seconds.
· Enable object: Movement Feedback: allows to know the direction of movement of the blind through the 1-bit
object, "[BL] Movement Feedback".
DINUY S.A. c/Auzolan 2, 20303 Irun (Spain) Tel.: +34943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com 7
· Enable Weather Alarms: enables Wind, Rain and Frost alarms. It must be considered that the alarms prevail over the
rest of the functions.
o Wind Alarms: up to three Wind Alarm objects can be enabled.
Enable Wind Alarm Watchdog: allows to enable the vigilance of the wind alarm and its period time. Wind Alarm Watchdog time (sec): period how often the alarm status is monitored. Behavior when starting Wind Alarm: behavior of the shutter when the alarm starts in one of the 3
objects. The different options are: No action, Up, Down or Stop.
Behavior when finishing Wind Alarm: behavior of the shutter when the alarm finishes in one of the 3
objects. The different options are: No action, Up, Down, Stop or Go to last position.
DINUY S.A. c/Auzolan 2, 20303 Irun (Spain) Tel.: +34943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com 8
o Rain Alarm: 1 Rain Alarm can be enabled.
Enable Rain Alarm Watchdog: allows to enable the vigilance of the rain alarm and its period time. Rain Alarm Watchdog time (sec): period how often the alarm status is monitored. Behavior when starting Rain Alarm: behavior of the shutter when the alarm starts in one of the 3
objects. The different options are: No action, Up, Down or Stop.
Behavior when finishing Rain Alarm: behavior of the shutter when the alarm finishes in one of the 3
objects. The different options are: No action, Up, Down, Stop or Go to last position.
o Frost Alarm: 1 Frost Alarm can be enabled.
Enable Frost Alarm Watchdog: allows to enable the vigilance of the frost alarm and its period time. Frost Alarm Watchdog time (sec): period how often the alarm status is monitored. Behavior when starting Frost Alarm: behavior of the shutter when the alarm starts in one of the 3
objects. The different options are: No action, Up, Down or Stop.
Behavior when finishing Frost Alarm: behavior of the shutter when the alarm finishes in one of the 3
objects. The different options are: No action, Up, Down, Stop or Go to last position.
DINUY S.A. c/Auzolan 2, 20303 Irun (Spain) Tel.: +34943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com 9
o Alarms Priority: sets the priority level of the different alarms.
Weather Alarms priority: establishes the hierarchy of priorities between the different alarms.
Forced vs Weather Alarm Priority: sets the priority between weather alarms and forced action.
· Enable Sun Protection: function that allows the protection of the indoor from the Sun.
o Type of Protection object: allows to set the protection based on a 1-Bit object or the Lux value received from
a brightness sensor.
1-Bit On/Off object: enables a 1-Bit input object for the sun protection function, "[BL] Sun Protection
Input". In this case, it is necessary to set:
· Sun Protection object polarity: protection triggered by 0 or 1.
· Delay time to Start Sun Protection: 1 ~ 3600 seconds.
· Behavior when starting sun protection:
DINUY S.A. c/Auzolan 2, 20303 Irun (Spain) Tel.: +34943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com 10
· Delay time to Start Sun Protection: 1 ~ 3600 seconds.
· Behavior when finishing sun protection:
Lux level value object: enables a 2-byte input object for sun protection function, “[BL] Lux level Input.
In this case, it is necessary to set:
· Lux value to Start Protection: 1 ~ 3600 Lux.
· Lux value to Finish Protection: 1 ~ 3600 Lux.
· Delay time to Start Sun Protection (sec): 1 ~ 3600 seconds.
· Behavior when starting Sun Protection:
· Delay time to Finish Sun Protection (sec): 1 ~ 3600 seconds.
· Behavior when finishing Sun Protection:
DINUY S.A. c/Auzolan 2, 20303 Irun (Spain) Tel.: +34943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com 11
· Enable Scenes Function: up to 8 different scenarios can be preset. In each Scene the position of the Blind and the
position of the Slats can be stablished.
· Enable Forced Function: its priority is higher than the standard operating orders and its priority, or not, over the
alarms, can be defined in the Alarms menu.
· Disable Manual Control: enables, or not, manual control of the Actuator from the front keypad of the device.
· Disable realy switching with zero-cross control: in the event of controlling slats, it will be necessary to activate this
parameter in order to achieve optimal results in their movement.
· Enable Central Function: sets the behavior of the blind in case of receiving a telegram from the Central Function. The
control object for channels configured as Blind is "[BL] Blind position Input Central Function" and "[BL] Slats position Input Central Function", depending on the number of objects enabled for centralized control (1 or 2).
No reaction: the channel does not respond to centralized commands.
Any value = Up: any value received in the object “[Central] Move Blind causes a rising of the blind
connected to this channel.
Any value = Down: any value received in the object “[Central] Move Blindcauses a lowering of the blind
connected to this channel.
Any value = Position: any value received in the object “[Central] Move Blindcauses a movement of the
blind connected to this channel to the set value.
0 = Up, 1 = Down: a 0 received in the object “[Central] Move Blindcauses a rising of the blind
connected to this channel, and an 1 causes a lowering.
1 = Up, 0 = Down: an 1 received in the object “[Central] Move Blindcauses a rising of the blind
connected to this channel, and a 0 causes a lowering.
DINUY S.A. c/Auzolan 2, 20303 Irun (Spain) Tel.: +34943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com 12
0 = No reaction, 1 = Down: a 0 received in the object “[Central] Move Blindwill not cause any action
on the blind connected to this channel, and an 1 will cause a complete lowering.
0 = Up, 1 = No reaction: an 1 received in the object “[Central] Move Blindwill not cause any action on
the blind connected to this channel, and an 1 will cause a complete rising.
DINUY S.A. c/Auzolan 2, 20303 Irun (Spain) Tel.: +34943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com
Advanced Communication Objects
DINUY S.A. c/Auzolan 2, 20303 Irun (Spain) Tel.: +34943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com 14
Number
Name
Function
Description
246
[BL] Forced Input
2 Bits control
Forcing order, with higher priority than standard operation. One of
the bits indicates if the Forcing is active (yes / no) and with the
second bit it is indicated if the Forcing is On or Off
247..249
[BL] Wind Alarm 1..3
1 = Alarm, 0 = No Alarm
Wind alarm input objects
250
[BL] Rain Alarm
1 = Alarm, 0 = No Alarm
Rain alarm input object
251
[BL] Frost Alarm
1 = Alarm, 0 = No Alarm
Frost alarm input object
252
[BL] Scene Input
Scene Control
1-Byte object for scene control
253
[BL] Movement Feedback
0 = Up, 1 = Down
Info object about the movement of the blind
256
[BL] Blind position Feedback
0% = Open, 100% = Closed
Info object about blind position
257
[BL] Slats position Feedback
0% = Open, 100% = Closed
Info object about slats position
258
[BL] Sun Protection Input
1 = On, 0 = Off
Sun protection input object
259
[BL] Sun Protection position Input
0% = Open, 100% = Closed
Input object that indicates the position to which the blind should
move if the sun protection is triggered
804
[BL] Blind position Input Central Function
0% = Open, 100% = Closed
1-Byte object for controlling the position of the blind with the
central function
805
[Out] Slats position Input Central Function
0% = Open, 100% = Closed
1-Byte object for controlling the position of the slats with the
central function