Dimplex XMX706N, XMS/X718N, XMS/X712N, XMS/X724N Installation And Operating Instructions Manual

XMS(N) AUTOMATIC XMX(N) MANUAL
STORAGE HEATER RANGE
MODELS: XMX706N - 6kWh XMS/X712N - 12kWh
XMS/X718N - 18kWh XMS/X724N - 24kWh
INSTALLATION AND OPERATING
INSTRUCTIONS
IMPORTANT
NOTE ALSO THE INFORMATION GIVEN ON THE HEATER
The installation must be carried out by a trained competent personnel. A means for disconnection must be incorporated in the xed wiring by a double pole switch with a contact separation
of a minimum of 3mm and in accordance with the current IEE Wiring Regulations
The heater must not be installed immediately below a xed socket outlet.
The heater is not suitable for connection to a 30A ring circuit (24 hour peak supply).
Do not position the heater under windows where curtains can contact the heater casing.
WARNING - THE SURFACES ON THIS HEATER CAN BE HOT This heater meets EN60335 safety requirements. However, any heater type becomes hot in normal operation. Care
must be taken to ensure that prolonged skin contact with the heater does not occur.
WHERE YOUNG CHILDREN, INFIRM PERSONS, OR THE AGED ARE PRESENT THIS APPLIANCE MUST BE
ADEQUATELY GUARDED. Contact your installer or manufacturer for further advice.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision for instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do
not play with the appliance.
This appliance is very heavy and must be securely fi xed to a wall. DO NOT UNDER ANY CIRCUMSTANCES
ATTEMPT TO MOVE OR REPOSITION THIS HEATER WITHOUT SEEKING EXPERT ADVICE.
To maintain stability, it is essential that the heater is placed on a level surface.This heater must be installed where it is impossible for switches and other controls to be touched by a person using
a bath or shower.
IMPORTANT - Due to the newness of materials the heater will produce a slight smell for the fi rst few days of
operation. ROOMS MUST BE WELL VENTILATED AND YOUNG CHILDREN, CAGED BIRDS, OR PERSONS WITH RESPIRATORY COMPLAINTS MUST NOT REMAIN IN CLOSE PROXIMITY TO THE HEATER DURING
THE FIRST 48 HOURS OF THE COMMISSIONING PERIOD.
IF, DURING ANY REASSEMBLY OF THE HEATER, A PART OF THE THERMAL INSULATION SHOWS DAMAGE
OR DETERIORATION WHICH MAY IMPAIR SAFETY, IT SHOULD BE REPLACED BY AN IDENTICAL PART.
INSTALLATION INSTRUCTIONS
PREPARATION
The heater will arrive separately from its storage bricks, the following bricks will be required:
Model 706N - 4 bricks
Model 712N - 8 bricks
Model 718N - 12 bricks
Model 724N - 16 bricks
Only heat resisting cable (min. rating T85) should be used. The wires in the mains cable will be coloured as follows:-
GREEN & YELLOW - EARTH BLUE - NEUTRAL BROWN - LIVE
SUGGESTED FIXINGS
SOLID BRICK/BLOCK: No. 10 Size plastic inserts,
8mm drill bit. Drill hole 15mm deeper than plastic insert length.
PLASTERBOARD - If possible locate studding and use No. 10 woodscrews directly into the wood, otherwise M5 rawlplug intersets are suitable.
NOTE: FOR OTHER WALL TYPES (e.g. Timber frame and hollow concrete) SEEK SPECIALIST ADVICE.
FIXING ASSEMBLY
ENSURE THAT FIXING KIT AND FEET HAVE BEEN LOCATED BEFORE DISPOSING OF PACKAGING.
Fit the feet with the open end of the foot to the front of the heater. Secure each foot using two taptite screws provided.
2.
Place the heater on its feet and in the desired position
against the wall. Ensure the heater is based on a fi rm level surface at least 75mm from any end wall and at least 250mm below any shelf or similar projection. Cut away any gripper rod or carpet which would prevent the heater sitting rmly on the fl oor.
3.
Mark the position of the two outside corners of the wall
bracket with the heater pushed tight against the wall. Remove the wall bracket from the heater by removing the screw at each end. Place the heater to one side and reposition the bracket against the wall using the corner marks for alignment.
Four fi xing positions must be chosen for the 724N, three for the 718N and two for the 712N and 706N. Mark the positions for the fi xing holes - two at the extreme ends and the others spaced evenly between them. Remove the bracket from the wall, drill the holes in the positions marked, and insert suitable fi xings previously described. Secure the wall bracket to the wall.
4.
4.
If mains connection is to be made from the left side, at this point the mains lead must be secured to the back of
the heater using ties provided in the fi xing kit.
5.
5.
WARNING - This appliance must be earthed
2.
1.
3.
LIMIT STAT
CUT OUT
ROOM STAT
XMS712/718 MODELS ONLY
XMS MODELS ONLY
LIMIT STAT
AND
CUT OUT
ROOM STAT
CIRCUIT DIAGRAM
STORAGE ELEMENTS